Military Engineer Services Tender
Search from a pool of business opportunities related to Odisha tenders on the online platform of BidAssist. Be it an Odisha PWD tender or a civil aviation tender, one can find every tender Odisha government, as well as PSUs and other organizations, post online. Every tender, active or achieved, is sourced from the eProcurement Odisha website and thus carries full credibility.
Costs
EMD
₹ 39,980Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_676324_1Bid Award Id
ViewTender No
8895/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
... More
125 KVA Capacity at Depot SS for perimeter area (1 Nos) (Make : Kirloskar)
1
-
-
... More
160 KVA capacity No-1 at NCN (1 Nos)
(Make : Cummins)
1
-
-
... More
160 KVA capacity No-2 at NCN (1 Nos)
(Make : Cummins)
1
-
-
... More
Maintenance and servicing of following mentioned Diesel Generator Sets including connected Alternator, and carrying our routine 'C' check of the engine complete for smooth functioning all as per manufacturer's instructions and as directed.
Note :- (a) Control switches such as MCCB, Main switch, contactors, multi display meter and engine control unit shall be out of scope of the item of work and the rate quoted shall exclusive of servicing/ maintenance of the above said fittings.
(b) 'C' check shall be carried out once in every YEAR or 500 hours of running of DG set whichever is earlier. Servicing of DG Set alonwith connected Alternator and Panel Board including items covered in 'A' & 'B' check of the Engine shall also be carried out in that month as directed by the Engineer-in-charge and the Contractor shall carry out periodical inspections during the maintenance period and he shall be responsible for the smooth functioning of the DG Set c) Spare parts, engine oil, distilled water and radiator coolant oil required for replacement during the maintenance period shall be measured and paid separately at supply only rates and cost of labour for fixing these spares/filling of oils shall be deemed to be included in the rate quoted for this item. (d) Cost of all consumables required during the maintenance period shall be deemed to be included in the rate quoted for this item. (e) List of checks to be carried out under 'C' check is attached as Appendix 'B' to the Particular specifications. QUOTED RATES INCLUDING all spares like B CHECK service kit and other consumable under 'C' check service, except oil & coolant
-
-
-
... More
62.5 KVA at Watch tower pump house(1 No) (Make : Mahindra)
1
-
-
... More
125 KVA Capacity at Depot SS area (1 Nos) (Make : Cummins)
1
-
-
... More
125 KVA Capacity at Depot SS for perimeter area (1 Nos) (Make : Kirloskar)
1
-
-
... More
160 KVA capacity No-1 at NCN (1 Nos)
(Make : Cummins)
1
-
-
... More
160 KVA capacity No-2 at NCN (1 Nos)
(Make : Cummins)
1
-
-
... More
Supply only fuel filter and water separator elements
-
-
-
... More
DG set of capacity 62.5 KVA
(Make : Mahindra)
2
-
-
... More
DG Set of capacity 125 KVA
(Make : Cummins/Kirloskar)
4
-
-
... More
DG Set of capacity 160 KVA (Make : Cummins/Kirloskar)
4
-
-
... More
Supply only lube /engine oil filter/cartridges as per sample and make of the following capacities of DG sets
-
-
-
... More
DG set of capacity 62.5 KVA
(Make : Mahindra)
2
-
-
... More
DG Set of capacity 125 KVA
(Make : Cummins/Kirloskar)
4
-
-
... More
DG Set of capacity 160 KVA (Make : Cummins/Kirloskar)
4
-
-
... More
Supply only Air Filter elements (inner/outer element set complete) of following DG Set as given bellow :-
-
-
-
... More
DG set of capacity 62.5 KVA
(Make : Mahindra)
2
-
-
... More
DG Set of capacity 125 KVA
(Make : Cummins/Kirloskar)
4
-
-
... More
DG Set of capacity 160 KVA (Make : Cummins/Kirloskar)
4
-
-
... More
Supply and filling radiator coolant
140
-
-
... More
Supply and filling distilled water
80
-
-
... More
Supply and filling engine oil of Grade 20W40
310
-
-
... More
Supply only fan belts for replacement of u/s fan belts of following capacities of DG set as per sample size complete all as specified and directed.
-
-
-
... More
DG set of capacity 62.5 KVA
(Make : Mahindra)
1
-
-
... More
DG Set of capacity 125 KVA
(Make : Cummins/Kirloskar)
2
-
-
... More
DG Set of capacity 160 KVA (Make : Cummins/Kirloskar)
2
-
-
... More
M&L for Overhauling of following mentioned radiator assy of following DG sets by disconnecting and removing from engine, dismantling the top & bottom chambers, descaling the sediments and scales, corrosion etc by means of acid cleaning and high pressure water washing, air cleaning, re-assembling the same with new gaskets, including arresting leakage, if any and fixing to the engine with new hoses, clipes complete all as specified and directed.
Note : The rate quoted shall be inclusive of transporting of the radiator to the workshop and back and all incidental charges.
-
-
-
... More
DG set of capacity 62.5 KVA
(Make : Mahindra)
1
-
-
... More
DG Set of capacity 125 KVA
(Make : Cummins/Kirloskar)
2
-
-
... More
DG Set of capacity 160 KVA (Make : Cummins/Kirloskar)
2
-
-
... More
Supply only Lead acid battery PVC body 12 volt 180 AH
2
-
-
... More
Supply only Lead acid battery PVC Body 12 volt 150 AH
2
-
-
... More
M&L for Dismantling/repairing the cylinder head assy for Cummins engine by stripping out the head assy from engine and carrying out the machining work such as head surfacing pressure testing, valve seat angle facing, lapping replacing the rusted water plugs and fixing the new brass water plugs etc., and replacing the worn out parts like inlet & exhaust valves guides , valves seat inserts, head gaskets, stem seal, silicon "O" rings and re-testing etc., complete as reqd. including the transportation and taking down all requisite parts as required and refixing the same of capacity 125 KVA complete all as specified and directed.
1
-
-
... More
M&L for overhauling the 125 KVA DG SET (Make-Cummins) by removing engine from chassis and disconnecting the fuel lines and exhaust connections and transporting to workshop replacing the u/s parts like piston - 6 Nos., rings - 6 sets cylinder liner 06 Nos. after cleaning the engine block and fixing the new parts like connecting rod, bearing. cylinder liners - 6 Nos. set of joints complete, oil seals, reassembling the engine with new parts. After reassembling cooling the engine testing and commissioning etc., as directed including taking down all requisite parts as required and refixing the same .
1
-
-
... More
M&L for Overhauling the fuel injection pump assembly and injectors for 125 KVA DG set , dismantling and taking out to workshop for repair including transportation by replacing the worn out/unserviceable parts like service kit, D - Valve, Element MICO - 4 Nos. Delivery valve MICO - 4 Nos, Swelling lever MICO -1 No, Bearings (SKF/NBC) - 2 Nos, Nozzle MICO - 4 Nos etc., as required, mentioned and calibration the same, commissioning etc., complete all as specified and directed.
1
-
-
... More
Supply only Voltage Regulator (AVR) suitable for DG set of capacity 125 KVA
2
-
-
... More
Supply only Voltage Regulator (AVR) suitable for DG set of capacity 62.5 KVA
1
-
-
... More
Supply only Low Oil pressure Switch 12V 1.7 kg/Sq.mm
1
-
-
... More
Supply only battery lead
10
-
-
... More
Supply only stopping solenoid 12 Volt suitable for the following DG sets
-
-
-
... More
DG set of capacity 62.5 KVA
(Make : Mahindra)
1
-
-
... More
DG Set of capacity 125 KVA
(Make : Cummins/Kirloskar)
1
-
-
... More
DG Set of capacity 160 KVA (Make : Cummins/Kirloskar)
1
-
-
... More
Supply only battery terminal made of brass with nut and bolt etc complete all as specified and directed.
10
-
-
... More
Supply only Radiator hose flexible suitable for the following DG sets
-
-
-
... More
DG set of capacity 62.5 KVA
(Make : Mahindra)
1
-
-
... More
DG Set of capacity 125 KVA
(Make : Cummins/Kirloskar)
2
-
-
... More
DG Set of capacity 160 KVA (Make : Cummins/Kirloskar)
1
-
-
... More
Supply only Hose plain for water pump suitable for the following DG sets
-
-
-
... More
DG set of capacity 62.5 KVA
(Make : Mahindra)
1
-
-
... More
DG Set of capacity 125 KVA
(Make : Cummins/Kirloskar)
2
-
-
... More
DG Set of capacity 160 KVA (Make : Cummins/Kirloskar)
1
-
-
... More
Supply and replace in repair - MCCB 3 pole 25-100A 16KA - in LT panel boards / feeder pillar boxes including disconnecting and removing existing defective item from electric circuit including necessary connected fasteners, burnt cables, accessories etc,. all as per site requirement/existing make/model complete all as specified and directed.
1
-
-
... More
Supply and replace in repair - MCCB 3 pole 200A 25KA - in LT panel boards / feeder pillar boxes including disconnecting and removing existing defective item from electric circuit including necessary connected fasteners, burnt cables, accessories etc,. all as per site requirement/existing make/model complete all as specified and directed.
2
-
-
... More
Supply and replace in repair - MCCB 3 pole 250A 25KA - in LT panel boards / feeder pillar boxes including disconnecting and removing existing defective item from electric circuit including necessary connected fasteners, burnt cables, accessories etc,. all as per site requirement/existing make/model complete all as specified and directed.
1
-
-
... More
S&F in repairs Change over switch 4 pole 200A in sheet metal enclosure.
2
-
-
... More
S&F in repairs Change over switch 4 pole 250A in sheet metal enclosure.
1
-
-
... More
M&L for Plates plain or chequered (Fe 410 -W (Gde- E- 250)) channels, square cut or notched (ordinary and counter sunk) forming holes, of required size with lifting hooks for cable / pipe line duct covers of pump house, painting complete with two coats of synthetic enameled paint over a coat of red oxide primer complete all as specified and directed.
440
-
-
... More
Supplying and laying synthetic Rubber insulated mats 2 mm thick for voltage upto 3.3 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m complete all as specified and directed.
8
-
-
... More
M&L in replacement of Mild Steel ERM pipe 150mm bore, 5.4mm thickness, heavy grade, ISI Marked, confirming to IS 3589-1991, with all fittings such as bends, elbows, tees, short pieces, connectors, back nuts, diminishing pieces, caps plugs and unions etc., including taking down old pipe in any position, complete all as specified and directed.
(Make: JINDAL / PRAKASH / ZENITH)
42
-
-
... More
M&L in replacement of Mild Steel ERM pipe 100mm bore, 5.4mm thickness, heavy grade, ISI Marked, confirming to IS 3589-1991, with all fittings such as bends, elbows, tees, short pieces, connectors, back nuts, diminishing pieces, caps plugs and unions etc., including taking down old pipe in any position, complete all as specified and directed.
(Make: JINDAL / PRAKASH / ZENITH)
12
-
-
... More
S&F in replacement of Fire hydrant stand post 80mm dia GI/MS both ends flanged type 1.50m height, with provn of single outlet confirming to IS 908, fixed in replacement of, complete all as specified and directed. (Make: MINIMAX / FIREX / SAFEX)
6
-
-
... More
S&F in replacement of Sluice valve 150mm dia, cast iron body, PN-1.6, with flanged ends drilled at both ends, conforming to IS-14846, ISI marked, having brass spindle with iron wheel at top, with nuts, bolts , washers, rubber gasket etc, complete all as specified. (Make: KIRLOSKAR / L&T / UPADHYAY/ LEADER )
2
-
-
... More
S&F in replacement of Sluice valve 100mm dia, cast iron body, PN-1.6, with flanged ends drilled at both ends, conforming to IS-14846, ISI marked, having brass spindle with iron wheel at top, with nuts, bolts , washers, rubber gasket etc, complete all as specified and directed. (Make: KIRLOSKAR / L&T / UPADHYAY/ LEADER )
2
-
-
... More
S&F in replacement of 63mm dia 15m long hose complete with male and female coupling, conforming to IS-903, complete all as specified and directed.
(Make: MINIMAX / FIREX / SAFEX)
12
-
-
... More
S&F in replacement of branch pipe gun metal 63mm dia instantaneous inlet, made threaded outlet, 15mm bore nozzle long, complete all as specified and directed. (Make: MINIMAX / FIREX / SAFEX)
12
-
-
... More
S&F in replacement of Hose box made of 18 gauge MS Sheet 800mm X 600mm X 250mm with double door with 4mm thick glasses door with necessary locking arrangements and door frame made of 16gauge MS sheet painted fire red out side and brilliant white inside yard, fixed to wall, internal, suitable for fixing two hose reel of 30m long, complete all as specified and directed.
(Make: MINIMAX / FIREX / SAFEX)
8
-
-
... More
S&F in replacement of Hose reel of 20mm dia and 30mtr long confirming to IS-5132, complete all as specified and directed.
(Make: MINIMAX / FIREX / SAFEX)
2
-
-
... More
S&F in replacement of Water pressure gauge standard dia [100mm dial 0-14Kgs] at delivery side of the pump set, complete tubing fitted with stop cock, complete all as specified and directed.
(Make: HGURU / TAYLOR/ FIEBIG)
2
-
-
... More
S&F in replacement of Gun metal gate valve of 50 mm dia complete all as specified.
4
-
-
... More
S&F in replacement of Gun metal gate valve of 25 mm dia complete all as specified and directed.
6
-
-
... More
S&F in replacement of Electrical operated Water Pressure switch with necessary mounting / connection with control wiring with conductor, and mechanical connection to operate at pressure range of 0-14Kg/Sqcm for automation, complete all as specified and directed.
(Make: HGURU / TAYLOR/ FIEBIG)
2
-
-
... More
Supply, and replace defective/ unserviceable four way fire brigade inlet with isolation valve with instantaneous gun metal coupling 63mm dia complete all as per fire standards made out of 150mm dia class 'B' MS pipe complete all as specified and directed.
(Make:-WINCO/ AAG / MINIMAX / NEW AGE)
1
-
-
... More
Excavation in trenches, not exceeding 1.5m wide and not exceeding 1.5m in depth for laying of pipe line and the like, getting out in hard/ dense soil, complete all as specified and directed.
11.66
-
-
... More
Removing excavated material to a distance n.ecx 50m and dipositing where directed at a leveln.exc. 1.50m above the starting point complete all as specified and directed.
10.36
-
-
... More
Returning, filling in including spreading levelling, watering and well ramming in layers n.exc. 25cm in hard/ dense soil, complete all as specified and directed.
1.3
-
-
... More
M & L for pressure testing of existing CI / DI / MS of water supply / fire lines of 150 mm dia for identifying leakages for rectifications including replacement of gland packing of sluice valves, rubber insertion packing, nut ,bolts etc of flanged joints / defective flanges etc complete for making the system leak proof complete all as specified and directed.
Note: (a) The rate quoted is deemed to be inclusive of T&P such as air compressor for pressure testing etc (b) Earthwork, DI / MS pipe & specials required for rectification if any shall be measured and paid separately under relevant items BOQ.
(c) Pressure test will be carried out either complete network or partial pipelines of any size / distance as per ground requirement.
1
-
-
... More
M & L for arresting water leakage from sluice valve, by refacing, regrinding of sluice Valve, Repacking stuffing box of sluice valve spindle including taking apart and reassembling the same including replacing old check nuts with new one made out of MS / CI material, with and including replacing perished gland packing, rubber gasket, bolts and nuts complete all as specified and directed for the following sizes :-
-
-
-
... More
80 mm dia bore
2
-
-
... More
100 mm dia bore
2
-
-
... More
150 mm dia bore
2
-
-
... More
M & L for rectification of existing defective / leakage flanged joints with rubber or fibre gasket complete with necessary nuts, bolts and washers all as specified for 80 mm dia pipe lines of DI / MS / GI pipes complete all as specified and directed.
Note:- (a) quoted rates are inclusive of cutting of DI / MS / GI Pipes, jointing materials and preparation of new flanged sockets and re fixing the same at existing place.
(b) Necessary excavation and pipes are measured and paid separately.)
8
-
-
... More
All as per item No 50.00 above but for 100 mm dia pipe
2
-
-
... More
All as per item No 50.00 above but for 150 mm dia pipe
6
-
-
... More
M & L Preparation of old painted steel surfaces of any description of Fire hydrant stand post 80mm dia GI/MS both ends flanged type 1.50m height with single outlet and Hose box made of MS Sheet 800mm X 600mm X 250mm with double door and the accessories of the fire hydrant post complete and applying with a coat of zinc chrome primer and two coats of postal red colour epoxy paint complete all as specified and as directed.
13
-
-
... More
Supply and Fix in replacement "Fire Hydrant Blanking Cap of PVC for closing the fire hydrant valves of 63/80 mm dia complete along with chain complete all as specified and directed.
10
-
-
... More
Supply and Fix in replacement "Fire Hydrant Hand Wheel" for closing the fire hydrant valves of 63/80 mm dia complete all as specified and directed.
8
-
-
... More
Supply and Fix in repair Female outlet (Adapter) Gun metal in existing Hydrant valve (both type A and B) of size 63mm all as specified and directed.
5
-
-
... More
Material and labour for taking down defective foot valves from UG Sump, removing corrosion and painting with one coat of red oxide along with black enamel paint and replacing rubber gaskets, foot valve bottom rubber with spring complete with renewal of necessary bolts, nuts, washers complete all as specified for 150 / 100 mm dia size of foot valves. complete all as specified and directed.
3
-
-
... More
M & L for taking down & re fixing the old fire hydrant valves of size 80mm dia from hydrant post by removing the corrosion, changing the damaged pins from pivot end, softening the shaft of iron wheel and applying the grease for lubrication of fire hydrant valves complete all as directed by EIC. Note : quoted rates are inclusive of Nut & Bolts and other connected items.
12
-
-
... More
M & L for repair/ maintenance of fire hose box by changing of damaged doors along with locking arrangements, front glass of existing size and necessary rubber gaskets for doors complete all as specified and directed.
Note:- Quoted rates are inclusive of one coat red-oxide paint, paint red and inside clean white paint
12
-
-
... More
Opening, cleaning and checking of Air Tank and connected accessories, and kept in operational condition without any leakages, complete all as specified and directed.
1
-
-
... More
Opening, cleaning and checking of NRV valves and system and replacing washers, gaskets and kept in operational condition without any leakages, complete all as specified and directed.
3
-
-
... More
Removing hose and branch pipe from hose cabinet, cleaning and checking of box, locking arrangements, replacement of glass and unserviceable items, complete all as specified and directed.
6
-
-
... More
Checking and pressure testing of CP hoses and binding of hoses with copper wire, checking, testing and rectification of male and female couplings, complete all as specified and directed.
6
-
-
... More
Repair/maintenance and servicing of step down transformer 11 KV/433 Volt of capacity 160 KVA, comprising following work services mentioned in below :- (Make: Alfa Electricals) :-
1
-
-
... More
Disconnection carefully of cable end termination of HT & LT side.
-
-
-
... More
Opening of top cover by removing nuts, bolts and all mounting accessories and conservator tanks.
-
-
-
... More
Draining out transformer oil and keeping aside in barrel for re-use and then again pouring back after necessary filteration and dehydration including top up with new transformer oil to make up the reduced quantity.
-
-
-
... More
Replacement of top and bottom Gaskets.
-
-
-
... More
Servicing of tap changing gears by cleaning and polishing tapping contact points.
-
-
-
... More
Labour only for Cleaning of bush and stud both HT/LT side and refixing the same with new cock sheet as required
-
-
-
... More
Replacing unserviceable stud and bush as required as directed by Engr-in-Charge.
-
-
-
... More
Reconnection of all cable terminals HV & LV sides and refixing the top cover after replacement of gaskets, conservator tank in position.
-
-
-
... More
Cleaning and heating of silica gel in breather and replenishing with new silica gel to make up the reduced quantity.
-
-
-
... More
Connecting HT & LT side with existing incoming and outgoing cables including reconnection of earth strip/lead.
-
-
-
... More
Filteration and dehydration of transformer oil, New transformer oil shall be measured separately.
-
-
-
... More
Ditto all as per Item No. 64.00 above but transformer of capacity 200 KVA.
1
-
-
... More
Ditto all as per Item No. 64.00 above but transformer of capacity 63 KVA.
2
-
-
... More
Filteration and dehydration of old transformer oil and removing of sludge by continuous circulation through transformer oil filtration plant with heater strips to achieve dielectric strength of not less than 50 KV at 2.5 mm gap of electrode as per IS-1866(1985) and improvement of acidity by minimizing percentage of acidity using chemical reagents all as spedified and as directed.
1100
-
-
... More
Supply and filling in replacement of transformer oil having di-electric strength not less than 50 KV at 2.5 mm gap after initial dehydration/filteration conforming to IS 335 and ISI marked all as directed.
320
-
-