Military Engineer Services Tender
Search from over 12139+ business opportunities that have been announced from the biggest Mahatenders, e tender Maharashtra, Maharashtra government tenders, and the Online Tender Notices posted on Maharashtra e tenders till date. Find opportunities that have come in from the multiple corporations, Maharashtra government departments, State PSUs, and Private companies from the state.
Military Engineer Services - MES Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date29 Oct 2024
Closing Soon4 Dec 2024
Tender Amount₹ 59,98,000
Costs
EMD
₹ 1,15,000Document Cost
₹ 1,000Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_681887_1Tender No
CWE/KKE/TOKEN-48 OF 2024-25Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Carry out oil inspection as and when required including testing of the same for the serviceability for better life of lubrication parts and semi hermetic motor.
-
-
-
Checking the set parameters in the controller checking safety fault trips taking control test, contacts cleaning etc.
-
-
-
Checking the actual performance /operationing parameters of the chiller with the help of log reading recorded during the previous month and actual parameter of the chiller
-
-
-
Taking up repair /replacement of parts /spares/driers/oil as required by OMC Engineer.
-
-
-
Servicing, including detail check up and Calibration of relays of microprocessor based Control panel of all three 200 TR AC Plant to keep the same functional all as specified and directed.
-
-
-
Note for item No.1: The following works are deemed to be inclusive in the quoted rate and no extra payment will be provided by the dept.
-
-
-
Reorient leak test is to be carry out under supervision of OEM or OEM Authorised person.
-
-
-
Any type of special tools / general purpose tools required for the maintenance of the plant to be supplied by contractor
-
-
-
The responsibility of Payment in advance to OMC shall rest with contractor
-
-
-
This contractor shall cover lifting /shifting of any type material, up/down the building or shipment cost or freight of any material from site to OMC or any sub vendors works. All other charges and transit insurance.
-
-
-
All spare /store required during repair and maintenance which shall be genuine Parts of OEM and shall be measured and paid under relevant item of this BOQ..
-
-
-
Supply and replacing the following defective / worn out spares / controls for the chiller Plant all as specified and as directed Make Kirloskar / voltas / Blue star
-
-
-
Sensor Pressure TI 500, 20 FT for MCS Controller for KW4 220.17 OS Make : Kirloskar/Blue star / Dun-Ham-Bush
2
-
-
Sensor Temperature TI100 for MCS Controller for KW4 220.17OS. Make : Kirloskar/Blue star / Dun-Ham-Bush
3
-
-
Valve Solenoid Model- EVR 20, Connection Size -1-1/8 INCH X 1-1/8 INCH ODF, supply 24V AC For KW4 220.17 OS. Make : Kirloskar/Blue star / Dun-Ham-Bush
2
-
-
Gasket and O-Ring Kit, Oil Filter For KW4 220.17 OS
Make : Kirloskar/Blue star / Dun-Ham-Bush
3
-
-
Valve Solenoid 7/8IN. ODS 110V/10W for KW4 220.17 OS .
Make : Kirloskar/Blue star / Dun-Ham-Bush
2
-
-
Valve Non return 36 Bar Flange type for KW4 220.17 on discharge line .
Make : Kirloskar/Blue star / Dun-Ham-Bush
2
-
-
Valve Electronic Expansion, Model-EX8-I21, Connection-1-5/8 OD for KW4 220.17 OS Make : Kirloskar/Blue star / Dun-Ham-Bush
2
-
-
Suction Strainer F-4 for KW4 220.17 OS Make : Kirloskar/Blue star / Dun-Ham-Bush
2
-
-
Valve Safety, Set PR-21 Bar,size-1" NPT(M)X1"NPT(F), CE Certified as per PPS-NM40011 for KW4 220.17 OS Make : Kirloskar/Blue star / Dun-Ham-Bush
3
-
-
Valve Safety, Set PR-13 Bar,size-1/2" NPT(M)X3/4"NPT(F), CE Certified as per PPS-NM40011 For KW4 220.17 OS Make : Kirloskar/Blue star / Dun-Ham-Bush
3
-
-
Glass fuse for master Board power supply Make : Kirloskar/Blue star / Dun-Ham-Bush
2
-
-
Gasket for water nozzle-round flange (Condenser) Make : Kirloskar/Blue star / Dun-Ham-Bush
2
-
-
Glass for water nozzle (Evaporator) Make : Kirloskar/Blue star / Dun-Ham-Bush
2
-
-
Pressure relief valve Make : Kirloskar/Blue star / Dun-Ham-Bush
2
-
-
Current transformer 250/0.2A with AC to DC Converter card and mounting bracket for KW4. Make : Kirloskar/Blue star / Dun-Ham-Bush
1
-
-
Current sensor Make : Kirloskar/Blue star / Dun-Ham-Bush
2
-
-
Replacement of PLC Controller and SMPS Make : Kirloskar/Blue star / Dun-Ham-Bush
1
-
-
Expansion Board and EVD board Make : Kirloskar/Blue star / Dun-Ham-Bush
2
-
-
PGD O LED Display, Feed Batch Make : Kirloskar/Blue star / Dun-Ham-Bush
2
-
-
T Lan Card and control fuse and accessories Make : Kirloskar/Blue star / Dun-Ham-Bush
2
-
-
Cut out switch as per existing size and range Make : Danfoss/ Honeywell / Castle
2
-
-
Repair and replacement of leaking cooling coil of AHU various size of cooling coil as per existing size and material and testing all as specified and as directed by engineer -in-charge
8
-
-
Supply and fix control transformer with incoming voltage 380/400/420/440 VAC with outgoing 12/24/36/48/110 VAC with Capacity 300 to 600 VA all as per existing plant design and parameter all as specified and as directed by engineer -in-charge
2
-
-
Painting of 200 TR capacity existing cooling tower with existing colour all as per directed and specified
2
-
-
M&L for descaling of complete condenser units for central/ package type AC plant Model No : T7FAA48 - 02 MK-1of capacity 200TR by means of adding descaling chemical solution or equivalent in the cooling tower sump of required quantity and circulating the liquid to remove the scales inside the pipes and removing side covers of condenser, cleaning the water tubes by scrubbing with nylon brushes and flushing with fresh water, re fixing the covers, Inlet and outlet pipes including replacement of neoprene rubber gasket etc. complete all as specified and directed.
3
-
-
Repairing /servicing and overhauling the centrifugal pump by dismantling the pump coupled with induction motor, opening the pump, inspecting for defects and replacing the worn out parts like gland bush, bearings, gland bolts and nuts,gland packing, gasket, water seal etc including repairs to pump shaft by remetalling, grinding, polishing and reassembling the same and replacing the rusted nuts, bolts, washers etc and coupling with motor testing complete for the following capacity of pumps complete all as specified and as directed.
-
-
-
Chiller Pump 60 HP Make : Kirloskar
2
-
-
Condenser pump 25 HP Make : Kirloskar
3
-
-
M & L for taking out the centrifugal pump motor and transporting to work shop, split opening the motor removing the unserviceable burnt winding wire, cleaning the slots, re winding with super enamelled copper conductor wire of suitable size including insulating materials, varnishing and drying and reassembling and transporting back to site , coupling with pump testing and commissioning all as specified and as directed by Engineer -in-charge for the following capacities of motors : -
-
-
-
Chiller Motor 60 HP Make : Kirloskar
1
-
-
Condenser Motor 25 HP Make : Kirloskar
2
-
-
M & L for taking out the motor and transporting to work shop, split opening the motor removing the unserviceable burnt winding wire, cleaning the slots, re winding with super enamelled copper conductor wire of suitable size including insulating materials, varnishing and drying and reassembling and transporting back to site, refixing the motor, testing and commissioning all as specified and as directed by Engineer -in-charge for the following capacities of motors : -
-
-
-
Blower Motor of Capacity 7.5 HP Make : Kirloskar/ Bharat Bijali
2
-
-
Blower Motor of Capacity 5 HP Make : Kirloskar/ Bharat Bijali
4
-
-
Blower Motor of Capacity 3 HP Make : Kirloskar/ Bharat Bijali
5
-
-
Dismantling the covers of cooling tower and the cooling fan blades from the position, electrical connections and taking down the cooling tower motor, split opening the motor, removing the burnt out winding, cleaning the slots re winding with super enamelled copper conductor wire of suitable size including insulating materials, varnishing and drying and reassembling and transporting back to site and testing on commissioning of AC Plant 200TR Capacity complete all as specified and as directed by Engineer -in-charge
2
-
-
Descaling of cooling tower by dismantling the cooling tower fins removing the scales in the fins, sump by scrubbing with wire / nylon brush and refixing the fins in position including replacing the float valve for supply water line, painting the steel/wooden surfaces with two coats of enamel paint over a coat of zinc oxide primer and testing the cooling tower of AC Plant 200TR capacity complete all as specified and as directed by Engineer -in-charge
2
-
-
M & L for prepartion of old steel surfaceand applying two coats of approved synthetic enamel paint on following pump set complete all as specified and as directed by Engineer -in-charge
-
-
-
Condenser Pump
3
-
-
Chilled water Pump
2
-
-
Supply and replace the worn out 'V' belts of blower motor.
-
-
-
SPA1600 mm
6
-
-
SPA1400 mm
3
-
-
SPA1200 mm
6
-
-
SPB 1600 mm
8
-
-
SPA 1250 mm
6
-
-
SPB 2000 mm
6
-
-
SPA 2300 mm
4
-
-
SPA 1030 mm
6
-
-
Supply only Gas R-407C in cylinder for charging / topping up whenever required including leak testing all as specified and as directed by Engineer -in-charge
140
-
-
S&F in replacement of double fitted polymer fabric HDPE fresh air filter(Filter class-G3 as per EN 779) washable/cleanable type having efficiency 95% to 99% down to particle size of 20 micron, fabricated out of CRCA sheet metal duly painted with two coat of grey hammer tone spray painted over two coats of red oxide primer, with lifting handle, Box/flanged type, aluminium spacer etc, of make Thermadyne/ Pall supralon filter / Micron filter complete all as specified and as directed by Engineer -in-charge of following sizes :-
-
-
-
600x500x45mm
32
-
-
600x600x45mm
6
-
-
600x400x45mm
4
-
-
500x500x45mm
6
-
-
500x400x45mm
16
-
-
S&F in replacement of double fitted polymer fabric HDPE fresh air filter(GL-type) washable/cleanable type having efficiency 95% to 99% down to particle size of 5 micron, fabricated out of CRCA sheet metal and applying two coat of grey hammer tone spray painted over a coat of red oxide primer including prepartion of steel surface with lifting handle, Box/flanged type, aluminium spacer etc, including taking down all as specified and as directed by Engineer -in-charge of following sizes :-
Make Thermadyne/ Pall supralon filter / Micron filter
-
-
-
600x500x300 mm
37
-
-
600x600x300 mm
6
-
-
600x400x300 mm
6
-
-
500x500x300 mm
7
-
-
500x400x300 mm
8
-
-
500mm x 400 mm x 300 mm bag type filter 5 micron
10
-
-
S&F in replacement of filter "HEPA"(EN-1882) with fibre glass paper filtering media capacited 1000 CFM efficiency 99.97% down to particle size of 0.3 to 0.5 micron aluminium frames box type of size 500x400x300mm including taking down all as specified.
Make Thermadyne/ Pall supralon filter / Micron filter
10
-
-
Supply and fix in replacement butter fly valve of dia 100 mm suitable for condensing /chiller water line with ISI marked including jointing with proper gasket ,nut,bolts washer all as specified.
4
-
-
Supply and fix in replacement butter fly valve of dia 125mm suitable for condensing /chiller water line with ISI marked including jointing with proper gasket ,nut,bolts washer all as specified.
6
-
-
Supply and fix in replacement butter fly valve of dia 150 mm suitable for condensing /chiller water line with ISI marked including jointing with proper gasket,nut,bolts washerall as specified.
4
-
-
Supply and fix in replacement NRV of dia 150 mm suitable for condensing /chiller water line with ISI marked including jointing with proper gasket ,nut,bolts washer all as specified.
6
-
-
Supply & fixing in replacement of water pressure gauge 4" dial type with cock 0-7 Kg/Sqm all as specified and as directed.
14
-
-
Supply& fixing in replacement of refrigerant/ Water Temp. gauge 4" dial type cock 0C to 50C all as specified and as directed. Make Emerald/ Wika / Rexroth
14
-
-
Supply & fix in repair 3 KW Strip Heater suitable for existing AHU incuding taking down all as directed.
12
-
-
Supply & fix in repair 2 KW Strip Heater suitable for existing AHU incuding taking down all as directed.
24
-
-
S&F in replacement of following ball bearing suitable for cooling tower motor,chillar motor, Blower motor, condenser motor etc removing of existing unserviceable bearing of any type or make all as directed.
-
-
-
Number - 6204zz
6
-
-
Number - 6205zz
6
-
-
Number - 6206zz
5
-
-
Number - 6207zz
5
-
-
Number - 6208zz
5
-
-
Number - 6304zz
6
-
-
Number - 6308zz
2
-
-
Number - 6309zz
2
-
-
Number - 6311zz
1
-
-
Number - 6313zz
2
-
-
S&F in replacement of following ball bearing model - P212 with housing suitable for AHU Blower etc removing of existing unserviceable bearing of any type or make all as directed.
3
-
-
Supply, Erection, testing and commissioning in repair O closed cell elastomeric nitrile rubber with aluminum foil laminated on oneside, having thermal Temperature, of 20c as per EN 12667, moisture diffusion resistance factor or u Value of minimum 7000 for base insulation material without the foil as per EN 12086, fire performance such that it passes Class 1 as per BS476 Part 7 for surface spread of flame and also fire performance of V0, HB as per UL 94, 1996, density without the foil between 40 to 55 KG/ Cum. the insulation material shall be FM ( factory Mutual) USA approved and dust & fiber free. the Aluminium foil shall be 60 microns thick and its weight shall be 193 gms as per EN ISO 2286-2, tensile strength 90 N/ 15 mm as per EN ISO 527-3 with elongation10% as per EN ISO 527-3. All complete as specified in particular specification 19 mm thick thermal insulation as directed.
105
-
-
Supply and fix in replacement MCCB of following capacities
-
-
-
400A,TP.415V,50 Hz, 36 KA adjustable type
1
-
-
250A,TP.415V,50 Hz 36 KA adjustable type
1
-
-
160A,TP.415V,50 Hz 36 KA adjustable type
2
-
-
125A,TP.415V,50 Hz, 16KA adjustable type
1
-
-
25 to 100A,TP,415V,50Hz,16KA
6
-
-
Supply and fixing 415 Volt 10 kA 'C' curve MCB of TP upto 100 Amps and current carrying capacity in the DB / Panel complete all as specified and as directed by Engineer -in-charge
15
-
-
Supply and fix in replacement of contactor of following capacities suitable for existing of panel and sample complete all as specified and as directed by Engineer -in-charge
-
-
-
70A, TP with 2 NO + 2 NC
3
-
-
40A, TP
3
-
-
32A, TP
3
-
-
25A, TP
5
-
-
18A, TP
5
-
-
12A, TP
8
-
-
9A, TP
4
-
-
3TF 52 with 2 NO + 2 NC
1
-
-
3TF 54 with 2 NO + 2 NC
3
-
-
Supply and fix in replacement of over load relay following capacities suitable as per the existing sample and all as directed.
-
-
-
MN5 of rating 20-33A
1
-
-
30-50A
1
-
-
14-23A
5
-
-
9-15A
6
-
-
6-10A
6
-
-
4.5-7.5A
2
-
-
Supply and fix in replacement of Fuse holder Suitable for Bolted fuse-links rating 20 Amp suitable as per site requirement complete all as specified and as directed by Engineer -in-charge
35
-
-
Supply and fix in replacement of Bolted fuse links SG BS type rating 2 Amp to 20 Amp suitable as per site requirement complete all as specified and as directed by Engineer -in-charge
35
-
-
Supply only Lub oil for Frame 4 compressor Part No . 55.400.81.303 for topping up whenever required all as specified and directed.
120
-
-
Supply and replace the temperature and humidity sensor coupled with actuators all as specified and as directed.
8
-
-
Supply and replace three way mixing /modulating valve (Actuator) of diameter 125 mm proportional linear type, motorised mixing valve BS 4540 PN-10 -PN 40 having manual over ride facility with proportional thermostat/Humidity sensor and interconnection wiring with 1.5 sq mm copper conductor multi core cable all as specified and directed
3
-
-
Supply and replace three way mixing /modulating valve (Actuator) of diameter 80 mm proportional linear type, motorised mixing valve BS 4540 PN-10 -PN 40 having manual over ride facility with proportional thermostat/Humidity sensor and interconnection wiring with 1.5 sq mm copper conductor multi core cable all as specified and directed
3
-
-
Supply and replace three way mixing /modulating valve (Actuator) of diameter 50/65mm proportional linear type, motorised mixing valve BS 4540 PN-10 -PN 40 having manual over ride facility with proportional thermostat/Humidity sensor and interconnection wiring with 1.5 sq mm copper conductor multi core cable all as specified and directed
3
-
-
Supply and replace unserviceable cooling pad in AHU's with necessary supports etc of following size as per OEM
-
-
-
450x900x200 mm
1
-
-
1000x900x200 mm
2
-
-
700x750x200 mm
2
-
-
1000x1080x200 mm
2
-
-
1200x1200x200 mm
4
-
-
700x900x200 mm
2
-
-
500x600x200 mm
5
-
-
Supply and replace unserviceable blower motor base plate suitable for 5 HP and 3 HP as per site requirement all as directed
8
-
-
Repair and replacement of old unserviceable AHU doors of any size door double skin pannel with pressure injected CFC & HCFC free PUF having 'K' value of 0.02 W/C/m & dinsity of 40 kg/ms pre coated, pre plasticized , galvanized outer and inner skin 0.06mm thick, air tight casing using gasket and self adhesiv,PVC Nylon hinges, handels view port and marine lamp ,limit switch etc complete all as direct
Make : Kirloskar / Blue star / Voltas
14
-
-
Supply and Replacement AHU blower DIDW fan blower having out velocity not exceeding S.P.(mm/wg) 50-60 m/s energy efficient fan with double inlet , double with forward or backward curved impeller for high static pressure mounted on aluminium extended side rail base frame, existing AHU of following Make: Kruger
-
-
-
Model : BDB-250-CM D20
4
-
-
Model: KAT"9/9" S D20
4
-
-
M&L for disconnecting and removing old unserviceable AHU drainage line of MS pipe, S & F of new drainage line of 50 mm dia UPVC Pipe including all fittings and necessary clamping all as directed and as specified.
62
-
-
Supply & replace unserviceable syphon with cock 3/8" complete all as specified and as directed by Engineer -in-charge Make : Sant / H Guru / Poineer
16
-
-
Supply & replace unserviceable HRC fuse 315 Amps complete all as directed and as specified. Make : L & T/ Seimense / Havells / Legrand
6
-
-
Supply & replace unserviceable water flow switch complete all as specified and as directed by Engineer -in-charge .
6
-
-
Supply & replace unserviceable float valve 25 mm complete all as specified and as directed by Engineer -in-charge
2
-
-
Supply & replace unserviceable dehumidifier pump 0.75 hp complete all as specified and as directed by Engineer -in-charge
5
-
-
Supply & replace unserviceable dehumidifier pump 0.5 hp complete all as specified and as directed by Engineer -in-charge .
3
-
-
Repair to Microprocessor based control panel display unit for 200 TR AC chiller unit. Make : Kirloskar / Dun-Ham-Bush / Blue star
2
-
-
M&L for descaling of Cooling coil of AHU's of any capacity by means of adding descaling chemical solution or equivalent of required quantity and circulating the liquid to remove the scales inside the pipes and cleaning the water tubes by scrubbing with nylon brushes and flushing with fresh water, re fixing the covers, Inlet and out let pipes including replacement of neoprene rubber gasket if required etc. complete all as specified and as directed by Engineer -in-charge
12
-
-
Supply and fix supply air diffuser for the 4-way square, air terminal shall be of aluminium powder coated construction with easily removable central core & 4-way uniform air distribution. Volume control damper to be of opposed blade, nylon geared with aerofoil blades & blank matt powder coated (out to out) size shall be as per existing with full louvers with required duct connection size (as per approved layouts) & as per approved sample (Colour to match architects requirements)complete all as specified and as directed by Engineer -in-charge
42
-
-
S& F air diffuser for the 4-way square return air terminal should be in aluminium powder coated construction with easily removable central core & 4-way uniform air distribution.(Out to out size shall be as per existing with full louvers with required duct connection size (as per approved layouts) & as per approved sample (Colour to match architects requirements)complete all as specified and as directed by Engineer -in-charge
42
-
-
Supply, assembly and erection of GI sheet with TDF flange rectangular/square duct made out of L shaped hollow profile, duly factory boxed including all accessories such as corner, cleat, carriage bolt, gasket and appropriate sealant on longitudinal joints etc. complete with GI sheet of thickness 22 gauge complete all as specified and as directed by Engineer -in-charge
22
-
-
Supply, assembly and erection of GI sheet with TDF flange rectangular/square duct made out of L shaped hollow profile, duly factory boxed including all accessories such as corner, cleat, carriage bolt, gasket and appropriate sealant on longitudinal joints etc complete with GI sheet of thickness 24 gauge complete all as specified & directed.
17
-
-
Material and Labour for leak testing of gas by evacaveting the gas by suitable means and filling with nitrogen gas for 24 hours rectifying the leakages with and including required material / brazing etc. and refilling gas testing chiller all specified and directed.
3
-
-
Supply, Install, Testing and commisiong by OEM new control panel for 200 TR Chiller unit Retrofit item for MCS-8 TO K SMART with advance technology including taking down of the exsting system with following conditions:-
i) The panel spare part guarentee is not less than 12 months inclusive in quotated rate.
ii) The cost of training to the working staff / operator inclusive in quotated rate.
iii) The cost of programming inclusive in quotated rate.
iv) Trial run is not less than 72 hours from the changing of panel.
v) Checking the set parameters in the controller checking safety fault trips taking control test, contacts cleaning etc. should described to the existing staff.
1
-
-
M&L for rewiring of K-SMART controller installation wiring and restarting charges of installed panel from the original OEM complete all as specified and directed.
1
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements
Past BiddersThis list is curated from the bidders of the similar tenders in the past
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%