Military Engineer Services Tender
View complete overview of Nagaland MES Tender
Costs
EMD
₹ 77,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_639309_1Bid Award Id
ViewTender No
8587/C/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
REPAIR MAINT OF LT OH LINES DISTR LINES LT POLES ACSR LT PANEL BOARDS AND CONNECTED ACCESSORIES AT RMS AND DIMAPUR
BOQ Items
Removing excavated material n.exc 50 m and depositing where directed at a level n exc 1.5 m above the starting point etc complete all as specified and directed by Engr-in-Charge.
206.39
-
-
M&L for spreading fine river sand in trenches complete all as specified and as directed by Engr-in-Charge. Note: For measurement purpose, punned down thickness shall only be taken.
153.9
-
-
M&L for laying sub class 'B', old size burnt bricks for cable protection, of size 230mmx115mmx75mm complete all as specified and directed by Engr-in-Charge.
16521
-
-
Dismantling steel poles/struts, any size etc complete all as specified and directed by Engr-in-Charge.
10
-
-
Dismantling cross -arms of MS channel or angle sections etc complete all as specified and directed by Engr-in-Charge.
2
-
-
Dismantling insulators any type, any size etc complete all as specified and directed by Engr-in-Charge.
75
-
-
Dismantling stay assembly complete (demolition of concrete, etc. and excavation measured separately), etc complete all as specified and directed by Engr-in-Charge.
6
-
-
Taking down carefully aluminium conductor of any size from LT OH Lines after unbinding from insulators for replacement of multijointed / undersize conductors or loose conductor etc complete all as specified and directed by Engr-in-Charge.
6.5
-
-
Supply, laying & testing XLPE insulated screened PVC bedded galvanised steel strip or wire armoured, electric power cable (Heavy duty) with stranded aluminium conductor 1100 volts grade of size 10 Sqmm, 2 core incl taking out old unsv cable in trenches etc complete all as specified and directed by Engr-in-Charge.
750
-
-
All as per Srl item No 12 (here-in-before) but 16 Sqmm 2 core
300
-
-
All as per Srl item No 12 (here-in-before) but 16 Sqmm 4 core
200
-
-
All as per Srl item No 12 (here-in-before) but 25 Sqmm 4 core
250
-
-
All as per Srl item No 12 (here-in-before) but 35 Sqmm 3.5 core
410
-
-
All as per Srl item No 12 (here-in-before) but 50 Sqmm 3.5 core
250
-
-
All as per Srl item No 12 (here-in-before) but 70 Sqmm 3.5 core
150
-
-
All as per Srl item No 12 (here-in-before) but 95 Sqmm 3.5 core
210
-
-
All as per Srl item No 12 (here-in-before) but 120 Sqmm 3.5 core
200
-
-
All as per Srl item No 12 (here-in-before) but 185 Sqmm 3.5 core
100
-
-
All as per Srl item No 12 (here-in-before) but 240 Sqmm 3.5 core
100
-
-
M & L for galvanised steel tubing 40 mm bore light grade laid in trenches, road crossings pole/wall etc. for cable protection including providing MS flat iron 50mm x 6mm clamps (02 Nos) complete all as specified and directed including taking down the existing UNSV steel tubing etc complete all as specified and directed by Engr-in-Charge.
48
-
-
All as per Ser item No 23 (here-in-before) but 50mm dia.
30
-
-
All as per Ser item No 23 (here-in-before) but 80mm dia.
24
-
-
All as per Ser item No 23 (here-in-before) but 100mm dia.
6
-
-
M&L for steel tubular swaged pole 9 mtr long with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP 31, including painting with anti corrosive paint internally complete and externally up to planting depth, alternative Black & white strips with synthetic enamal paint, of 30 cm width upto 1.5 mtr above ground level all as required at site or directed by Engr-in-charge.
10
-
-
M&L for cross arms, bracings, supports, clamps and back plates fabricated from steel section including nuts, bolts, washers, welding bending cold or hot drilling holes for bolts in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminium paint etc complete all as specified and directed by Engr-in-Charge.
2
-
-
S&F in replacement of existing unserviceable anti climbing device spikes type fabricated out of MS bars (round ,spuare or flat ) including nuts, bolts washers and welding into two halves made to shape to suite the cross section of the pole including one coat of primer, one under coat and one finishing coat of aluminium paint including preparation of suraface etc complete all as specified and directed by Engr-in-Charge.
0.8
-
-
M&L for Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 100mm height, 65mm dia for 1100 volts grade etc complete all as specified and directed by Engr-in-Charge.
30
-
-
M&L for shackle type insulators of 100mm high, 115mm dia porcelain, vitreous, white, brown or green insulators for working pressure 1100 volts including mild steel straps of size 31x5mm including 14mm dia bolts etc complete all as specified and directed by Engr-in-Charge.
35
-
-
M&L for stay assembly using GI stay rod 20mm dia complete with stay plate mild steel of size 300x300x6.00mm thick, stay bow, complete all as specified and shown in Electrical Plate No 1 . (Necessary excavation and PCC and one set of stay clamps at top of pole & loop insulator of size 90x140mm porcelain, vitreous, white, brown or green shall be measured and paid seperately)
6
-
-
S&F Galvanised stay wire of size 7/4mm complete all as specified and directed by Engr-in-Charge.
0.6
-
-
S&F loop type insulator porcelain vitirious of size 90 x 140 mm clearence of hole 25.5mm complete all as specified and directed by Engr-in-Charge.
6
-
-
M&L for ACSR of any size drawn straight horizontal on over head lines on poles including binding wire, binding with insulators, jointing jumpers etc including connections of incoming and out going cables complete all as specified and directed.
3.75
-
-
Restringing/restretching aluminium conductor or GI wire on existing over head lines including necessary binding with binding wire with insulators, connections of incoming and out going cables, binding with spacers where required, complete all as specified. (Note i. Replacement of conductor shall be measured and paid separately under respective item of BOQ. Total No of conductor in over head line to be taken down shall comprise of a minimum of one phase, one neutral and one continuous earth wire and for measurement length of each conductor shall be taken seperately etc complete all as specified and directed by Engr-in-Charge.
7
-
-
M&L for GI wire of 4mm dia galvanised iron wire drawn straight horizontal as continuous earth wire on poles/cradles inlc connections of incoming and out going cables complete all as specified and directed by Engr-in-Charge.
1.3
-
-
Trimming up of tree branches upto 3 mtr all around LT overhead lines, removing cut branches from site as directed, Note :- (i) The overhead lines will be kept clear from all trees by trimming of tree branches with 3 mtr all around the line. Necessary permission will be obtained from department by the contractor one week prior to trimming in particular area and shut down of that area will be arranged by department. (ii) Total length of line from supply point to load end will be measured for the purpose of payment, irrespective of the No of trees required to be trimed. (iii) Fortnightly inspection of lines will be made jointly by contractor or his authorised rep and rep of Engr-in-Charge and out come whether lines are free from tree branches or not & shall be kept on record. No payment will be made for whole length if even a single tree is within the reach of OH line. (iv) The OH line will be maintained for whole period of contract and the payment will be made with final bill only. The payment for the period for which line is not maintained will be deducted proportionately based on fortnightly inspection carried out as detailed above. (vii) Quoted rates are deemed to include necessary T&P. One span comprises of distance between one pole to another including all trees in its vicinity including switch off/on, electric cable connection or disconnection etc complete all as specified and directed by Engr-in-Charge.
21
-
-
M&L for replacement of unserviceable MCCB 160 Amp current carrying capacity 36 KA , AC 415 Volts, four pole including terminals, with microprocessor release setting complete including dismentling the existing with all connections & fixing the new with all connections all as directed by Engg-in-charge.
3
-
-
M&L for replacement of unserviceable MCCB 4 Pole including terminals, 415 V, adjustable type 200 Amps with breaking capacity 36 KA complete all as specified and directed. including dismentling the existing with all connections & fixing the new with all connections all as directed by Engg-in-charge.
3
-
-
M&L for replacement of unserviceable MCCB 160 Amp current carrying capacity 36 KA including terminals, AC 415 Volts three pole including terminals, with microprocessor release setting complete including dismentling the existing with all connections & fixing the new with all connections all as directed by Engg-in-charge.
2
-
-
M&L for replacement of unserviceable MCCB 250 Amp current carrying capacity 36 KA , AC 415 Volts, three pole including terminals, with microprocessor release setting complete including dismentling the existing with all connections & fixing the new with all connections all as directed by Engg-in-charge.
1
-
-
M&L for replacement of unserviceable MCCB 3 Pole , 415 V, adjustable type 250 Amp with breaking capacity 36 KA including terminals, complete including dismentling the existing with all connections & fixing the new with all connections all as directed by Engg-in-charge.
2
-
-
M&L for replacement of unserviceable MCCB 4 Pole , 415 V, fixed type 125 Amp with breaking capacity 16 KA including terminals, complete including dismentling the existing with all connections & fixing the new with all connections all as directed by Engg-in-charge.
2
-
-
M&L for replacement of unserviceable MCCB 4 Pole , 415 V, fixed type 25 to 100 Amp with breaking capacity 16 KA including terminals, complete including dismentling the existing with all connections & fixing the new with all connections all as directed by Engg-in-charge.
3
-
-
Supply and laying or fixing or passing through pipe, 1100 volts grade heavy duty cable with PVC insulated aluminium stranded conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed 10 sqmm, 2 core all as specified and as directed.
300
-
-
Supply and laying or fixing or passing through pipe, 1100 volts grade heavy duty cable with PVC insulated aluminium stranded conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed 16 sqmm, 2 core all as specified and as directed.
300
-
-
M&L for replacement of heat shrinkable end termination cable jointing kit for PVC/XLPE insulated ,armoured electric cable of size upto 16 sqmm, 4 core 1100 Volts garde for indoor/outdoor use complete with jointing materials and accessories.
13
-
-
M&L for replacement of heat shrinkable end termination cable jointing kit for PVC/XLPE insulated ,armoured electric cable of size 25 to 50 Sqmm, 3.5 core 1100 Volts garde for indoor/outdoor use complete with jointing materials and accessories.
13
-
-
All as per Ser item No 49 (here-in-before) but electric cable of size 70 sqmm to 150 Sqmm, 3.5 core
7
-
-
All as per Ser item No 49 (here-in-before) but electric cable of size 185 sqmm to 300 Sqmm, 3.5 core
3
-
-
All as per Ser item No 49 (here-in-before) but electric cable of size 400 sqmm to 630 Sqmm, 3.5 core
3
-
-
M& L for replacement of cable lugs with aluminium alloy tubular bimetallic terminals suitable for cable of size 10 Sqmm incl crimping with help of crimping tools all as specified and directed . Make :- Dowells/Jainsons or equivalent as approved by GE
70
-
-
All as per Ser item No 53 (here-in-before) but size of cable 16Sqmm
60
-
-
All as per Ser item No 53 (here-in-before) but size of cable 25sqmm
50
-
-
All as per Ser item No 53 (here-in-before) but size of cable 35Sqmm
40
-
-
All as per Ser item No 53 (here-in-before) but size of cable 50 Sqmm
30
-
-
All as per Ser item No 53 (here-in-before) but size of cable 70 Sqmm
35
-
-
All as per Ser item No 53 (here-in-before) but size of cable 95 Sqmm
26
-
-
All as per Ser item No 53 (here-in-before) but size of cable 120 Sqmm
25
-
-
All as per Ser item No 53 (here-in-before) but size of cable 185 sqmm
10
-
-
All as per Ser item No 53 (here-in-before) but size of cable 240 Sqmm
15
-
-
All as per Ser item No 53 (here-in-before) but size of cable 300 Sqmm
6
-
-
All as per Ser item No 53 (here-in-before) but size of cable 400 sqmm
4
-
-
All as per Ser item No 53 (here-in-before) but size of cable 630 sqmm
4
-
-
M&L for 40 mm graded course stone aggregate without any vegitation or chemical including levelling /spreading surrounding the pole structures, LT panels all as specified directed . Note :-( Quoted rate is deemed to include for bricks reqd for rataining the aggregare)
2
-
-
M&L for aluminium strip of any size cut to length as required at site including drilling holes, bend to shape for repairing of LT panels all as required or directed by Engr-in-Charge.
6
-
-
M&L for Copper strip of any size cut to length as required at site including drilling holes, bend to shape for repairing of LT panels all as required or directed by Engr-in-Charge.
6
-
-
M&L for Galvanisied MS nut, bolts & washers all as specified and directed by Engr-in-Charge.
5
-
-
M&L for Brass nut, bolts & washers all as specified and directed by Engr-in-Charge.
4
-
-
M&L for 20 mm graded coarse stone aggregate around indoor/outdoor substation/ 2 pole/4 pole structure boundry complete all as specified and directed by Engr-in-Charge
2
-
-
M&L for cement concrete (1:5:10) type E2 (using 40mm graded stone aggregate) as in sub base including form work etc complete all as specified and directed by Engr-in-Charge.
2
-
-
M&L for cement concrete (1:4:8) type D2 ( using 40mm graded stone aggregate) as foundation of pole / stay including form work etc.
9.05
-
-
M&L for cement concrete (1:3:6) type C1 (using 20mm graded stone aggregate ) as in coping of poles studs including form work etc complete all as specified and directed by Engr-in-Charge.
2.36
-
-
Cutting bushes, levelling the area around E/M installations, sub stations, pole structures etc including surface excavation not exceeding 30 cm deep and avearaging 15cm deep and geeting out roots etc and throw away not less than 50 mtrs from the site and making good complete all as specified and directed by Engr-in-Charge.
80
-
-
M&L for scraping of old paint from the steel tublar poles 9 mtr high without removing accessories and preparation of surfaces for repainting. Repainting the pole with one coat of alternate black and white strips of 30 cm wide upto height of 1.5 mtr using synthetic paint enamel. Marking the pole number with black synthetic enamel paint. Repainting the remaining surface of poles and also painting iron parts of steel cross arms i.e 'U' clamps etc above 1.5 Mtr height by applying two coats of aluminium paint all as required at site complete all as specified and directed by Engr-in-Charge.
734
-
-
Supply, install, test and commission out door type bus bar chamber having tapered roof outer shell made out of 3.15 mm thick MS sheet and inner shell made out of 2 mm thick MS sheet and MS angle section 50x50x6 mm mounted on PCC (1:2:4) type B-1 using 20mm graded stone aggregate as in platform, 90 cm above and 45 cm below the ground level, frame factory fabricated with front openable door system , 04 Nos Al bus bar 400 amps cap fixed over epoxy insulators duly insulated with different sleeves and neccessary holes of suitable dia in Bus bar strip with locking arrangements “U” type gasket shall be used to make the outer shell completely vermin proof suitable for 3 phase, 4 wire, 415 Volt, 50 Hz, tested at factory approved from CPRI having thickness of powder coat not less than 100 microns provided with suitable gasket to make it dust/vermin proof including taking out old unserviceable bus bar boxes complete all as specified and directed by Engr-in-Charge.
2
-
-
M&L for scraping of old paint from the steel tubular poles 11 mtr height with out removing accessories and preparation of surfaces for repainting. Repainting the pole with one coat of alternative green and white strips of 30 cm wide upto 1.5 mtr height using synthetic enamell paint . Marking the pole Number inside a circular ring with black enamell paint. The numbers/letters should be symetrically same in size as directed by Engr in-Charge on each and every pole and visible from appropriate distance. Repainting the remaining poles and iron parts i.e U clamps, chanels etc above 1.5 mtr height by applying two coats of aluminium paint all as required at site or directed.
2
-
-
Supply and fixing LED street light fitting 60 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, with suitable size bracket incl nuts, bolts, washers etc corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete. including taking down old unsv light fittings all as per specified and as directed.
15
-
-
S & F PVC street light junction boxes of size 380mmx225mmx140mm with front openable shutter and locking arrangement with one 6 Amp MCB, connectors including fixing to pole with MS flat iron clamp of size 25mm x 3mm size with nuts and bolts washers, etc. complete including taking down unserviceable one all as specified and directed. Make : Sintex/Havells/Bajaj
5
-
-
M&L for painting of LT panel outdoor/indoor by removing existing old paint with the help of sand/emery paper etc. Preparing surfaces including cleaning etc and applying one coat of synthetic enamel paint, including cleaning and surface dressing upto 15cm depth all around the panel upto 1 mtr complete all as specified and directed by Engr-in-charge.
3
-
-
M & L for repair/maint of LT panel board by dismantling all cable connection i.e incoming and outgoings and trenching out cable / cable loop after digging, cutting burnt portion of cable, cleaning and fixing of lugs with crimping tool, cleaning of bus bar with emery paper, tightening of bus bar with busbar insulators, re-fixing of cable with busbars/circuit breaker, by providing new bolts, nuts and washers cable lugs to be provided for all incoming and outgoing cables all as specified and as directed.
7
-
-
S&F in replacement of existing unserviceable Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20x15cm size complete all as specified and directed.
43
-
-
S&F new spacer 2 way PVC flat/clamp/twisted type LT with nuts, bolts of suitable size for fixing with existing conductor complete including taking down old UNSV spacer etc complete all as specified and directed by Engr-in-Charge.
16
-
-
All as per Ser item No 84 (here-in-before) but 3 way
18
-
-
All as per Ser item No 84 (here-in-before) but 4 way
14
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements