Military Engineer Services Tender
Know all about the latest MP tenders along with the tender details and downloadable document on BidAssist. Here, on this page, we shall help you search for every MPtender posted on the official website of mptenders.gov.in according to authority, district, etc. Be it an irrigation tender or MP PWD tender, and we will tell you how to bid for these and more.
Military Engineer Services - MES Tender
Eprocure
Opening Date24 Nov 2023
Closing Date24 Jan 2024
Tender Amount₹ 4,15,00,000
Costs
EMD
₹ 4,90,000Document Cost
₹ 2,000Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2023_MES_597761_2Bid Award Id
ViewTender No
958430/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Lump sum price worked out by the contractor for Internal Water Supply as listed in Sch ‘A’ Part II.
1
-
101302.11
... More
Sch A Part III (INTERNAL ELECTRIFICATION)
-
-
-
... More
Lump sum price worked out by the contractor for Internal Electrification as listed in Sch ‘A’ Part III .
1
-
679184.39
... More
Sch A Part IV (EXTERNAL ELECTRIFICATION)
-
-
-
... More
Lump sum price worked out by the contractor for EXTERNAL ELECTRIFICATION as listed in Sch ‘A’ Part IV .
1
-
510129.4
... More
Sch A Part V (EXTERNAL WATER SUPPLY)
-
-
-
... More
Lump sum price worked out by the contractor for EXTERNAL WATER SUPPLY as listed in Sch ‘A’ Part V.
1
-
243503.18
... More
Sch A Part VI (UG SUMP)
-
-
-
... More
Lump sum price worked out by the contractor for UG SUMP as listed in Sch ‘A’ Part VI.
1
-
244452.72
... More
Sch A Part VII (AADN/ALTN OF BLDG WORK)
-
-
-
... More
Lump sum price worked out by the contractor for Addn/Altn of Bldg work as listed in Sch ‘A’ Part VII
1
-
3295808.76
... More
Sch A Part VIII (LIGHTENING PROTECTION)
-
-
-
... More
Lump sum price worked out by the contractor for LIGHTENING PROTECTION as listed in Sch ‘A’ Part VIII
1
-
56419.65
... More
Sch A Part IX (SPECIAL ITEMS OF WORK (B/R))
-
-
-
... More
Lump sum price worked out by the contractor for SPECIAL ITEMS OF WORK (B/R) as listed in Sch ‘A’ Part IX
1
-
2166999.05
... More
Sch A Part X (ROAD/PATH/CULVERT AND HARDSTANDING)
-
-
-
... More
Lump sum price worked out by the contractor for ROAD/PATH/CULVERT AND HARDSTANDINGl as listed in Sch ‘A’ Part X.
1
-
1959293.35
... More
Sch A Part XI (SEWAGE DISPOSAL)
-
-
-
... More
Lump sum price worked out by the contractor for SEWAGE DISPOSAL as listed in Sch ‘A’ Part XI
1
-
292960.33
... More
Sch A Part XII (AREA DRAINAGE)
-
-
-
... More
Lump sum price worked out by the contractor for AREA DRAINAGE as listed in Sch ‘A’ Part XII
1
-
164625.24
... More
Sch A Part XIII (BOUNDARY WALL/FENCING/GATE)
-
-
-
... More
Lump sum price worked out by the contractor for BOUNDARY WALL/FENCING/GATE as listed in Sch ‘A’ Part XIII
1
-
493890.1
... More
Sch A Part XIV (SITE CLEARANCE AND DEVELOPMENT)
-
-
-
... More
Lump sum price worked out by the contractor for SITE CLEARANCE AND DEVELOPMENT as listed in Sch ‘A’ Part XIV
1
-
109781.85
... More
Sch A Part XV (Miscellaneous Items of B/R and E/M)
-
-
-
... More
M & L for point wiring with 2.5 sqmm single core 1100v grade FRLSH PVC insulated unsheathed multistranded copper conductor with in and including PVC concealed conduit medium grade with all fittings including pressed MS sheet (1.6mm thick) sunken box with 3mm laminated sheet cover ISI marked suitable for an independant 6 pin 15/16 amps socket outlet ,including 2.5 sqmm single core 1100v grade FRLSH PVC insulated unsheathed multistranded copper conductor as earth continuity conductor connected to comman earth dolly including cutting chases in walls / floors for concealed conduiting and making good disturbed surface area to match with the adjoining surface complete all as specified and directed.
25
-
-
... More
M & L for point wiring with 4 sqmm single core 1100v grade FRLSH PVC insulated unsheathed multistranded copper conductor with in and including PVC concealed conduit medium grade with all fittings for an independant 20 Amps socket outlet ,including 4 sqmm single core 1100v grade FRLSH PVC insulated unsheathed multistranded copper conductor as earth continuity conductor connected to comman earth dolly including cutting chases in walls / floors for concealed conduiting and making good disturbed surface area to match with the adjoining surface all as specified and directed.
16
-
-
... More
S & F Wall / surface mounted type LED light fitting batten type complete with LED lamp 5- watt (1 feet long), poly carbonate body and integrate electronic drive complete with all accessories internally pre-wired and including connecting up with twine core twisted flexible copper conductor cable complete all as specified and as directed.
6
-
-
... More
Supply & fix Wall Mounted Air Circulator fans 230 volts single phase oscillating 450 mm sweep suitable for wall mounting complete all as specified an directed.
22
-
-
... More
S&F LED Street Light Fittings having Ingress Protection class minimum IP-65 , suitable for road lighting luminaire with high power LED and maintenance free system for capacity 20 W complete with 32 mm bore light grade GI pipe bracket (1.5m long) duly bent to shape including 2 Nos M.S. Flat (25mmx5mm) clamps, nuts, bolts, washers etc. all as specified and as directed. Note : The M.S. Clamps are to be painted with 2 coats of Aluminium Paint over a coat of Red Oxide Metal Primar before fixing at different positions.
6
-
-
... More
S & F concealed type GI Sheet enclousure for Modular switches / sockets etc. with module cover complete with a 20 Amps modular type motor starter(2 Module) with one single pole Modular type MCB of capacity 20 Amps (1 Module) including electrical connections complete all as specified and directed.
16
-
-
... More
S & F MCB single pole 240 volts, 'B' curve of rating from 63 amps, with rupturing capacity 10 KA,including providing thimble for out going cables complete all as specified and directed.
1
-
-
... More
M&L for earthing complete with galvanised steel plate electrode 600mm x 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25 Mts deep below ground level with top edge of the plate not less than 1.50 Mtrs below ground level connected to glavanised iron Wire 4.0 mm dia by means of bolts, nuts check nuts and washers of galvanised iron or steel connected to earthing test point all as specified incl 15 mm GI tubing medium grade and necessary fitting for protection of GI wire incl laying of charcoal dust and common salt in alternate layer, PCC Pit (1:3:6) type C-1 using 20 mm graded stone aggregate, RCC cover 40mm thick (1:2:4) type B-0 using 12.5mm graded stone aggregate reinforced with 6 mm dia round bar @ 75mm C/C both ways with MS handle 8mm dia, plastering 15mm thick CM (1:6) externally upto 150mm below ground level , GI funnel with 20mm dia medium grade GI pipe for watering and wire mesh incl excavation and earth work and disposal of surplus soil complete all as specified and shown on electrical plate No 3 of SSR Part-I (2009) and connected to earth test point incl testing and marking Bldg Nos and writing Test Results on a 3.0mm thick painted M.S. earth pit marking Plate (200mm x 100mm) duly welded with a 450mm long 10mm dia round M.S. rod, fixed with the earth pit chamber by grouting complete all as specified and directed. Note:- (i) GI wire and GI pipe medium grade, up to 7.5mtr shall be deemed to be included in the rates quoted for earthing. (ii) Excavation and earth work in any type of soil strata shall be deemed to be included in rates quoted for earthing. (iii) The rates quoted by the contractor are deemed to be included for MS sheet of size 300x300x3mm th, fixed with necessary nuts and bolts on angle iron of size 40X40x5mm, 60cm long and grouted with PCC block of size 200x200x250mm (PCC 1:3:6 using 20mm grade stone aggregate including necessary earth work for marking the result and purpose.
2
-
-
... More
Supply, installation, commissioning and testing of Split type Air Conditioner of 2 TR (6000 Kcal/Hr) capacity with heating arrangement complete with cordless remote control unit, 5 star rating and EER of 3.5 and above, Indoor unit Hi wall mounted type suitable for 230 volts, 50 Hz, single phase AC supply and capable of performing the function as cooling and heating, Outdoor unit of the air conditioner shall be fitted with discharge cool type rotary/ scroll compressor operating on non-CFC refrigerants (like R410 A or equivalent) with over load protection and mounted on resistant mountings for quite operation. The filters packs provided shall be washable. Remote cordless control with LCD/LED display shall be provided with ON/OFF timer, fan speed selector (min 3 speed), mode selector (heating/cooling/drying/fan) and setting -up of temperature. Display of temperature and mode shall be provided on indoor unit and on handset. Overall power factor of the unit shall not be less than 0.85 at operating conditions complete all as specified and directed. Note: The installation shall include mounting/ fitting indoor and outdoor unit at respective locations. Laying refrigerant piping, drain pipe up to 6 mtr length and connecting both units after drilling holes, putting PVC sleeve, sealing and finishing the same duly matched with adjoining surface. Refrigerant pipe shall be insulated with expanded polyethylene foam not less than 5mm thick. Leak testing of the entire system after installation to be carried out. Rate quoted will include Charging refrigerant gas in the unit, suitable electric connection between indoor and outdoor unit (up to 6 mtr) and up to switch (up to 3 mtr).
16
-
-
... More
Supply and fix copper wound voltage stabiliser of 4 KVA capacity for automatic operation, single phase naturally air cooled indoor type and designed for input variation between 170 to 270 volts with out put voltage stabilised at 230 volts with accuracy +/-1%, Operating frequency 50 Hz.complete all as specified and directed.
16
-
-
... More
M&L for compete removal of exsiting painted surface of wall, pillasters, cornices etc. complete etc and applying two coats of exterior emulsion paint over a coat of primer complete all as specified and as directed.
745
-
-
... More
M&L for preparation of new plastered surface of wall, pillasters, cornices etc complete etc and applying two coats of exterior emulsion paint over a coat of primer complete all as specified and as directed.
80
-
-
... More
S & F Vitreous China soap tray embedded in the wall complete all as specified and as directed.
2
-
-
... More
Complete removal of existing bitumeneous felt treatment/cement plaster etc over roof surfaces including wire brushing, cleaning surfaces and removing malba out of Def land exc 1.5 KM but n.exc 5.00 KM complete all as specified and as directed.
720
-
-
... More
S & F Powder coated anodised aluminium Partition wall (for Cubicals) 2.1 mtr high with 5mm glass of make Modi/Atul and partly/fully fixed with 12mm thick prelaminated particle board fixed with aluminium snap beading and rubber gasket complete all as specified and directed.
40
-
-
... More
S&F stainless steel for railings Jindal stainless ateel ERW Pipe Nominal Bore 40mm all as specified and directed.
85
-
-
... More
S&F stainless steel for railings Jindal stainless ateel ERW Pipe Nominal Bore 20mm all as specified and directed.
84
-
-
... More
S & F Powder coated anodised three track aluminium sliding window(ALSW/18) or as per site requirement including all necessary fittings such as roller, rubber beading locking arrangement clit , galzing, guazing etc. complete all as specified & directed by Engr-in-charge.
104
-
-
... More
S & F powder coated aluminium deco grills of approved make. Weight of grill 2.50 Kg per Sqm appx including frame alaround, fixed to window opening with necessary fixing arrangement complete all as specified and directed.
104
-
-
... More
S & F Powder coated anodised aluminium door (ALD/10 or size as specified) incl 5mm glass of make Modi/Atul and partly/fully fixed with PVC sheet fixed with aluminium snap beading and rubber gasket and necessary joining cleats, glazing clips,rubber neoprene packing, Each shutter fitted with one 04 lever mortice lock, tower bolts, handles and one hydraulic floor spring of approved make complete all as specified & directed by Engr-in-charge.
30
-
-
... More
S & F Powder coated anodised aluminium ventilaors including glass panes ,gauge and all necessary fittings complete all as specified and directed.
4
-
-
... More
Cutting the existing road/hard standing etc of any description of surface and excavation in trenches 30cm wide and 60cm depth for laying of UG electric cable complete all as specified and directed. (The rate includes returning, filling, watering and ramming in layers and making good the surface as the existing after laying of electric cables)
6
-
-
... More
Supply, Install, Testing and Commissioning CPRI type tested, factory made, totally enclosed, min IP 51, dust, weather and vermin proof, 2 mm thick CRCA sheet indoor type LT Panel , compartmentalized to accomodate each control gear, front openable, single door system lockable/openable with "U' type gasket to make the inner shell completely vermin proof having chromium plated flush pattern locks (2 Nos in each compartment)for 415V, 3 phase 4 wire , 50 Hz AC system with TPN tinned copper bus bar of rating 1.5 times that of controlling MCCB with heat shrink color coded sleeve, supported on F class DMC/FRP insulator with short circuit withstand capacity 21MVA for 1 second, neutral bus bar of capacity of that of phase bus bar , general construction confirming to IS-8623/93, having bottom base channel of MS section not less than 75x75x5mm, louvers & air vent with gasket for natural flow of air, entire panel having common aluminium earth bar of size 25mm x 5mm at the rear with 2 Nos earth stud, solid connection from main bus bar to switchgears with required size ( minimum 1.5 Sqmm) PVC insulated copper conductor cable , properly bunched, tied, ferruled for proper identification and crimped with adequite size of lugs, cable alleys, cable gland plates thickness 3.15 mm in two half , inculding LED indicating lamp for all phases,earthing studs at bottom and threaded lifting lugs of suitable size at top , mounted on suitable PCC foundation for the complete panel base with following detailed specification, control and accessories complete:- (a) MCCB, 200 Amps, 4 pole 415 volts, 50Hz, AC supply, 25KA breaking capacity, adjustable thermal and magnetic setting, Ics=Icu - 1no. (Main incoming) (b) Anodised copper busbar of suitable length mounted on insulator of 300 Amps capacity - 4 nos. (c) MCCB, 125 Amps, 4 pole 415 volts, 50Hz, AC supply, 16KA breaking capacity, fixed thermal magnetic setting, Ics=Icu -1 No. (d) MCCB, 63 Amps, 4 pole 415 volts, 50Hz, AC supply, 16KA breaking capacity, fixed thermal magnetic setting, Ics=Icu -1 No. (e) Indicators Assy with LED (R,Y,B) - 3sets (on main incoming and all outgoings) (f) Digital ammeter 0-200 Amps with CTs and selector switch - 1set (on Incoming Main) (g) Digital voltmeter 0-500 Volts with selector switch - 1set (on Incoming Main)
(h) MCB, 16 Amps, TP, 415 V, 50 Hz, AC supply, 10 KA breaking capacity-01 No
(j) DOL starter, 3hp, 16 Amps-01 No.
1
-
-
... More
Material and labour for construction of new valve chamber size 600x600x600mm including necessary earth work in any type of soil, PCC foundation (1:3:6)type C-2, 40mm graded stone aggregate as in base concrete, brick work in CM 1:6 with 10 mm thick plaster internally and 15mm thick externally in CM 1:4, 4mm thick MS cover with hinges and locking arrangement fixed to angle iron frame made out of 40x40x6mm MS angles complete with two coats of synthetic enamel paint over one coat of red oxide primer on all metal works and three coats of white wash on all plastered surface of valve chambers complete all as specified and as directed.
1
-
-
... More
S & F Open well submersible pump, single phase, 230volts, copper wound of suitable RPM, 2HP with motor starter, submersible cable 3corex6sqmm upto 10 mtr complete all as specified and directed.
1
-
-
... More
Excavation in trenches nexc 1.50mtr wide and nexc 1.50m in depth and getting out in any type of soil complete all as specified and as directed.
41.32
-
-
... More
M&L for RCC Septic tank 100 Users designed to carry sewage and sullage water including earth work in any type of soil complete all as specified and shown in drawings.
2
-
-
... More
M&L for Construction of soak well 1.2 m dia and 3.00 m effective depth including earth work in any type of soil complete all as specified and shown in drawings.
2
-
-
... More
Supply and laying bricks (old size) for cable protection by using common burnt clay building bricks, sub-class ‘B’ designation 75 laid dry flat across length of the cable with width of the trenches equal to length of bricks complete all as specified and directed.
1
-
-
... More
M&L for Chemical earthing with copper plate 900x600x5mm thick, buried directly in ground (top edge of the plate should not be less than 1.50Mtrs below ground level) connected to copper strip 32x6mm by means of copper/brass nut, bolt duly brazed earth strip protected with 40mm bore medium grade GI pipe from electrode and upto and including the earth test point of gun metal/ phosphorous bronzed of size 75x75x25mm, watering pipe medium grade 15mm bore GI pipe including funnel, wire mesh, providing alternate layer of 150mm th each charcoal and megnesium sulphate upto 1.2mtr, PCC chamber using PCC (1:3:6) type C-1 using 20mm graded stone aggregate, RCC cover 40mm thick (1:2:4) type B-0 using 12.5mm graded stone aggregate reinforced with 6mm dia round bar @ 75mm C/C both ways with MS handle 8mm dia, plastering 15mm thick CM (1:6) externally up to 150mm below ground level, GI funnel with 20mm dia medium grade GI pipe for watering and wire mesh incl excavation and earth work and disposal of surplus soil complete all as specified and shown on Electrical plate No.3 of SSR Part-I (2009) and connected to earth test point incl testing and marking Bldg Nos and writing Test Results (in white) on a black painted M.S. Plate (size 300x300x3mm th) duly welded with angle iron of size 40X40x5mm, 60cm long, fixed with the earth pit chamber by grouting complete all as specified and directed.
Note :- (i) Copper strip and GI pipe medium grade, up to 7.5mtr shall be deemed to be included in the rates quoted for earthing. (ii) Excavation and earth work in any type of soil strata shall be deemed to be included in rates quoted for earthing. (iii) The rates quoted by the contractor are deemed to be included for MS sheet of size 300x300x3mm th, fixed with necessary nuts and bolts on angle iron of size 40X40x5mm, 60cm long and grouted with PCC block of size 200x200x250mm(PCC 1:3:6 using 20mm grade stone aggregate including necessary earth work for marking the result and purpose.
2
-
-
... More
M&L for earthing complete with galvanised steel plate electrode 600x600x6mm thick buried directly in ground (top edge of the plate should not be less than 1.50Mtrs below ground level) connected to galvanised iron strip 32x6mm by means of bolts, nuts check nuts and washers of galvanised iron or steel connected to earthing test point all as specified incl 40 mm GI tubing medium grade and necessary fitting for protection of GI strip incl laying of charcoal dust and common salt in alternate layers of 150mm th, PCC chamber using PCC(1:3:6) type C-1 using 20mm graded stone aggregate, RCC cover 40mm thick (1:2:4) type B-0 using 12.5mm graded stone aggregate reinforced with 6mm dia round bar @ 75mm C/C both ways with MS handle 8mm dia, plastering 15mm thick CM (1:6) externally up to 150mm below ground level, GI funnel with 20mm dia medium grade GI pipe for watering and wire mesh incl excavation and earth work and disposal of surplus soil complete all as specified and shown on Electrical plate No.3 of SSR Part-I (2009) and connected to earth test point incl testing and marking Bldg Nos and writing Test Results (in white) on a black painted M.S. Plate (size 300x300x3mm th) duly welded with angle iron of size 40X40x5mm, 60cm long, fixed with the earth pit chamber by grouting complete all as specified and directed.
Note :- (i) GI strip and GI pipe medium grade, up to 7.5mtr shall be deemed to be included in the rates quoted for earthing. (ii) Excavation and earth work in any type of soil strata shall be deemed to be included in rates quoted for earthing. (iii) The rates quoted by the contractor are deemed to be included for MS sheet of size 300x300x3mm th, fixed with necessary nuts and bolts on angle iron of size 40X40x5mm, 60cm long and grouted with PCC block of size 200x200x250mm(PCC 1:3:6 using 20mm grade stone aggregate including necessary earth work for marking the result and purpose.
6
-
-
... More
Cutting of existing main distribution GI pipe 50mm dia and inserting tee, bends etc. including necessary all connected accessories for tapping onnection complete all as specified and directed.
1
-
-
... More
Supply, installing, testing and commissioning of Automatic Phase Sequence corrector (APSC) with power coated wall mounted cabinet, 440 Volts, 75 KVA, 100 Amps, separate LED indication for normal & reverse input phase sequence with protection from under/over voltage, phase loss, phase reverse, voltage imbalance and avoid damages during phase sequence changes all as directed.
3
-
-
... More
Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 25 sqmm 4 core complete all as specified and directed.
30
-
-
... More
Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 50 sqmm 3.5 core complete all as specified and directed.
40
-
-
... More
Supply, laying and testing submersible cable PVC insulated, flat, electric power cable (heavy duty) 1100 volts grade with stranded copper conductor of size 4 sqmm 3 core complete all as specified and directed.
50
-
-
... More
Material and labour for GI tubing light grade of 40 mm dia for cable protection on pole/wall/floor or laid in trenches and drain etc complete with necessary clamp, nut, bolts and washers and socket and making good the disturbed surface of wall, floor or roof etc all as specified and directed.
40
-
-
... More
M&L for cutting chases, pinning in making good to facings where required and pointing in cement mortar 1:3 to ends or edges of landings, steps, sills, sunshades, shelves, lintels, etc. and cutting chases for concealed conduit wiring etc. and making good, cutting not exec. 10 cm girth all as specified and directed.
70
-
-
... More
S & F in repair PVC (SWR) Pipes of 110mm dia single socketed in any length with rubber ring joints fixed to wall complete all as specified and directed.
33
-
-
... More
S&F in repair Vitreous China bowl urinal flat back, size of 465 x 355 x 265 mm white (minimum), with grating and union for discharge pipe (excluding flushing cistern, flush pipe and waste pipe) fixed in repair complete all as specified and directed.
8
-
-
... More
S & F in repair Vitreous China wash basin, white, flat back, size 630x450mm excluding taps,waste, chain and plug and porcelain stopper but including brackets fixed in repair complete all as specified and directed.
2
-
-
... More
S & F in repair Towel Rail 600mm long of PTMT fixed with and including Chromium plated brass screws and wooden/plastic cleats (Minimum weight 190gms) complete all as specified & directed.
2
-
-
... More
Schedule of Credit (MINUS) Rs.78,550.00 B/F from Serial Page No. 26 [Note : Details of items for schedule of credit is given on Serial Page No.26]. This amount shall be automatically deducted to arrive at tendered sum
-
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements