Military Engineer Services Tender
Search from over 12139+ business opportunities that have been announced from the biggest Mahatenders, e tender Maharashtra, Maharashtra government tenders, and the Online Tender Notices posted on Maharashtra e tenders till date. Find opportunities that have come in from the multiple corporations, Maharashtra government departments, State PSUs, and Private companies from the state.
Military Engineer Services - MES Tender
Civil And Construction
Civil Works Others
Building Construction
Eprocure
Opening Date8 Oct 2024
Closing Date4 Nov 2024
Tender Amount₹ 48,30,000
Costs
EMD
₹ 97,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_678503_1Bid Award Id
ViewTender No
8883/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
M &L for forming expansion joints 100 mm deep x 12 mm wide filled with pre-formed bituminous filler and top 30mm primed and sealed with sealing compound, grade A complete all as specified and directed.
40
-
-
M&L for Forming Contraction (Dummy) joints 65mm deep x 10mm wide,filled with sealing compound.grade A complete all as specified and directed.
44
-
-
Taking down cement plaster on brick or stone walls etc including raking out joints,hacking for key ,scrubbing down with water etc complete all as specified and directed.
300
-
-
M&L for 15 mm thick cement plaster on brick or concrete surface in cement mortar1:6 included finishing surface even and smooth without using extra cement on walls etc complete all as specified and directed.
200
-
-
M&L for 10mm thick cement plaster on concrete surface in cement mortar (1:3) included finishing surface even and smooth without using extra cement on ceiling etc complete all as specified and directed
100
-
-
M&L for preparation of new plastered surfaces of walls and applying two coats of oil bound distemper over one coat of alkali registant priming paint etc complete all as specified and directed.
200
-
-
Ditto all as per item No 9 above here-in-before but in ceiling etc complete all as specified and as directed.
100
-
-
M& L for complete removal of existing treatment of old wall surfaces and applying two coats of distempering with 1st quality acrylic distemper (ready mixed) having VOC content less than 50 gms/litre of approved manufacturer of required shade and colour complete over a coat of wall primer as per manufacturer's specification complete all as specified and as directed
800
-
-
M&L preparation of newly plastered surfaces of wall and applying two coats of cement base paint white or tinted including scaffolding arrangement, trestles, ladders etc complete all as specified and directed.
50
-
-
Dismantling asbestos cement (corrugated , semi corrugated etc, ) sheets in roof covering . complete all as specified and directed.
1070
-
-
S&F Galvanised corrugated mild steel sheeting 0.80mm thick with two corrugations side lap, fixed with 'L' type or 'J' type of cranked hook in lieu of screws and washers in roofs, walls etc with grade of zinc coating 275 complete all as specified and directed
980
-
-
S&F Galvanised plain mild steel sheeting 0.80mm thick in Ridge, hips, valley gutter, drip and straight flashing (length and girth as fixed) with grade of zinc coating 275 complete all as specified and directed.
90
-
-
Taking down of existing tarfelt of any description and thickness on roof top including flashing and junction of parapet and cleaning existing roof top surface by brooming , wire brushing incl removing the debrish out complete all as specified and directed
185
-
-
Demolition Concrete of any description and in any position not otherwise specifically provided for complete all as specified and directed
9
-
-
M&L for cement concrete type B0 (1:2:4) 12.5mm size graded stone aggregate ) in roof padding complete all as specified and directed
6
-
-
M&L for 10mm thick rendering on concrete surface on roof in cement plaster 1:3 finished even and fair without using extra cement by using liquid WPC( Dr.fixit or equivalent) @ 200ml of 50kg of cement complete all as specified and directed
Note: Water proofing Compound measured and paid seprately
185
-
-
Supply only liquid water proofing compound all as directed
6.22
-
-
M&L for cutting grooves in brick / stone wall, 75mm wide and 65mm deep and shaping horizontal face of groove with cement mortar (1:3). complete all as specified and directed
110
-
-
M&L for preparing plastered surfaces,with approved bituminous primer @300 gms/sqm and applying water proofing treatment on wall,roof,chajja's,gabble walls, edges (at any respective height of bldg )etc and stick with non-woven polyster matt modified APP Membrane 3mm thick as reinforcement weighing not less than 3.5 Kg/sqm and applying one coat of aluminium paint on top of the membrane (at any height ) complete all as specified and directed
185
-
-
M&L for providing cement concrete PCC (1:2:4) type B1 (20mm graded stone aggregate) as in coping to parapet wall/kerbs in roof with projection of 50mm from the outer surface with a groove of 12 mm x 12mm as drip course in bottom side including necessary form work etc complete all as specified and as directed
3
-
-
Demolition of brick work or stone/boulder masonry built in cement mortar including all quions /archers etc and removing debris from site to outside MoD land complete all as specified and directed..
5
-
-
Material and labour for plastering 15mm thick on fair faces of brick work or concrete surfaces in CM 1:4 finished even and smooth without using extra lime or cement complete all as specified and directed.
95
-
-
M&L for Walling of squared rubble, regular coursed, well bonded, bedded and solidly hearted, built in cement mortar 1:6 complete all as specified and directed.
5
-
-
Raking out joints/pointing to squared rubble masonry, coursed or uncoursed built in cement mortar complete all as specified and directed.
20
-
-
M&L for flush pointing to random or squared rubble, uncoursed on brought upto courses in cement mortar 1:4 complete all as specified and directed.
30
-
-
Taking down chowkhats or frame not exc 1.5 sqm each with shutters (without taking off shutters from the frames) complete all as directed.
66
-
-
Taking down chowkhats or frame exc 1.5 sq. m but n exc 4 sq m each with shutters (without taking off shutters from the frames) complete all as directed.
2
-
-
S&F 35 mm thick factory made plain framed, panelled shutters with 2nd class hard wood rails and panel of 9mm BWP commercial ply 12mm thick veneered particle board with commercial veneers on both faces.The size of rail or style shall be as per IS 1003 Part-I Kiln seasoned and chemically pressure treated complete all as specified and directed
5.1
-
-
S&F second class hard wood Plain, solid, straight, chowkats and frames, wrought, framed rebated on the solid, rounded or chamfered, put together with glue pinned at joints, supplied and fixed incl cutting holes and hold fasts fixing (split at one end) complete all as specified and directed.
0.24
-
-
S&F Steel windows or ventilators, fixed type, with glazing bars etc complete all as specified and directed
28.12
-
-
S&F Steel windows with side hung shutters including projecting type hinges with steel handle, and steel peg stay, complete with glazing bars, dovetailed or welded etc complete all as specified and as directed
5
-
-
S&F Sheet glass 4mm thick ordinary quality and glazing with oil putty incl wooden beads supply & fixing in square n exc 0.5 sqm in each pane etc complete all as specified and directed.
20.02
-
-
Dismantling structural steel work including, rafter , Purlin , doors , gate but excluding framed trusse etc complete all as specified and directed.
22
-
-
S & F wind ties for roof including securing bolts, posts and struts in fencing incl cutting tops to shape as directed, drilling holes, notching for wire etc. including all necessary drilling, bolting or confirming to Fe-290 Gde E-165 complete all as specified and directed.
700
-
-
M&L for Roof trusses (framed), trussed,purlins, crane gantries, rails and fastenings and heavy bracket framing (Beam, tee, angle, channel or flat sections) including distance pieces, cleats etc. confirming to Fe 410-W(Gde-E- 250) quality-A complete all as specified and directed.
1500
-
-
M & L for two coats of synthetic enamel paint over a coat of red oxide primer on new steel surfaces incl preparation complete all as specified and directed
150
-
-
M&L for preparing old painted surfaces of steel and iron surfaces over 10 cm in width or girth by cleaning, sand papering, brushing with wire brushes, scrapping by steel scrappers etc and applying one coat of synthetic enamel paint to give an even and smooth surface having no sign of brush marks complete all as specified and directed.
100
-
-
Dismantling of Wall and ceiling boards (fibre, pulp, insulation, etc.) or insulation boards/slabs/ blankets, any thickness, including cover fillets andincluding re-fixing in position complete all as specified and directed.
42
-
-
S & F 6 mm thick Non asbestos fibre cement building boards fixed or laid/inserted to timber/GI/Alumi- nium frame work with screw as work in ceiling flat or sloping complete all as specified and directed..
42
-
-
S&F anodised aluminium snap grid frame work Size of grid 605 x 605mm for false ceiling etc complete all as specified and directed.
42
-
-
S&F 100mm butt hinges cold rolled mild steel medium weight and fixed complete all as specified and directed
12
-
-
S&F 100mm Aluminium handles, cast type, anodised complete all as specified and directed
4
-
-
S&F Aluminium anodised barrel tower bolts of extruded section 150mm long complete all as specified and directed
2
-
-
S&F 300 mm long aluminium alloy, anodised sliding door bolt with hasp staple (bolt type) and fixing clips of sheet cast or extruded section and fixing bolts and sliding bolts of extruded sections complete all as specified and directed
4
-
-
Dismantling floor or wall tiling of any description and size including cement mortar bedding (but not backing), removing rubbish off the premises com[plete all as directed.
46
-
-
Dismantling of Stone slabs and tiles of any description or thickness in floors, aprons etc including cleaning off premises where directed by Engr-in-charge.
4.6
-
-
Material and Labour for Joint free non-skid coloured ceramic tiles 7 to 8mm thick (square/rectangular) area of each tile exceeding 0.18 Sqm but not exceeding 0.38 Sqm as in flooring etc set and jointed in neat cement slurry and pointed in white or coloured cement to match the tile laid etc complete all as specified and directed
42
-
-
All as per item No 50 above but in skirting/vertical surface etc complete all as specified and directed.
4
-
-
M&L for machine cut superior quality Kota stone slab flooring 20-25 mm thick over cement screed , laid and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and mirror polishing complete match including bulnosed to edges complete and incl 20 mm thick screed bed or bedding layer in CM (1:6) complete all as specified and directed
42
-
-
M & L Kota stone slab 20-25mm thick in riser of steps, skirting, dado and pillar laid over cement screed and jointed, incl 10mm thick rendering in CM (1:4) on vertical surface for receiving complete all as specified and directed
4
-
-
M&L for 25 mm thick cement concrete type B-1, (1:2:4) (20 mm graded stone aggregate) as in sub base of tiles complete all as specified and directed.
84
-
-
Taking down exiting copper/aluminium point wiring (light, fan, socket or power) complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc. removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc as directed
124
-
-
M&L for point wiring in and including new PVC conduit medium grade with the help of multi-stranded unsheathed FRLSH copper cable 1.5 sqmm 650/1100V conforming IS:3419 -1988 adhereing to colour code including earth wire of the size 1.5 Sqmm green colored with modular steel or cast iron terminal boxes and modular cover plates as required at site including making good the distrubed surfaces and matching it with existing surface for the following :- (a) One light/Fan point controlled by one way switch 6 Amps 240 volts
78
-
-
(b) One 3 pin socket outlet, 5/6 Amps on the same board with other switches
2
-
-
(c ) One 3 pin socket outlet, 5/6 Amps, independent
8
-
-
(d) M&L point wiring for one 3 pin socket outlet 15 Amp Independent with 4 sq mm copper conductor FRLSH (multistrand) PVC insulated ISI marked unseathed cable in and including PVC conduit not less than 25 mm with all fitting & other accessories and also including PVC insulated ISI marked unseathed FRLS cable size 4 sq mm copper conductor as earth wire to common earth dolly all as specified by Engr-in-charge.
36
-
-
S&F modular switch 1 way 10 A 1 module complete all as specified and directed.
88
-
-
S&F Modular socket 6 A 2/3 Pin 2 module complete all as specified and directed.
10
-
-
S&F modular switch 1 way 16 A 1 module complete all as specified and directed.
36
-
-
S&F Modular socket 6 A/16A 2/3 Pin 2 module. complete all as specified and directed.
36
-
-
S&F modular fan regulator, 2 module, suitable for ceiling fan of 1200/1400mm sweep complete all as specified and directed.
8
-
-
S&F in replacement for ceiling rose, 3 terminals / PVC / Polycarbonate, isolated body complete all as specified and directed.
78
-
-
S&F in replacement of 18/20watt,230V surface and wall mounted LED batten, extruded aluminium housing with polycarbonate diffuser and integrated electronic driver including connecting up with twin core twisted flexible copper condctor cable from ceiling rose complete all as specified and directed. Make- Luker LT5M20 or equivalent make as mentioned in makes list in PS
47
-
-
S & F in replacement of 150 watts flood light, LM6 aluminium or higher grade powder coated and water proof pressure die cast aluminium enclosure, with inbuilt electronic drivers and IP 66 protection complete ,Single phase, etc fixing in MS chanel by drilling hole of suitable , size, using nut, bolts and washers of suitable size including suitable mounting structure on existing pole as reqd at the site complete all as specified and directed Make: Luker-LFL150LN5Y or equivalent make as mentioned in makes list in PS
14
-
-
S&F in replacement LED building security Sensor light fiitting 24 W, IP-65 protection made up of die cast alluminium housing with high power LED as lighting source and lens embeded PC cover having seperate driver compartment complete fixing with GI bracket made out of suitable GI pipe light grade suitable length bend to shape and fixed to pole/wall with necessary MS clamp accessories complete all as specified and directed by Engr-in-charge Make- Luker LST-24SEN or equivalent make as mentioned in makes list in PS
16
-
-
Dismantling and refixing the ceiling fan/Exhaust Fan complete of any type and size , cleaning, servicing, painting greasing to bearings checking of nuts bolts , safety split pin, bushes , capacitor and complete spray painting as directed by Engr-in- charge.
Note :- Expendable stores like cotton waste/cleaning materials, grease, lubricants, machine screws, safety split pin, bots/nuts and transportation to and from site to work place are deemed to be included in rate quoted.
2
-
-
Supply and fixing ceiling fan complete with blades, down rods and other accessories, 230 V, 1200 mm sweep with Minimum air delivery of 210 CMM BEE Five star rated with brushless direct current motor (BLDC), white/Ivory in colour all as specified and directed .
Note:- Old U/s fan dismantled from site and deposited at MES store Yard.
6
-
-
Supply and fixing Metal body exhaust fan, AC single phase, 240 V,900 RPM, size 300 mm sweep double ball bearing with louvers all as specified and as directed . Note:(i) Separate louvers of suitable size is to be provided and the cost of same is deemed to be included .
1
-
-
M & L for Making of hole for fixing of New exhaust fan / Shifting of exhaust fan from one place to another place required at site making good the disturbed surfaces all as specified and directed
1
-
-
Taking down exiting copper/aluminium sub main wiring complete for taking credit (credit for above items should be made as per conditions separately) and making good disturbed surfaces of walls, floors, etc complete all as specified and directed
530
-
-
M&L for sub main wiring with two single core PVC insulated FRLS cables with stranded copper conductors 2.5 Sqmm , 1100 Volts grade in and including PVC conduit medium grade with all fitting & other accessories and copper cable 2.5 sqmm continuous earth wire complete all as specified and directed Note:Two runs of 2.5 Sqmm cable with 01run of 2.5 Sqmm earth wire along with PVC conduit medium grade shall be measured as one RM
400
-
-
M&L for sub main wiring with two single core PVC insulated FRLS cables with stranded copper conductors 4 Sqmm , 1100 Volts grade in and including PVC conduit medium grade with all fitting & other accessories and copper cable 4 sqmm continuous earth wire complete all as specified and directed . Note: Two runs of 04 Sqmm cable with 01run of 4 Sqmm earth wire along with PVC conduit medium grade shall be measured as one RM
80
-
-
M&L for sub main wiring with Two single core PVC insulated FRLS cables with stranded copper conductors 6 Sqmm , 1100 Volts grade in and including PVC conduit medium grade with all fitting & other accessories and copper cable 6 sqmm continuous earth wire complete all as specified and directed . Note: Two runs of 06 Sqmm cable with 01 run of 6 Sqmm earth wire along with PVC conduit medium grade shall be measured as one RM
50
-
-
Supply and fix in replacement sheet metal enclosures double pole MCB 20 Amps with a two pin and earth plug and socket complete with all accessaries etc all as specified and directed . Make: Legrand Cat part: 5078 10 or equivalent make as mentioned in makes list in PS
1
-
-
S&F in replacement MCB DB 8 way SPN Double door sheet metal enclosure factory made suitable for MCB DB's 240 volts,concealed in wall complete including taking down the existing DB of any type & size alongwith its accessories by removing from existing circuits and refixing the new DBs and circuits complete as reqd at site complete all as specified and directed . .
Note - MCBs will be measured & paid separately under respective item of sch A, if required to be replaced.
6
-
-
S&F replacement MCB DB 02 way SPN single door sheet metal enclosure factory made suitable for MCB DB's 240 volts with 200 amp rated busbar, neutral & earthing link bar,surface mounting complete including taking down the existing DB of any type & size alongwith its accessories by removing from existing circuits and refixing the new DBs and existing circuits complete as reqd at site complete all as specified and directed
14
-
-
S&F MCB DB 04 way SPN single door sheet metal enclosure factory made suitable for MCB DB's 240 volts with 200 amp rated busbar, neutral & earthing link bar,surface mounting complete including taking down the existing DB of any type & size alongwith its accessories by removing from existing circuits and refixing the new DBs and existing circuits complete as reqd at site complete all as specified and directed
2
-
-
S&F MCB SP 6 to 32 Amps 240V,10 KA breaking capacity , B curve as per IS/IEC 60898-1 2002 with IP 20 protected terminals all as specified including complete connection with copper /aluminium cable lugs with suitable size for incoming and outgoing complete all as specified and directed
36
-
-
Supply and fix in replacement of C Curve MCB SPN 40 Amps working on 240 volts, 50 HZ,10 KA all as specified and directed
6
-
-
Supply and fix in replacement of C Curve MCB SPN 32 Amps working on 240 volts, 50 HZ,10 KA all as specified and directed
14
-
-
S&F MCB TPN 40 Amps 415V,10 KA breaking capacity , C curve as per IS/IEC 60898-1 2002 with IP 20 protected terminals all as specified including complete connection with copper /aluminium cable lugs with suitable size for incoming and outgoing complete all as specified and directed.
2
-
-
Supply and installing 300mm width x 50mm depth x 2mm thickness size of perforated hot dipped Galvanised Iron cable tray (Galvanisation thickness not leass than 50 microns) with perforation not more than 17.5% inconenient sections, jointed with connectors, suspended from the ceiling with GI suspenders including GI Bolts & nuts as required all as specified and directed.
Note : 1. All necessary fixing/ connecting arrangements of nut, bolt, MS rod, to be provided by the contractor without any extra payment from department.
2. Quoted rate is to be deemed the charges of necessary boom lift.
80
-
-
Earthing complete with galvanised iron earth plate electrode 600 x 600 x 6mm as earthing lead buried directly in ground vertically to depth not less than 2.25 mtr below GL with the top edge of the plate not less than 1.5 mtr from GL, connected to GI earth lead of 4.0mm dia, by means of bolts & nuts, to GI and connected to earthing test point all as shown in elecrical plate No. 3 of SSR Part-I of 2009* specified or indicated and testing on completion including excavation / earth work in any type of starta, PCC (1:3:6) type C1 earthing chamber pre cast slab 50 mm thick in cement concrete (1:2:4) type B1, reinforced with welded steel wire fabric (XPM) weight not less than 4 KG/sqm cast iron frame, funnel with wire mesh GI watering pipe of 20 mm bore medium grade and lugs with and including GI earth wire 4 mm dia with GI protection pipe of 15 mm medium grade 7.5 meter long etc complete tested on completion all as specified and directed.
Note: 1. Rate quoted shall deemed to include cost of excavation in any type of strata, RFR and removal upto 50metre, PCC pit, funnel and RCC cover plate. 2. GI wire above 7.5m will be measured and paid seperately.
2
-
-