Military Engineer Services Tender
Search from over 12139+ business opportunities that have been announced from the biggest Mahatenders, e tender Maharashtra, Maharashtra government tenders, and the Online Tender Notices posted on Maharashtra e tenders till date. Find opportunities that have come in from the multiple corporations, Maharashtra government departments, State PSUs, and Private companies from the state.
Military Engineer Services - MES Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date27 Nov 2024
Closing Date23 Dec 2024
Tender Amount₹ 88,00,000
Costs
EMD
₹ 1,57,000Document Cost
₹ 1,000Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_685908_1Tender No
8225/CWE(NW)MUMBAI/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
All as per Item No.1.00 above but for near R22 Bldg and scope of work including provision of housing the following accessories:-
Incoming: - (i) MCCB 630 Amp 4 pole 36 KA 415 V with microprocessor release having protection against over current, earth fault, short circuits and inbuilt battery and display system - 01 No. (ii) On Load Changeover switch 630 Amp, 415V, 4 pole with open execution with front handle - 01 No. (iii) Digital type Voltmeter ( 0-500 Volts), 3 phase, 4 digit, high resolution, LED type with onsite programmability- 01 Nos. (iv) Digital type Ampermeter ( 0-300 Amps) three phase with copper wound CT coil assy of suitable ratio & size Class I accuracy, 0.5 VA burden & onsite programmability - 01 Nos. (v) Indicating lamp LED type with holder key flush mounted, Red, Yellow, blue with toggle switch - 1 set (set of three) as in incoming phases.
(vi) Tinned copper bus bar strips made of copper of size not less than 60x10mm of suitable length-04 Nos Outgoing: - (i) MCCB 200 Amp 4 pole 36 KA 415 V with thermal magnetic release, Ics=100% Icu.- 05 No. (ii) MCCB 100 Amp 4 pole 36 KA 415 V with thermal magnetic release, Ics=100% Icu.- 04 No.
(iii) Power contactor 4 pole 32 Amp, 415 V - 01 No. (iv) Analog time switch 3 module - 01 No. (v) MCB 10 Amp SPN 10 KA 230 V with thermal magnetic release, Ics=100% Icu.- 02 No.s
(vi) MCB 40 Amp 3P 10 KA 415 V with thermal magnetic release, Ics=100% Icu. - 02 No.s
(vii) All outgoing MCCB shall be connected through spreader and copper busbar not less than 5 mm thick strip.
1
-
-
Note :- (i) Before fabrication of panel the contractor has to take approval from GE on drawing. (ii) All existing cable connections will be disconnected from old Panel carefully and re-connected with new Panel by providing glands and thimble all as directed by Engineer-in-Charge.
-
-
-
All as per Item No.1.00 above but for R3 Garden and scope of work including provision of housing the following accessories:-
Incoming: - (i) MCCB 630 Amp 4 pole 36 KA 415 V with microprocessor release having protection against over current, earth fault, short circuits and inbuilt battery and display system - 01 No. (ii) On Load Changeover switch 630 Amp, 415V, 4 pole with open execution with front handle - 01 No. (iii) Digital type Voltmeter ( 0-500 Volts), 3 phase, 4 digit, high resolution, LED type with onsite programmability- 01 Nos. (iv) Digital type Ampermeter ( 0-300 Amps) three phase with copper wound CT coil assy of suitable ratio & size Class I accuracy, 0.5 VA burden & onsite programmability - 01 Nos. (v) Indicating lamp LED type with holder key flush mounted, Red, Yellow, blue with toggle switch - 1 set ( set of three) as in incoming phases.
(vi) Tinned copper bus bar strips made of copper of size not less than 60x10mm of suitable length-04 Nos Outgoing: - (i) MCCB 200 Amp 4 pole 36 KA 415 V with thermal magnetic release, Ics=100% Icu.- 07 No. (ii) MCCB 100 Amp 4 pole 36 KA 415 V with thermal magnetic release, Ics=100% Icu.- 02 No. (iii) MCB 32 Amp SPN 10 KA 230 V with thermal magnetic release, Ics=100% Icu.- 04 No.s
(iv) MCB 40 Amp TP 10 KA 415 V with thermal magnetic release, Ics=100% Icu.- 02 No.s (v) All outgoing MCCB shall be connected through spreader and copper busbar not less than 5 mm thick strip. Note :- (i) Before fabrication of panel the contractor has to take approval from GE on drawing. (ii) All existing cable connections will be disconnected from old Panel carefully and re-connected with new Panel by providing glands and thimble all as directed by Engineer-in-Charge.
1
-
-
All as per Item No.1.00 above but for near R39 Bldg and scope of work including provision of housing the following accessories:-
Incoming: - (i) MCCB 630 Amp 4 pole 36 KA 415 V with microprocessor release having protection against over current, earth fault, short circuits and inbuilt battery and display system - 01 No. (ii) On Load Changeover switch 630 Amp, 415V, 4 pole with open execution with front handle - 01 No.
1
-
-
(iii) Digital type Voltmeter ( 0-500 Volts), 3 phase, 4 digit, high resolution, LED type with onsite programmability- 01 Nos. (iv) Digital type Ampermeter ( 0-300 Amps) three phase with copper wound CT coil assy of suitable ratio & size Class I accuracy, 0.5 VA burden & onsite programmability - 01 Nos. (v) Indicating lamp LED type with holder key flush mounted, Red, Yellow, blue with toggle switch - 1 set ( set of three) as in incoming phases.
(vi) Tinned copper bus bar strips made of copper of size not less than 60x10mm of suitable length-04 Nos Outgoing: - (i) MCCB 630 Amp 4 pole 36 KA 415 V with thermal magnetic release, Ics=100% Icu. - 01 No. (ii) MCCB 200 Amp 4 pole 36 KA 415 V with thermal magnetic release, Ics=100% Icu.- 05 No.
(iii) MCCB 100 Amp 4 pole 36 KA 415 V with thermal magnetic release, Ics=100% Icu. - 07 No. (iv) MCB 32 Amp SPN 10 KA 230 V with thermal magnetic release, Ics=100% Icu. - 04 No.s (v) MCB 40 Amp TP 10 KA 415 V with thermal magnetic release, Ics=100% Icu.- 02 No.s
(vi) All outgoing MCCB shall be connected through spreader and copper busbar not less than 5 mm thick strip. Notes :- (i) Before fabrication of panel the contractor has to take approval from GE on drawing. (ii) All existing cable connections will be disconnected from old Panel carefully and re-connected with new Panel by providing glands and thimble all as directed by Engineer-in-Charge.
-
-
-
All as per Item No.1.00 above but for motivation hall complex and scope of work including provision of housing the following accessories:-
Incoming: - (i) MCCB 400 Amp 4 pole 36 KA 415 V with thermal magnetic release, Ics=100% Icu. - 01 No. (ii) On Load Changeover switch 400 Amp, 415V, 4 pole with open execution with front handle - 01 No. (iii) Digital type Voltmeter ( 0-500 Volts), 3 phase, 4 digit, high resolution, LED type with onsite programmability- 01 Nos. (iv) Digital type Ampermeter ( 0-300 Amps) three phase with copper wound CT coil assy of suitable ratio & size Class I accuracy, 0.5 VA burden & onsite programmability - 01 Nos. (v) Indicating lamp LED type with holder key flush mounted, Red, Yellow, blue with toggle switch - 1 set ( set of three) as in incoming phases.
(vi) Tinned copper bus bar strips made of copper of size not less than 50x10mm of suitable length-04 Nos
1
-
-
Outgoing: - (i) MCCB 160 Amp 4 pole 36 KA 415 V with thermal magnetic release, Ics=100% Icu. - 01 No. (ii) MCCB 100 Amp 4 pole 36 KA 415 V with thermal magnetic release, Ics=100% Icu.- 04 No.
(iii) MCB 32 Amp SPN 10 KA 230 V with thermal magnetic release, Ics=100% Icu. - 04 No.s (iv) MCB 40 Amp TP 10 KA 415 V with thermal magnetic release, Ics=100% Icu. - 02 No.s (v) All outgoing MCCB shall be connected through spreader and copper busbar not less than 5 mm thick strip. Notes :- (i) Before fabrication of panel the contractor has to take approval from GE on drawing. (ii) All existing cable connections will be disconnected from old Panel carefully and re-connected with new Panel by providing glands and thimble all as directed by Engineer-in-Charge.
-
-
-
All as per Item No.1.00 above but for near R8 Bldg and scope of work including provision of housing the following accessories:-
Incoming: - (i) MCCB 630 Amp 4 pole 36 KA 415 V with thermal magnetic release, Ics=100% Icu. - 01 No. (ii) On Load Changeover switch 630 Amp, 415V, 4 pole with open execution with front handle - 01 No. (iii) Digital type Voltmeter ( 0-500 Volts), 3 phase, 4 digit, high resolution, LED type with onsite programmability- 01 Nos. (iv) Digital type Ampermeter ( 0-300 Amps) three phase with copper wound CT coil assy of suitable ratio & size Class I accuracy, 0.5 VA burden & onsite programmability - 01 Nos. (v) Indicating lamp LED type with holder key flush mounted, Red, Yellow, blue with toggle switch - 1 set ( set of three) as in incoming phases.
(vi) Tinned copper bus bar strips made of copper of size not less than 60x10mm of suitable length-04 Nos s Outgoing: - (i) MCCB 250 Amp 4 pole 36 KA 415 V with thermal magnetic release, Ics=100% Icu.- 04 No. (ii) MCCB 200 Amp 4 pole 36 KA 415 V with thermal magnetic release, Ics=100% Icu.- 04 No.
(iii) MCCB 100 Amp 4 pole 36 KA 415 V with thermal magnetic release, Ics=100% Icu.- 02 No. (iv) MCB 32 Amp SPN 10 KA 230 V with thermal magnetic release, Ics=100% Icu.- 04 No.s (v) MCB 40 Amp TP 10 KA 415 V with thermal magnetic release, Ics=100% Icu.- 02 No.s
1
-
-
(vi) All outgoing MCCB shall be connected through spreader and copper busbar not less than 5 mm thick strip. Notes :- (i) Before fabrication of panel the contractor has to take approval from GE on drawing. (ii) All existing cable connections will be disconnected from old Panel carefully and re-connected with new Panel by providing glands and thimble all as directed by Engineer-in-Charge.
-
-
-
Taking down old unserviceable and Supply, install, testing and commissioning of meter cabin panel mounted on angle iron frame 40 x 40 x 5 mm grouted on floor,cubical indoor type for 415V, 3 phase, 4 wire made out of CRCA sheet not less than 2 mm thick , vermin proof factory fabricated, CPRI approved, front open hinged door with locking arrangement powder coated, individual compartment for MCCBs and 400 Amps rated copper bus bar alongwith compartment for fixing of Electronic Smart Prepaid Single Phase Meters, top and bottom cable entry with proper size glands including provisions of vision glasses for meter readings as directed. Meter cabin panel shall be comprising of the following :- (a) MCCB 4 pole, 160 Amps, 25 kA, 415 volt, thermal magnatic realease type, Ics=100% Icu -01 Nos, (as incomer) (b) MCCB 4 pole, 63/100 Amps, 16 kA, 415 volt, thermal magnatic realease type, Ics=100% Icu -03 Nos, (as outgoing) (c) MCB SPN 32 Amps 10 KA - 28 Nos (d) Digital type Voltmeter ( 0-500 Volts), 3 phase, 4 digit, high resolution, LED type with onsite programmability- 01 Nos. (e) Digital type Ampermeter ( 0-300 Amps) three phase with copper wound CT coil assy of suitable ratio & size Class I accuracy, 0.5 VA burden & onsite programmability- 01 Nos. (f) Indicating lamp LED type with holder key flush mounted, Red, Yellow, blue with toggle switch - 1 set ( set of three) as in incoming phases.
(g) Tinned copper bus bar strips made of copper of size 40x5mm suitable length-(01Set of four) including provision of new vision glasses-28 Nos. (h) Submain cable 2 core 6 Sqmm copper conductor from MCB SPN to each Meters. (j) Making good the disturbed surface of meter cabin room if any damages occures during fixing/shifting of panel.
4
-
-
Note :- (i) Before fabrication of panel the contractor has to take approval from GE on drawing. (ii) All existing cable connections will be disconnected from old Panel carefully and re-connected with new Panel by providing glands and thimble all as directed by Engineer-in-Charge. (iii) Taking out old electronic energy meters from existing Meter panel and shall be refixed to new panel.
-
-
-
All as per Item No.7.00 above but scope of work including provision of housing the following accessories:-
(a) MCCB 4 pole, 200 Amps, 25 kA, 415 volt, thermal magnatic realease type, Ics=100% Icu -01 Nos, (as incomer) (b) MCCB 4 pole, 125 Amps, 16 kA, 415 volt, thermal magnatic realease type, Ics=100% Icu -01 Nos
(c) MCCB 4 pole, 63/100 Amps, 16 kA, 415 volt, thermal magnatic realease type, Ics=100% Icu -03 Nos
(d) MCB SPN 32 Amps 10 KA - 30 Nos (e) Digital type Voltmeter ( 0-500 Volts), 3 phase, 4 digit, high resolution, LED type with onsite programmability- 01 Nos. (f) Digital type Ampermeter ( 0-300 Amps) three phase with copper wound CT coil assy of suitable ratio & size Class I accuracy, 0.5 VA burden & onsite programmability- 01 Nos. (g) Indicating lamp LED type with holder key flush mounted, Red, Yellow, blue with toggle switch - 1 set ( set of three) as in incoming phases.
(h) Tinned copper bus bar strips made of copper of size 40x5mm suitable length-(01Set of four) including provision of new vision glasses-30 Nos. (j) Submain cable 2 core 6 Sqmm copper conductor from MCB SPN to each Meters. (k) Making good the disturbed surface of meter cabin room if any damages occures during fixing/shifting of panel. Notes :- (i) Before fabrication of panel the contractor has to take approval from GE on drawing. (ii) All existing cable connections will be disconnected from old Panel carefully and re-connected with new Panel by providing glands and thimble all as directed by Engineer-in-Charge. (iii) Taking out old electronic energy meters from existing Meter panel and shall be refixed to new panel.
6
-
-
All as per Item No.7.00 above but scope of work including provision of housing the following accessories:- (a) MCCB 4 pole, 125 Amps, 16 kA, 415 volt, thermal magnatic realease type, Ics=100% Icu -01 Nos, (as incomer)
6
-
-
(b) MCCB 4 pole, 63/100 Amps, 16 kA, 415 volt, thermal magnatic realease type, Ics=100% Icu -03 Nos, (c) MCB SPN 32 Amps 10 KA - 29 Nos (d) Digital type Voltmeter ( 0-500 Volts), 3 phase, 4 digit, high resolution, LED type with onsite programmability- 01 Nos. (e) Digital type Ampermeter ( 0-300 Amps) three phase with copper wound CT coil assy of suitable ratio & size Class I accuracy, 0.5 VA burden & onsite programmability- 01 Nos. (f) Indicating lamp LED type with holder key flush mounted, Red, Yellow, blue with toggle switch - 1 set ( set of three) as in incoming phases.
(g) Tinned copper bus bar strips made of copper of size 40x5mm suitable length-(01Set of four) including provision of new vision glasses-29 Nos. (h) Submain cable 2 core 6 Sqmm copper conductor from MCB SPN to each Meters. (j) Making good the disturbed surface of meter cabin room if any damages occures during fixing/shifting of panel. Notes :- (i) Before fabrication of panel the contractor has to take approval from GE on drawing. (ii) All existing cable connections will be disconnected from old Panel carefully and re-connected with new Panel by providing glands and thimble all as directed by Engineer-in-Charge. (iii) Taking out old electronic energy meters from existing Meter panel and shall be refixed to new panel.
-
-
-
M&L for in replacement of MCCBs thermal magnetic release,lcs=100% lcu in existing FP/panel, connecting to bus-bar with all connecting accessories and modification in busbar (if Necessary), connection complete and testting after complition, all as specified and directed, of following capacities :-
-
-
-
MCCB 63/100 Amps,16 kA, TP, 50 Hz.
7
-
-
MCCB 160 Amps, 36 kA, FP, 50 Hz.
4
-
-
MCCB 200 Amps, 36 kA, FP, 50 Hz.
3
-
-
MCCB 250 Amps, 36 kA, FP, 50 Hz.
2
-
-
MCCB 400 Amps, 36 kA, FP, 50 Hz.
2
-
-
M&L for in replacement of Digital type Voltmeter ( 0-500 Volts), 3 phase, 4 digit, high resolution, LED type with onsite programmability- 01 Nos.
3
-
-
M&L for in replacement of Digital type Amperemeter ( 0-300 Amps) three phase with copper wound CT coil assy of suitable ratio & size Class I accuracy, 0.5 VA burden & onsite programmability complete all as specified.
3
-
-
Excavating in trenches not exc 1.5 mtr wide and not exc 1.5 mtr in depth for laying of cables etc. in any type of soil and getting out all as specified and directed by Engineer-in-Charge. Note : Rate includes removing of paver blocks carefully and stack properly for refixing after laying of cables .
252.45
-
-
Returning filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm in soils.
200.58
-
-
Removing excavated material from the site of work to outside MD land complete all as specified.
51.87
-
-
Supply, filling, spreading levelling and well ramming the river sand around cable in trenches for cable cushioning all as specified and directed. Note : Punned thickness shall be measured and paid.
6.32
-
-
Supply and laying un-reinforced pecast concrete cable covers class LV, Type 1, flat, size 250mmx 150mm x 40mm all as specified and directed.
2559
-
-
Cutting existing road surface or hard standing, bituminous topping 15 cm but n exc 30cm girth for laying of pipes/ cables and making good distrubed surface to match with existing complete.
115
-
-
M&L for making good of road cutting upto 450 mm wide, clean the cutting surfaces and filling hard core and match the existing bitumen surface of road with premix bitumenus material ready to use complete all as specified and directed by Engr-in-charge.
115
-
-
M & L for cement concrete 1:4:8 type D2 (using 40mm grade stone aggregate) as in foundations, filling and mass concrete finished fair and even comlpete all as specified
4.73
-
-
Supply, Fixing, testing and commissioning of XLPE insulated armoured, heavy duty electric cable with aluminium conductor of size 300 sqmm 3.5 core, 1100 volt grade laid in trenches, fixed on wall, passing through pipes complete including connecting with MCCB/ busbar with the help of proper size thimble, glands, properly as directed by engineer-in-charge and taking out existing damaged unserviceable cable. Note : Excavation, earthwork and cable protection shall be measured and paid separately under relevant items.
150
-
-
Same as Item No 21.00 above but size 150 Sq mm, 3.5 core
175
-
-
Same as Item No 21.00 above but size 120 Sq mm, 3.5 core
150
-
-
Same as Item No 21.00 above but size 95 Sq mm, 3.5 core
200
-
-
Same as Item No 21.00 above but size 50 Sq mm, 3.5 core
200
-
-
Same as Item No 21.00 above but size 35 Sq mm, 3.5 core
200
-
-
Same as Item No 21.00 above but size 25 Sq mm, 3.5 core
200
-
-
M&L for in replacement of GI pipe ,light grade 50mm dia for road crossing of cable for cable protection or above ground surface including taking out old one all as specified and directed.
40
-
-
M&L for in replacement of GI pipe ,light grade 80mm dia for road crossing of cable for cable protection or above ground surface including taking out old one all as specified and directed.
30
-
-
M&L for in replacement of GI pipe, light grade 100mm dia for road crossing of cable or for cable protection of cable above ground surface all as specified and directed.
45
-
-
M & L for refixing of old interlocking paver tiles/blocks of any sizes recovered form item SI. No. 13.00 including laying over 50 mm thick sand bed compacted complete as specified and directed.
15
-
-
M & L for machine pressed precast concrete interlocking paver block any shape and size confirming to IS 15658-2006 of 60mm thickness, M-35 Grade, with grey cement and pigment laid over, lacquer finish of existing size and existing type and including laying over 50 mm thick sand bed compacted complete as specified and directed.
5
-
-
M&L for in replacement of High density poly-ethylene pipes (HDPE) of pressure 6 kgf/cm2 pipe material grade PE-63, 40mm dia for road crossing of cable or for cable protection of cable above ground surface all as specified and directed.
300
-
-
M&L for in replacement of High density poly-ethylene pipes (HDPE) of pressure 4 kgf/cm2 pipe material grade PE-63, 75mm dia for road crossing of cable or for cable protection of cable above ground surface all as specified and directed.
320
-
-
M&L for in replacement of High density poly-ethylene pipes (HDPE) of pressure 4 kgf/cm2 pipe material grade PE-63, 100/110mm dia for road crossing of cable or for cable protection of cable above ground surface all as specified and directed.
338.5
-
-
Material and labour for fault finding on LT cables of any size and any length with fault detective machine by thumbing method and suitable high voltage and all as and directed by Engineer-in-charge.
12
-
-
Supply and fixing cable jointing kit Straight Through Joint for 1.1 KV grade cable complete with Jointing material (Heat shrinkable) and accessories suitable for 3.5 core XLPE armoured, alluminum conductor cable of size 25 to 95 sq mm after taking out and cutting the faulty cable area, inserting 1 mtr Cable of existing size for jointing Cables if required at site and all as directed by Engineer-In-Charge.
6
-
-
All as per Item No 37.00 above but for 3.5 core XLPE armoured, alluminum conductor cable of size 120 to 185 sq mm and all as directed by Engineer-In-Charge.
3
-
-
All as per Item No 37.00 above but for 3.5 core XLPE armoured, alluminum conductor cable of size 240 to 300 sq mm and all as directed by Engineer-In-Charge.
4
-
-
M&L for taking out existing Panel and shifting of LT panel of any size with all accessories and fixing it to other location as directed by Engr-in-Charge at site, connecting cable connection with connecting accessories, incl foundation in PCC 1:3:6 type C2 all as specified and directed.
4
-
-
M&L disconnecting, scrapping old worn out paint from complete indoor/outdoor type LT panels and painting with one coats of synthetic enamel paint (incl front door in side and individual compartment outer side etc also) over a coat of primer and spray painting complete including fixing sticker danger sign board suitable for LT panel board and energizing all as specified and as directed by engr-in-charge.
5
-
-
M & L for earthing complete with Galvanised steel earth plate eletrode 60cm x 60cm x 6mm thick buried directly in ground vertically to (earth pit not less than 2.25 meters deep below normal ground level) with top edge of plate not less than 1.5 meters below normal ground level, connecting to the Galvanised Iron Strip of size 32x6mm size, by means of Bolts, Nuts, Check Nuts and washer made of GI or Steel Earth connecting with test point, provision of Charcoal and salt in alternate layers, watering pipe 20mm dia medium grade MS funnel with jali, PCC M-15 Type B-1 in pit with XPM not elss than 4 Kg per Sqm and Earth pit with cover returning, filling, removing excavated material all as specified in electrical plate No 3 of SSR Part-I making good excavated surfaces such as hard standing refixing machine pressed precast concrete interlocking paver blocks removed during excavation on earthpit to mach existing surfaces after taking out old/unserviceable one complete and testing on completion all as specified and directed by Engr-in-Charge
44
-
-
Taking down carefully copper/ aluminium point wiring i.e. light, fan, socket or power/points complete, including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets,etc. and making good disturbed surfaces of ceiling, walls, floors, etc.
1205
-
-
M & L for point wiring with PVC insulated unsheathed single core multi stranded copper conductor 1.5 sqmm, 1100 volts grade cable, FRLS, passing through PVC casing caping including accessories as required at site as directed by Engineer-in-Charge including one run of PVC insulated unsheathed multistranded copper conductor cable 1.5 sqmm (green colour) FRLS earth wire and connected to earth dolly for the following:-
NOTE : Circuit conductor from MCB DB to Switch boards should not be less than 2.5sqmm.
-
-
-
One light/Exhaust/Ceiling fan point controlled by one switch.
700
-
-
One 3 pin switch socket combination 5 Amps on the same board with other switches.
200
-
-
One 3 pin switch socket combination 5 Amps, independent.
200
-
-
One bell point controlled by one push button
5
-
-
All as per item No 44.00 above but with 2.5 sqmm cable for one three pin 15 Amps socket out let controlled by one switch.
100
-
-
S & F modular switch, 1 module, single pole one way 6 Amp conforming to IS:3854 and ISI marked complete all as direcred.
1100
-
-
S & F in replacement with modular switch, 1 module, single pole one way 6 Amp conforming to IS:3854 and ISI marked complete all as direcred.
1200
-
-
S & F modular switch, 1 module, single pole one way 16 Amp conforming to IS:3854 and ISI marked complete all as direcred.
100
-
-
S & F in replacement with modular switch, 1 module, single pole one way 16 Amp conforming to IS:3854 and ISI marked complete all as direcred.
150
-
-
S & F ceiling rose with earth terminal connection, 3 terminal/ PVC/ polycarbonate, isolated body of size 60x50mm
700
-
-
S & F in replacement with ceiling rose with earth terminal connection, 3 terminal/ PVC/ polycarbonate, isolated body of size 60x50mm
100
-
-
S & F modular socket 6A, 3 pin, 2 module conforming to IS:1293 : 2019 and ISI marked complete all as direcred.
250
-
-
S & F in replacement with modular socket 6A, 3 pin, 2 module conforming to IS:1293 : 2019 and ISI marked complete all as direcred.
200
-
-
S & F modular socket 6/16A, 3 pin, 2 module conforming to IS:1293 : 2019 and ISI marked complete all as direcred.
100
-
-
S & F in replacement with modular socket 6/16A, 3 pin, 2 module conforming to IS:1293 : 2019 and ISI marked complete all as direcred.
150
-
-
S & F modular bell push switch, 1 module, single pole one way 6Amp ISI marked.
5
-
-
S & F in replacement with modular bell push switch, 1 module, single pole one way 6Amp ISI marked.
10
-
-
S & F in replacement with modular electric bell ding dong, AC, 230V single pole.
5
-
-
S & F modular stepped type fan regulator, 2 module, single pole one way ISI marked.
50
-
-
S & F in replacement with modular stepped type fan regulator, 2 module, single pole one way ISI marked.
150
-
-
Supply & Fixing Retrofit LED lamp 7 Watts (min 110 lumen/watt) complete all as specified and directed.
150
-
-
Supply & Fixing Lamp holder, PVC/Polycarbonate type with back plate suitable for batten fittings complete all as specified and directed.
150
-
-
Taking out old wooden/PVC board and disconnecting all electric connection from switches, board and S & F modular PVC Gang box, screwless, with silver border of 8 module for mounting of modular switches and sockets including blank plate for blank module.
300
-
-
All as per Item No- 63.00 above but of modular PVC Gang box, 6 module.
250
-
-
All as per Item No- 63.00 above but of modular PVC Gang box, 3 module.
350
-
-
All as per Item No- 63.00 above but of modular PVC Gang box, 2 module.
150
-
-
All as per Item No- 63.00 above but of modular PVC Gang box, 1 module.
120
-
-
S&F modular white cover plate with frame, 8 module.
300
-
-
S&F modular white cover plate with frame, 6 module.
250
-
-
S&F modular white cover plate with frame, 3 module.
350
-
-
S&F modular white cover plate with frame, 2 module.
150
-
-
S&F modular white cover plate with frame, 1 module.
300
-
-
Taking down unserviceable FTL/batten fittings with supply and fix LED batten fitting 20 Watt (min 110 lumen/watt), 240V, 4ft CDL/NW comprises of extruded channel in thermally conductive material with decorative end cap and high translucent serration milky white diffuser of high optically efficient plastic FR grade. The luminaire is pre-wired with high efficiency electronic driver having operating voltage 140-270V, P.F 0.95, THD 20% and IP20 protected alongwith provision of two Nos of PVC box of size 75x75x20mm for mounting light fittings including ceiling rose. The contractor shall provide test certificate from authorized lab.
600
-
-
Taking down unserviceable FTL/batten fittings with supply and fix LED integrated batten of 10 Watt 2ft LED give minimum output lumen 1150 lm, efficiency 110, CCT 4000/6500K, CRI 80, power factor 0.9, operating temperature 45 degree celcious, THD 20% of housing aluminium extrusion with LED dimension 603mmx22mmx36mm upto 50% energy saving.
300
-
-
Taking out any type of fitting bulkhead/FTL and S&F 10 watt (min 110 lumen/watt) linear LED batten, 2 feet, aluminium extruded channel, powder coated with diffuser for glare free light, inbult motion sensor prewired with 25% dimmer illuminiuos in ideal time with all accessories including two nos of PVC box of size 75 x 75 x 20mm for mounting light fittings complete in common area and staircase.
100
-
-
S&F MCB DB SPN conforming to IP 43 - IK 09 with acrylic door, 8 way complete with din rail, Neutral and Earthing bar after taking out the old unserviceable DBs, connection complete and making good the disturbed surfaces by plastering or PCC work inclding distembering to the affetced to walls.
81
-
-
Taking out Old U/S and S&F MCB SPN, 32 Amp, 10 KA, 230 Volt.
81
-
-
Taking out Old U/S and S&F MCB, single pole, upto 20 Amp, 10 KA, 230 Volt.
486
-
-
Taking out unserviceable ceiling fan and deposit to MES Store, supply and replacement with ceiling fan 230V, 50 Hz, AC, 1200mm sweep, min air delivery 210 CFM with service value 6.00 BEE, five star rated with brushless direct current motor (BLDC) complete with hanging arrangement by down rod alongwith steel wire rope for additional safety in ceiling fan with all allied accessories and connecting up with three core, 0.75 sqmm PVC insulated copper conductor cable complete all as sepecified.
60
-
-
Taking out unserviceable exhaust Fan and deposit to MES Store, supply and replacement with exhaust fan, Steel body 4 blade, heavy duty, double ball bearing, 230V, 50Hz, 300mm sweep having power input 70W speed 1440RPM, with protective bird guard including connecting with three core, 0.75 sqmm PVC insulated copper conductor cable complete all as sepecified and directed.
30
-
-
Taking out & Overhauling of ceiling fan any size and Make, dismantling parts, properly cleaning/removing old existing grease oil and applying new oil grease, varnishing of winding, cleaning dust rust and replacing petty items with new as required such as Nuts, Bolts, washers, bushes, ball bearing, cap, fan shaft, rotor, capacitor 2.5/4 Mfd, body cover etc and assembling and connecting complete with copper conductor multi stranded 3 core wire of size 14/0.0076 including one coat of painting and testing after refixing at site complete all as specified and as directed by Engr-in-Charge. Note: Rate of petty items to be replace shall be included in quoted rate.
20
-
-
Taking out & Overhauling of Exhaust fan any size and Make, dismantling parts, properly cleaning/removing old existing grease, oil and applying new oil grease, varnishing for winding, cleaning dust, rust and replacing petty items with new as required such as Nuts, Bolts, washers, bushes, ball bearing, cap, fan shaft, rotor, capacitor 2.5/4 Mfd, body cover etc and reassembling, connecting with copper conductor multi stranded 3 core wire of size 14/0.0076 including one coat of painting complete and testing after refixing at site. Note: Rate of petty items to be replace shall be included in quoted rate.
10
-
-
Taking down deteriorted louvers and supplying and fixing new louvers fixed type made out of 1.6mm GI sheet with horizontal ventilation, bending into shape of size 45cmx45cm (outer) with 20x3mm flat iron base of size 45cmx45cm complete by providing of fixing arrangement for louvers upto 5th floor of including rate all as specified and directed by Engr-in-Charge
30
-
-
S & F cable PVC insulated, PVC sheathed, armoured, FRLS, 1100V grade, 2 core 6 sqmm stranded copper conductor electric cable laid on wall/ roof/ duct complete with proper saddling and connecting to DBs with glands including taking out existing unserviceable cable complete all as specified.
1750
-
-
S&F in relplacement with new cable PVC insulated three core over all PVC sheathed 2.5 Sqmm stranded copper conductor cable for connecion from DB to connector junction box for power supply to security light fittings drawn in PVC conduit not less than 20mm including taking out old one all as directed.
1120
-
-
S & F junction box of size not less than 4x4 inch with connector encloser, 3 terminal/ PVC/ polycarbonate, isolated body including taking out old one.
70
-
-
S&F street light bracket bend to shape made as required of 40mm dia 1.0 mtr long GI pipe light grade fixed to pole/ Wall including M&L for fixing with the help of flat iron clamp of size 40x6mm two numbers with the help of nuts and bolts for fixing of street light fitting on the wall complete after taking out old U/S one all as specified and as directed.
71
-
-
Taking out Old, U/s one Supply and fixing LED street light fitting 35 Watt (min 110 lumen/ watt) 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete.
39
-
-
Taking down old unserviceable security light fittings from any height and Supply & fixing LED security light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 6000 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 60 watt, with ingress protection IP 65/66 and SPD of capacity 5 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed. Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items.
15
-
-
Taking down old unserviceable security light fittings from any height and Supply & fixing LED security light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 7000 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 70 watt, with ingress protection IP 65/66 and SPD of capacity 5 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed. Note: The GI pipe bracket if required will be measured and paid separately under relevant schedule items.
15
-
-
Taking down old unserviceable flood light fittings from any height and Supply & fixing LED flood light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 20000 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 200 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed. \
20
-
-
Taking down old unserviceable flood light fittings from any height and Supply & fixing LED flood light fittings comprising of epoxy powder coated housing, enclosed with glass cover in frame,(with total lumen output not less than 12000 lumens and suitable wattage for efficiency not less than 100 lumens/Watt) min wattage 120 watt, with ingress protection IP 65/66 and SPD of capacity 10 KV etc incl necessary clamps etc complete and testing on completion all as specified and as directed.
10
-
-
S&F in repair, MCCBs in existing FP/panel, connecting to bus-bar with all connecting accessories and modification in busbar (if Necessary), connection complete and testing after completion, all as specified and directed, of following capacities :-
-
-
-
MCCB 63 Amps,16 kA,FP, 50 Hz,Thermal magnetic release,lcs=100% lcu.
5
-
-
MCCB 100 Amps,16 kA,FP,50 Hz,Thermal magnetic release,lcs=100% lcu.
4
-
-
MCCB 160 Amps,25 kA,FP,50 Hz,Thermal magnetic release,lcs=100% lcu.
5
-
-
MCCB 200 Amps,25 kA,FP,50 Hz,Thermal magnetic release,lcs=100% lcu.
6
-
-
MCCB 250 Amps,36 kA,FP,50 Hz,Thermal magnetic release,lcs=100% lcu.
5
-
-
MCCB 320 Amps,36 kA,FP,50 Hz,Thermal magnetic release,lcs=100% lcu.
4
-
-
MCCB 400 Amps,36 kA,FP,50Hz,Thermal magnetic release,lcs=100% lcu.
4
-
-
MCCB 630 Amps,36 kA,FP,50Hz,Thermal magnetic release,lcs=100% lcu.
3
-
-
Earthing complete with Galvanised Steel earthplate of size 60x60cmx6.3mm thick electrode and GI wire 4 sqmm dia as earth lead, buried directly in ground (earth pit not less than 2.25m deep below ground level) with top edge of the plate not less than 1.5m below ground level, connected to earth wire 4 sqmm by means of nuts, bolts, check nuts and washers of GI all as shown in electrical plate No.3 of SSR Part-I, including testing on completion (Rates inclusive of neccessary excavation in any type of soil, earth work, PCC pit, CI cover, funnel with watering pipe, suitable size of light grade GI Protection pipe for earth strip in ground etc. all as required at site for complete earthing).
30
-
-
Taking out unserviceable exhaust Fan and deposit to MES Store, supply and replacement with exhaust fan, 4 blade, heavy duty, double ball bearing, 230V, 50Hz, 400/450mm sweep having power input 70W speed 1440RPM, with protective bird guard including connecting with three core, 0.75 sqmm PVC insulated copper conductor cable complete all as sepecified and directed.
8
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements
Past BiddersThis list is curated from the bidders of the similar tenders in the past
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%