Military Engineer Services Tender

Search from over 12139+ business opportunities that have been announced from the biggest Mahatenders, e tender Maharashtra, Maharashtra government tenders, and the Online Tender Notices posted on Maharashtra e tenders till date. Find opportunities that have come in from the multiple corporations, Maharashtra government departments, State PSUs, and Private companies from the state.

Military Engineer Services - MES Tender

Works
Civil And Construction
Building Construction
Eprocure
Opening Date7 Feb 2024
Closing DateCancelled
Tender Amount₹ 2,98,00,000 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Get the Best Price For TMT
Starting from
₹46,700/MT*
Maharashtra

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Demolition of brickwork or stone/ boulder masonry, built in cement mortar including all quoins, arches, pillars, etc., but excluding ashlar facings, dressed stonework and precast concrete articles and removing debris/rubbish material outside MD land, complete all as specified and directed.

30.42

-

-

... More
Demolition of reinforced Cement Concrete of Roofs, floors (other than ground floors), beams, staircase, landing, chajjas and similar suspended work (reinforcement cut as required to facilitate demolition) and removing debris/rubbish material outside MD land, complete all as specified and directed.

17.56

-

-

... More
Demolition of existing False Ceiling all as directed and removal of debris/rubbish materials outside MD land.

198

-

-

... More
Dismantling Stone slabs and tiles of any description or thickness in floors, aprons etc. laid bedded and pointed in any mortar and removing debris/rubbish material outside MD land. complete all as specified and as directed.

18

-

-

... More
Taking down shutters of any description exc. 1 sq. m and not exc. 2 sq. m each complete all as specified and as directed.

354

-

-

... More
Rendering 10mm thick cement plaster in C.M. (1:6) on internal wall finished even & smooth without using extra cement Complete all as specified and directed.

881.73

-

-

... More
Rendering 5mm thick cement Plaster in CM (1:3) on ceiling finished even and smooth without using extra cement Complete all as specified and directed.

719.3

-

-

... More
Rendering 15mm thick cement plaster in two coat , 10mm thick first coat in Cement Mortar (1:4) and 5mm thick Second Coat in cement mortar (1:4) with WPC @ 3% by weight of cement or as per manufacturer instructions complete all as specified and directed. Note:- WPC shall be measured & paid separately.

674.04

-

-

... More
Supply only Integral waterproofing compound.

86.14

-

-

... More
Priming surfaces and applying normal treatment (for moderate conditions) using glass fibre base bitumen felt, grade 2 and applying APP based polymeric membrane minimum weighing 3kg/sqm and minimum 3mm thick reinforced with polyster non woven fabric (wt. not less than 150 gms/sqm) land on primed surface by forced application complete all as specified.

658.8

-

-

... More
110mm thick cement concrete type B- 2, 1:2:4 (40mm graded stone aggregate) complete all as specified.

4350

-

-

... More
40mm thick wearproof topping as specified (incorporating an approved metallic floor hardner), laid on concrete floors and pavings, and finished even and smooth (except metallic hardner) complete all as specified and directed. Note: Metallic floor hardener shall be measured and paid separately.

4350

-

-

... More
Supply Only Metallic Floor Hardener.

58000

-

-

... More
Precast cement concrete block masonry ( 1:3:6 ) type C1 (20mm graded aggregate) with solid blocks, exc. 10 cm in width and setting in CM (1:6) complete all as specified and directed.

34.5

-

-

... More
Anodised aluminium powder coated (minimum thickness of powder coating 50 micron) frame for doors, windows, ventilators with one or more rebates including joining cleat for fixing etc. complete all as specified and directed.

679.23

-

-

... More
Anodised aluminium powder coated (minimum thickness of powder coating 50 micron) window and ventilator shutters, fixed type without sash bar, aluminium section weighing 0.55 kg/m including necessary joining cleats, glazing clips, rubber packing, anodised aluminium snap beading, screws etc. complete all as specified and directed.

174.75

-

-

... More
5.50mm thick sheet glass, ordinary quality and glazing with oil putty in square exc. 0.5 sq. m in each pane complete all as specified and as directed.

119.25

-

-

... More
35mm plain framed, panelled shutter (two panel) with lock rail and panel of 9 mm B.W.P. commercial ply or 12 mm veneered particle board with commercial veneering on both faces. The size of rail and stile as per IS : 1003 (Part I), kiln seasoned and chemically pressure treated completed all as specified and as directed.

42.84

-

-

... More
Framed work such as grills, gratings, etc.. with ends of bars shouldered and/or riveted, or forged into spikes; framed guard bars; barred iron doors; ladders; framed balusters; walk ways; railings; framework of water tanks and similar work conforming to Fe.290.Gde-E-165 complete all as specified and directed.

1788.75

-

-

... More
Hangers 6 mm dia. G.I. (upto 1200mm length) adjusting level fixed to roof slabs by means of ceilling cleats made out of G.I. flat 40 x 3 mm size 60mm long and expansion hold fasteners 12.5mm dia. 40mm long complete all as specified and directed.

198

-

-

... More
Gl frame work for seamless ceiling comprising of Gl perimeter channnel 0.55 mm thick with two unequal flanges of 20 and 30 mm and web of 27 mm fixed to surrounding wall using nylon sleeves and screws at 450 mm centre to centre/intermediate channel 0.9 mm thick having two equal flanges of 15 mm each and web of 45 mm suspended from soffit at approx 900 mm centre to centre with Gl cleat and steel expansion fasteners with and including ceiling section (not exc 1.2 m length) of 0.55 mm thickness having kurled web of 50 mm and flange of 26 mm each with lips of 10.5 mm fixed to the intermediate channel with connecting clips across the intermediate channel at 457 mm centre to centre complete all as specified and directed.

198

-

-

... More
Providing and fixing Gypsum Board 12mm thick in ceiling fixed with screw as per manufacturer's instructions complete all as specified and directed.

198

-

-

... More
Preparation of newly plastered surface and applying two coats of oil bound distemper over a coat of alkali resistant priming paint on wall, complete all as specified and directed.

4725.22

-

-

... More
Preparation of newly plastered surface and applying three coats of White Wash on Ceiling complete all as specified and directed.

872.3

-

-

... More
Acrylic Smooth exterior paint of aprroved shade : New work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm) complete all as specified and as directed.

6589.53

-

-

... More
Light Shade Virified Ceramic tiles 10 mm thick (square/ rectangular) polished, area of each tiles not exceeding 0.36 sqm, in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match complete all as specified and as directed.

180

-

-

... More
Brickwork with fly ash bricks, straight or curved on plan exc 6m mean radius, built in CM ( 1:6 ). complete all as specified and directed.

15

-

-

... More
Removal of existing affected, distressed, loose cover concrete including loose damaged concrete from all structural members up to and beyond the corroded steel reinforcements to a depth of 10 mm minimum behind the reinforcement only at affected concrete surfaces (Good & sound concrete should not be chipped / damaged) by chipping / hacking with chisel and hammer or by mechanical means like light weight chisel hammer, pneumatic chippers, making saw cut at periphery to avoid feather edge and removal and disposal of debris outside MD land. complete as directed by Engg.in charge. Depth of chipping may vary upto 100 mm.

626.7

-

-

... More
Drilling and installing the 12 mm dia holes about 100 mm to 200 mm deep (Nozzle spacing should be as per the methologay "Nozzle spacing" defined in DPR) on the member wall avoiding microfine cement location, cleaning the holes with compressed air and spiral brush to make it free from drill dust, fixing and including twin lock nozzles of 11 mm dia OD (to sustain pressure up to 10 Kg/cm2) in 12 mm dia holes, made of PVC with non return valve fixed with epoxy putty, complete in all respect and all as directed by Engineer-in-Charge.

2023

-

-

... More
Injection Grouting - Low viscous epoxy pressure grouting in cracks: grouting in cracks in the parent concrete by fixing PVC nipples at 500mm distance or specified distances as per design and detailed specifications. Pressure grouting using low viscous epoxy grout shall be done at required pressure etc. complete as per specification and methodology given in DPR, complete all as specified and as directed Note: Payment shall be made on basis of quantity of actual grout consumed. Make: BASF, Krishna conchem, Fosroc

1885

-

-

... More
Pressure grouting with low viscosity epoxy approved quality (Low viscosity solvent free prepacked resin and hardener, free flow epoxy system after mixing) with pressure of 3-4Kg/Sq.cm. to be carried out until refusal is reached, as per specification and all as directed by Engineer-in-charge Make: BASF, Krishna conchem, Fosroc

138

-

-

... More
Cleaning of rust/ scales/corrosion from reinforcement bars using rust remover from any of the manufacturer mentioned below. The material shall be applied using brush and left to dry for 30 mins & washing surface with fresh water, complete all as directed by Engineer-in-Charge. Make: BASF, Krishna conchem, Fosroc

1746.7

-

-

... More
Providing & applying inhibition coats/system to exposed reinforcement bars (after cleaning & removing scales and rust completely under item 35 above) as per manufacturer’s specification in two coats Make: BASF, Krishna conchem, Fosroc

1746.7

-

-

... More
Epoxy Bonding agent to the concrete and steel surface as per following specifications and as per manufacturer insturcitons. Bonding agent having a mixed density of 1.45 – 1.5 Kg /Litre and a pot life of minimum 2 Hours at 35 Dig C. It shall have an open time of 6 hours and shall become fully hard at 24 hours. It shall achieve a minimum compressive strength of 40 M/mm2 @ 7days when tested as per ASTM D 695 or BS 6319 Part 2 and a flexural Strength of 25 N/mm2 @ 7 Days when tested as per ASTM C-550 or BS 6319 Part 3. It shall achieve a tensile strength of 15 N/mm2 @ 7 days when tested as per BS 6319 Part 7 or ASTM D 638. It shall achieve a slant shear bond strength of minimum 11 N/mm2 with concrete when tested as per ASTM C 881. It shall provide a coverage of around 2 – 2.5 Sqm per Litre. Material should be compatible for use up to 70 degree surface / ambient temperature. Make: BASF, Krishna conchem, Fosroc

1746.7

-

-

... More
Corrosion Resistance single component, polymer modified cement mortar to patch up the damaged concrete section in planks of 40mm thickness in two layers all as per manufacturer's insturctions and as directed by Engineer-in-Charge. Providing and applying Corrosion Resistance Single Component, Polymer modified, fibre reinforced cementitious repair mortar having water powder ratio in the range of 0.16 and the mixed density of around 2.05 – 2.20 Gms/cc. The repair mortar shall achieve a minimum compressive strength of 45 MPa @ 28 days when tested as per ASTM C-109 and a flexural strength of 7 MPa when tested as per ASTM C 348. It shall achieve a minimum Adhesion Bond Strength of 2 MPa when tested on Standard Elctometer as per ASTM D 4541 – 85. The modulus of Elasticity shall be a minimum of 28 kN/mm2 when tested as per BS 1881. Material should be compatible for use up to 70 degree surface / ambient temperature.including applaying of Curing compound after final layer. Make: BASF, Krishna conchem, Fosroc

1746.7

-

-

... More
Providing injection / pressure grouting in cracks in the parent concrete by fixing PVC nipples at 150mm to 200mm distance or specified distance as per design and detailed specifications. Pressure grouting using polymer cement grout as per detail specification shall be done at required pressure etc. complete as per specification and approvals complete as directed. Make: BASF, Krishna conchem, Fosroc Note: The rates for shall include the cost of providing, erecting and maintaining leak-proof shuttering /formwork /scaffolding, etc. to be used for the purpose, providing and erecting props, temporary frame work and maintain them in position for required time, to existing elements for reliving loads coming on to structural members being repaired/strengthened but excludes the cost of reinforcement complete all as specified and as directed. B51:B52

300

-

-

... More
75mm Thick Plinth Protection with type C-2, PCC (1:3:6) using 40mm graded aggregate complete all as specified and directed.

55.31

-

-

... More
RCC (design mix) M-30 using 20 mm graded stone aggregate as as in staircase including steps ( square or spandril), string pieces, carriages etc complete any section straight or winding, but excluding landings, complete all as specified and directed.

13.11

-

-

... More
RCC (design mix) M-30 using 20 mm graded stone aggregate in Slabs supported on walls, beams and columns in floors, roofs, landings, balconies, canopies, deck slabs and in shelves and the like complete all as specified and directed.

4.46

-

-

... More
Form work for rough finished surfaces of concrete measured flat as in Formwork to staircases with sloping or stepped soffits including risers and stringers (excluding landing) complete all as specified and directed.

92.77

-

-

... More
Form work for rough finished surfaces of concrete measured flat as in Formwork to soffits of suspended slabs such as roof slabs, floor slabs, landings and similar work; not exceeding 200mm thick (Horizontal or sloping) complete all as specified and directed.

29.7

-

-

... More
TMT bars 10 MM dia and over cut to length bent to shape required including crancking bending spirally for hooping for columns, hooking ends and including mild steel wire (annealed) not less than 0.9 M dia or securing with clips complete all as specified and directed.

1622.46

-

-

... More
Steel windows with side hung shutters including projecting type hinges with steel handle, and steel peg stay, complete with glazing bars, dovetailed or welded complete all as specified and directed.

45

-

-

... More
5.50mm Thick sun tinted sheet glass, ordinary quality and glazing with oil putty in square exc 0.5 sq. m in each pane complete all as specified and directed.

171.42

-

-

... More
Aluminium Anodised grill (anodised transparent or dyed to required shade according to IS: 1868 with minimum anodic coating of grade AC 15) of approved design/pattern, with approved standard section and fixed to the existing window frame with C.P. brass/ stainless steel screws @ 200 mm centre to centre, including cutting the grill to proper opening size for fixing and operation of handles and fixing approved anodised aluminium standard section around the opening, all complete as per requirement and direction of Engineer-in-charge.

354.84

-

-

... More
INTERNAL ELECTRIFICATION Taking down copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. removing materials to store for keeping in safe custody for taking credit.

1536

-

-

... More
Taking down carefully by unscrewing from boards/outlet boxes, fittings and fixtures such as switches,sockets, ceiling roses, lamp holders, brackets, ceiling fittings,bulk head fittings, tube light fittings and regulators, etc. removing materials to store for keeping in safe custody for taking credit.

1601

-

-

... More
Taking down copper/aluminium sub main wiring complete all as directed.

600

-

-

... More
Point wiring using 1.1 kV grade single core FR-LSH flexible cable, conforming to IS 694: 2010, having multi-drawn thin strands of electrolytic copper conductors and insulation for phase, neutral, and earth continuity conductor connecting to earth dolly, colour-coded as per IS 11353: 1985, drawn in medium grade UPVC surface / recessed conduits, conforming to IS 9537 (Part- 3): 1983, of size not less than 20 mm NB, including cutting chases, factory made not less than 1.2 mm thick sunken, modular flush sheet galvanized metal enclosure haing zinc coating not less than 120 GSM, , conforming to IS 14772: 2000, having top, bottom, side and back-wall knockouts for conduit entry from any direction, suitable modular cover-plates and making good of disturbed surfaces of wall / ceiling / floor, etc. complete all as specified in IS 732: 2019 and directed by the engineer-in-charge for the following:- NOTES : [i] Sunken modular flush sheet metal enclosures shall be measured and paid for as a separate item. [ii] Modular cover plates shall be measured and paid for as a separate item.

-

-

-

... More
One light point controlled by one switch, with cables 1.5 sqmm size

628

-

-

... More
One fan/exhaust point controlled by one switch, with cables 1.5 sqmm size

197

-

-

... More
One 6 A socket outlet, independent, with cables 1.5 sqmm size

496

-

-

... More
One 16 A socket outlet, independent, with cables 2.5 sqmm size

215

-

-

... More
Modular type 6 A 1-way SP switch conforming to IS 3854: 2012 with finger-proof terminal complete all as specified in IS 732: 2019 and directed by the engineer-in-charge. Make: Legrand Arteor Cat-Part No. 5734 00 or equivalent model of Anchor Cat-Part No. Penta 65001 or L & T Cat-Part No. OS11W06

1321

-

-

... More
Modular type 16 A 1-way SP switch conforming to IS 3854: 2012 with finger-proof terminal complete all as specified in IS 732: 2019 and directed by the engineer-in-charge. Make: Legrand Arteor Cat-Part No. 5734 10 or equivalent model of Anchor Cat-Part No. Penta 65007 or L & T Cat-Part No. OS11W16

215

-

-

... More
Modular type 2/3 pin combined shuttered type 6 A socket, conforming to IS 1293: 2005 complete all as specified in IS 732: 2019 and directed by the engineer-in-charge. Make: Legrand Arteor Cat-Part No. 5734 70 or equivalent model of Anchor Cat-Part No. Penta 65222 or L & T Cat-Part No. OC32W06

496

-

-

... More
Modular type 2/3 pin combined shuttered type 16 A socket, conforming to IS 1293: 2005 complete all as specified in IS 732: 2019 and directed by the engineer-in-charge. Make: Legrand Arteor Cat-Part No. 5734 71 or equivalent model of Anchor Cat-Part No. Penta 65266 or L & T Cat-Part No. OC32W66

215

-

-

... More
Modular type 120 W step fan regulator, conforming to IS 11037: 1984 complete all as specified in IS 732: 2019 and directed by the engineer-in-charge. Make: Legrand Arteor Cat-Part No. 5734 69 or equivalent model of Anchor Cat-Part No. Penta 65001 or L & T Cat-Part No. OS15W06 NOTES:[i] Item No. 2.0 to 6.0 shall be of the same manufacturer.

127

-

-

... More
3 pin, 6 A, 250 V ceiling rose conforming to IS 371: 1999 and having terminal capacity 3 X 1.5 mm² with IK 04 and IP 20 protection complete all as specified in IS 732: 2019 and directed by the engineer-in-charge. Make: Legrand, Anchor, MK or Havells

825

-

-

... More
Single pole & neutral, modular type, double door, metallic distribution board conforming to IEC 61439-3, suitable for flush / surface mounting with provision for DP RCCB / RCBO / Isolator / MCB as incomer and SP MCBs as outgoing, reversible metal door, 100 A copper busbar, fully shrouded neutral bar, earth bar, wire set & cable ties for cable management, pre fitted masking sheet, etc. having IK 09 & IP 43 protection complete all as specified in IS 732: 2019 and directed by the engineer-in-charge as per details below:- Make: Schneider, Legrand, L & T NOTES:[i] DP RCCB / RCBO / Isolator / MCB & SP MCBs shall be measured and paid separately.

-

-

-

... More
single pole & neutral double door DB, 12 way.

3

-

-

... More
single pole & neutral double door DB, 8 way.

15

-

-

... More
single pole & neutral double door DB, 4 way.

1

-

-

... More
Triple pole & neutral double door, 4 way, modular type, double door, metallic distribution board conforming to IEC 61439-3, suitable for flush / surface mounting with provision for FP RCCB / RCBO / Isolator / MCB as incomer and SP/TP MCBs as outgoing, reversible metal door, 100 A copper busbar, fully shrouded neutral bar, earth bar, wire set & cable ties for cable management, pre fitted masking sheet, etc. having IK 09 & IP 43 protection complete all as specified in IS 732: 2019 and directed by the engineer-in-charge. Make: Schneider, Legrand, L & T NOTES: [i] FP RCCB / RCBO / Isolator / MCB & SP/TP MCBs shall be measured and paid separately.

11

-

-

... More
Vertical triple pole & neutral, double door, metallic modular distribution board conforming to IEC 61439-3, suitable for flush / surface mounting with provision for MCCB up to 250 A as incomer and SP/TP MCBs as outgoing, reversible metal door, fully insulated 250 A copper busbar for each phase, two fully insulated & shrouded neutral bars, two earthbars, cable ties for cable management, prefitted masking sheet, etc. having IK 09 & IP 43 protection complete all as specified and directed by engineer-in-charge of following details:- Make: Legrand, Schneider, L & T NOTES:[i] FP MCCB & SP/TP MCBs shall be measured and paid separately.

-

-

-

... More
verticle triple pole & neutral double door DB, 8 way

2

-

-

... More
verticle triple pole & neutral double door DB, 4 way

3

-

-

... More
MCB for AC applications conforming to IS/IEC 60898-1-2002, having breaking capacity Icn = 10 kA, sliding bottom clamp, colour coded on/off indication on dolly, bi-connect IP 20 protected lower terminals and sliding shutters, etc. complete all as specified in IS 732: 2019 and directed by the engineer-in-charge of following details:- Make: Schneider, Legrand, L & T

-

-

-

... More
6- 32 A, 230 V, 50 Hz, SP MCB (C curve)

241

-

-

... More
6- 32 A, 230 V, 50 Hz, SPN / DP MCB (C curve)

19

-

-

... More
6- 32 A, 415 V, 50 Hz, TP MCB (C curve)

12

-

-

... More
6- 32 A, 415 V, 50 Hz, FP MCB (C curve)

11

-

-

... More
Moulded case circuit breaker (MCCB) with thermal magnetic trip unit (TMD), compression lug connectors, protection against overloads (Ir adjustable from 0.7- 1 X In), protection against short circuits (Isd adjustable from 1.5- 10 X Ir), inbuilt encapsulated double break roto active type instanteneous protection, earth fault leakage protection, etc. having Ics = 100% as per IEC 60947-2 complete all as specified and directed by engineer-in-charge of following details:- Make: Schneider, Legrand, L & T

-

-

-

... More
200 A, 25 kA, 415 V, 50 Hz, FP MCCB

2

-

-

... More
63 A, 25 kA, 415 V, 50 Hz, TP MCCB

2

-

-

... More
63 A, 25 kA, 415 V, 50 Hz, FP MCCB

3

-

-

... More
Submain wiring using 1.1 kV grade single core FR-LSH flexible cable conforming to IS 694: 2010, having multi-drawn thin strands of electrolytic copper conductors and insulation for phase, neutral and earth continuity conductor connecting to earth dolly, colour-coded as per IS 11353: 1985, drawn in medium grade UPVC surface / recessed conduits, conforming to IS 9537 (Part- 3): 1983, of size not less than 25 mm NB, including making good of disturbed surfaces of wall / ceiling / floor all complete as specified in IS 732: 2019 and directed by engineer-in-charge of following sizes:- Make: FR-LSH flexible cable: Polycab, RR Kabel, Havells; Medium grade UPVC conduits: Precision, Prince, Supreme NOTES:[i] Phase & neutral conductors (02 runs), earth continuity conductor (01 run) and surface / recessed conduit (01 run) shall be measured combined as one length.

-

-

-

... More
2 X 4.0 sqmm + 1 X 4.0 sqmm earth wire

500

-

-

... More
Submain wiring using 1.1 kV grade single core FR-LSH flexible cable conforming to IS 694: 2010, having multi-drawn thin strands of electrolytic copper conductors for phase, neutral and earth continuity conductor connecting to earth dolly, drawn in medium grade UPVC surface/recessed conduit conforming to IS 9537 (Part 3): 1983, colour coded as per IS 11353: 1983, including making good of disturbed surfaces of wall / ceiling / floor all complete as specified in IS 732: 2019 and directed by engineer-in-charge. Make: FR-LSH flexible cable: Polycab, RR Kabel, Havells; Medium grade UPVC conduits: Precision, Prince, Supreme NOTES:[i] Phase & neutral conductors (04 runs), earth continuity conductor (02 run) and surface / recessed conduit (01 run) shall be measured combined as one length.

-

-

-

... More
4 X 4.0 sqmm + 2 X 4.0 sqmm earth wire

200

-

-

... More
4 X 6.0 sqmm + 2 X 6.0 sqmm earth wire

300

-

-

... More
Earthing complete with galvanized steel earth plate electrode of 60 cm x 60 cm x 6 mm size, buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level, connected to galvanised strip of size 32 mm x 6 mm as earth lead, by means of bolts, buts, check nuts and washers of galvanised iron or steel, galvanized iron pipe of 40 mm diameter, connected to earthing test point, all as shown in electrical plate No. 5 connected to earthing test point all as specified or indicated including testing on completion and including excavation, earthwork, PCC earth pit of dimensions 550 mm X 550 mm (outer) and 300 mm X 300 mm (inner) and 250 mm deep, with a 10 mm thick CI cover, hinged to CI frame on ground level, GI watering pipe, funnel, etc. as all specified and directed.

4

-

-

... More
Galvanised strip of size 32 mm x 6 mm as earth lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. all as specified and directed.

80

-

-

... More
20 W surface / wall mounted LED batten capable of delivering 2000 lumen, having PC diffuser, luminous efficacy of 90 lumen/W, CRI 80, PF 0.9, CCT 6500K, independent isolated SMPS based constant current electronic LED driver with THD 20%, surge voltage protection and other safety tests as per IS 15885 (Part-2/Sec-13): 2012, polycarbonate diffuser, housed in powder coated white extruded aluminium channel housing. white coloured ABS end caps, IP 20 protection, input voltage range 140- 270 V, input frequency 50- 60 Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and directed by the engineer-in-charge. Make: Philips Cat-Part No. BN 021C LED20S- PSU CW GR S2 or equivalent model of Havells Cat-Part No. LHEXAPP7IN1W020 or Wipro Cat-Part No. LL20-281-XXX-65AL1

236

-

-

... More
10 W surface / wall mounted LED batten capable of delivering 1150 lumen, having PC diffuser, luminous efficacy of 110 lumen/W, CRI 80, PF 0.9, CCT 6500K, independent isolated SMPS based constant current electronic LED driver with THD 20%, surge voltage protection and other safety tests as per IS 15885 (Part-2/Sec-13): 2012, polycarbonate diffuser, housed in powder coated white extruded aluminium channel housing. white coloured ABS end caps, IP 20 protection, input voltage range 140- 270 V, input frequency 50- 60 Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and directed by the engineer-in-charge. Make: Philips Cat-Part No.RC380B LED30S-4000 L60W60 PSU OD S1 or equivalent model of Havells Cat-Part No. VENUSNEOHE2X2R28WLED857PIRSENSOR or Wipro Cat-Part No. CRCO10R038HP57G1

79

-

-

... More
30 W recessed mounted square shape 2' X 2' LED panel capable of delivering 3000 lumen having high efficiency long life LED package in integral module with luminous efficacy of 100 lumen/W, independent isolated SMPS based constant current electronic LED driver with THD 20%, surge voltage protection and other safety tests as per IS: 15885 (Part-2/Sec-13): 2012, high transmittance polystyrene opal diffuser, housed in white powder coated pressure die-cast aluminium heat sink having input voltage 220- 240 V, input frequency 50- 60 Hz, PF 0.95, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fixture complete all as specified and directed. Make: Philips Cat-Part No.RC380B LED30S-4000 L60W60 PSU OD S1 or equivalent model of Havells Cat-Part No. VENUSNEOHE2X2R28WLED857PIRSENSOR or Wipro Cat-Part No. CRCO10R038HP57G1

313

-

-

... More
BEE five star rated energy efficient high-speed ceiling fan having 1200 mm blade sweep, air-flow not less than 200 CMM, operating voltage 220-240 V and frequency 50 Hz, including a downroad of suitable size complete with electrical connection through 3 core PVC insulated copper conductor unarmoured cable of suitable size as specified and directed by engineer-in-charge. Make: Crompton Cat-Part No. ENTRUST 50- 5 STAR or equivalent model of Havells Cat-Part No. ES - 50 Premium or BAJAJ Cat-Part No. Electra 50

127

-

-

... More
Engery efficient metalic exhaust fan having blade sweep 300 mm, air delivery not less than 6000 CMH, operating voltage 220-240 V and frequency 50 Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size from ceiling rose to the fresh-air fan complete all as specified and directed by engineer-in-charge. Make: Crompton Cat-Part No. EXHD300- 4-1 or equivalent model of Havells Cat-Part No. Ventil Air - DSP or BAJAJ Cat-Part No. Max Air

70

-

-

... More
Pedestal fan having blade sweep 450 mm, air delivery not less than 125 m³/min, operating voltage 220-240 V and frequency 50 Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size complete all as specified and directed by engineer-in-charge. Make: Crompton Cat-Part No. SSTORM2 or equivalent model of Havells Cat-Part No. Windstorm or BAJAJ Cat-Part No. Victor VP01 18"

45

-

-

... More
Wall fan having blade sweep 400 mm, air delivery not less than 125 m³/min, operating voltage 220-240 V and frequency 50 Hz, including electrical connection with 3 core flexible Cu conductor cable of appropriate size complete all as specified and directed by engineer-in-charge. Make: Crompton Cat-Part No. WMSDX 120 or equivalent model of Havells Cat-Part No. Turbo Force or BAJAJ Cat-Part No. Esteem

65

-

-

... More
FIRE FIGHTING Fire alarm panel complying with BS EN 54 Single loop panel of capacity from 99 detector & 99 modules upto 200 detector and moudules. Make: Notifier NFS 3030 + DVC or equivalent model of JC, Esser

2

-

-

... More
Addressable type Multisensor Detectors with heat & smoke combination with base, FM approved and UL listed. Make: Honeywell morley IAS, Ravel RE 316SH-2L

103

-

-

... More
Beam Master Detectors with transmitter & receiver. Make: Ravel RE- 428FR, Ravel RE-428HR, BOSCH D-296

5

-

-

... More
Flush / ceiling wall mounted remote response indicator to duplicate detector alarm latching LED(s), compatible for two wire detectors, having 12 VDC operating voltage, dual LEDs for 360⁰ visibility in case the detector is placed above the false ceiling / inside closed room complete all as specified and directed by the engineer-in-charge. Make: Honeywell, System Sensor, Agni

12

-

-

... More
FM approved and UL listed fault isolator module powered by SLC loops directly to protect system against wire-to-wire short circuits on the SLC loops by limiting the number of modules or detectors that may be rendered inoperative by a short circuit fault on the SLC loop, having integral LED indicators, high noise immunity, SEMS screws with clamping plates for ease of wiring complete all as specified and directed by engineer-in-charge. Make: Notifier IXO-X or equivalent model of JC, Esser

12

-

-

... More
FM approved and UL listed addressable control module to provide FACP a circuit for notification appliances (e.g. Horns, Strobes, Horn Strobes, etc.) having built-in type identification, integral LED indicators, high noise immunity, SMES screws with clamping plates for wiring ease, direct-dial entry of address, etc. complete all as specified and directed by engineer-in-charge. Make: Notifier FCM-1 or equivalent model of JC, Esser

15

-

-

... More
FM approved and UL listed surface / semi- flush mounted Dual Action Manual Pull Station "Push In & Pull Down" including an addressable interface for the intelligent FACP having built-in bicolour LED which is visible, flashing in normal operation and latching steady red in alarm condition, captive screw terminals wire-ready for easy connection to SLC loop complete all as specified and directed by engineer-in-charge. Make: Notifier NBG-12LX or equivalent model of JC, Esser

15

-

-

... More
UL listed of sounder come Horn Strobe, wired as a primary notification appliance, flashing 75 cd at 1 Hz over the strobe's entire operating voltage range, xenon flash tube and associated lens / reflector system, built-in synchronization feature keeping strobes in sync for up to 30 minutes, horn producing audible annunciation of 75 dBA at 3 m distance complete all as specified and directed by engineer-in-charge. Make: Notifier SYS-HS or equivalent model of JC, Esser

15

-

-

... More
FM approved & UL listed remote power supply conforming to UL 864 & 1481 and NFPA 72 with integral battery charger capable of charging up to 18 Ah batteries to provide regulated and filtered 24 VDC power to notification appliance circuits, having power-supervision relay, fully regulated and filtered power output, AC trouble report selectable for immediate 2-hour delay, selectable earth fault detection, etc. complete all as specified and directed by engineer-in-charge. Make: Notifier HPF24S6E or equivalent model of JC, Esser

2

-

-

... More
Low smoke zero halogen (LS0H) flame retardant fire alarm cable, conforming to BS 7629-1, BS 6387 & BS EN 50200 and rated for 500 V, drawn through concealed PVC conduit and having plain annealed stranded copper conductor with primary insulation of glass mica fire resistant tape and secondary insulation of high performance silicone rubber, earth/drain wire of annealed tinned copper, electrostatic screen of aluminium fire barrier and type LTS3 outer sheath conforming to BS 7655, suitable for operating temperature range -30 ˚C to +70 ˚C and minimum bending radius being 6 times the overall cable diameter, RED in colour, including laying, termination and ferruling complete all as specified and directed by engineer-in-charge. Make: RR Kabel, Polycab, Havells

-

-

-

... More
2 core, 1.5 sqmm size

1600

-

-

... More
2 core, 2.5 sqmm (supply to hooter/strobe) size

500

-

-

... More
20 mm NB rigid steel conduit inclusive of boxes (junction / terminal), all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc. concealed in wall / ceiling for fire alarm / control cabling complete all as specified and directed by engineer-in-charge. Make: United power, Techno flex

1590

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.