Military Engineer Services Tender

Search from over 12139+ business opportunities that have been announced from the biggest Mahatenders, e tender Maharashtra, Maharashtra government tenders, and the Online Tender Notices posted on Maharashtra e tenders till date. Find opportunities that have come in from the multiple corporations, Maharashtra government departments, State PSUs, and Private companies from the state.

Military Engineer Services - MES Tender

Works
Electrical and Electronics
Eprocure
Opening Date31 Aug 2024
Closing Date8 Oct 2024
Tender Amount₹ 45,00,000 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
M&L for applying evenly 0.30 ltr per Sqm of bitumious primer over plastered suraces of Roof surfaces complete all as specified and as directed.

534

-

-

... More
M & L for Applying evenly a tack coat of industrial bitumen 85/25 at the rate of 1.2 kg per sq.m including cleaning surfaces complete all as specified and as directed.

534

-

-

... More
S & F APP based polymeric membrane minimum weighing 3kg/sqm and minimum 3mm thick reinforced with polyster non wove fabric (wt. not less than 150 gms/sqm) laid on primed surface complete all as specified and directed.

2

-

-

... More
Dismantling of water tanks and removing to store of capecity exc 250 Ltr but not exc 500 Ltr complete all as specified and as directed.

100

-

-

... More
M & L for cutting "V" grooves in brickwalls / stone masonery / RCC 75mm wide and 20-30mm deep and filling with cement mortar 1:3 mixed with WPC on vertical surfaces for fixing the edges of water proofing membrane complete all as specified and as directed.

2

-

-

... More
S&F in repair 20 mm dia float valve high pressure of PTMT with epoxy coated aluminium rod & high density plastic ball screwed for iron pipe and fixed (minimum weight 15mm - 142 gms / 20mm -210 gms / 25mm - 455 gms /40 mm - 690 gms / 50 mm - 1240 gms) complete all as specified and as directed.

2

-

-

... More
S&F in repairs gun metal globe or gate valves of 20mm dia pipes with iron wheel head screwed both ends for iron pipe or for unions, fixed in repairs etc complete all as specified and as directed.

30

-

-

... More
Taking down GI tubing "medium grade" galvanized with all fittings and fixed complete to walls and ceiling or laid in floors etc. of the 20 mm bore pipe complete all as specified and as directed.

30

-

-

... More
S&F GI tubing "medium grade" galvanized with all fittings and fixed complete to walls and ceiling or laid in floors etc. of the 20 mm bore of pipe complete all as specified and as directed.

2

-

-

... More
S & F Rotational moulded polythene water storage tanks of 500 ltr capacity, tripple layer (ISI Marked), cylindrical vertical with closed top hoisted and fixed in position complete all as specified and as directed.

16

-

-

... More
Taking down of chowkat with shutter without taking off shutters from the frame n exceeding 1.50 Sqm with shutters without taking off shutters from frame complete all as specified and as directed.

50

-

-

... More
S & F powder coated Anodised aluminium frame for doors,windows, ventilators with one or more rebates, alu beadings and aluminium grills including joining cleat for fixing etc. complete all as specified and as directed.

3

-

-

... More
S & F 4.80 mm Sheet glass, ordinary quality, tinted and glazing with rubber beading to Alu windows/ doors in square etc complete all as specified and as directed.

534

-

-

... More
M & L for Applying two coats of Aluminium paint over APP membrane incl preparation of surfaces complete all as specified and as directed.

7

-

-

... More
M & L for steel tubular swaged pole 410 SP-55 (11.0 metre long) including CI base plate, final taper plug, bolts, nuts & screws as per IS 2713 Part -I & II including cross arms, GI brackets, PCC coping complete all as specified and as directed comprising the following: -

2.5

-

-

... More
Ser. Item No. 18.00 Contd.... (a) Two coats of synthetic enamel paint in white colour over a coat of primer on PCC coping (b) Making 4 Nos of strips of 30 cm wide in alternate red and white colour using two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer (c) Providing 30 cm wide retro reflective sheet of 30 cm wide, grade 1, pressure bonding type, red colour as per IS 14221: 1995 (d) Two coats of synthetic enamel paint in red colour over a coat of primer from top of electric pole to downward upto 1 metre length including cross arms, GI brackets etc. (e) Writing pole number and voltage level encompassed by circle of suitable dia using two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer (the colour of base shall be black and the colour of font shall be white). Number and voltage level shall be handwritten, and circle shall be stencilled. (f) Painting with two coats of aluminium paint over a coat of aluminium red oxide primer on remaining exposed portions

-

-

-

... More
M & L for cross arms, bracings, supports, clamps, back plates and stay clamp fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and applying two coats of aluminium paint over a coat of red oxide primer complete all as specified and as directed.

0.35

-

-

... More
M&L for Anti-climbing device; spikes type fabricated out of M.S. bars (round, square and flat) including nuts,bolts, washers and welding in two halves made to shape to suit the cross section of the pole complete all as specified and as directed.

2

-

-

... More
S & F gang operated air break switch as per IEC 62271-103 amended upto date, rocking/ tilting type, suitable for both horizontal and vertical mounting, three poles, outdoor type, nominal system voltage 22 kV, rated frequency 50 Hz, continuous current rating 200 Amps, minimum isolating distance in open position 520 mm, phase to phase clearance 1220 mm, minimum cross sectional area of fixed contact 300 sqmm, minimum cross sectional area of moving contact 250 sqmm, copper connector having minimum cross sectional area of 250 sqm, maximum current density of 1.6 Amps/ sqmm for all current carrying parts, single number of brake per phase, medium grade galvanised iron pipe of 32 mm nominal bore and 5 to 6 metre length in single piece for operating pipe, pad-locking in both ‘on’ and ‘off’ position with indicators, electroplated nonferrous parts, hot dip galvanised ferrous parts, 3 Nos porcelin post insulator per phase as per IEC 61109 amended upto date having rated voltage 22 KV, complete all as specified and as directed.

2

-

-

... More
Supply and fix metal oxide lighting arrester without gap for AC system as per IEC 60099-4: 2014, outdoor type, Porcelin housing, single column and single phase construction, distribution class, heavy duty, nominal discharge current 10 kA, repetitive charge transfer rating (Qrs) more than 0.4 C, thermal charge transfer rating (Qth) more than 1.1 C, nominal system voltage 22 kVcomplete all as specified and as directed.

2

-

-

... More
Supply and fix in repairs DO fuse assembly, suitable for horizontal and vertical operation, triple pole mounted on Porcelin HT insulator 6 Nos and mild steel galvanised steel frame rating upto 200 Amp, 22 kV complete with DO fuse and electrical connections, jumpering by ACSR conductor and connectors complete all as specified and as directed.

12

-

-

... More
S & F 22 KV polymeric composite pin insulator, conforming to IEC 61109, material of core (FRP rod): borron free ECR, material of sheds: silicon rubber, material of top end fittings: spheroidal graphite cast iron, malleable cast iron or forged steel, material of bottom end fittings: forged steel, sealing compound for end fitting: RTV Silicon, colour of sheds: grey, rated voltage: 22KV, complete all as specified and as directed.

20

-

-

... More
M&L for HT bus bar for 2/4/6 pole structure made out of aluminium tube having outer dia 32 mm and 06 mm thick suitable for 22 KV complete with all suitable joints with SS nut bolts etc and colour sleeves as per colour coding complete all as specified and as directed.

44

-

-

... More
M&L for aluminium strip 25x3.15 mm with PVC sleeves for jumpering purpose fixing to pole by means of clamp, nut bolts& washers etc of suitable size complete all as specified and direction.

20

-

-

... More
M&L for Galvanised iron strip 32 x 6mm with PVC sleeves & fixing of pole by mean of nut bolt and waher etc of suitable size for LA earthing purpose etc complete all as per the direction of Engineer-in-charge

1

-

-

... More
Supply, install, test and commissioning copper wound, step down transformer outdoor type complete with standard fittings, HT,22KV, 3 phase, LT, 433 V, 3 Phase, 4 wire with off loadtap changer on primary side to vary secondary voltage + 7.5% with tapings at every 2.5% rating of capacity 100 KVA. The transformer shall be complete with all standard fitting and accessories, gauges first fill of transformer oil upto appropriate level etc., all as per IS-1180 Level 1 and all jointing materials connected with elect system earthing etc. complete including platform as per manufacturer design all as specified and directed comprising following accessories:-

14

-

-

... More
Ser. Item No. 28.00 Contd.... (a) One cable box HV side consisting of 3 Nos porcelain terminal points including nuts, bolts and washers with two Nos cable gland suitable for 3 core 150 sqmm HT UG cable. (b) Suitable cable box LV side for mounting two LV cable consisting of 4 Nos porcelain with brass bushing rods, complete with nuts and washers with two nos cable gland suitable for LT UG cable providing with bimettalic lugs. (c) Oil conservator with filler type drain valve and oil level gauge. (d) Dehydrating breather with fast fill of dehydrating agent. (e) Explosion vents (f) Thermometer pocket on tank cover including thermometer. (g) Rating plate and terminal marking plate. (h) The earthing terminal two Nos to faciliate fixing of earth strip (i) Oil level gauge (j) Lifting lugs (k) Oil filling hole with cap/plug with connection plate complete. (l) Air relief valve plug (m) Initial filling of transformer oil of dielectric strength not less than 60 KV. (Note :- (i) Suitable size concrete foundation shall be made as per direction of Engineer-in-Charge. (ii) The rate quoted by the contractor shall deemed to be included the cost of PCC foundation. No extra payment shall be made on this account.)

-

-

-

... More
M & L for earthing complete with galvanised steel plate earth electrode 600 mm X 600 mm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to earthing lead of 32 mm X 6 mm galvanised mild steel strip by means of bolts, nuts, check nuts and washers of galvanised iron from earth plate to test point upto 7.5 metre including all as shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete chamber in cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate, precast RCC cover slab in cement concrete M15 (Nominal mix) using 20 mm nominal size coarse aggregate of size 40 cm X 40 cm X 5 cm reinforced with 8 mm dia TMT bars @ 150 mm c/c both ways with one handle for lifting made out of 8 mm dia bar, GI funnel, GI wire mesh filter, 20 mm dia GI pipe medium grade for watering, 40 mm dia GI pipe medium grade for protection of earthing lead, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil/ strata and testing complete all as specified and as directed by the Engineer-in-charge. (Note :- On testing after completion if the desired earth resistance( 1 Ohm)not obtained the earthing will be redone at no extra cost. Testing tools shall be arranged by the contractor at own cost.

2

-

-

... More
Supply,installing,commisnning and testing of Advance Maintenance Free environment friendly ring Earthing system.Each set consisting of 3 Nos of 10 feet length, 17.0 mm dia earth electrode made of high tensile low carbon steel circular rods, molecularly bonded copper on outer surface (minimum copper bonding thickness-250 microns) with terminals to connect incoming strips with 3 bags (25 Kgs each) of environment freindly backfill compound with RoHs test cerificate for each. 150x25x6 mm Cu Bar with 4 hole shall be exothermically welded ontop to copper bonded rod to make terminal. Manufacturar name shall be embosed on rod.25x3 mm Cu shall be used to intercorrect the earths and to make the ring. If desired Ohmic value ( 1 Ohm ) should not achive by this then multiple number of earthing electrode shall be interconnected .The earth pit cover polypropeline (300mm x 300mm) shall be included in the scope of work . (Note :-On testing after completion if the desired earth resistance ( 1 Ohm) not obtained the earthing will be redone at no extra cost. Testing tools shall be arranged by the contractor at own cost.)

480

-

-

... More
Supply, laying and testing cross linked polyethylene (XLPE) insulated, PVC sheathed cables for working voltages 22KV, three phase, earthed system, 3 core, screened, armoured power cable, 120 sqmm of nominal area of conductor, aluminium conductor, ISI marked as per IS 7098 (Part-II): 2011 laid in trenches or under floors making all connections with necessary glands, lugs, bushing etc complete all as specified and as directed.

4

-

-

... More
Supply and fix cable jointing kit for 22 KV grade cable for outdoor termination, heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 120 sqmm complete all as specified and as directed.

90

-

-

... More
Supply and laying & testing and commisioning LT underground cable 1100 volts grade, XLPE insulated and PVC sheathed heavy duty armoured with multi staranded aluminium conductor laid in pipes, of 3.5 core x 240 sqmm complete all as specified and as directed.

67

-

-

... More
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth (for cable, pole, stay etc) not exc. 10 sqm on plan and getting out in soft/loose soil complete all as specified and directed.

113

-

-

... More
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth (for cable, pole, stay etc) not exc. 10 sqm on plan and getting out in hard dense soil complete all as specified and directed.

5

-

-

... More
Excavation in trenches not exceeding 1.5 m wide and exceeding 1.5 m in depth and getting out in hard dense soil complete all as specified and directed.

159

-

-

... More
Returning, filling in including spreading, leveling, watering and well ramming in layers not exceeding 25 cm each complete all as specified and directed.

26

-

-

... More
Removing excavated soil not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.

490

-

-

... More
M&L for laying reinforced concrete pipes , class NP2 of dia 100 mm , 2 nos half round (for bottom and top for cable protection) and levelling of excavated area complete all as specifiedn and as specified by Engr-in-Charge

50

-

-

... More
S&F pipe galvanised iron light grade 80 mm dia ( ISI marked )with all fittings laid in trenches or on pole, crossing of road,fixed on wall for protection of cables including necessary road cutting work and making good with PCC 1:2:4 , type B-1 , using 20 mm graded stone aggregate, fixing on wall/poles of any type, secured with clamps etc complete all as specified and directed by Engr-in-Charge

5

-

-

... More
M & L plain cement concrete (1:4:8) type D-2 using 40mm graded stone aggregate as in base of pole or in any situation all as specified and directed by Engr-in-Charge

2

-

-

... More
M & L plain cement concrete (1:2:4) type B-1 using 20mm graded stone aggregate as in coping including necessary form work or in any situation all as specified and directed by Engr-in-Charge

1

-

-

... More
Supply,installing, testing and commissioning of outdoor type free standing weather proof, dust and vermin proof LT cubicle/ Modular construction fully compartmentalized panel out door type,with bus bar chamber and cable ally on both side, IP-54 and all as per IE rules fabricated with 3.0 mm CRCA double door type (Front side ; out side with main panel door and inside with compartmentlised door for each cubicle ) (Rear side main panel door and inside bolted door for each cubicle) Sheet for load bearing members and 2 mm thick for doors and covers and shall be powder coated with 7-tank process on all internal and external surfaces. the panel to be suitable for 1100 volt grade, 3 phase, 415 volts, 50 cycles AC supply. The panel shall be provided with MS angle iron frame 50x 50x 6 mm welded in shape and including necessary grouting in PCC 1:3:6 type C-1 with 20 mm grade stone aggregate completed with legs 30 cm in ground in PCC and 40 cm above ground including connecting to cable with cable gland, lugs etc”and comprising the following :

534

-

-

... More
Ser. Item No. 43.00 Contd.... (a) Aluminium bus bar cap 500 Amp-04 Nos, (b) MCCB three pole with thermal magnetic release adjustable type with breaking capacity 35 KA, 250 Amp with rotary handle - (incoming) 01 nos. (c) MCCB three pole with thermal magnetic release adjustable type with breaking capacity 35 KA, 200 Amp with rotary handle - (outgoing) 01 nos. (d) MCCB three pole with thermal magnetic release adjustable type with breaking capacity 25 KA 100 Amp -02 Nos.(Out going) (e )MCB SPN 16 Amps - 02 nos (f) Digital Voltmeter-96 x 96 mm flush secure Panel mounting type 0-500V with selector switch - 01 nos. (g) Digital Amp meter 96 mm X 96 mm flush secure Panel mounting type with selector switch with CT - 01 nos. (h) RYB neon indicating lamp set of three- 01 set

-

-

-

... More
Supply, Installation, testing and commissioning of Higher efficient models of SPLIT AC FIVE STAR rating of BEE (Beureu of Energy Efficient) Air Conditioners 2 Ton Machines confirming to latest Indian Standards and suitable for operation on 230 Volts ± 10%, single phase, 50 Hz AC supply with rotary compressor, Refrigerant 410 A/R-32 and capable to perform cooling, dehumidifying, Air Circulating, Auto Mode, Auto Swing, Anti Bacteria Filtering, Ventilation and circulating, auto mode, auto swing, anti bacteria filtering, ventilation with remote control including cool/Fan/Dry/Auto mode, sleep & On/Off timer with suitable thermostat. The Out Door unit should be Anti-rust powder coated. Indoor Unit should have LED Display and complete connection with 4 Sqmm 3 core cable outdoor unit to socket outlet. The quoted rates includes installation charges after making hole in wall, minor capentary and civil work and U PVC drain piping of 25mm bore with insulation as site requirement with its all accessories like bend, solution etc as per site condition complete all as specified and as directed by Engr-in-Charge.

7

-

-

... More
Supply and fix voltage stablizer for automatic operation, single phase naturally air cooled indoor type and designed for inpur variation between 170 volts to 250 volts with out put voltage stablized at 230 volts with accuracy of + 2.5% and capacity 5 KVA suitable for A/C including all accessories with installation suitable for wall mounting complete all as specified.

7

-

-

... More
Supply and fixing earthed metal clad socket outlet with earthed plug top 20Amp capacity , sheet metal enclosed and one 20 Amp MCB SP all as specified and diredted.

140

-

-

... More
M&L for sub main wiring with approved colour coding as per IS with two single core PVC insulted FRLS cable with stranded copper conductor of size 4 Sqmm nominal cross sectional area, 1100 volts grade, stranded, PVC insulated, unsheathed copper conductor FRLS flexible wiring cable conformingto IS:694-1990 with ans including continuous earth wire of size 4 Sqmm nominal cross sectional area, single core, PVC insulated, copper conductor cable and including ISI marked PVC casing caping including fitting in wall etc and connected to common earth dolly making good to match the existing complete all as specified and as directed. (Note : 1. Three runs of 4 Sqmm cable incl. earth wire & one run of PVC Cassing Capping will be measured as one unit length.)

7

-

-

... More
S&F fabricated/ factory made angle iron stand suitable for fixing/mounting to outdoor unit of split AC, including grouting nut bolts, etc. complete all as specified and as directed.

60

-

-

... More
M & L for copper tubing, confirming to relevant IS, of size 5/8 & 3/8" flare size or nearest size, 3 core 2.5sqmm copper cable, PVC drain pipe and insulation with superlon insulation to copper tubing as required length from indoor to outdoor unit of split AC complete as directed by Engineer in charge.

1

-

-

... More
S&F IP-54, IK 09, protection metal double door Vertical TPN -DB rated busbar, 415 volts, 50 HZ complete with interconnection links, blanking plates, cable ties, identification labels TPN 4 way, 12 modules suitable for accommodating 100 Amps MCCB 4 pole as incomer and SP/TP MCB as out going and concealed in wall including all cutting holes in or through walls, making good to walls, ceiling etc including two coats of white / colour washing / distempering etc to the disturbed surfaces to match the existing finishes complete all as specified and as directed.

1

-

-

... More
Supply and Fix MCCB 100 Amps, 16 KA, 4 Pole,415V, electronic protection unit complete all as specified and as directed.

7

-

-

... More
S & F MCB Single pole rated capacity 5 to 32 amps, 240 Volts breaking capacity 10 KA complete all as specified and as directed.

50

-

-

... More
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35.0 sq mm 3.5 core fixed in wall with MS saddles complete all as specified and as directed.

2

-

-

... More
M & L for earthing complete with galvanised steel plate earth electrode 600 mm X 600 mm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level,connected to and incld GI wire 4 mm dia and GI pipe 15 mm dia light grade for protection to extent of 7.5m as earthing by means of nut and boltsetc connecting to equipment with provn of charcoal and salt all as per electrical plate no 3 of SSR part I incld RCC cover and MS angle iron frame ,watering arrangementswith GI pipe 20 mm dia and MS funnel,concete pit incld excavation and earth work in any type of soil/ strata and testing complete all as specified and as directed by the Engineer-in-charge. (Note :-(On testing after completion if the desired earth resistance is not obtained the earthing will be redone at no extra coast. Testing tools shall be arranged by the contractor at own cost.)

800

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.