Military Engineer Services Tender
View complete overview of Lakshadweep MES Tender
Military Engineer Services - MES Tender
Electrical Generators And Transformers
Electrical and Electronics
Eprocure
Opening Date23 Sep 2024
Closing Date24 Oct 2024
Tender Amount₹ 10,15,000
Costs
EMD
₹ 20,500Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_676108_1Tender No
81154/NB/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Supply and Fix in replacement of vacuum interrupters 11KV with all fittings suitable for existing make HT11 KV VCB/RMU and testing complete all as specified and directed by Engineer in charge.
2
-
-
Supply and Fix in replacement of current transformer 5/5 A suitable for existing make HT11 KV VCB/RMU and testing complete all as specified and directed by Engineer in charge.
1
-
-
Supply and Fix in replacement of current transformer 20/5 A suitable for existing make HT11 KV VCB/RMU and testing complete all as specified and directed by Engineer in charge.
2
-
-
Supply and Fix in replacement of Potential Transformer with primary voltage 11KV and secondary voltage 110/220 V suitable for existing make HT11 KV VCB/RMU and testing complete all as specified and directed by Engineer in charge.
2
-
-
Supply and Fix Charging motor operates on single Phase 230 V AC,50 Hz power supply for auto charging of HT breaker suitable for existing make HT11 KV VCB including taking down old unserviceable one complete all as specified and directed by Engineer in charge.
1
-
-
Supply and Replacement of unserviceable Battery 12 Volts 150 AH including taking down unservisable battery complete all as specified and directed by Engineer in charge.
Make - Exide /Amaron/Standard farukwa/AMCO or as approved by GE
1
-
-
Disconnection and removing old unserviceable Power Pack unit providing, installation & commissioning of Power Pack Input 230 V AC, Output 12 V DC suitable for 11 KV HT VCB/RMU Panel complete all as specified and directed by Engineer in charge.
1
-
-
Topping up / complete renewal of transformer oil having breakdown strength not less than 60 KV/Min for oil cooled Transformers complete all as specified and directed by Engineer in charge. Make : Power oil/Servo /any ISI make as approved by GE
240
-
-
Supply and replace the silica gel for transformer of any capacity complete all as specified and directed by Engineer in charge.
136
-
-
Disconnection and removing unserviceable Transformer Tap changer and Supply and Fix new Transformer Tap changer made of Brass/Copper material for regulating LT volage suitable for existing Transformer of any capacity complete all as specified and directed by Engineer in charge.
1
-
-
Disconnection and taking down the Transformer of any capacity from the existing position and transporting to work shop and opening the outer cover, draining out the oil and lifting the core along with winding, finding the faulty /burnout primary and secondary winding and rewinding with fine enameled insulated copper winding of same size/guage, turns keeping in hot air oven till the moisture evoporates, reassembling the transformer parts such as core, winding, outer cover, refilling back the Transformer oil complete and transporting back to its original position and reconnecting the LT/HT cable connections complete all as specified and directed by Engineer in charge.
400
-
-
Material and labour for cable jointing kit for 11KV grade cable for outdoor termination heat shrinkable type end termination joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm complete all as specified and directed by Engineer in charge.
2
-
-
Material and labour for cable jointing kit for 11KV grade cable for outdoor termination heat shrinkable type end termination joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm complete all as specified and directed by Engineer in charge.
2
-
-
Material and labour for cable jointing kit for 11KV grade cable for indoor termination heat shrinkable type end termination joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm complete all as specified and directed by Engineer in charge.
2
-
-
Material and labour for cable jointing kit for 11KV grade cable for indoor termination heat shrinkable type end termination joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm complete all as specified and directed by Engineer in harge.
2
-
-
Material and labour for outdoor type straight through jointing kit heat shrinkable for 11KV grade UG cable suitable for 3 core Aluminium conductor complete along with jointing material all as specified and as directed of size 120 Sqmm to 185 Sqmm complete all as specified and directed by Engineer in charge.
2
-
-
Material and labour for outdoor type straight through jointing kit heat shrinkable for 11KV grade UG cable suitable for 3 core Aluminium conductor complete along with jointing material all as specified and as directed of size 50 Sqmm to 95 Sqmm complete all as specified and directed by Engineer in charge.
2
-
-
Material and labour in replacement of XLPE insulated, screen, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 3 core, 11000 volts, grade of the size 95 Sqmm complete all as specified and directed by Engineer in charge.
20
-
-
Material and labour in replacement of XLPE insulated, screen, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 3 core, 11000 volts, grade of the size 185 Sqmm complete all as specified and directed by Engineer in charge.
20
-
-
Excavation in trenches not exceeding 1.5 meter wide and not exceeding 1.5 meter depth for taking out/laying of cable and getting out in soft/loose soil complete all as specified and directed by the Engineer-in-charge.
8
-
-
Returning filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick in any type of soil complete all as specified and directedby Engineer in charge.
6
-
-
Removing excavated material (Soil) to a distance n exc. 50 m and depositing where directed at a level n exc. 1.5 m above starting point complete all as specified and directed by Engineer in charge.
2
-
-
Material and labour for sand cushioning with sand in two layer, first layer of 80mm thick before laying of cable and second layer of 150mm thick after laying of cable in trenches/ducts for cable including consolidation of each layer complete all as specified and directed by Engineer in charge.
Note:- Punned thickness only shall be measured for the purpose of payment.
2
-
-
Supply and laying unreinforced precast concrete cable cover class HV, Type I, flat, size 300x180x40 mm for HT cable all sizes complete all as specified and directed by Engineer in charge.
160
-
-
Supply and fix in repair of transformer LT side bushing/insulator with neoprene washer with terminal studs and bolt, nuts, etc complete all as specified and directed by Engineer in charge.
2
-
-
Supply and fix in repair of transformer HT side bushing/insulator with neoprene washer with terminal studs and bolt, nuts, etc complete all as specified and directed by Engineer in charge.
2
-
-