Military Engineer Services Tender
View complete overview of Nagaland MES Tender
Costs
EMD
₹ 47,500Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2020_MES_391730_1Bid Award Id
ViewTender No
8322/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
M&L for spread fine river sand in trenches complete all as specified ans as directed. Note: For measurement purpose, punned down thickness shall only be taken.
125
-
-
M&L for laying brick sub class 'B' old size burnt bricks for cable protection of size 230mmx115mmx75mm complete all as specified and as directed
15000
-
-
Material and labour for GI tubing light grade 40 mm dia under road crossing/ on pole for protection of cable incl taking out old unsv pipe all specified and as directed.
Make:- Jindal/Prakashsurya/Nezone(NTL)
50
-
-
All as per iem No 6 above but 50mm dia.
50
-
-
All as per iem No 6 above but 80mm dia.
24
-
-
All as per iem No 6 above but 100mm dia.
20
-
-
M&L for house service bracket (hook type) complete with 3 m long GI pipe 40mm dia Med grade with two Nos 90 degree bend MS hook and stay or guy fixed to wall will MS clamps 2 Nos and taking down old unsv one complete all as specified.
5
-
-
M&L for PVC/XLPE insulated twin core aluminum stranded conductor round/flat cable size 10 Sqmm 1100 Volts grade served with an sheathing of PVC tape and overall PVC shaetehed in service connection suspended by insulating hangers not more than 1 mtr apart including 4mm GI suspension wire incl taking down old unsv cable.
500
-
-
All as item No 11 above but 16 Sqmm
500
-
-
Supply, laying & testing XLPE insulated screened PVC bedded galvanised steel strip or wire armoured, electric power cable (Heavy duty) with stranded aluminium conductor 1100 volts grade of size 10 Sqmm 2 core incl taking out old unsv cable from trenches all as specified and as directed.
Make:- Plaza/Havells/Finolex
400
-
-
All as item No 13 above but 16 Sqmm 2 core
300
-
-
All as item No 13 above but 25 Sqmm 3.5 core
400
-
-
All as item No 13 above but 35 Sqmm 3.5 core
250
-
-
All as item No 13 above but 50 Sqmm 3.5 core
250
-
-
All as item No 13 above but 95 Sqmm 3.5 core
150
-
-
All as item No 13 above but 120 Sqmm 3.5 core
150
-
-
All as item No 13 above but 185 Sqmm 3.5 core
100
-
-
All as item No 13 above but 240 Sqmm 3.5 core
100
-
-
M&L for earthing complete with galvanized earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.25 M deep below normal GL) with top edge of the earth plate not less than 1.5M below normal GL, connected with galvanised earth lead wire 4 mm dia by means of bolts, nuts, check nuts & washers of GI or steel incl excavation, PCC (1:3:6) type C-1 chamber with CI cover 10mm thick plate fixed to angle iron frame work and 15 mm dia light grade GI protection pipe, funnel with wire mesh,watering pipe of size 20 mm dia med. grade, lugs, main Earthing lead upto 7.5 mtr incl. Charcoal dust, salt etc. all as shown in electrical plate No. 3 of SSR Pt-I, 2009 specification.
6
-
-
Dismantling cross -arms of MS channel or angle sections etc complete and setting aside for re-use with in 50 mtr.
1
-
-
Dismantling insulators any type, any size.
30
-
-
Dismantling of ACSR/ AAC conductors.
1
-
-
Supply, install, test and commission out door type cubical panel board outer shell made out of 3.15 mm thick MS sheet and inner shell made out of 2 mm thick MS sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platform 90 cm above and 45 cm below the ground level, frame factory fabricated with front and back openable double door system (Each door hinged with body at 4 places with body and hinges should be welded with body and door) lockable/open able by Keys having chromium plated 19 mm dia fancy lock, “U” type gasket shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, tested at factory approved from CPRI for 35 MVA rupturing capacity at 415 Volts factory fabricated having modern fabrication and testing process followed by powder coat painting having thickness not less than 100 microns provided with suitable gasket to make it dust/vermin proof and general construction confirming to IS:8623/93 comprising of the following :-
1
-
-
INCOMING
(a) TPN Aluminium bus bar 500 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators not less than 1.0 mtr long
(b) MCCB 250 Amps 4 pole, 415 volts,electronic release with rupturing capacity 36 KA-01 No
(c) Voltmeter digital type 0-500Amps with inbuilt selector switch-01 No
(d) Ammeter digital type 0-400 Amps with selector switchand suitable CTs-01 No
(e) Phase indicator lamp LED type RYB (set of three)-01 set
OUT GOING
(a) MCCB 200 Amps 3 pole 415 Volts, thermal Magnetic releasewith rupturing capacity 25KA.-01No
(b) MCCB 160 Amps 3 pole 415 Volts, thermal Magnetic releasewith rupturing capacity 16 KA.-02Nos
(c) MCB TP 40 Amps, 415 volts thermal magnetic release with rupturing capacity 16 KA - 01 No
(d) One spare cabinet for accomadating MCCB 63 Amps for future expansion.
0.1
-
-
Supply, install, test and commission out door type bus bar chamber having tapered roof outer shell made out of 3.15 mm thick MS sheet and inner shell made out of 2 mm thick MS sheet and MS angle section 50x50x6 mm mounted on PCC 1:2:4 type B-1 platform 90 cm above and 45 cm below the ground level, frame factory fabricated with front openable door system , 04 Nos Al bus bar 400 amps cap fixed over epoxy insulator s duly insulated with different sleeves and neccessary holes of suitable dia in Bus bar strip with locking arrangements “U” type gasket shall be used to make the outer shell completely vermin proof suitable for 3 phase 4 wire 415 Volt, 50 Hz, tested at factory approved from CPRI having thickness of powder coat not less than 100 microns provided with suitable gasket to make it dust/vermin proof including taking out old unserviceable bus bar boxes l all as specified and directed..
7
-
-
M&L for replacement of heat shrinkable end termination cable jointing kit for PVC/XLPE insulated ,armoured electric cable of size 25 to 50 Sqmm 3.5 core 1100 Volts garde for indoor/outdoor use complete with jointing materials and accessories. Make:- Raychem/3M/Densons
7
-
-
All as per item No 28 above but electric cable of size 70 sqmm to 150 Sqmm 3.5 core
6
-
-
All as per item No 28 above but electric cable of size 185 sqmm to 300 Sqmm 3.5 core
6
-
-
M&L for replacement of heat shrinkable straight through cable jointing kit(cold applied insulation and sealing system) for PVC/XLPE insulated ,armoured electric cable of size 25 to 50 Sqmm 3.5 core 1100 Volts garde for indoor/outdoor use complete with jointing materials and accessories. Make:- Raychem/3M/Densons
6
-
-
All as per item No 31 above but electric cable of size 70 sqmm to 150 Sqmm 3.5 core
4
-
-
All as per item No 31 above but electric cable of size 185 sqmm to 300 Sqmm 3.5 core
4
-
-
M& L for boring of hole under road with mechanical arrangement upto 100mm dia without disturbing the top surface of the road for passing the UG electric cable across the road complete all as specified and as directed.
35
-
-
M & L for repair/maint of LT panel board by dismantling all cable connection i.e incoming and outgoings and trenching out cable / cable loop after digging, cutting burnt portion of cable, cleaning and fixing of lugs with crimping tool, cleaning of bus bar with emery paper, tightening of bus bar with busbar insulators, re-fixing of cable with busbars/circuit breaker, by providing new bolts, nuts and washers cable lugs to be provided for all incoming and outgoing cables all as specified and as directed.
10
-
-
M& L for replacement of Cable lugs with aluminium alloy tubular bimetallic terminals of size 25/35 Sqmm incl crimping with help of crimping tools all as specified and directed. Make :- Dowells/Jainsons or equivalent
100
-
-
All as per item No 36 above but of size 50/70 sqmm
100
-
-
All as per item No 36 above but of size 95/120 sqmm
100
-
-
All as per item No 36 above but of size 150/185 sqmm
50
-
-
All as per item No 36 above but of size 240/300 sqmm
50
-
-
All as per item No 36 above but of size 400 sqmm
25
-
-
Material and labour taking out seviceable electric cable of size upto 95Sqmm x 3.5 from trenches complete after removing brick/PCC cover,sand , protection pipes and shifting the cable to other location within RMS for relaying complete all as specified and directed.
Note: Excavation and earthwork, brick, sand shall be measured and paid separately.
200
-
-
All as item No 42 above but cable of size upto 240 Sqmm.
150
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements