Military Engineer Services Tender
Bidassist is designed as a single destination for all government tenders from across the world in one place. If you require any information or detail about any e-tender the Ladakh government has posted, Bidassist helps a registered bidder to get the same.As BidAssist is a very user-friendly website it will help you find the specific Ladakh etender you're looking for. Read further to learn how to search and bid for etender Ladakh.
Costs
EMD
₹ 63,000Document Cost
₹ 500Tender Fee
Refer Documents
Summary
Provn Of Chs False Ceiling And Wooden Panelling Of Cook House And Dinning Hall At Khumbathang
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_669295_2Tender No
80051/16/8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
9mm thick, prelaminated particle board, interior grade, prelaminated one side with decorative choice lamination and other side balancing white lamination, fixed with screws to timber frame work as in ceiling, complete all as specified and directed by the Engr-in-Charge.
172.7
-
-
12 mm thick, prelaminated particle board, interior grade, prelaminated one side with decorative choice lamination and other side balancing white lamination, fixed with screws to timber frame work as in walls, complete all as specified and as directed by Engineer-in-charge.
217.8
-
-
Point wiring with PVC insulated single core cable of multistranded copper conductors of size 1.5 sqmm, FRLS 1100 volt grade drawn in and including rigid PVC casing caping/ PVC conduit with all accessories lain on wall/ceiling surface and fixed with PVC saddles and back-plate and GI screws, including PVC insulated single core cable of multistranded copper conductor of size 1.5 sqmm FRLS as earth continuous wire connected to common earth and PVC Board for housing like switches, sockets, fan regulators, One light point/one fan point controlled by one switch, complete all as specified and as directed by Engineer-in-charge.
17
-
-
Point wiring with PVC insulated single core cable of multistranded copper conductors of size 1.5 sqmm, FRLS 1100 volt grade drawn in and including rigid PVC casing caping/ PVC conduit with all accessories lain on wall/ceiling surface and fixed with PVC saddles and back-plate and GI screws, including PVC insulated single core cable of multistranded copper conductor of size 1.5 sqmm as earth continuous wire connected to common earth and PVC Board for housing like switches, sockets, fan regulators, One 3 pin 5 amps socket outlet independent, complete all as specified and as directed by Engineer-in-charge.
12
-
-
Switch piano, flush type single pole, one way 5 Amp, complete all as specified and as directed by Engineer-in-charge.
17
-
-
Switch socket combination 2 in 1, 3 pin, 5 Amp flush type, complete all as specified and directed by the Engr-in-Charge.
12
-
-
Ceiling rose surface Bakelite 65x50mm two to three terminal, complete all as specified and directed by the Engr-in-Charge.
17
-
-
All same as per item No 7 here in before but with conductor of size 2.5 sqmm (Nominal area) FRLS for one 3 pin socket outlet 15 Amps on independent board complete and earth continuity wire with 2.5 sqmm FRLS PVC insulated multi stranded copper conductor Cable, complete all as specified and directed by the Engr-in-Charge.
10
-
-
Switch Socket Combination 2 in 1, 3 pin, 15/16 amp flush type Universal, complete all as specified and directed by the Engr-in-Charge.
10
-
-
Wall mounted LED light fitting 1x20 watts AC decorative box type with driver holder including LED tube light , energy efficient type 4 feet long including neccessary conection prewired and making connection with 3 core copper flexible cable of appropriate size from ceilling rose., complete all as specified and directed by the Engr-in-Charge.
6
-
-
LED security light fitting 35/36 watts 230 volts AC outdoor type with high pressure die cast aluminium housing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection, complete all as specified and directed by the Engr-in-Charge.
8
-
-
LED light fitting 1x9 W/1x10W bulkhead luminaires including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size, complete all as specified and directed by the Engr-in-Charge.
3
-
-
Sheet metal enclosure SPN DB 08 way,single phase 240 volts double door with 200 amp rated bus bar, complete all as specified and directed by the Engr-in-Charge.
1
-
-
Circuit breaker single pole, 5 to 32 Amp 240 volt C curve 10 KA, IP 20 complete all as specified and directed incl taking down old one, complete all as specified and directed by the Engr-in-Charge.
6
-
-
Circuit breaker single pole & neutral 240 volt C curve 10 KA 40 Amps capacity IP 20 including taking down old one, complete all as specified and directed by the Engr-in-Charge.
1
-
-
Two single core 6 sq mm for Sub Main wiring with copper conductor multistranded PVC insulated and unsheathed 1100Volts grade in and including PVC casing capping/ pvc conduit with fixing accessories including one run of 6 Sq mm copper conductor, complete all as specified and directed by the Engr-in-Charge. (Note - Two runs of 06 Sq mm cable, one run of 6 Sq mm earth cable and one run of PVC casing Capping shall be measured as one running meter.)
50
-
-
Earthing complete with galvanized steel earth plate 60 cm x 60cm x 6.0mm thick buried directly in ground vertically to a depth not less than 2.25 mtr below ground level with top edge of the earth plate at a depth not less less than 1.5 mtr filled around with 15 cm thick alternate layers of charcoal dust and salt and connected to earth lead wire 4mm dia (8 SWG) by means of bolt, nut and check nuts and washers of galvanized iron or steel and thimble and other ends of the earth wire connected to main switch board and protected by galvanized iron pipe light grade 15mm bore and watering pipe 20mm dia light grade with funnel and wire mesh, pcc 1:3:6 type C-1 in chambers RCC 1:2:4 type B-1 in pit cover reinforced with 8 mm dia deformed bars 15cm center to center both ways all as directed by Engr-In-Charge, complete all as shown in electric plate No 3 of MES SSR Part I , complete all as specified and directed by the Engr-in-Charge.
3
-
-
Supply, installation and commissioning of stand alone air heater for space heating of capacity 50000 Kcal /Hr suitable for operation with diesel fuel complete with fuel filter, burner, blower fan, blower motor, automatic digital temperature controller, control panel (prewired type complete with audio/visual controls, safety interlocks, MCB, overload relays, timers and alarm hooters), blower fan gaurd , fuel tank all as per standard specifications of manufacturer. The air heater suitable for following specifications:- (a) Hot air delivery of minimum 1750 Cum/Hr at 80 degree centigrade.
(b) The motor should be capable of operating on single phase supply. (c) The complete unit shall be mounted on PCC plateform of suitable size as recommended by the manufacturer. The unit shall be installed outdoor. The chimney to carry out the exhaust beyond roof level all as per recommendation of manufactures shall be provided by the contractor.
(d) Make and Model to be offered by the contractor shall be got approved from GE before procurement.
(e) Voltage regulator for burner assembly shall also be supplied with air heater. Voltage regulators shall be supplied by the manufacturers of the air heater.
(f) MS fuel tank of capacity 100 Ltrs including mounting stand of suitable height shall be provided by the manufactures within the overall cost quoted. (g) To manufacturer shall provide 02 Nos of temprature sensor for the mesurement of temprature inside the building. (h) All piping network from fuel tank to standalone heaters shall be included in the overall cost quoted , complete all as specified and directed by the Engr-in-Charge.
3
-
-
Supply, fabrication, installation and commissioning of air ducting made of Galvanised steel sheet metal casing cross section 400x400mm (24 gauge) alongwith 50 mm glass wool insulation with neoprene rubber gaskets, Elbow, air diffuser grills for supply air, split dampers, vanes, hangers, supports etc, complete all as specified and directed by the Engr-in-Charge.
128
-
-
Supply, fabrication, installation and commissioning of aluminium cladding of any ducting size as required at site , complete all as specified and directed by the Engr-in-Charge.
40
-
-
Supply, fabrication, installation and commissioning of return air ducting made of Galvanised steel sheet metal casing cross section 400x400mm (24 gauge) with neoprene rubber gaskets, Elbow, split dampers, vanes,hangers, supports etc, complete all as specified and directed by the Engr-in-Charge.
48
-
-
4 pole MCCB 12 to 63 Amp 50HZ, 415 V with rupturing capacity 25 KA, complete all as specified and directed by Engineer-in-Charge.
4
-
-
Excavation in trenches not exc 1.5 m wide and not exc 1.5 m in depth and getting it out for laying of cable / pole etc, not exc 10 Sq mtr on plan and not exc 1.5 mtr in depth and getting out in hard/dense soil, complete all as specified and directed by Engineer-in-Charge.
46
-
-
Returning, filling in including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick in hard/dense soil complete all as specified and directed by the Engr-in-Charge.
32.2
-
-
Removing excavated surplus soil to d distance upto 50m deposting where directed at a level not exceeding 1.5 m above the starting point, complete all as specified and directed by the Engr-in-Charge.
13.8
-
-
Sand curshioning with fine sand to under ground cables in trenches/ducts in layers of 8 cm deep before laying the cable and 15 cm deep after laying and stretching the cable as specified in clause 19.75 of SSR Part-I, complete all as specified and directed by the Engr-in-Charge.
Note :- Punned thickness shall be measured.
14
-
-
Supplying and laying un-reinforced precast concrete cable cover Class LV, Type I, flat, size 2500mm x 150mm x 40mm laid over electric cable for protection, complete all as specified and directed by the Engr-in-Charge.
1120
-
-
Supply laying and testing cable XLPE insulated screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables heavy duty 1100 volts grade with stranded aluminium conductor of size 16 sqmm 4 core, complete all as specified and directed by Engineer-in-Charge.
250
-
-
Supply laying and testing cable XLPE insulated screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables heavy duty 1100 volts grade with stranded aluminium conductor of size 6 sqmm 4 core, complete all as specified and directed by Engineer-in-Charge.
80
-
-
Earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6mm as earthing lead buried directly in ground vertically to a depth not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 Mtr below normal ground level connected to and including galvanised iron strip 32X6 mm as earthing lead by means of bolts, nuts, check nuts & washers etc made of GI and connected to earthing test point all as shown in electrical plate No. 3 of SSR Part I of 2009.00 & as specified or indicated and testing on completion including exaction/earth work in any type of strata PCC ( 1:3:6 ) type C1 earthing chamber, pre cast slab 50 mm thick in cement concrete ( 1: 2 : 4 ) type B 1 (reinforced with welded steel wire fabric (XPM) weight not less than 4 Kg / Sqm), funnel with wire mesh, I watering pipe of 20 mm bore medium grade and lugs, including galvanised iron strip 32X6 mm with GI protection pipe of 40 mm medium grade 7.5 meter long, etc complete all as specified.
2
-
-
Distribution board double door made out of sheet metal enclosure (CRCA sheet) dust and vermin proof TPN 4 way with 200 Amps rated copper bus bar neutral bar, earth bar IP 43 protection, single pole and neutral 415 volts, flush to wall / fixed on surface, complete all as specified and directed.
4
-
-
Supply and fix ON LOAD change over switch 415 V in sheet metal enclosures 4 pole of capacity 63 Amps, complete all as specified and directed by Engr-in-Charge.
1
-
-
Supply and Fix highly accurate temprature / humidity sensor thermostat controller on / off indoor to control CHS unit to measure the temp inside the buildings from the minus 35 degree celsius to plus 35 degreee celsius range with robust design and recording last 10 readings of temp and humidity, complete all as specified and directed by Engr-in-Charge.
2
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements