Military Engineer Services Tender
Search from over 12139+ business opportunities that have been announced from the biggest Mahatenders, e tender Maharashtra, Maharashtra government tenders, and the Online Tender Notices posted on Maharashtra e tenders till date. Find opportunities that have come in from the multiple corporations, Maharashtra government departments, State PSUs, and Private companies from the state.
Military Engineer Services - MES Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date11 Nov 2024
Closing Soon2 Dec 2024
Tender Amount₹ 43,09,000
Costs
EMD
₹ 86,180Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_683197_1Tender No
GE/LONAVLA/8276/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
eneral Pages, Errata on NIT, Schedule Of Credit, Special Conditions, Particulars Specifications
BOQ Items
All as per Sl item No 3 herein before but in hard/dence soil
49.95
-
-
M&L for crushed stone sand for cable cushoining laid in trenches for protection of cable
89.91
-
-
M&L for Returning and filling including spreading levelling watering and well ramming in layers not exceeding 25 cm
221.31
-
-
M&L for Removing excavated material not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point
126.79
-
-
Supply and laying factory cast, unreinforced precast concrete cable cover factory made embossed the mark “LT CABLE” class LV type1 flat size 250x150x40 mm laid in trenches as specified and as directed.
7400
-
-
Taking out under ground 1.1 KV (E) Grade LT cable of size upto 10 sqmm to 300 sqmm 2/3/ 3.5/4 Core from pole/trenches/walls / ducts etc., for carrying out repairs , relaying, rerouting, laying back through same / different route after carrying out repair / issue under schedule of credit all as directed by Engineer-in-Charge at site.
900
-
-
Supply, laying and testing in replacement of cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 2 core. Including taking down old unserviceable cable any size by dismantling of all electrical connection etc all as diercted
250
-
-
All as per item no 10 above but of size 16 sq mm ,4 core.
1100
-
-
All as per item no 10 above but of size 25 sq mm ,4 core.
650
-
-
All as per item no 10 above but of size 35 sq mm ,31/2 core.
350
-
-
All as per item no 10 above but of size 50 sq mm 3,1/2 core.
550
-
-
All as per item no 10 above but of size 70 sq mm 3,1/2 core.
50
-
-
Supply and fix cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material heat Shrink type and accessories suitable for 3 ½ / 4 core XLPE, armoured, Aluminium conductor cable of size upto 50 sqmm,Indoor/Outdoor type complete all as specified and as directed. The cable fault location digghing,removing, and after cable joint kit fixing returning rate shall be deemed to be included in quoted rates.Make: M-seal,denson.
15
-
-
Cutting and filling bituminus road as per direction of Engr in Charge for laying of UG cable and match the existing road to the existing system.
80
-
-
S&F in replacement of MCCB 415 Volt 16 KA, 4 Pole 63 Amps capacity. Complete all as specified and directed by Engineer-In-Charge. Make:ABB/Siemens/Hager.
2
-
-
All as per item No. 18 above but 160A, 25KA. Complete all as specified and directed by Engineer-In-Charge.
2
-
-
Taking down unserviceable street light any type from their existing postion ie. Poles and fixing new street light all as directed by Engr In Chrarge.
30
-
-
Supply and fix FR PVC insulated cable 1100 V grade with multistranded copper conductor of size 1.5 Sqmm 3 core conductor all as specified and directed by Engineer-In -Charge at site.
200
-
-
Supply & fix in replacement of ,New generation energy saving and environmental friendly long life LED street ligh 90 Watt made up of pressure die cast aluminium housing with high power LED as lighting source and lens embedded PC cover having TOP Opening seperate driver compartment with IP66 protection and impact resistance of IK07 .
45
-
-
Supply and laying in replacement of GI pipe light grade 15 mm dia for proctedtion of service connection on pole from bracket to junction box not less than 4.0 mtr length all as specified and directed by Engr In Chrage.
100
-
-
Supply & laying in replacement of GI pipe light graded of size 50mm dia in trenches and fixing on wall / pole with help of suitable size MS clamp for cable protection from cable ground to junction box all as Engr in charge directed.
100
-
-
Supply and fixing in replacement of Higher wattage flood light luminaire with ultra sleek, light weight and secondary optics,made of pressure die cast housings with IP66 ingress protection and impact resistance of IK07.4kv inbult and 10kv external surge protection .
6
-
-
S&F in replacement MCB DB TPN 4 ways double door with 440 Volt, 200 amps rated bus bar with all accessories flush in the wall including matching the existing surface all as specified and directed
1
-
-
S&F in replacemen MCB DB SPN 4 ways double door with 240 Volt, 200 amps rated bus bar with all accessories flush in the wall including matching the existing surface all as specified and directed
2
-
-
S&F in replacemen MCB DB SPN 8 ways double door with 240 Volt, 200 amps rated bus bar with all accessories flush in the wall including matching the existing surface all as specified and directed
2
-
-
S&Fin replacement of MCB SPN 40 to 63 AMP, 240 Volts 10KA 'C' curve , Complete all as specified and directed.
4
-
-
S&F in replacement of MCB 415V 10KA 'C' Curve TPN 40 To 100 AMP , complete all as specified and directed.
3
-
-
S&Fin replacement of MCB SP 5 to 32 ,single pole 240 Volts 10KA 'C' curve, Complete all as specified and directed.
20
-
-
M&L for sub main wiring drawing through PVC casing and capping / in PVC codute as per site requirment with two single core 2.5 sq mm and one run of 4 sq mm as earth wire of stranded copper conductor PVC insulated and unsheathed cable of 1100 volts grade all as directed. Note:- Two run of 2.5 sqmm wire and One run of PVC casing caping will be measured as one running meter.
350
-
-
M&L for sub main wiring drawing through PVC casing and capping / in PVC codute as per site requirment with two single core 4 sq mm and one run of 4 sq mm as earth wire of stranded copper conductor PVC insulated and unsheathed cable of 1100 volts grade all as directed. Note:- Two run of 4 sqmm wire and One run of PVC casing caping will be measured as one running meter.
460
-
-
M & L for LT route marker made of 50mm x50mmx 6 mm angle iron fix on PCC block of size 200 x 200mmx 200mm including indicating LT 1100V U/G Cable and fixing on ground above the cable of every 50 meter length.
50
-
-
Renewal/ Repairs to LT Panel Board of any size complete as mentioned below:-
(I) Repair/ replacement of damaged hinges of each compartment
(ii) Taking down existing bus bars cleaning with CTC applying with becktol red solution, providing bus bar insulation and refixing with new s/s nuts, bolts, washers etc.
(iii) Replacement of damaged copper flexible cable and fixing new copper flexible cable of suitable size for incoming and out going connections of each MCCB terminals to bus bars.
(iv) Replacement of damaged/ worn out/ loose connections/ cable lugs for incoming & outgoing cables.
(v) Replacement of u/s CT's, ammeters, Volt meters, Indication Lamps (01 Set each) including provision of new wiring for the same.
Note : Ammeters and CT's shall be wired with 2.5 sqmm copper wire.
(vi) Replacement of neoprene gasket for all doors of panel board.
Note : i) Cost for replacement of spares are deemed to be included in the quoted rates.
ii) The rate shall be deemed to be included for replacement of worn out rusted, Channels, hinges, bolts, split pins and cable lugs, cable glands and neoprene gasket with painting to all doors including raising of foundation to 0.3 M height etc.
iii) Cost of replacement of MCCB's, Repairs to ACB's not included in the scope of work.
3
-
-
Supply and fixing in replacement of Decorative Globe LED Post Top (25W) LED wall light in spherical hape polycarbonate diffuser IP 65 protection all as specifiend as direction.
18
-
-
Supply and fixing in replacement of Higher wattage flood light luminaire with ultra sleek, light weight and secondary optics,made of pressure die cast housings with IP66 ingress protection and impact resistance of IK07.4kv inbult and 10kv external surge protection .
20
-
-
Taking down unserviceable GI pipe line of 40 mm dia from the trenches by removing of connections, nut and bolts.
190
-
-
Taking down unserviceable GI pipe line of 25 mm dia from the trenches by removing of connections, nut and bolts.
170
-
-
S & F GI tubing medium grade 40 mm bore with all new connections and fittings such as tees, bends, elbows, short pieces, connector back nuts, diminishing pieces, caps, plugs unions etc Laid in trenches for following size of pipes complete all as specified and as directed.
190
-
-
S & F GI tubing medium grade 25 mm bore with all new connections and fittings such as tees, bends, elbows, short pieces, connector back nuts, diminishing pieces, caps, plugs unions etc Laid in trenches for following size of pipes complete all as specified and as directed.
170
-
-
Supply and installation of Hot dip galavanised iron pole 7 mtr long sheet thickness 3 mm. C/s A/F - top = 70mm, bottom =130 mm, base plate 200x200x12 mm, long weatherproof reinforced door opening with junction box mounting arrangement but including of junction box with 4 Nos aluminium Bus bar and including 1.0 M long single bracket made of 40NB B class pipe having top 70 mm, 20 dia threaded made to J shape M20x600mm long steel grade EN8 grade foundation bolts - 4 nos with nuts, templates and all complete as per approved drawing (with internal accessorises like connectors, one run of FRLS PVC insulated cable 1100 V grade with multistranded copper conductor of size 1.5 Sqmm 3 core conductor as per required and mcb) . including taking down old rusted steel/pcc pole of any size by digging or cutting all as directed . Foundation RCC 1:1.5:3 shall be of size 550x550mm and depth 1500 mm with 8 nos. 12mm dia. tor bars as main bars and 8mm dia. tor bars stirrups @ 190 mm c/c as per approved drawing(Including form work). This reinforcement shall conform to IS:1786 latest edition. The foundation shall extend above sorrounding ground/driveway level for 200 mm and have slant 63mm dia. PVC sleeve cast insitu foundation for cable entry as per the drawing. Excavation, PCC, RCC,Form work and reinforcement shall be deemed to be included in quoted rates.Make:Bajaj,Valmont,Wipro
22
-
-
Supply and installation of Hot dip galavanised iron pole 7 mtr long sheet thickness 3 mm. C/s A/F - top = 70mm, bottom =130 mm, base plate 200x200x12 mm, long weatherproof reinforced door opening with junction box mounting arrangement but including of junction box with 4 Nos aluminium Bus bar and including 1.0 M long double arm bracket wich required as per site 180 degree angle or 60 degree angle made of 40NB B class pipe having top 70 mm, 20 dia threaded made to J shape M20x600mm long steel grade EN8 grade foundation bolts - 4 nos with nuts, templates and all complete as per approved drawing (with internal accessorises like connectors, one run of FRLS PVC insulated cable 1100 V grade with multistranded copper conductor of size 1.5 Sqmm 3 core conductor as per required and mcb) . including taking down old rusted steel/pcc pole of any size by digging or cutting all as directed . Foundation RCC 1:1.5:3 shall be of size 550x550mm and depth 1500 mm with 8 nos. 12mm dia. tor bars as main bars and 8mm dia. tor bars stirrups @ 190 mm c/c as per approved drawing(Including form work). This reinforcement shall conform to IS:1786 latest edition. The foundation shall extend above sorrounding ground/driveway level for 200 mm and have slant 63mm dia. PVC sleeve cast insitu foundation for cable entry as per the drawing. Excavation, PCC, RCC,Form work,welding and reinforcement shall be deemed to be included in quoted rates.Make:Bajaj,Valmont,Wipro
11
-
-
Supply and installation in replacement of Translucent conical poles 7 mtr long.weatherproof & socked proof reinforced door opening with junction box mounting arrangement but including of junction box with 4 Nos aluminium Bus bar and including 1.0 M long single arm bracket and foundation bolts - 4 nos with nuts, templates and all complete as per approved drawing (with internal accessorises like connectors, one run of FRLS PVC insulated cable 1100 V grade with multistranded copper conductor of size 1.5 Sqmm 3 core conductor as per required and mcb) . including taking down old rusted steel/PCC pole of any size by digging & cutting with foundation or shiftting and reinstallation at other place as per direction of Engr-in -charge . Foundation RCC 1:1.5:3 shall be of size 550x550mm and depth 1500 mm with 8 nos. 12mm dia. tor bars as main bars and 8mm dia. tor bars stirrups @ 190 mm c/c as per approved drawing(Including form work). This reinforcement shall conform to IS:1786 latest edition. The foundation shall extend above sorrounding ground/driveway level for 200 mm and have slant 63mm dia. PVC sleeve cast insitu foundation for cable entry as per the drawing. Excavation, PCC, RCC,Form work and reinforcement shall be deemed to be included in quoted rates.Note: 1) Existing pole shiftting other location and reinstallation charge demeed including this rate. Make:Bajaj,Helipole,Voltmount
28
-
-
Supply & fix in replacement of LED street light of 72 watt along with fixture making necessory arrangement for fixing existing bracket by means of prority necessory size pipe,welding,reveting,screw complete for fixing street light. Make:Bajaj equivalent to Shakti/havells/Wipro complete all as specified and directed Note: If Street light not fixed on existing/New pole arms pipe,it will fix on additional pipe conecting by welding work which rate demmed including this quated rate
50
-
-
M & L for GI pipe/ tubes light grade of size 50 mm dia for UG cable protection with all fittings laid in trenches, on poles to crossing the roads/Nalah etc .
68
-
-
M & L for Earthing complete with galvanized steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.’25 mtr below normal ground level) with top edge of the plate not less 1.5 mtr below normal ground level connected to galvanized earth plate with 4.0 mm thick GI wire by means of suitable size of GI nuts, bolts, check nuts and washers all as specified in electrical plate SSR Part I including necessary .Exc & earth work, providing charcoal and salt dust layers and construction of PCC pit in 1:3:6 using 20 mm size graded stone aggregate, precast RCC 40 mm thick cover in 1:2:4 type B 1 with 12 mm dia steel MS plain bar, lifting handle GI pipe of 50 mm bore for earth lead protection andGI pipe 15 mm dia for watering, with funnel and wire mesh including testing on completion. All as specified and as directed incl dismentling existing unsserviciable earthing .
8
-
-
M&L for Marking of any size pole , Scrubing of existing rusted/unread surface of poles and prepration surfaces for marking, Marking done by two colour. numbers marking done by white colour and back side colour and shape as per direction of Engr in Charge .
130
-
-
Supplying and fixing HOT moulded (FRP) junction box for street light pole with locking arrangement with IP 65 protection of size 300 x 200x 100 mm with 32 Amp 4way heavy duty terminal block with 6 Amp MCB SP and two number of canle entru gland (stainless steel )of standard size with suitable size clamp to fix with pole incudinmg taking old u/s complete all as directed Make Sintex of equivalent
26
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements
Past BiddersThis list is curated from the bidders of the similar tenders in the past
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%