Military Engineer Services Tender
View complete overview of Lakshadweep MES Tender
Military Engineer Services - MES Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date27 Mar 2024
Closing Date18 Apr 2024
Tender Amount₹ 11,00,000
Costs
EMD
₹ 22,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_643036_2Bid Award Id
ViewTender No
8388/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Disconnecting and taking down outgoing cables from the DG sets and cutting removing the burnt cable ends and thimbling and refixing back including provision of cable glands, lugs, tools and testing of 62.5 KVA capacity of DG set complete all as specified and directed by Engr-in-charge.
1
-
-
Supply only (in replacement) spin on fuel filter (pre and fine filter) element with O ring for generator set of 62.5 KVA capacity complete all as specified and directed by Engr-in-charge.
1
-
-
Supply only (in replacement) Dry type Air filter element Inner and Outer unit as required at site with O' Ring of suitable for 62.5 KVA capacity DG Set complete all as specified and directed by Engr-in-charge.
1
-
-
Supply only (in replacement) Lub oil filter element with O Ring suitable for 62.5 KVA capacity DG Set complete all as specified and directed by Engr-in-charge.
1
-
-
Supply only (in replacement) By pass filter element with O ring of suitable for 62.5 KVA capacity DG Set complete all as specified and directed by Engr-in-charge.
1
-
-
Supply only V-belt suitable for 62.5 KVA capacity DG set including removing old unserviceable fan belt complete all as specified and directed by Engr-in-charge.
1
-
-
Supply and fixing (in repairs) Water Pump Assy suitable for 62.5 KVA capacity DG set including removing old unserviceable water pump assy complete all as specified and directed by Engr-in-charge.
1
-
-
Supply & fixing common rail diesel sensor suitable for DG Set engine complete all as specified and directed by Engineer-in-charge.
1
-
-
Supply and replacement Water outlet and inlet hose pipe from radiator to Engine and back from Engine to radiator complete all as specified and directed by Engr-in-charge.
1
-
-
Supply and replacement Lub oil pipe armoured of suitable length and socket size complete all as specified and directed by Engr-in-charge.
1
-
-
Supply and replacement Anti vibration rubber pad for side radiator.
1
-
-
Supply and replacement Lub oil pressure guage 0 to 10 kg / sq cm.
1
-
-
Supply and top up coolant oil.
15
-
-
Supply and top up engine oil 15W40 grade.
20
-
-
Supply and replace battery connecting single core copper cable 16sqmm with battery terminal made of brass with nuts/bolts/washer complete all as specified and as directed by Engr-in-Charge.
1
-
-
Supply and top up Battery Distilled water.
5
-
-
Supply and fixing SMPS battery charger 12V/24V DC including all fixing accessories and re-wiring with suitable size copper conductor FRLS grade PVC insulated two core cable drawn through PVC conduit not less than 20mm dia as required at site and complete all as specified and directed by Engr-in-charge.
1
-
-
Disconnecting, dismantling 12V/24V battery charging alternator assembly replacing the unserviceable burnt coil assembly, re-assembling, refixing to engine and testing for satisfactory charging of battery complete all as specified and directed by Engr-in-charge.
1
-
-
Supply and fixing (in repairs) AVR (Auto Voltage Regulator) suitable for Gen Set having input voltage 2 phase + neutral sensing voltage 415 output voltage 95V DC, output current 4 A DC voltage regulation +/- 1% average volts, over excitation current tripping fuse protection 4A, fast acting and frequency 50Hz for 62.5 KVA capacity complete all as specified and directed by Engr-in-charge.
1
-
-
Supply and fixing in replacement of Digital DG Controller suitable for any type DG Set of any capacity complete and connecting with existing electrical circuit complete all as specified and as directed by Engr-in-Charge.
1
-
-
Supply and fixing (in repairs) Diods set(Rectifier) of Main alternator of DG Set of capacity 62.5 KVA complete all as specified and as directed by Engr-in-Charge.
1
-
-
Supply and fixing (in replacement) CT Coil with CT Ratio 100/5A, 5VA Cl 1.0 accuracy all as per IS 2705-1992 complete all as specified and directed by Engr-in-charge.
1
-
-
Supply and fixing (in repairs) fuse unit 12V/24V DC (as per sample) suitable for DG Set control panel complete all as specified and directed by Engr-in-charge.
1
-
-
M&L Minor Repair/cleaning of fuel tank, removing sludge, arresting leak using metal paste/sealent or by welding/soldering, replacement of diesel receiver pipe from lock to tank with clamp set all as required at site complete for 62.5 KVA Gen Set complete all as specified and as directed by Engr-in-Charge.
1
-
-
Dismantling, removing the self starter, motor from the engine of following capacity DG sets, opening the self starter body and overhauling/servicing, replacement of carbon brushes with holders, contact plates, jumping leads and seals, re-varnishing the field coil, armature, re-assembling, testing for smooth functioning and re-fixing with the engine and connecting complete all as specified and directed for 62.5 KVA DG set complete all as specified and as directed by Engr-in-Charge.
1
-
-
S&F asbestos rope 12 mm dia wrapped over the exhaust pipe and painting with heat proof paint of approved colour including taking down the old rope complete all as specified and as directed by Engr-in-Charge.
4
-
-
Supply and fixing in replacement Volt meter digital type with 01 x selector switch complete all as specified and as directed by Engr-in-Charge.
1
-
-
Supply and fixing in replacement Ampere meter digital type with 01 x selector switches & CTs of suitable rating complete all as specified and as directed by Engr-in-Charge.
1
-
-
Supply and fixing in replacement LED phase indicator lamp assy RYB complete all as specified and directed by Engr-in-charge.
1
-
-
Supply and fixing (in replacement) Water separator suitable for DG set of capacity 62.5 KVA complete all as specified and as directed by Engr-in-Charge.
1
-
-
M & L for checking of AMF panels including replacement of unserviceable parts such as Relays, Timers, Power contactors, Auxilary contactors, defective copper wiring, MCCBs etc. for DG Set,complete all as specified and as directed by Engr-in-Charge. Note: - Spare parts shall be measured and paid separately under Supply only items
1
-
-
Supply only Auxiliary contactor 240 V 3 No & 1 NC
1
-
-
Supply only ON and OFF delay timer 240 V AC
1
-
-
Supply only Earth fault relay.
1
-
-
Supply only Over load relay.
1
-
-
Supply only Under voltage relay.
1
-
-
Supply only Power Contactor MCX 22, 4 Pole
1
-
-
Supply only Power Contactor MCX11, 4 Pole
1
-
-
Dismantling of 62.5 KVA Capacity alternator from Generator after Dismantling from Generator shifting to workshop, taking out burnt out winding from Stator & Rotator, Cleaning thoroughly and rewinding the stator with suitable guage of super enameled copper conductor similar to that of existing size including necessary insulating material varnishing, heating, reassembling of alternator, bringing back to the sight refixing and installation and foundation with proper alignment, testing and commissiong complete all as specified and as directed by Engr-in-Charge.
Note :- Taking up and down from the site to workshop with vehicle and labour is deemed to be included in quoted rates.
1
-
-
WATER SUPPLY
Dismantling the centrifugal /submesible pump set of capacity 1 HP and transportation to workshop for replacing unserviceable parts such as impeller,shaft, bearing, winding etc and reconnecting back the pumpset to its original position after repair and testing complete all as specified and as directed by Engr-in-Charge.
2
-
-
All as per item No.43 above but of capacity 1. 5 HP
2
-
-
All as per item No 43 above but of capacity 2.0 HP
1
-
-
Disconection and removing the defective DOL starter and S & F the new DOL starter three phase 440 Volts , 50 Hz suitable for motor capacity up to 5 HP testing complete all as specified and as directed by Engr-in-Charge.
1
-
-
S & F in replacement of DOL starter single phase 240 Volts , 50 Hz suitable for motor capacity & testing complete all as specified and as directed by Engr-in-Charge.
1
-
-
Supply and fix in replacement of PVC foot valve of following sizes complete all as specified and as directed by Engr-in-Charge.:-
-
-
-
a) 50 mm bore.
2
-
-
b) 40 mm bore.
2
-
-
c) 32 mm bore.
2
-
-
S&F in replacement of CPVC ball valve of following sizes complete all as specified and as directed by Engr-in-Charge.:-
-
-
-
a) 25mm
2
-
-
b) 32mm
2
-
-
c) 40mm
2
-
-
d) 50mm
2
-
-
Supply & laying in replacement of CPVC pipes SDR 13.5 and plain CPVC SDR 11 fittings on wall/ceiling or laying in floors complete all as specified and directed by Engineer-in-charge of following sizes complete all as specified and as directed by Engr-in-Charge :-
-
-
-
a) 25mm
19
-
-
b) 32mm
20
-
-
c) 40mm
20
-
-
d) 50mm
19
-
-
S&F in replacement of CPVC brass elbow of following sizes complete all as specified and as directed by Engr-in-Charge :-
-
-
-
a) 25mm
2
-
-
b) 32mm
2
-
-
c) 40mm
2
-
-
d) 50mm
2
-
-
S&F in replacement of CPVC brass tee of following sizes complete all as specified and as directed by Engr-in-Charge. :-
-
-
-
a) 25mm
2
-
-
b) 32mm
2
-
-
c) 40mm
2
-
-
d) 50mm
2
-
-
S&F in replacement of CPVC male brass threaded adaptor of following sizes complete all as specified and as directed by Engr-in-Charge.:-
-
-
-
a) 25mm
2
-
-
b) 32mm
2
-
-
c) 40mm
2
-
-
d) 50mm
2
-
-
S&F in replacement of CPVC female brass threaded adaptor of following sizes complete all as specified and as directed by Engr-in-Charge.:-
-
-
-
a) 25mm
2
-
-
b) 32mm
2
-
-
c) 40mm
2
-
-
d) 50mm
2
-
-
S&F in replacement of CPVC UNION of following sizes complete all as specified and as directed by Engr-in-Charge. :-
-
-
-
a) 25mm
2
-
-
b) 32mm
2
-
-
c) 40mm
2
-
-
d) 50mm
2
-
-
Material and labour for cutting the existing hardstanding/road not less than 25cm in deep and 45cm in width for laying of CPVC pipes/cables and making good the disturbed surfaces complete all as specified and directed by Engineer-in-charge.
6
-
-
M&L construction of 200mm thick PCC solid block wall masonary valve chamber built in CM 1:6 with 150mm thick PCC foundation 1:2:4 type B-1 coping 50mm thick finished even and smooth, rendering 10mm thick in cement mortar (1:6), finished fair and and even externally including excavation earthwork in any strata, 6mm thick MS sheet cover fixed on angle iron frame 25x4mm embedded in PCC coping with locking arrangement and mild steel hold fast, mild steel handles and painting to steel surface with two coats of black bituminus paint over one coat of red oxide primer etc, complete all as specified and directed for internal size 600x600x600mm including the demolishing PCC Chamber complete all as specified and as directed by Engr-in-Charge.
2
-
-
External Electric Supply
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 depth and getting out soft/loose soil for laying pipes cmplete all as per specification and upto the satisfaction of Engineer in charge.
75
-
-
Returning filling in, with excavated soils incl. spreading, levelling, watering and well ramming in layers n.exc. 25 Cms. all as specified and directed and upto the satisfaction of Engineer in charge.
59
-
-
Removing excavated materials not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed and upto the satisfaction of Engineer in charge.
16
-
-
Taking down old unserviceable LT UG cable from existing position and Supply & laying, connecting and commissioning of LT UG cable 1100 volts grade XLPE insulated armoured heavy duty electric cables with aluminium conductor including connecting with suitable size of cable glands lugs etc. laid in trenches or fixed on walls of the following size complete all as specified and as directed by Engr-in-Charge.
-
-
-
a) 6 sqmm 4 core
50
-
-
b) 10 sqmm 4 core
50
-
-
c) 16 sqmm 4 core
50
-
-
d) 50 sqmm 3.5 core
50
-
-
e) 95 sqmm 3.5 core
50
-
-
M&L for sand cushioning with Sand in two layer,first layer of 80mm thick before laying of cable and second layer of 150mm thick after laying of cable in trenches/ducts for cable including consolidation of each layer complete all as specified.Note:Thickness of sand cusioning shall be measured after punning complete all as specified and directed by Engr-in-Charge.
18
-
-
supply and Laying unreinforced precast concrete cable cover class LV 1 flat size of size 250x150x40 mm for LT Cable all sizes complete all as specified and as directed by Engr-in-Charge.
1490
-
-
S & F GI tubing 50 mm dia light grade ISI marked laid in trenches complete with all accessories such as Tees union , bend ,elbow nipple reducer etc as required for protection of UG Cable on floor, Pole etc complete all as specified and as directed by Engr-in-Charge.
5
-
-
S & F GI tubing 80 mm dia light grade ISI marked laid in trenches complete with all accessories such as Tees union , bend ,elbow nipple reducer etc as required for protection of UG Cable on floor ,Pole etc complete all as specified and as directed by Engr-in-Charge.
5
-
-
S & F in replacement of MCCB 4 Pole, 415 V 50 Hz of following capacity including all connections complete all as specified and as directed by Engineer-in-charge :-
-
-
-
a) MCCB 63 Amps 16 KA
2
-
-
b) MCCB 100 Amps 25 KA
2
-
-
c) MCCB 160 Amps 36 KA
1
-
-
d) MCCB 250 Amps 36 KA
1
-
-
M&L for painting of existing LT panels by using two coat of synthetic enamell paint after removal of the rusted portions complete all as specified and as directed by Engineer-in-charge.
2
-
-
M&L for repair to existing LT panels front and rear doors of locking arrangements by using suitable hinges complete all as specified and as directed by Engineer-in-charge.
2
-
-
S& F in replacement of Aviation obstruction light including all connections complete all as specified and as directed by Engr-in-Charge.
2
-
-
Supply and fixing in replacement of LED street light fitting 70 Watt230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed by Engineer-in-charge.
4
-
-
M & L for complete removal of existing paint of steel tubular poles length up to 9 mtr including prepration of outer surface and applying two coats of aluminium paint over a coat of red oxide primer and two strip of blue colour paint of size 30 cm width from bottom of pole height 30 cm, including numbering to pole with base paint of yellow colour and Black for numbering which shall not be less than 100 mm in height and 10 mm in width complete all as specified and as directed by Engr-in-Charge.
2
-
-
Earthing complete with galvanized iron earth plate electrode 60cmx60cmx6mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr below ground level connecting to the Galvanised iron earth lead 32x6 mm size, by means nut, bolt, check nuts and washer of galvanized iron and 32x6 mm as earth lead protected by provision of GI light grade pipe 40mm bore incl provn of concrete pit in PCC (1:2:4) type B-1 using 20mm graded stone aggregate with 40mm thick cover of RCC (1:2:4) reinforced (weight not less than 4Kg/Sqm) and frame of angle iron 25x25x6mm with lugs 2 Nos and with 6mm dia MS bar handle made to shape, GI light grade 20mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge of earth plate, common salt and charcoal filling, test point with fixing arrangement CI funnel wire mesh and earth work in hard/dense soil, returning filling in and removal of surplus soil to a distance not exc 50 mtr all as per electrical plate No.3 of SSR Part I and connecting to earth test point all as specified incl testing on complete all as specified and as directed by Engr-in-Charge.