Military Engineer Services Tender
Know all about the latest MP tenders along with the tender details and downloadable document on BidAssist. Here, on this page, we shall help you search for every MPtender posted on the official website of mptenders.gov.in according to authority, district, etc. Be it an irrigation tender or MP PWD tender, and we will tell you how to bid for these and more.
Military Engineer Services - MES Tender
Electrical Cables And Wires
Electrical and Electronics
Electrical Works
Eprocure
Opening Date9 Dec 2023
Closing Date13 Jan 2024
Tender Amount₹ 2,38,00,000
Costs
EMD
₹ 3,13,000Document Cost
₹ 2,000Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2023_MES_631985_1Bid Award Id
ViewTender No
CA NO. CEBZ / DHA / TOKEN / 06 OF 2023-24Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Dismantling of insulator any type, any size etc complete all as specified and directed.
1547
-
-
Dismantling of existing cable from pole/panel/DB/wall/ceiling/roof of size 10sqmm, 2 core etc complete all as specified and directed.
40
-
-
Dismantling of existing cable from pole/panel/DB/wall/ceiling/roof of size 16sqmm, 2 core etc complete all as specified and directed.
155
-
-
Dismantling of existing cable from pole/panel/DB/wall/ceiling/roof of size 10sqmm, 4 core etc complete all as specified and directed.
2525
-
-
Dismantling of existing cable from pole/panel/DB/wall/ceiling/roof of size 16sqmm, 4 core etc complete all as specified and directed.
1090
-
-
Dismantling of existing cable from pole/panel/DB/wall/ceiling/roof of size 25sqmm, 4 core etc complete all as specified and directed.
15
-
-
Dismantling of existing cable from pole/panel/DB/wall/ceiling/roof of size 35sqmm, 4 core etc complete all as specified and directed.
45
-
-
Dismantling of existing cable from pole/panel/DB/wall/ceiling/roof of size 50 sqmm, 4 core etc complete all as specified and directed.
120
-
-
Dismantling of existing cable from pole/panel/DB/wall/ceiling/roof of size 70 sqmm, 4 core etc complete all as specified and directed.
108
-
-
Dismantling of existing cable from pole/panel/DB/wall/ceiling/roof of size 95 sqmm, 4 core etc complete all as specified and directed.
201
-
-
Dismantling of existing cable from pole/panel/DB/wall/ceiling/roof of size 120 sqmm, 4 core etc complete all as specified and directed.
70
-
-
Dismantling of existing cable from pole/panel/DB/wall/ceiling/roof of size 150 sqmm, 4 core etc complete all as specified and directed.
78
-
-
Dismantling of existing cable from pole/panel/DB/wall/ceiling/roof of size 185 sqmm, 4 core etc complete all as specified and directed.
80
-
-
Dismantling of old unserviceable panel of any size including MCCB's/switchgears etc complete all as specified and directed.
8
-
-
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 185 sq mm 3.5 core.
3152
-
-
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 150 sq mm 3.5 core.
1020
-
-
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 sq mm 3.5 core.
150
-
-
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sq mm 3.5 core.
835
-
-
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 sq mm 3.5 core.
1615
-
-
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 sq mm 3.5 core.
1860
-
-
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sq mm 3.5 core.
950
-
-
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm 4.0 core.
1090
-
-
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sq mm 4.0 core.
4655
-
-
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 4.0 core.
13000
-
-
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sq mm 2.0 core.
1300
-
-
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 2.0 core.
3000
-
-
Supply, installation, commissioning and testing of main LT panel Made out of CRCA sheet 3.15mm thick sheet steel, outdoor type, factory made by CPRI approved manufacturer, totally enclosed, dust and vermin proof (protection class IP 54), (front opening) with locking arrangement, double door duly compartmentalized with extended canopy at the top, the panel shall be duly powder coated with colour shade RAL 7035 Siemens grey pure polyester or as directed by AGE (I) / GE, adopting 8 tank pretreatment of fabricated job before powder coating & including One Danger notice plate 1.6mm thick, main aluminum bus bar of 400A TPN, all inter connections to outgoing feeders shall be made with TPN alumium bus bar of rating not less than the current carrying capacity of respective feeder, all bus bar shall be covered with colour coded heat shrinkable sleeve, the complete panel shall be mounted on ISMC of 75X40mm, length of leg not less than 90cm including 30cm grouting duly painted with black enamel paint. Digital ammeter (0-400) with ASS-1No., current transformer of rating 400/5A-3No., Digital voltmeter with VSS (0-500)V - 1No., RYB LED set-1, including suitable size of cable lugs and PCC (1:2:4) type B1 foundation complete all as specified and directed by Engr-in-charge. the panel shall consist of the following switchgear :-
Incomer - MCCB 4P 225 A 38kA - 1No.
Out Going - MCCB 3P 160A 38kA - 1 No., MCB 3P 100A 38kA - 1 No., MCCB 3P 32A 16kA - 12 Nos, or as directed by AGE / GE (I)
1
-
-
All as per item 30.00 above but 300 Amps rated bus bar & comprising the following switchgear for (FP-1)
Incoming - (a) MCCB 4P 160A 38kA - 1 No.
Out Going - (b) MCCB 3P 32A 16kA - 5 No.
1
-
-
All as per item 30.00 above but 200 Amps rated bus bar & comprising the following switchgear for (FP-2)
Incoming - (a) MCCB 4P 100A 38kA - 1 No.
Out Going - (a) MCCB 3P 63A 38kA - 1 No.
(b) MCCB 3P 32A 16kA - 5 No.
1
-
-
All as per item 30.00 above but 100 Amps rated bus bar & comprising the following switchgear for (FP-3)
Incoming - (a) MCCB 4P 63A 38kA - 1 No.
Out Going - .
(a) MCCB 3P 32A 16kA - 5 No.
1
-
-
All as per item 30.00 above but 525 Amps rated bus bar & comprising the following switchgear for (LTP-2) (T-2)
Incoming :-
(a) MCCB 4P 350A 38kA - 1 No.
Out Going - (a) MCCB 3P 160A 38kA - 1 No.
(b) MCCB 3P 125A 38kA - 2 No.
(c) MCCB 3P 32A 16kA - 7 No.
1
-
-
All as per item 30.00 above but 300 Amps rated bus bar & comprising the following switchgear for (FP-4)
Incoming :-
(a) MCCB 4P 160A 38kA - 1 No.
Out Going - .
(a) MCCB 3P 32A 16kA - 7 No.
1
-
-
All as per item 30.00 above but 200 Amps rated bus bar & comprising the following switchgear for (FP-5)
Incoming :- (a) MCCB 4P 125A 38kA - 1 No.
Out Going - .
(a) MCCB 3P 32A 16kA - 6 No.
1
-
-
All as per item 30.00 above but 200 Amps rated bus bar & comprising the following switchgear for (FP-6)
Incoming :-
(a) MCCB 4P 125A 38kA - 1 No.
Out Going - .
(a) MCCB 3P 32A 16kA - 9 No.
1
-
-
All as per item 30.00 above but 525 Amps rated bus bar & comprising the following switchgear for (LTP-3) (T-3)
Incoming :-
(a) MCCB 4P 350A 38kA - 1 No.
Out Going - (a) MCCB 3P 160A 38kA - 1 No.
(b) MCB 3P 125A 38kA - 1 No.
(c) MCCB 3P 63A 38kA - 1 No.
(d) MCCB 3P 32A 16kA - 8 No.
1
-
-
All as per item 30.00 above but 300 Amps rated bus bar & comprising the following switchgear for (FP-7)
Incoming :-
(a) MCCB 4P 160A 38kA - 1 No.
Out Going - .
(a) MCCB 3P 32A 16kA - 11 No.
1
-
-
All as per item 30.00 above but 200 Amps rated bus bar & comprising the following switchgear for (FP-8)
Incoming :-
(a) MCCB 4P 125A 38kA - 1 No.
Out Going - .
(a) MCCB 3P 32A 16kA - 7 No.
1
-
-
All as per item 30.00 above but 100 Amps rated bus bar & comprising the following switchgear for (FP-9)
Incoming :-
(a) MCCB 4P 63A 38kA - 1 No.
Out Going - .
(a) MCCB 3P 32A 16kA - 6 No.
1
-
-
All as per item 30.00 above but 300 Amps rated bus bar & comprising the following switchgear for (LTP-4) (T-4)
Incoming :-
(a) MCCB 4P 160A 38kA - 1 No.
Out Going - (a) MCCB 3P 125A 38kA - 1 No.
(b) MCCB 3P 32A 16kA - 1 No.
1
-
-
All as per item 30.00 above but 200 Amps rated bus bar & comprising the following switchgear for (FP-10)
Incoming :- (a) MCCB 4P 125A 38kA - 1 No.
Out Going - (a) MCCB 3P 100A 38kA - 1 No.
(b) MCCB 3P 32A 16kA - 4 No.
1
-
-
All as per item 30.00 above but 200 Amps rated bus bar & comprising the following for (FP-11)
Incoming :-
(a) MCCB 4P 100A 38kA - 1 No.
Out Going - (a) MCCB 3P 63A 38kA - 1 No.
(b) MCCB 3P 32A 16kA - 4 No.
1
-
-
All as per item 30.00 above but 100 Amps rated bus bar & comprising the following for (FP-12)
Incoming :-
(a) MCCB 4P 63A 38kA - 1 No.
Out Going - (a) MCCB 3P 50A 38kA - 1 No.
(b) MCCB 3P 32A 16kA - 4 No.
1
-
-
All as per item 30.00 above but 100 Amps rated bus bar & comprising the following switchgear for (FP-13)
Incoming :-
(a) MCCB 4P 50A 38kA - 1 No.
Out Going - (a) MCCB 3P 40A 38kA - 1 No.
(b) MCCB 3P 32A 16kA - 4 No.
1
-
-
All as per item 30.00 above but 100 Amps rated bus bar & comprising the following switchgear for (FP-14)
Incoming :-
(a) MCCB 4P 40A 38kA - 1 No.
Out Going - (a) MCCB 3P 32A 16kA - 4 No.
1
-
-
All as per item 30.00 above but 200 Amps rated bus bar & comprising the following switchgear for (LTP-5),(T-5)
Incoming :-
(a) MCCB 4P 100A 38kA - 1 No.
Out Going - (a) MCCB 3P 63A 38kA - 2 No.
(b) MCCB 3P 32A 16kA - 1 No.
1
-
-
All as per item 30.00 above but 300 Amps rated bus bar & comprising the following switchgear for (LTP-6),(T-6)
Incoming :-
(a) MCCB 4P 160A 38kA - 1 No.
Out Going - (a) MCCB 3P 125A 38kA - 1 No.
(b) MCCB 3P 100A 38kA - 1 No.
(C) MCCB 3P 32A 16kA - 1 No.
1
-
-
All as per item 30.00 above but 200 Amps rated bus bar & comprising the following switchgear for (FP-15)
Incoming :-
(a) MCCB 4P 100A 38kA - 1 No.
Out Going - (a) MCCB 3P 63A 38kA - 3 No.
1
-
-
All as per item 30.00 above but 100 Amps rated bus bar & comprising the following switchgear for (FP-16)
Incoming :-
(a) MCCB 4P 63A 38kA - 1 No.
Out Going - (a) MCCB 3P 32A 16kA - 8 No.
1
-
-
All as per item 30.00 above but 300 Amps rated bus bar & comprising the following switchgear for (LTP-7),(T-7)
Incoming :-
(a) MCCB 4P 160A 38kA - 1 No.
Out Going - (a) MCCB 3P 125A 38kA - 1 No.
(b) MCCB 3P 32A 16kA - 1 No.
1
-
-
All as per item 30.00 above but 200 Amps rated bus bar & comprising the following switchgear for (FP-17)
Incoming :-
(a) MCCB 4P 100A 38kA - 1 No.
Out Going - (a) MCCB 3P 63A 38kA - 1 No.
(b) MCCB 3P 32A 16kA - 8 No.
1
-
-
All as per item 30.00 above but 200 Amps rated bus bar & comprising the following switchgear for (FP-18)
Incoming :-
(a) MCCB 4P 125A 38kA - 1 No.
Out Going - (a) MCCB 3P 32A 16kA - 13 No.
1
-
-
All as per item 30.00 above but 100 Amps rated bus bar comprising the following switchgear for (FP-19)
Incoming :-
(a) MCCB 4P 63A 38kA - 1 No.
Out Going - (a) MCCB 3P 32A 16kA - 5 No.
1
-
-
All as per item 30.00 above but 400 Amps rated bus bar & comprising the following switchgear for (LTP-8),(T-8)
Incoming :-
(a) MCCB 4P 250A 38kA - 1 No.
Out Going - (a) MCCB 3P 125A 38kA - 1 No.
(b) MCCB 3P 100A 38kA - 1 No.
(C) MCCB 3P 32A 16kA - 1 No.
1
-
-
All as per item 30.00 above but 200 Amps rated bus bar & comprising the following switchgear for (FP-20)
Incoming :-
(a) MCCB 4P 100A 38kA - 1 No.
Out Going - (a) MCCB 3P 63A 38kA - 3 No.
(b) MCCB 3P 32A 16kA - 1 No.
1
-
-
All as per item 30.00 above but 300 Amps rated bus bar & comprising the following switchgear for (FP-21)
Incoming :-
(a) MCCB 4P 125A 38kA - 1 No.
Out Going - (a) MCCB 3P 100A 38kA - 2 No.
(b) MCCB 3P 32A 16kA - 1 No.
1
-
-
All as per item 30.00 above but 200 Amps rated bus bar & comprising the following switchgear for (FP-22)
Incoming :-
(a) MCCB 4P 100A 38kA - 1 No.
Out Going - (a) MCCB 3P 32A 16kA - 9 No.
1
-
-
All as per item 30.00 above but 300 Amps rated bus bar & comprising the following switchgear for (LTP-9),(T-9)
Incoming :-
(a) MCCB 4P 225A 38kA - 1 No.
Out Going - (a) MCCB 3P 100A 38kA - 2 No.
(b) MCCB 3P 63A 38kA - 1 No.
(C) MCCB 3P 32A 16kA - 1 No.
1
-
-
All as per item 30.00 above but 200 Amps rated bus bar & comprising the following switchgear for (FP-23) & (FP-24)
Incoming :-
(a) MCCB 4P 100A 38kA - 1 No.
Out Going - (a) MCCB 3P 32A 16kA - 6 No.
2
-
-
M&L for earthing complete with galvanised steel earth plate 60cmx60cmx3.15 mm thick burried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level connected to galvanised mild steel earthing lead strip 32X6mm by means of bolts nuts check-nuts and washers of galvanized iron or steel as shown in electrical plate No 3 of MES schedule Part-I connecting to earthing test point and testing on completion with including 40mm bore light grade GI protection pipe and watering pipe shall be 20 mm bore, medium grade including excavation & earth work in any type of soil & disposal of soil, providing alternate layers of charcoal and common salt, construction of PCC earth chamber in 1:3:6 type C-1 with 40mm thick RCC 1:2:4 type B-1 cover, reinforced with 8mm TMT bars 100mm C/C both ways with life hook made out oof 8mm dia bars, watering arrangement with funnel & wire mesh, complete all as specified and directed. Note:- (i) The concrete pit shall be PCC (1:3:6) type C-1, 40 mm thick pre cast cover slab of RCC (1:2:4) type B-1 using 20mm graded stone aggregate reinforced with 8mm TMT bars @ 10 cm C/C on both sides with suitable cast iron handle shall be provided in lieu of cast iron cover shown in electrical plate No 3 of MES SSR Part-I.
(ii) The unit rate includes the cost of GI pipe light grade for protection of earth strip and earh strip upto 7.5 M. (iii) PCC pit shall be provided at least 500 mm away from the pit and not on the earth pit itself
66
-
-
M&L for earthing complete with galvanised steel earth plate 60cmx60cmx3.15 mm thick burried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level connected to earth lead of 4.0mm dia. galvanished mild steel wire by means of bolts nuts check-nuts and washers of galvanized iron or steel as shown in electrical plate No 3 of MES schedule Part-I connecting to earthing test point and testing on completion with including 15mm bore light grade GI protection pipe and watering pipe shall be 20 mm bore, medium grade including excavation & earth work in any type of soil & disposal of soil, providing alternate layers of charcoal and common salt, construction of PCC earth chamber in 1:3:6 type C-1 with 40mm thick RCC 1:2:4 type B-1 cover, reinforced with 8mm TMT bars 100mm C/C both ways with life hook made out oof 8mm dia bars, watering arrangement with funnel & wire mesh, complete all as specified and directed. Note:- (i) The concrete pit shall be PCC (1:3:6) type C-1, 40 mm thick pre cast cover slab of RCC (1:2:4) type B-1 using 20mm graded stone aggregate reinforced with 8mm TMT bars @ 10 cm C/C on both sides with suitable cast iron handle shall be provided in lieu of cast iron cover shown in electrical plate No 3 of MES SSR Part-I.
(ii) The unit rate includes the cost of GI pipe light grade for protection of earth strip and earh strip upto 7.5 M. (iii) PCC pit shall be provided at least 500 mm away from the pit and not on the earth pit itself
40
-
-
Supply & Fixing 100mm bore GI tubing Medium grade with all fittings as required for passing through cables under floors, along the wall or along the pole, etc with suitable size M.S.flat iron clamps incl nut,bolt and washer complete all as specified and directed.
Note - Excavation & Earthwork shall be measured & paid Separetely
400
-
-
Supply & Fixing 80mm bore GI tubing Medium grade with all fittings as required for passing through cables under floors, along the wall or along the pole, etc with suitable size M.S.flat iron clamps incl nut,bolt and washer complete all as specified and directed.
Note - Excavation & Earthwork shall be measured & paid Separetely
350
-
-
Supply & Fixing 50mm bore GI tubing Medium grade with all fittings as required for passing through cables under floors, along the wall or along the pole, etc with suitable size M.S.flat iron clamps incl nut,bolt and washer complete all as specified and directed.
Note - Excavation & Earthwork shall be measured & paid Separetely
300
-
-
M & L for MS junction box made out of 2mm thick sheet of size 250mm X 200mm X 150mm with 4 Nos. aluminium busbar of size 20X3 mm thick mounted on porcelain insulators with and including MCB, 'C' curve, SP, 06 Amp-01 No. including incoming and out going connections with necessary welding work, clamps and mounting on poles etc complete all as specified & directed.
616
-
-
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150mm dia suitable for 0.4 mpa working pressure complete all as specified & directed.
200
-
-
Excavation in trenches not exceeding 1.5 mtrs wide & not exceeding 1.5 mtr in depth in soft or loose soil & getting out complete all as specified & directed.
4516
-
-
Returning , filling in spreading, levelling, watering & well Ramming in layers not exc 25cm thick complete all as specified & directed.
2065
-
-
Removing excavated material not exceeding 50mtr &deposited where directed at a level not exceeding 1.5 mtr above the ground level complete all as specified & directed.
2205
-
-
M & L For sand filling with clean dry fine sand unwashed including gently punning around cables in trenches for cable protection (8cm below cable & 15cm above cable) complete all as specified and directed.
Note: Compacted/punned thickness shall be measured & paid.
2062
-
-
Supplying and laying un- reinforced precast concrete cable cover, class LV, type 2 with peak, size 300mm x 180mm x 40mm for laying in trenches for cable protection laid adjacent to each other length wise perpendicular to the central axix of cable complete all as specified and directed.
37920
-
-
M&L for bricks old size sub class B designation for cable protection cover laid flat and dry in trenches over the cable perpendicular to the direction of cable complete all as specified and directed.
170.56
-
-
Material and Labour Cement Concrete (1:2:4) type B-1(20mm Graded Stone Aggregate) as in Coping of Poles, etc. including Formwork (as required), complete all as specified & directed.
20
-
-