Military Engineer Services Tender
View complete overview of Nagaland MES Tender
Costs
EMD
₹ 19,160Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_660360_1Bid Award Id
ViewTender No
8258/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
All as per item serial No 02 here-in-before but for One 3 pin 5 Amp switch socket outlet on independent board.
40
-
-
All as per item serial No 02 here-in-before but with 2.5 Sqmm single core multistranded copper conductor cable and earth continuity wire with 2.5 Sqmm cable for 6 pin 15 Amp socket outlet on independent board.
50
-
-
S & F switch piano, flush type single pole one way 5 Amps 230 volt complete all as specified and as directed.
230
-
-
S&F socket outlet 3 pin, 2-in-1, 5 Amps, flush type complete all as specified and as directed.
10
-
-
S & F switch socket combination outlet 5 pin, 2-in-1, 5 Amp flush type complete all as specified and as directed.
40
-
-
S & F in repairs, switch socket combination outlet 5 pin, 2-in-1, 5 Amp flush type complete all as specified and as directed.
60
-
-
S & F switch socket combination, multipurpose, 2 in 1, 6 pin, 5 & 16 Amp flush type complete all as specified and as directed.
50
-
-
S & F in repairs, switch socket combination, multipurpose, 2 in 1, 6 pin, 5 & 16 Amp flush type complete all as specified and as directed.
80
-
-
S & F ceiling rose surface bakelite, 65x50mm three terminal complete all as specified and as directed.
220
-
-
S&F PVC rectangular block for mounting, switches, sockets, fan regulator etc. with 3 mmthick plastic laminated sheet cover of size 250 mm x 200 mm and 50 mm deep complete all as specified and as directed.
30
-
-
S&F PVC rectangular block for mounting, switches, sockets, fan regulator etc. with 3 mmthick plastic laminated sheet cover of size 200 mm x 150 mm and 50 mm deep complete all as specified and as directed.
10
-
-
S&F PVC rectangular block for mounting, switches, sockets, fan regulator etc. with 3 mmthick plastic laminated sheet cover of size 100 mm x 100 mm and 50 mm deep complete all as specified and as directed.
10
-
-
S & F in repairs, single pole & neutral DBs 8 Ways, double door, protection class IP-43 suitable for mounting MCB, DBs conforming to IS-13032, IS-8623, BS-5484 with min 100 Amp rating copper bus bar complete all as specified and as directed.
Make :- Legrand Cat No 5076 11/Schneider Cat No A9HSND08 or equivalent model in Siemens / Schneider
20
-
-
S & F in repairs, single pole & neutral DBs 6 Ways, double door, protection class IP-43 suitable for mounting MCB, DBs conforming to IS-13032, IS-8623, BS-5484 with min 100 Amp rating copper bus bar complete all as specified and as directed.
Make :-Schneider Cat No A9HSND06 or equivalent model in Siemens / Legrand
10
-
-
S & F in repairs, single pole & neutral DBs 4 Ways, double door, protection class IP-43 suitable for mounting MCB, DBs conforming to IS-13032, IS-8623, BS-5484 with min 100 Amp rating copper bus bar complete all as specified and as directed.
Make :- Legrand Cat No 5076 10 or equivalent model in Siemens / Schneider/L&T
10
-
-
S & F in repairs, sheet metal enclosure when MCB to be used 2 way, Single pole & neutral without bus bar complete all as specified and asdirected.
10
-
-
S&F in repairs. MCB TPN 40 to 100Amps, 415V,50 HZ,C series breaking capacity 10KA complete all as specified and as directed. Make- Legrand ,cat part no-4086 18 to 20 / Schnider Cat No A9N2P40B to 63B or equivalent model of make Siemens/ABB/L&T
2
-
-
S&F in repairs. MCB SPN 40 to 63Amps, 415V,50 HZ,C series breaking capacity 10KA complete all as specified and as directed. Make- Legrand ,cat part no-4086 18 to 20 / Schnider Cat No A9N2P40B to 63B or equivalent model of make Siemens/ABB/L&T
6
-
-
S&F MCB SPN 40 to 63Amps, 415V,50 HZ,C series breaking capacity 10KA complete all as specified and as directed. Make- Legrand ,cat part no-4086 18 to 20 / Schnider Cat No A9N2P40B to 63B or equivalent model of make Siemens/ABB/L&T
30
-
-
S&F MCBs, SPN 6 to 32 Amps, 10 KA, 'C' curve IS/IEC 60898-1 2002 marked fixing in DBs complete all as specified and as directed.
Make :- Legrand Model 4086 09 to 17/Schnider Cat No A9N2P06B to 32B or equivalent model of make Siemens/ABB/L&T.
20
-
-
S&F in repairs, MCBs, SPN 6 to 32 Amps, 10 KA, 'C' curve IS/IEC 60898-1 2002 marked fixing in DBs complete all as specified and as directed.
Make :- Legrand Model 4086 09 to 17/Schnider Cat No A9N2P06B to 32B or equivalent model of make Siemens/ABB/L&T.
40
-
-
S&F MCBs, SP 6 to 32 Amps, 10 KA, 'C' curve IS/IEC 60898-1 2002 marked fixing in DBs complete all as specified and as directed.
Make :- Legrand Model 4085 90 to 95/Schnider Cat No A9N1P06B to 32B or equivalent model of make Siemens/ABB/L&T.
180
-
-
S&F in repairs, MCBs, SP 6 to 32 Amps, 10 KA, 'C' curve IS/IEC 60898-1 2002 marked fixing in DBs complete all as specified and as directed.
Make :- Legrand Model 4085 90 to 95/Schnider Cat No A9N1P06B to 32B or equivalent model of make Siemens/ABB/L&T.
70
-
-
S&F 1100 volts grade heavy duty flat cable of size 6 Sqmm 2 core, PVC insulated aluminium solid conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 m apart including replacing 4mm suspension wire including taking down old cable of any descrip[tion complete all as specified and as directed.
50
-
-
S&F 1100 volts grade heavy duty flat cable of size 10 Sqmm 2 core, PVC insulated aluminium solid conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 m apart including replacing 4mm suspension wire including taking down old cable of any descrip[tion complete all as specified and as directed.
50
-
-
S&F 1100 volts grade heavy duty flat cable of size 16 Sqmm 2 core, PVC insulated aluminium solid conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 m apart including replacing 4mm suspension wire including taking down old cable of any descrip[tion complete all as specified and as directed.
150
-
-
S&F House service bracket (Hook type) compleate with 3.0 meter long GI pipe 40 mm dia Med grade, one Nos 90 degree bends, MS hooks and stay or guy.
2
-
-
M&L for Sub main wiring with 2 runs of 6.0 sqmm, single core, FR-LSH PVC insulated & unsheathed cable conforming to IS-694, 1100 volts with copper conductor multi stranded drawn in and including 20mm dia non metallic PVC grey conduit with all accessories such as Tees, Elbows, junction box, reducers etc as requied alongwith one run of 6.0 sqmm single core FR-LSH PVC insulated & unsheathed copper conductor as continuos earth wire dolly and connecting to existing main switch board / distribution board of each building / qtr as ordered and testing on completion including taking down old submain wiring and type of conduit complete all as specified and directed. (Note: 2 run of 6 Sqmm cable and 1 run of 6 Sqmm cable along with conduit altogether shall be measured as one unit.)
10
-
-
M&L for Sub main wiring with 2 runs of 4.0 sqmm, single core, FR-LSH PVC insulated & unsheathed cable conforming to IS-694, 1100 volts with copper conductor multi stranded drawn in and including 20mm dia non metallic PVC grey conduit with all accessories such as Tees, Elbows, junction box, reducers etc as requied alongwith one run of 4.0 sqmm single core FR-LSH PVC insulated & unsheathed copper conductor as continuos earth wire dolly and connecting to existing main switch board / distribution board of each building / qtr as ordered and testing on completion including taking down old submain wiring and type of conduit complete all as specified and directed. (Note: 2 run of 4 Sqmm cable and 1 run of 4 Sqmm cable along with conduit altogether shall be measured as one unit.)
30
-
-
M&L for Sub main wiring with 2 runs of 2.50 sqmm, single core, FR-LSH PVC insulated & unsheathed cable conforming to IS-694, 1100 volts with copper conductor multi stranded drawn in and including 20mm dia non metallic PVC grey conduit with all accessories such as Tees, Elbows, junction box, reducers etc as requied alongwith one run of 2.50 sqmm single core FR-LSH PVC insulated & unsheathed copper conductor as continuos earth wire dolly and connecting to existing main switch board / distribution board of each building / qtr as ordered and testing on completion including taking down old submain wiring and type of conduit complete all as specified and directed. (Note: 2 run of 2.5 Sqmm cable and 1 run of 2.5 Sqmm cable along with conduit altogether shall be measured as one unit.)
90
-
-