Military Engineer Services Tender
View complete overview of Meghalaya MES Tender
Military Engineer Services - MES Tender
Civil And Construction
Eprocure
Opening Date13 Feb 2024
Closing DateCancelled
Tender Amount₹ 7,44,00,000
Costs
EMD
₹ 6,97,000Document Cost
₹ 3,000Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_642092_1Tender No
88984/SHL/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
SCHEDULE "A" PART-III (INTERNAL ELECTRIFICATION) Details of pre-priced Schedule is given in tender documents.
1
-
1919620.94
SCHEDULE "A" PART-IV (INTERNAL WATER SUPPLY)
Details of pre-priced Schedule is given in tender documents.
1
-
181174.65
SCHEDULE "A" PART-V (ROAD/ PATH/CULVERT)
Details of pre-priced Schedule is given in tender documents.
1
-
1416612.28
SCHEDULE "A" PART-VI (AREA DRAINAGE)
Details of pre-priced Schedule is given in tender documents.
1
-
305716.52
SCHEDULE "A" PART-VII (SEWAGE DISPOSAL)
Details of pre-priced Schedule is given in tender documents.
1
-
434650.44
SCHEDULE "A" PART-VIII (EXTERNAL WATER SUPPLY)
Details of pre-priced Schedule is given in tender documents
1
-
86759.64
SCHEDULE "A" PART-IX (EXTERNAL ELECTRIFICATION)
Details of pre-priced Schedule is given in tender documents
1
-
598203.35
SCHEDULE "A" PART-X (RETAINING WALL)
Details of pre-priced Schedule is given in tender documents
1
-
3606568.76
SCHEDULE "A" PART -XI (MISCELLANEOUS ITEMS) Note:- This schedule is not pre-priced by MES and the pre-priced rate indicated as "Rs 0.00" under Col.' F ' signifies this fact only.
-
-
-
S & F modular metal flush box with modular white cover plate with frame, 8 module complete all as specified and directed .
42
-
-
S & F modular metal flush box with modular white cover plate with frame, 6 module complete all as specified and directed .
28
-
-
S & F modular metal flush box with modular white cover plate with frame, 3 module complete all as specified and directed .
280
-
-
S & F modular metal flush box with modular white cover plate with frame, 1 module complete all as specified and directed .
22
-
-
S & F LED lamp 10 watt fixed to holder complete all as specified and directed.
112
-
-
S & F LED lights fitting, 4 feet, 1x 20W, 220V, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed.
242
-
-
S & F LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed.
42
-
-
S & F LED security light fitting of capacity 35 watt with integral reflector made of aluminium alloy LM6 with LED driver, lamp, surge protector and all accessories pre wired including connection with three core PVC insulated, sheathed copper conductor cable of suitable size complete with GI bracket 1.5 meter long bend to shape of dia 40mm GI medium grade pipe with MS clamp /nut & bolts/washers etc complete all as specified and directed.
27
-
-
S & F LED lights fitting, 1x 9W/10W, bulkhead luminaires, 220V, AC LED light with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed.
28
-
-
S & F LED wall bracket decorative light fittings,1x 9W/10W, polycarbonate body including LED light with driver, holder and LED Bulb of B22 base and connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed.
56
-
-
S&F Energy efficient five star rated ceiling fan 230 volts, single phase AC, 1200 mm sweep, BEE 5 star rated, Brushless Direct Current(BLDC) without remote type with accessories like holding down rod,hanging clamps, blades, fan hook including writing MES number (as per standard practice) including provision of three core flexible copper wire of suitable size from ceiling rose to ceiling fan complete in all respect all as specified and directed.
70
-
-
S&F exhaust fan metallic steel body, single phase, 230 volts, 50 Hzs of size 300mm sweep, 900/950 RPM, heavy duty type with suitable metallic louver, blades, frame and flexible three core copper conductor cable of suitable size for connecting with ceiling rose complete including making of hole in wall and making good to the disturbed surface complete all as specified and as directed.
70
-
-
S&F concealed distribution box, double door, vertical type, TPN, 415V, 6 way, IP 43 suitable for MCCB of 100/125 Amps, 4P, 16 kA as incomer and MCB SP/TP as out going complete with suitable bus bar, neutral link, earth link complete all as specified and directed.
Note : (i) MCCB/MCBs shall be measured and paid separately
(ii) Blank space shall be covered with blank plates and cost for the same shall be deemed to be included in the quoted rate.
3
-
-
S&F concealed distribution box, double door, TPN, 415V, 4 way, IP 43 suitable for MCB/RCBO of 63 Amps, 4P, as incomer and MCB SP/TP as out going complete with suitable bus bar, neutral link, earth link complete all as specified and directed.
Note : (i) MCCB/MCBs shall be measured and paid separately
(ii) Blank space shall be covered with blank plates and cost for the same shall be deemed to be included in the quoted rate.
16
-
-
S&F MCB TP 40-63Amps (C-Curve), breaking capacity 10 kA, 415 volts complete all as specified and directed.
14
-
-
S&F MCB TPN 63 Amps (C-Curve), breaking capacity 10 kA, 415 volts complete all as specified and directed.
2
-
-
S&F MCB SPN 32 Amps (C-Curve), breaking capacity 10 kA, 240 volts with cable connection and copper lugsing complete all as specified and directed.
30
-
-
S&F MCB SP 6 to 32 Amps (C-Curve), breaking capacity 10 kA, 240 volts with cable connection and copper luging complete all as specified and directed.
347
-
-
M&L for earthing complete with galvanized steel earth plate electrode 600 mm X 600 mm X 6 mm thick buried directly in ground (earth pit not less than 2.25 Mtr deep below normal ground level with top edge of plate not less than 1.5 Mtr below normal ground level connected to galvanised earth lead wire 4.0 mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No-3 SSR Part -1 2009 connected to earthing test point including earth wire protection pipe of dia 15 mm (light grade), excavation and earth work, disposal of surplus spoil, provn of RCC cover 50 mm thick, reinforced with 8mm dia TMT bars @100 mm /C/C both ways with one handle for lifting made out of 10 mm dia TMT bar embedded in precast RCC (1:2:4) type B1, cover slab of size 54 cm x 54 cm x 5 cm and PCC (1:3:6) type C-1 concrete pit, funnel with watering pipe 20 mm bore (medium grade) testing on completion complete all as specified and directed. [Note : (a) The unit rate includes for protection pipe and earth lead upto 7.5 m. Any variation in length of earth lead and protection pipe beyond 7.5 m shall be measured and paid seperately.
(b) PCC pit (with pit cover) shall be provided at least 500mm away and not on the earth pit itself and cost of additional height of watering pipe, bends, elbow etc shall deemed to be included in the unit rate. (c) Excavation/earthwork is deemed to be included in the quoted rate.]
15
-
-
S & F Smart RF/Cellelur/Hybrid (RF + Celluler) Three phase AC Meter Temper Proof, static meter of class 1.00, 415 V, 50 Hz, 10A-60A as per bearing IS No IS -16444 and relevant IEC standards with inbuilt Radio Frequency communication facility with self healing mesh network with default and no demand display, billing data generation facility, anti-temper features, Microprocessor and LED/LCD based circuitary including SMC meter box of minimum size 250 x 250 x 155mm or as suitable for 3 phase meter with viewing glass, concealed hinge and earth bolt plugged complete all as specified and as directed. Meter shall support sending the following data :- (i) 15/30 min instantaneous data for volgtage, current, power, cumulative energy and frequency, monthly billing survey for cumulative energy and max demand to software meter shall have connected/disconnected functionally operateable from mdm/billing software and prepaid features shall be MDM/Billing end as per previous IS.
14
-
-
Construction of RCC septic tank designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below in foundation, RCC M-30 Design Mix in walls, base slab, Baffle walls and roof slab including beams etc with vent shaft, manhole opening with cover connection etc, complete with effective depth of 1.5 meter and overall depth of 3 meter for 100 users complete all as specified and directed by Engineer -in-Charge.
Note:- The cost of basement shall be deemded to be inclusive in quoted rate.
1
-
-
Construction of RCC septic tank designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below in foundation, RCC M-30 Design Mix in walls, base slab, Baffle walls and roof slab including beams etc with vent shaft, manhole opening with cover connection etc, complete with effective depth of 1.5 meter and overall depth of 3 meter for 50 users complete all as specified and directed by Engineer -in-Charge.
Note:- The cost of basement shall be deemded to be inclusive in quoted rate.
1
-
-
M & L Soakage wells for 50 Users, excavation, in any type of soil, foundation in PCC 1:3:6, walls of honey combed masonry with top ring of M25 concrete including intercepting chamber and screen chamber made of Brick masonary in CM, RCC cover slab in M25/ SFRC cover, interconnecting pipes of RCC/DWC complete filled with brick bats complete all as specified and as directed.
1
-
-
M & L Soakage wells for 100 users, excavation, in any type of soil, foundation in PCC 1:3:6, walls of honey combed masonry with top ring of M25 concrete including intercepting chamber and screen chamber made of Brick masonary in CM, RCC cover slab in M25/ SFRC cover, interconnecting pipes of RCC/DWC complete filled with brick bats complete all as specified and as directed.
1
-
-
Supply only MS galvanised mesh of size 50 x 50mm, 3mm dia wire for fixing all around for weap holes, for holding aggregates complete all as specified and as directed.
30
-
-
M&L for preparation of new finished wall/roof surfaces of any description over 10cm girth or width, not otherwise described and apply two coats of exterior acrylic (anti fungal) paint (Camouflage pattern) over a coat of primer complete all as specified and as directed.
300
-
-
Supply, Installation, Testing and Commissioning of Fedder Piller outdoor type of size 1000x900x450mm, totally enclosed, cubical type, front openable, single door, made out of 3.15 mm thick CRCA sheet on MS angle 50x50x6mm frame welded to the bottom, powder coated finished over a coat of red oxide primer, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, and to accommodate following components. The Busbar Chamber shall be dust and vermin proof, IP 65 class protection with aprons for cable entry, with locking arrangement including provision of 65mm Godrej (Freedom) lock with 2 keys internal wiring with PVC insulated, multistranded copper conductor, FRLS cables, IS-694 marked of adequate size but not less than 4 sqmm. The scope of work includes the following:-
(a) Copper bus bar of rating 200 Amps for four pole including PVC heat shrink sleeves (RYB & N ) : 01 Set
(b) Incoming: MCCB four pole 125 Amp confirming to IEC 60947-2 & IS – 13947-3 thermal magnetic release and adjustable over load setting 0.8 – 1.0 x In and adjustable short circuit setting 6 – 10 x In and rupturing capacity 36 KA at 415 V AC , 50 Hz complete - 01 No. (c.) Outgoing: MCCB Three pole 100 Amps confirming to IEC 60947-2 & IS – 13947-3 Fixed magnetic release, adjustable thermal realese and adjustable over load setting 0.8 – 1.0 x In and adjustable short circuit setting 6 – 10 x In and rupturing capacity 25 KA at 415 V AC , 50 Hz complete - 02 Nos (d) Multifunction meter for V,A,F, PF,KW.KVA reading with accuracy class 1.0 - 01 No, including 1 set of phase indication lamps ( R, Y , B ) - 1 set
1
-
-
Item No 11.27 Contd......
NOTE : (i) Design / drawing of the Panel Board showing the dimensions shall be obtained from Manufacturer / Supplier & shall be got approved from the Dept before placing final order to the manufacturer.
(ii) Anything missed out in the technical specifications but technically required for efficient working is deemed to be included in the quoted rates.
-
-
-
Supply, Installation, Testing and Commissioning of Fedder Piller outdoor type of size 1000x900x450mm, totally enclosed, cubical type, front openable, single door, made out of 3.15 mm thick CRCA sheet on MS angle 50x50x6mm frame welded to the bottom, powder coated finished over a coat of red oxide primer, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, and to accommodate following components. The Busbar Chamber shall be dust and vermin proof, IP 65 class protection with aprons for cable entry, with locking arrangement including provision of 65mm Godrej (Freedom) lock with 2 keys internal wiring with PVC insulated, multistranded copper conductor, FRLS cables, IS-694 marked of adequate size but not less than 4 sqmm. The scope of work includes the following:-
(a) Copper bus bar of rating 200 Amps for four pole including PVC heat shrink sleeves (RYB & N ) : 01 Set
(b) Incoming: MCCB four pole 100 Amp confirming to IEC 60947-2 & IS – 13947-3 thermal magnetic release and adjustable over load setting 0.8 – 1.0 x In and adjustable short circuit setting 6 – 10 x In and rupturing capacity 36 kA at 415 V AC , 50 Hz complete - 01 No. (c.) Outgoing: MCCB Three pole 63 Amps confirming to IEC 60947-2 & IS – 13947-3 Fixed magnetic release, adjustable thermal realese and adjustable over load setting 0.8 – 1.0 x In and adjustable short circuit setting 6 – 10 x In and rupturing capacity 25 KA at 415 V AC , 50 Hz complete - 02 Nos (d) Multifunction meter for V,A,F, PF,KW.KVA reading with accuracy class 1.0 - 01 No, including 1 set of phase indication lamps ( R, Y , B ) - 1 set
1
-
-
Item No 11.29 Contd......
NOTE : (i) Design / drawing of the Panel Board showing the dimensions shall be obtained from Manufacturer / Supplier & shall be got approved from the Dept before placing final order to the manufacturer.
(ii) Anything missed out in the technical specifications but technically required for efficient working is deemed to be included in the quoted rates.
-
-
-
Supply and Laying sub class "B" bricks laid in trenches for protection of UG cable with width equal to length of bricks, laid dry & flat complete all as specified and as directed.
6.1
-
-
S & F cable jointing kit for 1.1 KV grade cable for end termination joint complete with Jointing material, heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Aluminium conductor cable of size 25 to 50 sqmm, Indoor/Outdoor type, complete all as directed and as specified
6
-
-
S & F cable jointing kit for 1.1 KV grade cable for end termination joint complete with Jointing material, heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Aluminium conductor cable of size 70 to 120 sqmm, Indoor/Outdoor type, complete all as directed and as specified
4
-
-
Supply and Laying PVC Insulated and sheathed three core Heavy duty cables 1100 volts each core having multi stranded aluminium conductor service cable size 4 sqmm complete all as directed and as specified
80
-
-
S & F bracket for street light fittings, mounting bracket fabricated out of GI tubing 40 mm bore light grade not less than 1.2m long made to shape including 2 Nos flat iron clamp 50x6mm tightened with nuts, bolts & washers of suitable size mounted on pole/wall including two coats of synthetic enamel paint over a coat of primer complete all as specified and directed.
8
-
-
S & F junction box made out of polycarbonate sheet, side hinged door and with locking arrangement including 01 x MCB SP 6 Amps mounted on DIN rail and 4 way connectors and fixed to pole with 2 Nos MS flat iron 25x3mm clamps with nuts and bolts complete all as directed and as specified
8
-
-
S & F LED street light fitting 70 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as directed and as specified
8
-
-
S & F sheet metal enclousures for VTPN DBs ,vertical type, 100/63 Amps MCCB as incomer MCB 415 volts, 4 way earth & neutral link, TPN double door, IP-54 complete all as specified and directed.
3
-
-
S & F MCCB four pole 63 Amp as per IEC60947-2 & IS-13947 thermal magnetic release and adjustable over load setting 0.8-1.0 x In and adjustable short circuit setting 6-10 x In and rapturing capacity 16kA, 415 V,AC, 50 Hz., complete all as directed and as specified
3
-
-
S & F MCB SP 5 to 32 Amps, 240 volts, B-curve, rupturing capacity 10kA conforming to IEC-60898, Part-I complete all as directed and as specified
36
-
-
M & L Earthing complete with Galvanized steel earth plate electrode 600 mm x 600mm x 6mm thick burried directly in ground vertically to a depth not less than 2.25 m below ground level with the top edge of earth plate at depth not less than 1.5 m below ground level connected with galvanised earth strip of size 32 x 6 mm by means of bolts, nuts, check nuts and washers protected by 40mm bore medium grade GI pipe, funnel with 20mm bore GI medium grade pipe for watering, wire mesh, including concrete pit in PCC (1:3:6) type C-1, with 50 mm thick Pre-cast R.C.C. (1:2:4) type B-I cover slab (reinforced with 8 mm dia deformed bar @ 15 cm C/C both ways and suitable handle of 10 mm dia round bar), including providing charcoal or coke and common salt in alternate layers of 15 cm compacted thickness all around the earth electrode, with funnel, wire mesh, aluminium lugs, complete in all respect and other end connected with main switch board or Earthing test point as directed, including necessary earth work and disposal of spoil to a distance not exceeding 50 metre and necessary testing on completion inclduing taking down old one complete all as specified and as directed by the Engineer-in-Charge.
[Note : (a) The unit rate includes for protection pipe and earth lead upto 7.5 m. Any variation in length of earth lead and protection pipe beyond 7.5 m shall be measured and paid seperately.
(b) Excavation/earthwork is deemed to be included in the quoted rate.]
23
-
-