Military Engineer Services Tender
View complete overview of Nagaland MES Tender
Costs
EMD
₹ 87,400Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_639653_1Bid Award Id
ViewTender No
8596/C/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
SPL REPAIR REPLACEMENT OF UNSV CHEMICAL DOZING CHLORINATION SYSTEM ELECTRIC CONTROL PANEL AND CERTAIN CONNECTED WORKS AT RMS
BOQ Items
c) Outgoing:- MCCB, 4 pole, 415 volt, AC supply 250 amp release range, with neutral link,36 KA breaking capacity, 50 Hz with microprocessor release- 02 Nos
make:- Havells cat No IHLLSEBFF0250 or equivalent in Siemens, ABB/legrand
d) Cabinet for supply and fixed with star delat starter fully automatic suitable for 75 HP motor, 415 volts AC- 01 Nos.
e) Voltmeter digital type 3 phase AC, 96 mm x96 mm square type, 0-500 volt incl selector switch for reading all 3 phase-01 Nos
f) Ampere meter digital type 3 phase AC, 96 mm x 96mm square type 0-800 amps woth suitable CTs incl selector switch for reading all 3 phase - 01 No
g) Phase reading indicating LED lamp with holder 230 volt for all 3 phase (RYB) - 03 Nos
-
-
-
supply,istallation, commissioning and testing in replacement of LT panel board of suitable shape and size as approved by the Engineer-in-charge, out door cubical type (415 volts, 50 Hz, 3 phase, 4 wire supply) floor block mounted, factory made, dust and vermin proof (protection class IP-54) made out of CRCA sheet for panel shall be mounted on 50mmx 50mm x 5mm angle iron frame and shall have channel base of appropriate size and mounted on PCC foundation built in PCC 1:3:6 type C-2 be using 40mm graded crushed stone aggregate including painted externally and internally providing one coat of any corrosive coating and finally epoxy powder coating of grey shade , platform height of the panel at least 2 feet from the ground level as recommended or directed by the Engineer in charge comprising of following.
a) 03 Nos Aluminium bu bar 600 amp capacity for phase, o1 No. Aluminium bus bar 600 amp capacity for neutral duly supported on suitable size of epoxy insulator fixed in dust and vermin proof MS enclosure having adequate clearance between conductor and earth for easy maintenenace. These should have color coding for RYB and neutral to enable immediate identification. all the incoming connection to MCCBs shall be made with suuitable size aluminium bus bars of rating 600 amp.
b) Incoming:- MCCB, 4 pole, 415 volt, AC supply, 400 Amp- 01 No
make:- Havells cat No -IHLLSEBF0400 eauivalent in Siemens, ABB/Legrand
1
-
-
c) Outgoing:- MCCB, 4 pole, 415 volt, AC supply 250 amp release range, with neutral link,36 KA breaking capacity, 50 Hz with microprocessor release- 03 Nos
make:- Havells cat No IHLLSEBFF0250 or equivalent in Siemens, ABB/legrand
d) Cabinet for supply and fixed with star delat starter fully automatic suitable for 75 HP motor, 415 volts AC- 02 Nos.
e) Voltmeter digital type 3 phase AC, 96 mm x96 mm square type, 0-500 volt incl selector switch for reading all 3 phase-01 Nos
f) Ampere meter digital type 3 phase AC, 96 mm x 96mm square type 0-800 amps woth suitable CTs incl selector switch for reading all 3 phase - 01 No
g) Phase reading indicating LED lamp with holder 230 volt for all 3 phase (RYB) - 03 Nos
-
-
-
Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised iron strip 25×4mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 5 connected to earthing test point all as specified or indicated including testing on completion
10
-
-
S & F PVC insulated multi stranded single core cable with copper conductor 1100 Volts grade conforming to IS: 694 / 1990 for 95 sqmm all as specified and directed.
Make : Richa/Havells/RR Kabel.
100
-
-
Supply and fixing 1100 volts grade heavy duty XLPE cable insulated aluminium stranded size of cable 6 sqmm 2 core .
320
-
-
Supply and replacement of automatic pressure pump of capacity 0.5 HP with connected accessories Make-Kirloskar/Grand fos/equal
5
-
-
Supply and fixing on Pole/Wall Flood light fittings for use with LED lamps, 120 watts, 240 Volt, with high quality lenses & reflector, 240 Volt, High grade aluminium pressure Die-Cast Housing with toughened glass cover, IP-65 class of protection, complete with control gear and all accessories including lamp.
13
-
-
S & F in repairs Weather proof street light junction box Made of FRP or MS Sheet of size 20 x 20 x 15 cm depth comprising of MCB, TPN, 25 Amps, connecting terminals 4 way including necessary Clamps made out of MS flat iron, nuts and bolts suitable for fixing with steel tubular Poles complete all as directed.
13
-
-
S&F in replacement of single pole MCB 6 to 32 Amps, 240 v, 50 Hz AC suitable for ‘C’ curve, 10 KA breaking capacity conforming to IS 8828 of 1996 all as specified
13
-
-
S&F in replacement of Double pole MCB 40 amp, 240 v, 50 Hz AC suitable for ‘C’ curve, 10 KA breaking capacity complete conforming to IS 8828 of 1996 all as specified
13
-
-
Taking up CI/DI/GI water main (including all fittings), with spigot and socketed ends jointed with run lead joints including burning out lead of joints and collecting run lead for re-use, cleaning serviceable pipe internally/externally for re-use, stacking properly in safe custody in store yard of AGE E/M and removing unserviceable pipe of 150 mm dia from site complete, all as specified and directed of following sizes:-
(Note :-Excavation and earth work shall be measured and paid separately)
350
-
-
All as per item No. 13 above here-in-before but of size 100 dia mm bore
150
-
-
Supply and laying Centrifugally Ductile iron pipe (Class K-9) spigot and socket end with all fittings complete in trenches incl taking down old U/s pipe line all as specified & directed of 150 mm dia Note : For Branch Connection fittings such as (union, Tees , bends, nipples, sockets, elbows etc), welding work and earth work as required at site will be included in the rate quoted by the contractor.
350
-
-
All as per item No 15 above here-in-before but size 100 dia mm bore
150
-
-
M&L for Ductile iron pipe Fittings upto 200 mm bore (Class K-9) for spigot and socket or flange pipes, such as bends (any type radius and angle) Tappers (any type straight, bend, increasing, decreasing or double socket etc.). Tee pieces (any type), single branch, Y junction. double branch, cross complete all as specified and directed.
450
-
-
Material & Labour for construction of brick masonry valve pit of internal dimension 0.9M x 0.9M x 0.9M complete with MS angle iron frame work (angle iron size 50mm x 50mm x 6mm) and 3.15 mm thick MS black sheet top cover openable through hinges of suitable size including necessary earth work, PCC, locking arrangement,rendering complete with two coats of black bituminous paint over a coat of red oxide zinc chrome primer to all iron surfaces all as specified and directed.
3
-
-
S&F sluice valve flanged type (PN:1.6) with brass spindle suitable for CI/DI pipe line including all jointing materials such as washers, nut bolts, rubber packing etc and testing complete all as specified ISI marked incloding taking out old sluice valve for 150 mm dia sizes all as specified & directed.
4
-
-
All as per item No 10 above here-in-before but size 100 dia mm bore
2
-
-
S&F butterfly valve flanged type (PN:1.6) with control gear suitable for CI/DI pipe line including all jointing materials such as washers, nut bolts, rubber packing etc and testing complete all as specified ISI marked incloding taking out old U/s valve, for size 150 mm dia .
5
-
-
S&F cast iron foot valve flanged type including all jointing materials such as washers, nut bolts, rubber packing etc and testing complete all as specified ISI marked for 150 mm dia pipe lines including taking out existing foot valve complete all as specified and directed by Engr-in-Charge.
Make:- kirlosker,Upadhay,Leader
3
-
-
M & L for PCC work 1:3:6 Type D2 (using 40mm Graded aggregate stone aggregate) as in foundation, mass concrete, sub base etc complete all as specified and directed.
6
-
-
M&L for boring under/cutting of existing road/cement concret/butuminous road of size not less than 0.6m for laying of GI/CI/DI pipe & making good to the disturbed surface by providing PCC or Same material After laying of pipe line and returning filling of soil complete all as specified and directed
10
-
-
Excavation in trenches not exc 1.5 mtr wide and not exc 1.5 mtr depth for laying of pipes and getting out in soft/loose soil.
150
-
-
Returning, filling , including spreading, levelling, watering and well ramming in layers not exc 25 cm as in soft/loose soil all as directed.
125
-
-
Removal of surplus soil not exceeding 50 mtr and deposited where as directed at a level n exc 1.5m above the starting point.
25
-
-