Military Engineer Services Tender
... More
Search from over 12139+ business opportunities that have been announced from the biggest Mahatenders, e tender Maharashtra, Maharashtra government tenders, and the Online Tender Notices posted on Maharashtra e tenders till date. Find opportunities that have come in from the multiple corporations, Maharashtra government departments, State PSUs, and Private companies from the state.
Military Engineer Services - MES Tender
Civil And Construction
Water Storage And Supply
Eprocure
Opening Date26 Sep 2024
Closing DateCancelled
Tender Amount₹ 2,28,50,000
AI Insights
Technical
Technical
Technical Capacity
... View More
The required prior work experience for the bidder is not explicitly stated. However, it is mentioned that contractors of one class below the eligible class may be considered if they have previously completed similar works satisfactorily and meet the criteria of upgradation in respect of past experience of completed works. There is no specific percentage or amount mentioned for similar works completed. The details of works completed and under progress in MES should be submitted, but specific values and percentages are not provided. The criteria for upgradation include individual work experience and/or average annual turnover, but the exact values are not mentioned.
Costs
EMD
₹ 3,03,500Document Cost
₹ 2,000Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_676690_1Bid Award Id
ViewTender No
890970ATender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Total amount of Sch 'A' part-IV (External Water Supply)
1
-
63874.1
... More
Total amount of Sch 'A' part-V (Retaining Wall)
1
-
217864.22
... More
SCH. 'A' PART -VI (MISCELLANEOUS ITEMS) Note :- This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
-
-
-
... More
External Water Supply:- Supply, laying, jointing, testing and commissioning of centrifugally cast (spun) ductile Iorn pressure pipes 200mm bore with Spigot and Socket ends , ISI marked, for water supply conforming to IS 8329/2000 with class K9, laid in trenches/ road crossings etc suitable for tyton joint (push-on) complete including rubber gaskets (ISI marked) for jointing materials complete all as specified as directed Note :- (a) Excavation and earthwork shall be measured and paid seperately. (b) DI fittings will be measured and paid seperately
290
-
-
... More
All as per item No 7.00 here-in-before but 150 mm bore.
230
-
-
... More
Ductile iron fittings class 12, PN-10 conforming to IS 8329-2000 with inside cement mortar lining and out side zinc followed by black bitumen coating of any type suitable for spigot, socket or flanged ends such as bends, tapers, socket, Tee, cross, collars, caps, lugs, flanges etc as per requirement of size upto 200mm bore including jointing materials complete all as specified and as directed.
2000
-
-
... More
M & L for brick masonary valve pit chambers with and including one brick thick masonary built in cement mortar (1:6) PCC in foundation 1:4:8 type D2 (using 40 mm graded stone aggregate, rendering 10 mm thick in cm 1:6 internally 10 mm thick rendering in cement mortar (1:4) finished even and fair externally, PCC 1:2:4, type B1 (Using 20 mm graded stoneaggregate) for coping 10 cm thick, 3 mm thick MS plate cover with locking arrangements with angle iron frame of size 40x40x6mm including painting to MS work with two coats of synthetic enamel black paint over one coat of red oxide primer including necessary excavation and earth in any type of soil/strata complete for size - Internal dimension 1050x1050x1050mm complete all as specified
5
-
-
... More
Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised iron strip 32×6mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion complete all as specified
4
-
-
... More
Insulator BMD 40 for mounting of earth continuity conductor complete all as specified and directed
45
-
-
... More
Supply and installation of Hot dip galavanised iron pole 7 mtr long sheet thickness 3 mm. C/s A/F - top = 70mm, bottom =130 mm, base plate 200x200x12 mm, 500 mm long weatherproof reinforced door opening with junction box mounting arrangement but including of junction box, single arm bracket 1 m, 20 dia threaded made to J shape M20x600mm long steel grade EN8 foundation bolts - 4 nos with nuts, templates and all complete as per approved drawing including taking down old rusted pole of any size by digging or cutting complete all as specified and directed. Make : Bajaj/ Philips/ Crompton/ Wipro/ Surya Foundation RCC 1:1.5:3 shall be of size 550x550mm and depth 1500 mm with 8 nos. 12mm dia. tor bars as main bars and 8mm dia. tor bars stirrups @ 190 mm c/c as per approved drawing. This reinforcement shall conform to IS:1786 latest edition. The foundation shall extend above sorrounding ground/driveway level for 200 mm and have slant 63mm dia. PVC sleeve cast insitu foundation for cable entry as per the drawing. Cost of foundation including excavation, earthwork, PCC, RCC, formwork and reinforcement shall be deemed to be included in the rate quoted against the item.
4
-
-
... More
45W pressure die cast aluminium housing LED street light, including connection with two core twisted copper flexible cable including taking down old street light fitting and diposited to MES store Yard for reuse. Make - Bajaj, Cat No - BRTGF45W LED or equivalent in other makes as specified
4
-
-
... More
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 6.0 sq mm 2 core complete all as specified
200
-
-
... More
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10.0 sq mm 4 core complete all as specified
70
-
-
... More
Integral LED Aviation light comprising of aluminium housing with polycarbonate enclosure complete all as specified and as directed. MakeBajaj,Cat Part No-BGAV 302 LED or equivalent in other makes as specified
1
-
-
... More
Supply, Installing,Testing and Commissioning of Ultrasonic Level Transmitter at Sump and overhead tank for measurement of level with following specification:- Range : 0-6 meters Accuracy : 0.5 % minimum Supply Voltage : 24V DC Output : 4-20 mA , 0-10V DC Make: Pepperl+ Fuchs / Nivelco / Siemens/Banner
1
-
-
... More
Supply, Installation Testing & Commissioning of Outdoor type having Canopy and Double Door for weather protection, PLC ( Programmable Logic Controller) based Valve Automation, Protection Panel with wireless Radio Frequency based communication suitable for control and monitoring of 02 Nos. motorized butterfly valves, 01 Nos. Ultrasonic Sensor. The front facia of the panel shall be made out of ink jet printed laminated latex on vinyl to clearly depict the layout of the PH in schematic format.The panel should be of minimum size 800(H) X 800(W) X 300(D) mm fabricated from 3.15 mm CRCA Sheet. The Panel should comprise the following items:- (a) Automatic Operation of Motor Actuated Butterfly Valves (b) Over & Under Voltage & Short Circuit Protection
(c) Manual Mode Operation (all connected sub systems including all valves in pump houses and connected buildings / overhead tank) from the PLC based Control Panel. (ii) 01 No. PLC with follwing specifications:- (MAKE:- SCHNEIDER/SIEMENS/ABB)
(a). Non isolated RS 485 communication port or Ethernet communication port, Support two redundant physical channel communication to one control centre.
(b). Suitable No. of digital / analog input and outputs.
(c). Programming Software based on IEC to facilitate building of custom build function blocks.
(d). 2 reduced single phase HSC channels, 2PTO/PWM Output, should support Server + Client with Industrial Grade Processor
(e). Protocol : Master/Slave Modbus ASCII/ RTU & ASCII, Expandable upto 248 I/O’s and 7 expansion module
1
-
-
... More
(Item No 19 (Continued)
(iii) 01 no. HMI - 7" Graphical Touch screen display (Make: SCHNEIDER / SIEMENS/ ABB/GE Automation) (a). 01 nos. RS 485 and 01 no. USB port (b). Serial multilink, USB downloading port (c). Support external data storage on a USB memory stick for storing production data and backing up applications (iv) 01 no. SMPS of 5/10A rating as suitable according to panel design. (Make: SCHNEIDER / SIEMENS/ ABB / OMRON)
(v) Suitable no. of interposing relays of 220VAC & 24 VDC coil rating and 6 A contact rating. (Make: OEN / OMRON / ALLEN BRADLEY) (vi) Suitable no. of relay cards with operating voltage 24VDC, with continuous current of 5A. Card must be of 8 channel & having 8 relays.( SCHNEIDER / SIEMENS/ ABB/PHEONIX CONTACT) (vii) MCB rating 32A, 10A, 6A. (Make:- Legrand/ Schneider/ABB) (viii) Illuminiated push button & indicator lamp (Make:- Schneider/ESBEE/ABB) (ix) Selector switches, Audio visual alarm indicator:- As per requirement (Make:- Schneider/ ESBEE/ABB) CRCA Enclosure:- Make (UNIVERSAL SWITCH GEAR CONTROL / HOFFMAN / TRICOLITE ) Make of the PLC based panel:- (Universal Switch Gear Control Cat. No. U- 753 / PLC /220V AC or equivalent in ABB Automation/Tricolite/GE Automation)
-
-
-
... More
Supply, Installation, Testing, Commissioning 1 KVA UPS / INVERTER with Sealed Lead Acid Maintenanace free Batteries for powering the panel for a minimum of 30 minutes in case of supply failure.
UPS should have following features:-
Charger:- Build in solit state three stage recharge.
Display:- LED Display
Audible Alarm:- Main Failure Alarm, Battery Low Alarm, UPS Warning, Fault.
(Make: APC / TATA LIEBERT / NUMERIC)
1
-
-
... More
Supply, Installation, Testing, Commissioning and Programming of Bi Directional Parabolic antenna with control station to generate strong directional effect with WLAN network support having mast mounting arrangment. Control station should operate on license free frequency with necessary hardware at a suitable location to be connected to the central scada server so as to establish connectivity with every station of the network after conducting a frequency survey of the entire area of interest and identify suitable locations to mount the station hardware and the height of the antennas to establish clear line of sight either directly or by multi hop so as to be able to send data.
Antenna type:- Omni and Bi Directional Parabolic antenna
Gain:- as per site requirement
Degree of protection:- IP65, seawater-resistant, Material:- Lexan EXL 9330 (Antenna housing), V2A (Bracket), V2A (Mast clip), Mounting type:- Mast mounting
The should have a approval of Wi-Fi compliance, Environmentally Friendly Use Period :- UNLIMITED = EFUP-e
Note:-Rate quoted is deemed to be included for making arrangemets of accessories such as mounting bracket and mast clips
Make:- Siemens / Schneider Electric / Universal Switch Gear Control / ABB Automation
1
-
-
... More
Supply, Installation, testing and Commissioning of 150 mm dia, single phase, Motor Actuated Butterfly valve with disc material of CI with nylon coating, hand wheel for manual operation and having 02 nos. limit switches for Open / Close condition and valve position indicator. Input Voltage: 230 V, A.C. Designed line pressure: 16 kg/sq cm.
In built CPU:- Quad-core 64-bit ARM Cortex A53 clocked at 1.2 GHz
Inbuilt 4 USB 2 ports
In built Base Ethernet Port
In built Micro SD port for loading your operating system and storing data In built wireless LAN and Bluetooth Low Energy
The mounting shall be indirect type using specialized extended type arrangement of GI pipe of suitable size/thickness, so that actuator mounting is at least 36 inches above ground level complete all as specified and directed.
Make : UNIVERSAL SWITCH GEAR CONTROL /EMERSON/ROTORK/SD TORK
1
-
-
... More
Supply, Installation, testing and Commissioning of 200 mm dia, single phase, Motor Actuated Butterfly valve with disc material of CI with nylon coating, hand wheel for manual operation and having 02 nos. limit switches for Open / Close condition and valve position indicator.
Input Voltage: 230 V, A.C. Designed line pressure: 16 kg/sq cm.
In built CPU:- Quad-core 64-bit ARM Cortex A53 clocked at 1.2 GHz
Inbuilt 4 USB 2 ports
In built Base Ethernet Port
In built Micro SD port for loading your operating system and storing data In built wireless LAN and Bluetooth Low Energy
The mounting shall be indirect type using specialized extended type arrangement of GI pipe of suitable size/thickness, so that actuator mounting is at least 36 inches above ground level complete all as specified and directed.
Make : UNIVERSAL SWITCH GEAR CONTROL /EMERSON/ROTORK/SD TORK
1
-
-
... More
Supply, Installation, Testing and Commissioning of 4 pair CAT 6 UTP cable for Sensors complete all as specified and directed. .
Make : D Link/ Finolex/ Polycab
80
-
-
... More
Supply & Fix 2 Core 1.5 sq. mm PVC sheathed PVC insulated copper armoured cable complete all as specified and directed.. Make: Havells/Polycab/Gloster
50
-
-
... More
Supply & Fix 6 Core 1.5sq.mm. PVC sheathed PVC insulated copper armoured cable complete all as specified and directed.. Make: Havells/Polycab/Gloster
150
-
-
... More
Upgradation of existing and Development and enhancement of existing SCADA software for including the following; a) Changes in the existing SCADA screens to accommodate the additional valves to be controlled through the software, b) Creation of suitable icons for monitoring thru additional valves and c) Creation of soft keys to facilitate the remote operation of the additional valves and levels of tanks incorporated in the water supply scheme.
1
-
-
... More
Cutting /breaking of cement concrete path or bituminous road of any thickness with or without reinforcement for taking up/down of GI/CI pipes and connection and making good to surface by PCC (1:2:4) type B1 (Using 20 mm graded stone aggregates) complete all as specified as directed.
2.5
-
-
... More
Cutting Existing CI pipe for insertion of Tee of size 150x150x150 complete all as specified and directed.
1
-
-
... More
Cutting Existing CI pipe for insertion of Tee of size 200x200x200 complete all as specified and directed.
1
-
-