Military Engineer Services Tender
Everything can be found here in your one-stop destination for all types of Kerala tenders online - be it Kerala PWD tenders or an LSGD Kerala tender. Search from across the categories, cities, and authorities while having the option to download tender-related documents. Also, get to know how to register as a bidder and how to bid online for Kerala tenders.
Costs
EMD
₹ 2,16,000Document Cost
₹ 1,000Tender Fee
Refer Documents
Summary
Special Repairs/ Replacement Of Lt And Ht Control And Dristribution System And Connected Works At Nad Main Power House (p-181) Ayudh Vihar And Periyar Vihar (p-30 And P-97) At Nad Alwaye
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2025_MES_692951_1Tender No
CWE(NW)Kochi/81505Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
... More
M & L for sand filling under floors or in foundations including watering and consolidation all as specified and directed for cable protection.
320
-
-
... More
Supplying and laying unreinforced precast concrete cable cover, class HV, type 1, flat, size 300 x 180 x 40 mm, complete.
11390
-
-
... More
Supplying and laying unreinforced precast concrete cable cover, class LV, type 1, flat, size 250 x 150 x 40 mm, complete.
10600
-
-
... More
M & L XLPE insulated, screened, PVC bedded, galvanised steel strip wire armoured, electric power cable (heavy duty) with aluminium conductor, 11000 Volts earthed grade cross sectional area 240 Sqmm 3 core all as specified and directed.
1330
-
-
... More
M & L XLPE insulated, screened, PVC bedded, galvanised steel strip wire armoured, electric power cable (heavy duty) with aluminium conductor, 11000 Volts earthed grade cross sectional area 185 Sqmm 3 core all as specified and directed..
125
-
-
... More
M & L XLPE insulated, screened, PVC bedded, galvanised steel strip wire armoured, electric power cable (heavy duty) with aluminium conductor, 11000 Volts earthed grade cross sectional area 150 Sqmm 3 core all as specified and directed..
145
-
-
... More
M & L XLPE insulated, screened, PVC bedded, galvanised steel strip wire armoured, electric power cable (heavy duty) with aluminium conductor, 11000 Volts earthed grade cross sectional area 120 Sqmm 3 core all as specified and directed.
160
-
-
... More
M & L XLPE insulated, screened, PVC bedded, galvanised steel strip wire armoured, electric power cable (heavy duty) with aluminium conductor, 11000 Volts earthed grade cross sectional area 95 Sqmm 3 core and all as specified and directed..
210
-
-
... More
M & L XLPE insulated, screened, PVC bedded, galvanised steel strip wire armoured, electric power cable (heavy duty) with aluminium conductor, 11000 Volts earthed grade cross sectional area 70 Sqmm 3 core all as specified and directed..
220
-
-
... More
M & L XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 Volts earthed grade cross sectional area 120 Sqmm 3.5 core and dismantling old one all as specified and directed..
80
-
-
... More
M & L XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 Volts earthed grade cross sectional area 95 Sqmm 3.5 core all as specified and directed..
135
-
-
... More
M & L XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 Volts earthed grade cross sectional area 70 Sqmm 3.5 core all as specified and directed..
240
-
-
... More
M & L XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 Volts earthed grade cross sectional area 50 Sqmm 3.5 core all as specified and directed..
335
-
-
... More
M & L XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 Volts earthed grade cross sectional area 35 Sqmm 3.5 core and all as specified and directed..
330
-
-
... More
M & L XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 Volts earthed grade cross sectional area 25 Sqmm 3.5 core all as specified and directed..
295
-
-
... More
M & L XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 Volts earthed grade cross sectional area 16 Sqmm 4 core all as specified and directed.
310
-
-
... More
M & L XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 Volts earthed grade cross sectional area 10 Sqmm 4 core all as specified and directed..
290
-
-
... More
M & L for Tubes, 'light grade' galvanised,with all fittings, laid in trenches of size 150mm all as specified and directed.
60
-
-
... More
M & L for Tubes, 'light grade' galvanised,with all fittings, laid in trenches of size 100mm all as specified and directed.
25
-
-
... More
M & L for Tubes, 'light grade' galvanised,with all fittings, laid in trenches of size 80mm and dismantling old one all as specified and directed.
20
-
-
... More
M & L for Tubes, 'light grade' galvanised,with all fittings, laid in trenches of size 50mm all as specified and directed.
35
-
-
... More
S & F Cable route indicator for 11 KV HT UG Cable including taking down old one complete all as specified
45
-
-
... More
S & F Cable route indicator for 1.1 KV LT UG Cable including taking down old one complete and dismantling old one all as specified
75
-
-
... More
Supply and fix HT 11 KV out door type gang operated air-break switch suitable for horizontal or vertical mounting rotating type complete with drop out fuse having 12 insulators of rating upto 400 Amps and dismantling old one all as specified and directed.
8
-
-
... More
Supply and erect 2 pole structure on 11 mtr steel tubular pole consisting of anti climbing device, PCC foundation & cross arms etc all as specified and directed.
8
-
-
... More
Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 sqmm to 300 sqmm all as specified and directed.
32
-
-
... More
Supply and fix lightning arrestor HT 11 kv 10 KA expulsion type complete with all fittings,transmission class, discharge capacity 65 kilo amp suitable for 11000 volts complete all as specified and directed..
8
-
-
... More
M & L for Earthing complete with copper earth plate as electrode 60×60cm× 3.15 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to GI strip 20x3 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion
26
-
-
... More
M & L for Danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters , figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size , for HT 25 x 20 cm size and dismantling old one all as specified and directed..
10
-
-
... More
S & F Synthetic rubber insulated mats 2 mm thick for voltage upto 3.3 kv for electrical purposes as per IS 15652-2006 (superseding IS 5424) suitable for electrical shock safety of sizes 2 m x 1 m all as specified and directed.
24
-
-
... More
M & L for Cros arms , bracing, supports, clamps and back plates fabricated from structural steel sections including nuts bolts washers welding bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint and dismantling old one all as specified and directed.
4.25
-
-
... More
M & L for Pin type, porcelain, viterous, white, brown or green insulator including one galvanised mild steel spindle , two galvanised iron washers and one galvanised iron nut, 100 mm height, 65 mm dia for 1100 volts grade and dismantling old one all as specified and directed
65
-
-
... More
Panel no. 01 (NAD Power house) Supply, install, testing and commissioning of CPRI IS/IEC 61439-1.2011 & IS/IEC 61439-2.2011 approved vender and tested LT Panel board indoor type suitable for 415 volts, 3 phase, 4 wire, 50 HZ, AC supply system having busbar chamber with colour coded air insulated PVC sleeved Aluminium busbar on DMC/SMC insulators. The panel board shall be weather proof with IP-54 protection and fabricated with 2 mm thick CRCA and detachable gland plate of 2 mm thick duly powder coated after seven tank process. and including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 1100 volts or PVC sleeved copper strips of appropriate size including electric connection including making good disturbed surfaces if floor/walls etc complete all as specified and as directed by Engr- in-charge all as specified and directed
1
-
-
... More
INCOMING
(a) 1000 Amps, 50 KA, lcu = lcu 4 pole MDO Air circuit breaker having Thermal Magnetic draw out type - 01 No
(b) 800 Amps 4P ON Load changeover Switch - 02 No.
( c) Digital Voltmeter with Selector switch 01 No., Digital Amp Meter with Selector switch 01 No., MF Meter- 01 No., 1000/5 cl 1 CT 1 set control MCB 01 set
(d) EB and DG ON indication lamp
( e) RYB Inidication lamp with control MCB - 03 Set
(f) Aluminium busbar 1200A Phase and neutral
OUTGOING
(a) 400A 4P MCCB 36 KA TM Release - 4 Nos.
(b) 320A 4P MCCB 36 KA TM Release - 1 No.
(c) 250A 4P MCCB 25 KA TM Release - 1 No.
(d) 200A 4P MCCB 25 KA TM Release - 2 Nos.
(e) 160A 4P MCCB 25 KA TM Release - 7 Nos.
(f) 125A 4P MCCB 25 KA TM Release - 5 Nos.
(g) 125A 4P MCCB 25 KA TM Release - 2 Nos. (spare)
(h) Timer, conductor, A/M selector switch
-
-
-
... More
APFC Panel 100 KVAR 8 steps APFC Controller
INCOMING
(a) 250 Amp 4P MCCB 25 kA TM release - 01 Nos
(b) Digital Voltmeter with selector switch - 01 No., Digital Amp meter with selector switch - 01 No., 400/5 cl 1 CT - 01 set control MCB - 01 set , 8 Steps APFC controller and auto manual selector switch - 01 No.
( c) Aluminium busbar 250A Phase and neutral
OUTGOING
(a) 63 A 4P MCB 10 kA - 01 No.
(b) 50 A 4P MCB 10 kA - 01 No.
(c) 32 A 4P MCB 10 kA - 01 No.
(d) 25 A 4P MCB 10 kA - 03 No.
(e) 16 A 4P MCB 10 kA - 02 No.
(f) 25 KVAr Heavy duty capacitor with capacitor duty contact - 01 No
(g) 20 KVAr Heavy duty capacitor with capacitor duty contact - 01 No
(h) 15 KVAr Heavy duty capacitor with capacitor duty contact - 01 No
(i) 10 KVAr Heavy duty capacitor with capacitor duty contact - 03 No
(j) 5 KVAr Heavy duty capacitor with capacitor duty contact - 02 No
(k) ON OFF push button with one indication lamp - 08 set
1
-
-
... More
Panel no. 02 (Periyar Vihar pump house) Supply, install, testing and commissioning of CPRI IS/IEC 61439-1.2011 & IS/IEC 61439-2.2011 approved vender and tested LT Panel board indoor type suitable for 415 volts, 3 phase, 4 wire, 50 HZ, AC supply system having busbar chamber with colour coded air insulated PVC sleeved Aluminium busbar on DMC/SMC insulators. The panel board shall be weather proof with IP-54 protection and fabricated with 2 mm thick CRCA and detachable gland plate of 2 mm thick duly powder coated after seven tank process. and including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 1100 volts or PVC sleeved copper strips of appropriate size including electric connection including making good disturbed surfaces if floor/walls etc complete all as specified and as directed by Engr- in-charge and all as specified and directed.
1
-
-
... More
INCOMING
(a) 400 Amps, 4P ON load change over switch - 01 No
(b) 400A 4P MCCB 36 kA TM release - 01 No
( c) Digital Voltmeter with Selector switch 01 No., Digital Amp Meter with Selector switch 01 No., 400/5 cl 1. CT - 1 set controll MCB 1 set,
(d) Aluminium busbar 500A Phase and neutral
OUTGOING
(a) 250 A 4P MCCB 36 kA TM release - 01 Nos
(b) 200 A 4P MCCB 25 kA TM release - 01 Nos
(c) 63 A 4P MCCB 16 kA TM release - 02 Nos
(d) 32A 4P MCB - 04 Nos
-
-
-
... More
Panel no. 03 (Periyar Vihar pump house) INCOMING
(a) 125A 4P MCCB 25 kA TM release - 01 No
(b) RYB indication lamp with control MCB - 01 set
(c ) Aluminium busbar 200A phase and neutral
OUTGOING
(a) 32 A 4P MCB - 04 Nos
(b) 7.5 HP DOL Starter - 02 Nos
1
-
-
... More
APFC Panel 50 KVAR 6 steps APFC Controller
INCOMING
(a) 125 Amp 4P MCCB 25 kA TM release - 01 Nos
(b) Digital Voltmeter with selector switch - 01 No., Digital Amp meter with selector switch - 01 No., 400/5 cl 1 CT - 01 set control MCB - 01 set , 8 Steps APFC controller and auto manual selector switch - 01 No.
(c) Aluminium busbar 150A Phase and neutral
OUTGOING
(a) 40 A 4P MCB 10 kA - 01 No.
(b) 25 A 4P MCB 10 kA - 03 No.
(c) 16 A 4P MCB 10 kA - 01 No.
(d) 15 KVAr Heavy duty capacitor with capacitor duty contact - 01 No
(e) 10 KVAr Heavy duty capacitor with capacitor duty contact - 03 Nos
(f) 5 KVAr Heavy duty capacitor with capacitor duty contact - 01 No
(g) ON OFF push button with one indication lamp - 06 set
1
-
-
... More
Panel no. 04 (Ayudh Vihar pump house) Supply, install, testing and commissioning of CPRI IS/IEC 61439-1.2011 & IS/IEC 61439-2.2011 approved vender and tested LT Panel board indoor type suitable for 415 volts, 3 phase, 4 wire, 50 HZ, AC supply system having busbar chamber with colour coded air insulated PVC sleeved Aluminium busbar on DMC/SMC insulators. The panel board shall be weather proof with IP-54 protection and fabricated with 2 mm thick CRCA and detachable gland plate of 2 mm thick duly powder coated after seven tank process. and including internal wiring in the panel with PVC insulated multi stranded copper conductor cable 1100 volts or PVC sleeved copper strips of appropriate size including electric connection including making good disturbed surfaces if floor/walls etc complete all as specified and as directed by Engr- in-charge all as specified and directed
1
-
-
... More
INCOMING
(a) 400 Amps, 4P ON load change over switch - 02 No
(b) 400 A 4P MCCB 36 kA TM release - 01 No
( c) Digital Voltmeter with Selector switch 01 No., Digital Amp Meter with Selector switch 01 No., 400/5 cl 1. CT - 1 set control MCB 1 set, RYB indication lamp with control MCB - 03 Set
(d) Aluminium busbar 500A Phase and neutral
OUTGOING
(a) 200 A 4P MCCB 25 kA TM release - 04 Nos
(b) 160 A 4P MCCB 25 kA TM release - 04 Nos
(c) 100 A 4P MCCB 25 kA TM release - 04 Nos
(d) 100 A 4P MCCB 25 kA TM release - 02 Nos (spare)
( e) Timer, conductor, A/M selector switch - 01 set
-
-
-
... More
APFC Panel 50 KVAR 6 steps APFC Controller
INCOMING
(a) 125 Amp 4P MCCB 25 kA TM release - 01 Nos
(b) Digital Voltmeter with selector switch - 01 No., Digital Amp meter with selector switch - 01 No., 400/5 cl 1 CT - 01 set control MCB - 01 set , 8 Steps APFC controller and auto manual selector switch - 01 No.
( c) Aluminium busbar 150A Phase and neutral
OUTGOING
(a) 40 A 4P MCB 10 kA - 01 No.
(b) 25 A 4P MCB 10 kA - 03 No.
(c) 16 A 4P MCB 10 kA - 01 No.
(d) 15 KVAr Heavy duty capacitor with capacitor duty contact - 01 No
(e) 10 KVAr Heavy duty capacitor with capacitor duty contact - 03 Nos
(f) 5 KVAr Heavy duty capacitor with capacitor duty contact - 01 No
(g) ON OFF push button with one indication lamp - 06 set
1
-
-
... More
Supply and fixing 400 Amps 4P MCCB 36kA TM release - 01 and dismantling old one all as specified and directed
1
-
-
... More
Supply and fixing of Ring main unit (RMU) 11 kv, 630 A, 21 kA, motor operated, compact , outdoor, both side Extensible, Non drawout type, +CV+ ( 1 No. load break switch as Incomer and 1 No. fixed type motor operated Vacuum Circuit Breaker (VCB) gas insulated ring main unit enclosed in stainless steel tank of IP 67 class of protection with 2 Nos terminal protecter and SF6 gas density manometer all as specified and directed by Engr in charge.
1
-
-
... More
M & L for Dismantling steel poles any size and transporting to store and stacking for taking credits all as specified
16
-
-
... More
M&L for taking down old and unserviceable underground cables of different sizes all as specified and directed
4205
-
-
... More
M&L for taking down old and unserviceable GI tubes of different sizes all as specified and directed
140
-
-
... More
M & L for Dismantling LT panels/APFC Panels of any size and transporting to store and for taking credits all as specified
7
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements
Past BiddersThis list is curated from the bidders of the similar tenders in the past
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%