Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_669559_1Bid Award Id
ViewTender No
8798/C/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Demolition of Concrete in ground floors and pavings n exc 15 cm thickness (below or above ground level) etc complete all as specified and directed.
51.2
-
-
Demolition of brick work or stone/boulder masonry, built in cement mortar including all quions, arches, pillers etc complete all as specified and as directed.
95
-
-
Taking down cement plaster on brick or stone walls, etc. including raking out joints, hacking for key, scrubbing down with water etc complete all as specified and as directed.
350
-
-
Demolition of reinforced cement concrete of any description and in any position not otherwise specifically provided for etc complete all as specified and directed.
20
-
-
Dismantling of frame work timber scantling 40 Sq cm and over in section in any position complete all as specifed and directed.
0.5
-
-
S&F pre-painted galvalume aluminium zinc coating GI based semi corrugated steel sheet 0.50 mm thick of an colour having tensile strength of 550 Mpa as in roof covering/ cladding to wall , fixed with self tapping screws etc complete all as specified and directed.
155
-
-
M & L for PCC (1:2:4) type B0 (using 12.5mm graded stone aggregate) 25 mm thick as in sub base to receive tiles finishing cement concrete surface even and smooth without using extra cement complete all as specified and directed by Engr-in-charge..
150
-
-
M&L for dark shade Non - skid Ceramic tiles 7 to 8 mm thick area of each tile exceeding 0.18 sqm but not exceeding 0.38 sqm, in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match the shade of tiles laid over and including screed bed of 15 mm thick in CM 1:6 and pointed in white or coloured cement to match complete all as specified.
150
-
-
All as per Item No 11.00 (here-in-before) but on vertical surfaces such as skirting over screed bed of 15mm thick in CM (1:4)
5
-
-
M&L for Glazed ceramic coloured tiles in vertical surface 350x 250x 7mm/ 450X 350X 7mm thick set and jointed in neat cement slurry and pointed in white or colour cement to match the shade of tiles laid over and including screed bed of 15mm thick in CM 1:4 and pointed in white or coloured cement to match complete all as specified.
5
-
-
M&L for Second class clean sawn hardwood in scantling fixed in timber framed work etc complete all as specified and directed.
0.4
-
-
M&L for preparation of new wooden surface exc 10 cm width or girth and applying two coats of synthetic enamel paint over a coat of pink primer complete all as specified and as directed by Engineer-in-Charge..
20
-
-
M&L for brick work with sub class 'B' bricks straight or curved on plan exc 6m mean radius built in CM 1:6 complete all as specified and as directed.
87
-
-
All as per Item No16.00 (here-in-before) but in half brick thick wall built in CM 1:4 complete all as specified and directed by Engr-in-charge.
27
-
-
M&L for brickwork with sub class ‘B’ bricks in one brick thick honey comb walling, built in cement mortar cement mortar 1:3 complete all as specified and as directed.
100
-
-
M&L for Rendering 15mm thick cement plaster in CM 1:6 on brick work/concrete surfaces finished even and fair without using extra cement etc complete all as specified and directed.
102
-
-
M&L for rendering 15 mm thick cement plaster in CM 1:4 on brick work/concrete surfaces finished even and fair with WPC @ 2% by weight of cement content and without using extra cement complete all as specified and directed.
355
-
-
M&L for PCC (1:3:6) type C-1 (using 20mm graded stone aggregate) as in coping, back filling, bed plates including necessary formwork etc complete all as specified and directed.
0.2
-
-
Material and labour for PCC (1:3:6) type C2 (using 40mm graded stone aggregate) as in surface channel and like etc complete all as specified and as directed.
18
-
-
M&L for TMT steel bars 10 mm dia and above, as in reinforcement for concrete, cut to length, bent to shape required including cranking, bending, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9 mm etc complete all as specified and directed.
2500
-
-
All as per item No 23.00 (here-in-before) but above 5mm dia and over upto and including 10mm dia as in stirrups, spacers and binders.
200
-
-
M&L for two coats of OBD on new plastered surfaces of walls over a coat of chalk white primer including preparation of newly plastered surfaces complete all as specified and as directed by Engr-in-Charge.
50
-
-
M&L for two coats of Cement base paints on new plastered surfaces of walls over a coat of chalk white primer including preparation of newly plastered surfaces complete all as specified and as directed by Engr-in-Charge.
80
-
-
Extra for forming fair finished drain or channel 30 cm inner girth in cement concrete, using ex- tra cement, including forms, moulds, mitred /stopped ends etc complete all as specified and directed.
1000
-
-
M&L for 75 mm thick PCC (1:3:6) type C-2 , using 40 mm graded stone aggregate in plinth protection/aprons/path laid to slope of 1:12, finished fair and even without using extra cement with and including all necessary formwork to divide tha area in panels, finishing exposed edges fair or rounding or chamfering where directed and providing 10 mm wide joints throughout thickness of plinth protection duly filled with mastic filling (one part of hot bitumen 85/25 and three part of fine sand by weight) etc complete all as specified and directed.
70
-
-
M&L for applying one coat of OBD on old plastered surfaces of walls including preparation of old plastered surfaces complete all as specified and as directed by Engr-in-Charge.
50
-
-
M&L for applying one coat of Cement base paint on old plastered surfaces of walls including preparation of old plastered surfaces complete all as specified and as directed by Engr-in-Charge.
50
-
-
M & L for in repair 110 mm dia PVC (SWR) pipes single socketed, in any length with rubber ring joints, fixed to floor complete all as specified and directed.
50
-
-
M & L for repair for 75 mm dia PVC (SWR) pipes single socketed, in any length with rubber ring joints, fixed to floor complete all as specified and directed.
20
-
-
Demolition and breaking up drain pipes(salt glazed,stoneware, AC or reinforced concrete) set in cement 'mortar 150 mm dia fixed in position etc complete all as specified and directed.
1000
-
-
M&L for DWCPE (SN8) 150 mm (ID) diameter pipes laid in trenches complete all as specified and directed.
930
-
-
M&L for Precast factory made manhole cover/Drain covers with plain faces using RCC (1:2:4) type B-1 using 20mm grade stone agg and set in CM 1:4 including formwork etc of required sizes complete all as specified and as directed by Engineer-in-charge.
15
-
-
Excavation in trenches, not exceeding 1.5 M wide and not exceeding 1.5 M depth for foundation, etc., and getting out in any type of Soil etc complete all as specified and directed.
540
-
-
M&L for plain Cement Concrete Type D2 (1:4:8) (using 40 mm graded granite stone aggregate) in foundations, filling and mass concrete etc complete all as specified and directed.
11.4
-
-
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick with soils etc complete all as specified and directed.
120
-
-
Removing Excavated soils not exceeding 50 M and depositing where directed at a level not exceeding 1.5 M above the starting point etc complete all as specified and directed.
420
-
-
M&L for RCC (1:1.5:3) A1 (Nominal Mix) (20 mm graded stone aggregate) as in slab supported on walls, beams and columns in floors, roofs, landings, balconies, canopies, deck slabs and shrlves and the like etc complete all as specified and directed.
5
-
-
M&L for formwork to soffits of suspended slabs such as roof slabs, floor slabs, landings and similar work, not exc 200mm thick (Horizontal or sloping) for fair finished flat surfaces of concrete etc complete all as specified and directed.
42
-
-
Cutting into existing manholes for connecting new drains, making good to pipe and rendering, cutting out existing benching for and forming branch channel (1/2 round or 3/4 section) in cement concrete (1:2:4) type B-1 smooth finished, and reforming benching as required etc complete all as specified and directed.
20
-
-
M&L for loose filling with broken bricks of gauge n exc 63mm in soakage pits, soakage wells complete all as specified and directed.
30
-
-
M & L for RCC (1:11/2:3) type A1 (Nominal Mix) (using 20mm graded stone aggregate) as in columns, pillars, piers, posts and struts etc complete all as specified and directed.
5
-
-
Use and waste of formwork to sides of pillars posts, struts, piers, columns and stanchions finished the suface rough etc complete all as specified and directed.
30
-
-
Supply only water proofing compound all as specified and as directed
40
-
-
Desilting of septic tank/soakage pit of any size, type and any depth and removing the sludge/solid content from the septic tank/soakage pit by manual/ mechanical method or any other suitable means at the discretion of the contractor at his own arrangements and make the septic tank/soakage pit fully functional to the entire satisfaction of Engineer-in-Charge also to remove the sludge/solid contents out of defence land including covering with a layer of earth and repositioning of the RCC/CI cover slab all as directed by the Engineer-in-Charge in NE Zone.
190
-
-
Demolition of reed lathing single or double including battens and plaster or chicken wire lathing etc complete all as specified and directed.
40
-
-
Demolition of brick work built in cement mortar or cement lime mortar including all quoins, arches etc complete all as specified and directed.
0.5
-
-
Taking down Chowkhat or frames but exceeding 1.5 Sqm but not exceeding 4 Sqm each etc complete all as specified and directed.
2
-
-
S&F for pre-painted galvalume aluminum zinc coating GI based Plain steel sheet 0.50mm thick of any colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws etc complete all as specified and directed.
5
-
-
M&L for rolled mild steel in roof trusses (framed), trussed, purlins, crane gantries, rails and fastenings and heavy bracket framing (Beam, tee, angle, channel or flat sections) including distance pieces, cleats etc conforming to Fe 410-W (Gde-E 250) quality-A etc complete all as specified and directed.
10
-
-
S & F second class hardwood weather boarding, clean sawn, plain, 20 mm thick or feather edged 15 mm to 20mm thick and fixed with 30mm laps etc complete all as specified and directed.
30
-
-
M & L for plain fillets, square, rectangular or triangular in section clean sawn, secured with nails 2nd class hard wood exc 13 and n.exc 25 sqcm etc complete all as specified and directed.
10
-
-
Material & labour 2nd class hardwood plain, solid straight chowkhats and frames, wrought, framed rebated on the solid,rounded or chamfered, put together with glue pinned at joints, 2nd class HW etc complete all as specified and directed.
0.3
-
-
M&L for 35 mm thick 2nd class hardwood plain framed pannelled shutter (any number of panels) with panels of timber flat on both sides or of veneered particle board medium density , wood particle board with commercial face veneers , supplied and fitted to chowkats complete all as specified and directed.
4
-
-
S &F 35mm thick 2nd class hardwood glazed and skeleton shutters open rebated and prepared to receive glass gauze etc divided into squares, with plain, chamfered or rounded mitred and rebated sash bars any number edges of framing plain, chamfered or rounded, fitted with cut and metered beads for securing glass etc size of members of shutters as specified in SSR Part I Sec 8 clause 8.23 (a) etc complete all as specified and directed.
4
-
-
S & F for 4 mm thick of size 600x600mm HSPC (high pressure Steam Cured) pre-Painted self embossed, textured designer board E-Board Classic to be fixed Gl frame work for seamless ceiling comprising of Gl perimeter channnel 0.55 mm thick with two unequal flanges of 20 and 30 mm and web of 27 mm fixed to surrounding wall using nylon sleeves and screws at 450 mm centre to centre/intermediate channel 0.9 mm thick having two equal flanges of 15 mm each and web of 45 mm suspended from soffit at approx 900 mm centre to centre with Gl cleat and steel expansion fasteners with and including ceiling section (not exc 1.2 m length) of 0.55 mm thickness having kurled web of 50 mm and flange of 26 mm each with lips of 10.5 mm fixed to the intermediate channel with connecting clips across the intermediate channel at 457 mm centre to centre. fixed in ceiling flat or Sloping complete all as specified.
130
-
-
Demolition Stone slabs and tiles of any description or thickness in floors, aprons etc complete all as specified and directed.
0.4
-
-
M&L for Virified Ceramic tiles (Light shade) 10 mm thick (square/ rectangular) polished, area of each tiles exc 0.18 sqm but not exceeding 0.36 sqm, in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match the shade of tiles etc, laid over and including screed bed of 15 mm thick 1:6 and pointed in white or coloured cement to match complete all as specified.
4
-
-
All as per Item No 60.00 (here-in-before) as skirting , dado risers but over screed bed of 15 mm thick 1:4 and pointed in white or coloured cement to match complete all as specified.
1
-
-
S&F steel work in pillars trusses including special shaped washer etc. complete using ERW or induction butt welded tubes conforming to I. S 1161-1979 grade St.-240 etc complete all as specified and directed.
10
-
-
S&F anodised aluminium frame for doors, windows, ventilators with one or more rebates including joining cleat for fixing etc. complete all as specified
6
-
-
S&F for anodised aluminium window and ventilator shutters, fixed type without sash bar, aluminium section of size 40 x 18 x 1.29mm thick including necessary joining cleats, glazing clips, rubber packing, anodised aluminium snap beading, screws etc. complete all as specified.
4
-
-
M&L for sheet glass 3mm thick ordinary quality, pin headed type and glazing with oil putty or wooden beads not exceeding 0.5 Sqm in each pane etc complete all as specified and directed.
4
-
-
S&F mild steel wire cloth, 0.56mm nominal dia of wire and average width of aperture 18mm, fixed with tinned tacks or galvanized wire staples etc complete all as specified and directed.
4
-
-
S & F 100 size stainless steel butt hinges complete all as specified and directed
24
-
-
S & F 75 size stainless steel butt hinges complete all as specified and directed
6
-
-
Supply & Fixing 150 mm Aluminium handles, cast type, anodised etc complete all as specified and directed.
8
-
-
Supply & Fixing 100 mm Aluminium handles, cast type, anodised etc complete all as specified and directed.
8
-
-
S & F 150 mm Aluminium, anodised, barrel tower bolts of extruded section and fixed etc complete all as specified and directed.
8
-
-
S & F 200 mm Aluminium, anodised, barrel tower bolts of extruded section and fixed etc complete all as specified and directed.
8
-
-
S & F 300 mm Aluminium alloy, anodised, sliding door bolt with hasp, staple (bolt type) and fixing clips of sheet, cast or extruded sections and fixing bolts and sliding bolts of extruded section or cast-aluminium alloy and fixed etc complete all as specified and directed.
4
-
-
S&F mild steel 300 mm, ordinary rat tail rod pattern springs including roller and roller plate etc complete all as specified and directed.
2
-
-
M&L for rendering 15 mm thick in CM 1:4 on one side of lathing finished even and smooth without using extra cement etc complete all as specified and directed.
40
-
-
M&L for rendering 12 mm thick in CM 1:6 on other side of lathing finished even and smooth without using extra cement etc complete all as specified and directed.
40
-
-
S & F 0.71 mm dia wire netting of galvanised steel wire of size 12 mm mesh fixed with tinned tack of wire staple etc complete all as specified and directed.
40
-
-
M&L for preparation of new plastered surfaces and applying three coats of white wash on walls all as specified & directed
92
-
-
M&L for Preparation of old decorated surfaces and appplying one coat of white wash on walls, cornices etc. complete all as specified and directed.
30
-
-
M&L for preparation of old painted wood and wood based surfaces of any description not otherwise described over 10 cm width or girth and applying one coat of synthetic enamel paint in any tint all as specified and directed
40
-
-
M&L for preparation of new painted wood and wood based surfaces of any description not otherwise described over 10 cm width or girth and applying one coat of synthetic enamel paint in any tint all as specified and directed
20
-
-
M&L for preparation of new surfaces of steel and iron work of any description over 10 cm width or girth not otherwise described and applying two coat of synthetic enamel paint over a coat of redoxide on new surfaces in any tint complete all as specified.
20
-
-
Taking down carefully copper/ aluminium point wiring (light, fan, socket or power) complete, including fitting & fixtures such as switches with board, ceiling roses, pendents, bell/ buzzer, bell push, lamp holders, regulators, sockets, light fittings etc., removing material from site and making good to the disturbed surfaces of walls, ceiling, floors etc. including making good the disturbed surfaces and paint touch up to match with the existing surface complete all as specified and as directed.
20
-
-
M&L for Point wiring complete with two runs of 1.5 sqmm single core PVC insulated FR-LSH cable 1100 volts grade with multi-stranded copper conductors, drawn through and including PVC double locked Casing & caping including provision of 1.5 sqmm, FR-LSH, PVC insulated copper cable as earth continuity conductor connected to common earth dolly, including PVC rectagular box for mounting switches / sockets / regulators etc. with 3 mm thick plastic laminated sheet cover of suitable size as required at site complete all as specified and as directed.Make:- Finolex/Havells/RR Kabel Make of caping/casing & PVC boxes :- Prestoplast/Finolex/supreme
-
-
-
One light Point controlled by one way switch .
8
-
-
One Exh/Ceiling fan point controlled by one, one way switch.
4
-
-
One 3 pin socket outlet 5 Amps on the same board with other switches.
2
-
-
One 3 pin socket outlet 5 Amps on the Independent board.
2
-
-
All as per item No 84.00 (here-in-before) but with 2.5 Sq mm for 3 pin 15 Amps socket point controlled by one switch on independent board and 2.5 Sq mm copper conductor green in colour as earth continuity conductor connected to common earth dolly complete all as specified and as directed.
4
-
-
M&L for Switch piano flush type single pole, one way 5A etc complete all as specified and directed
12
-
-
M&L for Socket outlet, 2 in 1, 3 pin 5A flush type etc complete all as specified and directed
2
-
-
M&L for Switch Socket combination, 2 in 1, 5 pin 5A flush type etc complete all as specified and directed
2
-
-
M&L Switch socket combination 2 in 1, 5A/16A, 5 in 1 flush type etc complete all as specified and directed
4
-
-
M&L for ceiling rose 3 terminal PVC/Polycarbonate isolated body complete all as specified and directed.
12
-
-
M&L for stepped type electronic fan regulator 100 Watt socket size flush type on the existing phenolic laminated sheet etc.
2
-
-
S&F for , IP= 20, Class-I, LED Light fitting 1 x 20 watt (4 Ft), 240 V, PF-0.9, CRI = 80, CT= 6000 K, Wall/ Surface mounted, intergrated type with all accessories internally prewired and incl connecting up with and incl twin/ three core twisted flexible copper conductor cable of suitable size in and incl flexible hose from ceiling rose to fitting complete all as specified and as directed.
6
-
-
Supply , fixing and testing of LED Bldg Security light fitting of capacity 25 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete including 1.2 mtr GI bracket of 25mm bore light grade bent to shape and fixed on wall with metal fastners 2 Nos 10mm dia incl drilling of holes as reqd and connecting up with flexible copper cable of size 0.75 sqmm 3 core from ceiling rose complete all as specified and directed by Engr-in-Charge.
2
-
-
M&L for MCB Distribution board double door type SPN 8 way, sheet steel, powder painted, with neutral link & earth bar etc. and fixing MCBs of various rating capacity including taking down old unsv MCB DBs complete all as specified and as directed.
1
-
-
M&L for MCB SPN 40 Amps 'C' series, 230 volts, 50 Hz suitable for fixing in MCB DB incl taking down old unsv MCB complete all as specified and as directed
1
-
-
M&L for MCB SP 6-32 Amps 'C' series, 230 volts, 50 Hz suitable for fixing in MCB DB incl taking down old unsv MCB complete all as specified and as directed.
4
-
-
Supply and fixing ceiling fans complete with blades, down rods, electronic regulator and accessories, 230 V, 1200 mm sweep. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) complete all as specified and as directed.
2
-
-
Supply and fix exhaust fan made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200, Copper winding of sweep 250 mm all as specified and as directed.
2
-
-
M&L for laying of LT UG cable, XLPE insulated, galvanised steel strip or wire armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area of 16 sq mm, 2 core complete all as specified and as directed. NOTE :- (i) Excavation and earth work, sand cushioning, cable protection cover, pipe etc. shall be measured and paid seperately under relevant items.
40
-
-
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m depth and getting out in soft/ loose soil complete all as specified ans as directed.
5.06
-
-
Returning filling in trenches including spreading leveling watering and well ramming in layers not exceeding 25 cm thick all complete all as specified ans as directed.
2.56
-
-
Removing of excavated material not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point all complete all as specified ans as directed.
2.5
-
-
M&L for spread fine river sand in trenches complete all as specified ans as directed. NOTE: For measurement purpose, punned down thickness shall only be taken etc complete all as specified and directed
2.03
-
-
M&L for laying brick sub class 'B' old size burnt bricks for cable protection of size 230mmx115mmx75mm complete all as specified and as directed
217.39
-
-
Supply & laying tubes ' light grade' galvanised, with all fittings, fixed complete to walls, poles, ceilings or laid in floors/ trenches/ road crossing for protection of cables of size 40 mm dia bore complete all as specified and as directed.
6
-
-
Materials and labour for earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connetced with galvanised iron wire 4mm as earthing lead by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe of required size (light grade) and other end connected to earthing test point or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (light grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion all as specified and as directed.
Note: Contractor should submit earth test report to GE