Military Engineer Services Tender
Everything can be found here in your one-stop destination for all types of Kerala tenders online - be it Kerala PWD tenders or an LSGD Kerala tender. Search from across the categories, cities, and authorities while having the option to download tender-related documents. Also, get to know how to register as a bidder and how to bid online for Kerala tenders.
Costs
EMD
₹ 62,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2025_MES_692132_1Tender No
8337E8AGERDKTender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://mes.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Dismantling floor, hearth or wall tiling including cement mortar bedding(but not backing), removing serviceable tiles to store and rubbish off the premises complete all as specified ..
25
-
-
... More
M&L Cement concrete type B-1,1:2:4 (20mm graded aggregate)25 mm thick
25
-
-
... More
M&L Screed bed or bedding layer of mortar in CM 1:4, 15 mm thick for laying floor finishes
25
-
-
... More
M&L Machine cut kota stone slab flooring 20-25mm thick over cement screed base laid and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete
25
-
-
... More
M&L Kota stone slab 20-25mm thick in riser of steps, skirting, dado and pillar laid over cement screed and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete
2
-
-
... More
Supply and fix foot operated door stopper of aluminium alloy body and tongue anodised with hard drawn steel spring and cover plate overall length 150 mm including taking down defective foot operated door stopper all as specified and as directed.
4
-
-
... More
S&F in repairs Aluminium alloy, anodised sliding door bolt with hasp staple (bolt type) and fixing clips of sheet, cast or extruded sections and fixing bolts of extruded sections or cast-aluminium alloy, 300 mm long
4
-
-
... More
Material and labour for taking down old plaster and rendering 10mm thick in CM 1:6 on other than fair faces of brick or concrete surfaces finishing smooth and even and smooth without using extra cement making good match the old surface finish.
10
-
-
... More
M&L two coats of OBD over a coat of primer on newly plastered surfaces of wall including cornices and preparation of surfaces.
10
-
-
... More
S&F Factory made single extruded WPC(wood polymer composite)solid door frame 45x70mm comprising of virgin PVC polymer of K value 58-60(Suspension grade) calcium carbonate and natural fibre and non toxic additives fabricated with mitred joints after applying PVC solvent cement and screwed with with full body threaded star headed SS screws having minimum frame density of 750 kg/cum, scew withdrawal strength of 2200N(Face ) and 1100N(Edge), minimum compressive strength of 58N/Sqmm, modules of elasticity 900N/sqmm and resistance to spread of flame of class A category with property of being termite/borer proof, water/moisture proof and fire retardant and fixed in position with MS hold fast/lugs/SS dash fasteners of required dia and length complete all as specified and directed by Engineer in charge
20
-
-
... More
S&Ff Factory made single extruded WPC(wood polymer composite) solid plain flush door shutter of 35mm thick comprising of virgin polymer of K Value 58-60(Suspension grade) calcium carbonate and natural fibre and non toxic additives having minimum frame density of 650 kg/cum, scew withdrawal strength of 1800N(Face ) and 900N(Edge), minimum compressive strength of 50/Sqmm, modules of elasticity 850N/sqmm and resistance to spread of flame of class A category with property of being termite/borer proof, water/moisture proof and fire retardant WPC to be laminated with PVC foil of minimum 14 microns thick of approved design pasted with hot melt adhesive on both faces of shutter and fixing with stainless steel butt hinges of required size with necessary full body threaded star headed counter sunk SS screws, all as specified and directed by Engineer in charge
8
-
-
... More
S&F Stainless steel butt hinges 125mm size all as specified and directed
9
-
-
... More
S&F Stainless steel tower bolt 150mm long, 10mm bolt all as specified and directed
3
-
-
... More
S& F Stainless steel dash fasteners all as specified and directed.
9
-
-
... More
S& F Stainless steel sliding door bolts 250 mm long all as specified and directed.
3
-
-
... More
Dismantling expanded metal, any thickness or mesh, fixed with steel or wood fillets, if any, weight n.excd 4 kg/sqm
50
-
-
... More
Fixing only MS galvanised chain link fencing including line wires, mesh size 125x125mm with , rails, straining bolts, etc. including provision of binding wire ®Chain link MS galvanized fencing, any size or type
50
-
-
... More
Supplied only Chain link MS galvanisd fencing, of size 125mmx 125mm made of 4mm dia MS GI wire
200
-
-
... More
S&F Hand rails, half round or other steel section or core for wooden hand-rail straight portion, drilled and countersunk for balusters running bars, for doors, balusters, nosing to steps including embedding in concrete and screwing etc. wind ties for roof including securing bolts posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc., and similar work conforming toFe-290 Gde E-165
60
-
-
... More
S&F Mild steel bolts purpose made with hexagonal or square head one end and screwed the other, or screwed both ends; each screwed end to be fitted with washers and one hexagonal or square nut. exc30cm long dia of neck excd 12mm and n.exc 20mm
5
-
-
... More
M&L painting with synthetic enamel paint two coats over one coat of primer on new steel surfaces including preparation Surfaces of any description, over10cm in width or girth, not otherwise described
5
-
-
... More
Taking down and removing to or from store chowkats or frames exc 1.5 sq. m and not exc 4 sqm each but with shutters (without taking off shutters from the frames)
3
-
-
... More
M&L one coat of white wash on soffits etc including preparation of surfaces
150
-
-
... More
M&L one coat of acrylic emulsion distemper over on old wall surfaces including preparation of surfaces all as specified.
300
-
-
... More
M&L one coat of white wash on wall etc including preparation of surfaces
45
-
-
... More
S&F Aluminium handles, cast type, anodised size of handle in 150mm
6
-
-
... More
Cleaning roof surface including uprooting of grass, shrubs etc
100
-
-
... More
M&L applying one coat of weather proof exterior emulsion paint on old wall surface(up to 15m height) complete all as specified and directed all as specified & directed by Engineer-in-charge.
300
-
-
... More
M&L for preparation of old painted steel surfaces of any description, over 10 cm width or girth, not otherwise described and applying one coat of synthetic enamel paint (First quality) all as specified & directed by Engineer-in-charge.
70
-
-
... More
Dismantling wrought iron or mild steelwork of any description not otherwise provided for
0.5
-
-
... More
M&L for Poly Urethane based water proofing treatment to existing RCC roof slab with the following specifications. i) Cleaning the existing surface by mechanical means to make it free from any bituminous residue/dirt, oil and grease all as directed by Engineer In Charge. ii)M&L for cracks treatment by cutting open cracks and cleaning it from dirts, loose materials etc and filling with Polyurethane based sealant with and including application of PU based primer all as directed by Engineer In Charge. iii) M&L applying water based polyurethane modified dispersion(single component, cold applied , non toxic , VOC compound) in three coats including one coat of primer of same material after dilution of water at 50% or specific primer matching same material as per manufacturer specification and as directed by Engineer In Charge. Note:- Properties of Poly urethane based chemical shall conform to following technical parameters a)Highly elastic b)UV resistance c)Adhesion to concrete 1N/ Sqmm )Tensile strength-not less than 2.0 N/Sqmm for free film Elongation not less than 300% e) Solid content by weight not less than 60% f)Air/Water permeability BSEN 12390 at 5 bar -72 hours should be NIL and minimum dry film thickness of water proofing membrane must be 1.00mm g)Accelerated weathering(ASTM 453) Pass 1000 hours h) Reaction to fire - Non inflammable
125
-
-
... More
M & L for XLPE insulated, armoured, heavy duty electric cable with aluminimum conductor, 1100 Volts grade, laying in trenches/fixed on wall and pole including taking down old unserviceable one complete all as specified and as directed of following crosssectional area
-
-
-
... More
Cable of size 70 Sqmm 3.5 Core
270
-
-
... More
Cable of size 50 Sqmm 3.5 Core
300
-
-
... More
Cable of size 25 Sqmm 4 core
300
-
-
... More
Cable of size 16 SQmmx 4 core
200
-
-
... More
M&L for XLPE insulated , armoured, heavy duty electric cable with Aluminium conductor,3x 150 Sqmm, 11000 Volts, laying in trenches / fixed on wall or pole including taking down old unserviceable cable complete all as specified and as directed.
30
-
-
... More
Note for XLPE Cable : (i) Rate include the cost of lugs of proper size, and cable gland.
(ii) Necessary Excavation, PCC cover and sand cushioning shall be measured & paid separately.
-
-
-
... More
Excavation in trenches not exceeding 1.5 mtr deep and 1.5 mtr width as in soft/loose soil complete all as specified.
248
-
-
... More
Returning filling incl leveling watering and well ramming in layer not exceeding 25 cm thick complete all as specified & directed by EIC.
146
-
-
... More
Removal of surface soil to a distance n.exc 50 m and deposited where directed at a level n. exc 1.5 m above the starting point complete all as directed by EIC .
102
-
-
... More
S & L for riddled earth for cushioning for cable protection in trenches 8 cm before laying cable and 15 cm deep over the cable complete ( Note: Punned thickness shall be taken for measurement)
77.1
-
-
... More
M & L for laying LT cable cover of size 250x150x75mm class LV type 1 flat for protection of cable in trenches complete all as directed by Engineer-in-Charge.
5833
-
-
... More
M & L for Straight through heat shrink joints 1100 Volts,PVC / XLPE insulated armoured Heavy duty LT UG cables with aluminium conductor including joint kits and labour for following cable size 3.5 core 70 sq.mm
2
-
-
... More
M & L for indoor termination heat shrinkable joints 1100 Volts, XLPE insulated armoured Heavy duty LT UG cables with aluminium conductor including joint kits and labour for following cable size 3.5 core 50sq.mm
2
-
-
... More
M & L for straight through heat shrinkable joints 1100 Volts, XLPE insulated armoured Heavy duty LT UG cables with aluminium conductor including joint kits and labour for following cable size 3.5 core 50sq.mm
2
-
-
... More
M & L for indoor termination heat shrinkable joints 1100 Volts, XLPE insulated armoured Heavy duty LT UG cables with aluminium conductor including joint kits and labour for following cable size 3.5 core 70sq.mm
1
-
-
... More
M&L for 11KV (earthed ) cable jointing kit outdoor end termination heat shrinkable type with jointing material and accessories suitable for 3 core XLPE armoured aluminium cable of size 150 sqmm all as specified and as directed.Make: M-Seal/3M/Deson
2
-
-
... More
Supply, Install, Testing and commissioning LT feeder pillar (in replacement of outdoor Type) suitable size, CPRI Approved factory made, Double door, Cubical type, Compartmentalized design, back door, openable, fabricated out of 3.15mm thick CRCA steel sheet, weather / dust / vermin proof, suitable spaced totally enclosed in chamber, earthing arrangement, locking arrangement with one lock with duplicate key duly painted with powder coated paint having danger notice boards and earthing terminals on both sides and including providing the following items incl connection of all incoming and outgoing cables using suitable size lugs and glands, Spreader terminal set, control wiring, panel to be mounted on cable trench if required with base channels as required complete in all respect all as specified & directed by Engineer-in-charge including comprising of following items :- 4 Nos Aluminium Busbars of high conductivity
1
-
-
... More
(a) 3 Nos for phase (R,Y,B) rating 200 amp and 1No for neutral rating 200 Amp, Mounted on DMC support with heat shrink sleeve - 1 Set
(b) Manual chnageover160A- 1 No
(c) MCCB 4P 160 Amps 25 KA 415 V 50 Hz – 1 No (I/C)
(d) MCCB 4P 100 Amps 25 KA 415 v 50 Hz - 2 No
(e) Panel socket 32A, 3P+N+E-- 1 No
(f) Time switch 24 Hr Digital-- 1 No
(g) MCB DP 32 Amps 10 KA 415 v 50 Hz - 2 Nos
(h) Multifunction meter, Class 1, three phase, digital type, with parameters like voltage, ampere, frequency, PF etc, and with suitable rated CT’s complete including selector switch for three phase etc
(i) Indication Lamp (R,Y,B), LED Type, With toggle switches – 1 Set of Three
-
-
-
... More
M&L for fixing standalone bus bar panel for XLPE cable termination of size minimum 50 sqmm including Aluminium bus bar of suitable size with provision for cable entry and earth termination. Note: The panel shall be fixed at least 30 CM above the ground with panel stand firmly grouted to the ground and necessary PCC and excavation shall be deemed to be included in the rate. The Bus bar shall be of Aluminium and max of length 80CM and of size 20x5mm. R, Y, B and Neutral shall have bus bars of same size and length.
1
-
-
... More
Dismantling of ACSR or AAC conductor squirrel type from poles of any size & capacity and unserviceable materials removing from the site complete all as specified and as directed.
0.2
-
-
... More
M&L for Arial Bunched Cable (ABC), 5 core,( 3 phase, 1 Neutral, 1 Messenger, 1 Street light) of size 70 Sqmm ( 3x70+1x70+1x50+1x16), 1100 Volt grade, confirming to IS 1455. All as specified and as directed by engg-in-charge.
Note: (1) The three phase cables, Neutral, and street light conductor shall be twisted around messenger to form cable assy.
(ii) The phase and neutral conductors shall be insulated with XLPE.
(iii) The quoted shall also include necessary fixing arrangement in the existing poles and connection to street lights.
240
-
-
... More
M& L for surface dressing once in every 2 months to E/M installations /1.5 Mtrs from outside of fencing , E/M store yards of following area not exceeding 15 cm deep getting out soft / loose soil removing shrubs, small trees height up to 1.0 Mtrs, removing the grass from route and cleaning the fencing by removing small trees /Vegetation on fencing complete all as specified and as directed. Note : (i) Rate includes removing all waste material and grass not exceeding 50 Mtrs distance from installation ,depositing where directed at a level not exceeding 1.5 Mtrs above the starting point and cleaning of yard , Complete all as specified and directed by Engineer-in Charge
-
-
-
... More
Tech area main incomer substation 100 Sqm
4
-
-
... More
Non tech area pumphouse 80 Sqm
4
-
-
... More
M & L for road cutting /removing the hard Standing/Cutting floor inside the Substation /E/M Installations / Path for laying of cables of any size complete all as specified. The item shall include cutting of road, and necessary PCC for making good all as specified and directed by engg in charge.
15
-
-
... More
Supply and fixing Onload Change over switch of capacity 125 A, 4 Pole, 415 Vols, 50 Hz, with Panel Mounted rotating handle, including dismantling old unserviceable change over switch by disconnection all incoming and outgoing electrical connection from existing indoor LT Panel complete all as specified and directed.
1
-
-
... More
Material and labor for laying 40 mm stones using hard stones, broken and sized up to 63 mm in the substation yard to reduce touch potential. .
1
-
-
... More
M&L for repairing/servicing calibrating testing and decommissioning ACB, upto 1.1 KV, outdoor/indoor type, including replacement of gasket set, adjusting reconditioning stationery moving contact, adjusting link mechanism within limit, nut, bolt and washer including replacement of damage thimbles of required size complete all as directed.
1
-
-
... More
M&L for medium grade GI pipe 40mm dia for cable protection all as specified and directed by Engr in charge.
62
-
-
... More
Supply and fix breather for transformer oil conservator tank including filled with silica gel for transformer of ratings 160 KVA complete all as specified and as directed by engineer-in charge
1
-
-
... More
M & L for filtration of transformer oil of different capacity/Rating to remove moisture ,sludge, carbon particles and to achieve the dielectric strength / rupturing capacity of oil not less than 50 KV/ minute with 2.5 mm gap and topping up of oil to the required level of transformer indicator level all as specified and directed by engineer-in-Charge.
Note: Topping up of transformer oil shall be measured and paid separately
(2) Contractor has to make his own arrangement for oil filtration plant.
320
-
-
... More
Supply, Install, Testing and commissioning LT feeder pillar (in replacement of outdoor Type) suitable size, CPRI Approved factory made, Single door, Cubical type, Compartmentalized design, back door, openable, fabricated out of 3.15mm thick CRCA steel sheet, weather / dust / vermin proof, suitable spaced totally enclosed in chamber, earthing arrangement, locking arrangement with one no lock with duplicate key duly painted with powder coated paint having danger notice boards and earthing terminals on both sides and including providing the following items incl connection of all incoming and outgoing cables using suitable size lugs and glands, Spreader terminal set, control wiring, panel to be mounted on cable trench if required with base channels as required complete in all respect all as specified & directed by Engineer-in-charge including comprising of following items :-
4 Nos Aluminium Busbars of high conductivity
1
-
-
... More
(a) 3 Nos for phase (R,Y,B) rating 200 amp and 1No for neutral rating 200 Amp, Mounted on DMC support with heat shrink sleeve - 1 Set
(b) MCCB 4P 200 Amps 25 KA 415 V 50 Hz – 1 No (I/C)
(c) MCCB 4P 63 Amps 16/18 KA 415 v 50 Hz - 4 No
(d) MCB DP 32 Amps 10 KA 415 v 50 Hz - 4 Nos
(e) Multifunction meter, Class 1, three phase, digital type, with parameters like voltage, ampere, frequency, PF etc, and with suitable rated CT’s complete including selector switch for three phase etc
(f) Indication Lamp (R,Y,B), LED Type, With toggle switches – 1 Set of Three
-
-
-
... More
M&L in repairs 4 pole, MCCB, 630A, adjustable thermal magnetic , 50KA breaking capacity all as specified and as directed by Engr-in-charge.Make: Havells/L&T/Legrand
1
-
-
... More
M&L for load line vertical MCCB DB, 4 Way, Double door with 125 A MCCB incomer and three/single phase outgoing. The DB should be fitted with suitably rated bus bar, neutral links, blanking plates etc.Make : Havells/L&T/Legrand
1
-
-
... More
S & F in replacement of MCCB 4 Pole 100-125 Amps 415V 25 KA. Make: legrand/Havells/L&T all as specified and as directed.
5
-
-
... More
S & F in replacement of MCCB 4 Pole 400 Amps 415V 36 KA. Make: legrand/Havells/L&T all as specified and as directed.
1
-
-
... More
S & F in replacement of MCB TPN 63 Amp, 4 Pole, 10 KA'C' Curve Make: legrand/Havells/L&T all as specified and as directed.
16
-
-
... More
S & F in replacement of MCB DP 32-40 Amp, 'C' Curve Make: legrand/Havells/L&T all as specified and as directed.
16
-
-
... More
S & F in replacement of MCB SP 6 to 32 Amp, 'C' Curve Make: legrand/Havells/L&T all as specified and as directed.
16
-
-
... More
M & L for cutting the tree branches at a distance not exceeding 2.0 Mtrs away from roof top of E/M Installation of G+0 Building of tree branch size up to 50 mm dia as directed and removing branches at a distance not exceeding 100 Mtrs from Road /Path.
20
-
-
... More
M & L for in replacement of galvanised iron strip 32 x 6 mm buried in ground with saddles and fixing screws etc for roof conductors and down conductors including removing and replacement of deteriorated SS bolts, nuts and washers as required at site etc in the existing GI strip of any size from the starting point to upto the end connected points all as specified and directed by Engr-in-Charge.
120
-
-
... More
M & L for topping up/ change oil for transformer of 11KV/433 Volt of different capacity / HT oil switch of 11 KV of different capacity of any rating of dielectric strength /rupturing capacity of oil not less than 50 KV ( tested at site with testing kit with 2.5 mm gap ) and test the the dielectric strength of transformer oil before and after the topping up and make oil to the required level of transformer indicator level all as specified and directed by EIC.
Note: The transformer oil container shall be ISI marked and brought at site in sealed container only. 2). The M & L for necessary T & P for collection of transformer oil samples , testing kit and filtration plant.
30
-
-
... More
Dismantling HT/ LT stay assembly complete including MS clamps with bolts, nuts & washers etc along with necessary excavation and earth work, demolition of cement concrete and removing from thr site necessary excavation & earth work complete all as specified and directed.
2
-
-
... More
M&L for stay assembly complete with accessories such as mild steel glavanised flat iron stay clamp, 7/3.15 mild steel galvanised stay strand/wire, one loo[p type porcelain vitreous insulator (white , brown or green) overall dimentions 65X90 mm & clearing hole 16 mm, stay grips, mild steel galvinsed stay bow, thimbles, 16 mm dia diameter of stay rod shown in electrical plate No 1 of MES SSR Part- I complete all as specified and as directed. (Note : Excavation & earthwork, cement concrete measured and paid separately relevant items of this schedule).
2
-
-
... More
Dismantling cross arms, MS channel or angle sections etc. complete and unserviceable removing from the site complete all as directed by Engr-in-Charge.
1
-
-
... More
M & L cross arms, bracings, support clamps and back plates fabricated from structural steel section including nut bolts washer, welding, bending cold or hot drilling holes for bolts in any shape or size as indicated or directed including two coats of aluminium paint over a coat of read oxide zinc chrome primer including preparation of surfaces complete all as specified and as directed.
1
-
-
... More
M&L in repairs GOD, tripple pole , mechanically operated, 11 KV, mounted on insulator and steel frame, with operating mechanism worked from ground level for a current rating up to 200A all as specified and ad directed by engg in charge.
1
-
-
... More
M&L in repairs to lightning arrestors expulsion type complete with all fittings, transmission class, with discharge capacity 65 Kilo Amps all as specified and as directed.
1
-
-
... More
Supply, Install, Testing and commissioning LT feeder pillar (in replacement of outdoor Type) suitable size, CPRI Approved factory made, Single door, Cubical type, Compartmentalized design, back door, openable, fabricated out of 3.15mm thick CRCA steel sheet, weather / dust / vermin proof, suitable spaced totally enclosed in chamber, earthing arrangement, locking arrangement with one no lock with duplicate key duly painted with powder coated paint having danger notice boards and earthing terminals on both sides and including providing the following items incl connection of all incoming and outgoing cables using suitable size lugs and glands, Spreader terminal set, control wiring, panel to be mounted on cable trench if required with base channels as required complete in all respect all as specified & directed by Engineer-in-charge including comprising of following items :-
4 Nos Aluminium Busbars of high conductivity
1
-
-
... More
(a) 3 Nos for phase (R,Y,B) rating 300 amp and 1No for neutral rating 300 Amp, Mounted on DMC support with heat shrink sleeve - 1 Set
(b) MCCB 4P 160 Amps 25 KA 415 V 50 Hz – 1 No (I/C)
(c) MCCB 4P 63 Amps 16/18 KA 415 v 50 Hz - 2 No
(d) MCB DP 32 Amps 10 KA 415 v 50 Hz - 4 Nos
(e) Multifunction meter, Class 1, three phase, digital type, with parameters like voltage, ampere, frequency, PF etc, and with suitable rated CT’s complete including selector switch for three phase etc
(f) Indication Lamp (R,Y,B), LED Type, With toggle switches – 1 Set of Three
Note: Necessary PCC and coping work for fixing the panel is inclusive in the quoted amount.
(ii) Drawings shall be pre approved from Engg in charge before making order.
-
-
-
... More
Material and Labor for dismantling the burnt winding (Primary/Secondary) and rewinding the distribution transformer (oil-cooled, copper-wound, 160 KVA capacity) from its installed position on the existing platform . This includes:
(a). Disconnecting the electric supply from HV and LV sides.
(b) Removing the transformer from its installed position and transporting it to the workshop. (c) Conducting a preliminary inspection and diagnosing faults. (d) Performing service tasks such as oil draining, removing the transformer top cover, dismantling the bush stem, removing the core coil assembly (CCA), and cleaning job components. (e) Dismantling the CCA and performing coil winding and refixing. (f) Conducting terminal gear cutting and rejoining, tanking, and all associated jobs.
(g) Replacing washers, sleeves, taps, kerb tapes, and cork sheets as necessary. (h) Refilling the transformer oil after checking and ensuring the functionality of the Winding Temperature Indicator (WTI) and Oil Temperature Indicator (OTI), including the replacement of unserviceable items if required. (i) Refilling the transformer oil after checking and ensuring the functionality of the Winding Temperature Indicator (WTI) and Oil Temperature Indicator (OTI), including the replacement of unserviceable items if required. (j) Reinstalling the transformer in its original position and making all electrical connections with thimbles and PG clamps. (k) Commissioning the transformer, which includes refilling transformer oil after dehydration with dielectric strength (minimum 60 KV) and conducting thorough testing to ensure proper operation and functionality.
1
-
-
... More
Material and labor for providing a transformer of the same rating on a rental basis on the same day, including installation to replace the burnt transformer, making the necessary connections to continue the supply at the site, and dismantling the temporary transformer after repairing the faulty one. It also includes the cost of transporting the transformer from the workshop to the site.
15
-
-
... More
M&L for Earthing complete with galvanized steel earth plate electrode 600x600x6.0mm thick buried directly in ground (earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level connected to galvanized iron strip 32x6 mm as earthing by means of bolts nuts and washers of galvanized iron including excavation and earth work and disposal of surplus soil including 40 mm GI tubing light grade and necessary fittings for protection of GI strip including laying of charcoal , dust and common slat , PCC 1:2: 4 type B 1 using 320 mm graded aggregate with earth piot with 40 X 40 X 6.0 mm MS angle iron frame RCC cover 40 mm thick (1:2: 4) type C1 using 20 mm graded stone aggregate reinforced with 8 mm dia round bar @ 75 mm C/C both way with MS handle 20 mm dia plastering 15 mm thick CM ( 1: 6) internally and up to 150 mm below ground level externally . PGI funel with wire mesh 20 mm dia GI pipe for watering complete all as shown on electrical plate No: 03 of SSR part -I 2009 and connected to earth test point including testing completed all specified and directed.
8
-
-
... More
M& L for removing of dirt by using sand paper completely and preparation of old painted steel surface of Transformer and any gauge/size with applying two coats of primer with red oxide Zinc chrome and a final coat of Japan paint as existing colour of paint by spray paint (Using Machine) at four sides, top and bottom of transformer capacity of rating160 KVA , complete painting of the transformer to match the existing color, with the MES number neatly displayed, all as specified and as directed by Engineer in charge. Note: (i) Contactor has to take the shutdown of Transformer 11/0.433 KV from substation before starting the execution of work and switch ON/OFF on the Transformer after completion of work all as directed. (ii) Cost of T & P also included in quoted rate. (iii) The contractor should be deployed the skilled electrician for handling the HT & LT installation smoothly without damaging/disturbing the existing installations.
1
-
-
... More
M & L for road cutting /removing the hard Standing/Cutting floor inside the Substation /E/M Installations / Path for laying of cables of any size complete all as specified. The item shall include cutting of road, and necessary PCC for making good all as specified and directed by Engg in charge.
20
-
-
... More
Repair to street light/flood light of any type , any description mounted on pole/ Roof/ wall ,disconnecting electrically, testing of all components to ascertain defective parts of the fitting and testing the conductivity of electric cable of internal wiring of the fittings, dismantling of defective components and testing the fitting after replacement of defective components and cable of internal wiring and making the fitting fully functional testing complete.
25
-
-
... More
All as pe Ser item No 82 above but post top / Bollard light
5
-
-
... More
Repair to high mast light fitting mounted on up to 16 mtr height structure of qty 09 to 12 light fitting , lowering disconnecting electrically, testing of all components to ascertain defective part of the fitting and testing the conductivity of electric cable of internal wiring of the fittings, dismantling of defective components, testing the fitting after replacement of defective components and making the fitting fully functional finally entire unit to be raised upto its original level complete. (The necessary components should be measured and paid separately)
2
-
-
... More
S&F LED street light luminaries 45 W, IP-66 with pressure die cast aluminium housing , Heat resistant toughened glass with frame, including taking down existing unserviceable HPSV/MH/LED fitting from from Steel /PCC pole up to 9.00 Mtrs height or from wall complete all as specified and as directed. Make: Crompton Cat part No LSTS-45-CDL-M or equivalent in Havells/Jaquar/Philips
Note: Height of new fitting should adjust to achive better illumination level so as to match with LED fittings as directed.
10
-
-
... More
S & F LED flood light fitting 150W, 110 L/Watt efficacy with 10KV SPD and high pressure die cast housing IP 66 protection for area lighting fwith necessary fixing arrangement on pole/Wall with suitable size MS clamp , nuts & bolts, for lights complete including taking down old unserviceable fitting of any type and depositing to store for credit all as directed by Engineer-in-Charge Make: Crompton Cat part No : LFLN 150CDL/60 M or equivalent in Havells/Philips/ Jaqua/ HPL
3
-
-
... More
All as per item No 86 above, but 300W, with 10KV SPD to be fixed on High mast of height up to 12m all as specified and as directed. Make: Crompton or equiv in Havells/Jaquar/Philips/ HPL
2
-
-
... More
S & F post top luminaries die cast housing and clear acrylic and spun aluminium reflector of IP 65 protection , resistance to corrosion of 40 Watt with LED lamp with all fixing arrangements fixed to post top complete including taking down old unserviceable fitting of any type and depositing to store for credit all as directed by Engineer-in-Charge. Make: Crompton Cat part No. LPTO-40-CDL-M Equivalent in Havells/Philips .
2
-
-
... More
S & F Bollard luminaries die cast housing and clear acrylic of IP 65 protection Inverted Tripod type , resistance to corrosion of 10 Watt with LED lamp with all fixing arrangements fixed with soft 360 deg light distribution complete including taking down old unserviceable fitting of any type and depositing to store for credit all as directed by Engineer-in-Charge.Make: Crompton Cat part No. LBLSN-10-CDL Equivalent in Havells/Philips/Luker
2
-
-
... More
Supply ,fix test and commissioning of 17W hybrid All in One Solar street light with not less than 3000 Lumens light output and more than 180 Lumens per watt system efficiency. 50,000 burning hours as per L70. Built in maintenance free Lithium Ferro Phosphate Battery(Life Po4) with 256Wh capacity, 35 wp solar panel module. The housing shall be made of Single piece Pressure diecast Aluminium Housing in non corrosive 500 hours NSS Salt spray tested finish and UV stabilised polycarbonate cover with embedded lens for each LED's. 3 step Adjustable Arm tilting option to adjust the light distribution with no additional pole support suitable for mounting on arm bracket directly on pole top. Hybrid type MPPT Charge controller and driver efficiency shall be greater than 90%.all including octagonal pole of 5m with FDN bolt and base plate size of 200x200x12mm and sheet thickness 3 mm fixed including RCC all as specified and as directed.
Make: Philips cat No:BRP710 LED30 CW MR S1 12V LFP or equiv in Crompton/Havells
2
-
-
... More
Supply and fixing passing through pole cable 3 core PVC insulated unsheathed multistranded copper conductor of size 2.5 Sqmm from junction box to fitting all as directed by EIC..Make: Havell's/Finolex/Poly cab
100
-
-
... More
M&L for cleaning of feeder pillar/ panel after dismantling the Incomming and outgoing connections from MCBs and replacing the old unserviceable Gland, lugs, nuts & bolts, push buttons, indicating lamps, supporting insulators etc., and checking the serviceability of MCBs, cables and earth continuity conductor including replacement of worn out and unserviceable minor accessories all as specified and directed by EIC.
Note: Spares / materials charge for repair/replacement of worn-out parts shall be measured and paid separately under relevant items
4
-
-
... More
S & F junction box transparent type readymade of size 133x205x95 mm with aluminium bus bar of 50 Amp capacity for RYB and half for neutral made in suitable size fixed inside the junction box with necessary supporting insulators fixed on hylem sheet ,MS sheet steel fixed inside the bottom portion of box to connect the cable gland complete , entire assembly fixed to pole /Wall with MS clamp 25 X 5 mm and nuts & bolts, or inside the Copping of pole /Post top including MCB SP 6 Amp 10 KA 240 V - 1 No, with necessary size copper lugs for connecting cables from junction box to fittings complete all as directed by Engineer-in-Charge . Make: Hensel/Sintex
20
-
-
... More
M & L for painting of PCC pole with cement base paint one coat suitable for outdoor including cleaning of poles removing creeper etc from pole and , as specified and as directed .Make: Asian Paints /Nerolac etc
2
-
-
... More
Material and labour for painting Steel Tubular Poles (Swaged Type) For Street Lighting of height maximum up to 15 Mtr single dome type up to light fitting complete including two coat of synthetic enamel paint over one coat of red oxide primer complete all as specified and as directed .
20
-
-
... More
M & L for cutting the tree branches at a distance not exceeding 3.0 Mtrs away from Street light poles /fitting incl removing the creeper which surrounded the poles and street lights , of tree branch size up to 50 mm dia as directed and deposited the removing branches at a distance not exceeding 100 Mtrs from Road /Path.
25
-
-
... More
M&L for PCC 1:4:8 type D2 40 mm graded aggregate Complete for foundations for post top lantern /PCC at road crossing etc , complete all as directed by Engineer-in-Charge.
1
-
-
... More
M&L for PCC 1:3:6 type C1 20 mm graded aggregate in coping of pole for post top lantern complete all as directed by Engineer-in-Charge.
1
-
-
... More
Dismantling of Unserviceable Pre-stressed concrete poles/ steel poles of any size & shape including necessary excavation and earth work, taking out of embedded portion of poles from concrete after necessary demolition of cement concrete foundation and disposal of same complete all as specified and directed. Note : Exacvation & earthwork, returning filling removing of surplus soil and demolition of concrete and disposed of the demolished concrete shall deemed to be included in the unit rate quoted by the tenderer.
3
-
-
... More
Supply, erecting & fixing steel tubular swaged poles complete with cast iron base plate, final taper plug, bolts, nuts & screws as specified type 410 SP - 31 ( 9.00 metres long), complete all as specified and directed. Note: (i) Earthwork, cement concrete, etc. will be measured and paid separately under relevant items of this schedule . (ii) Excavation & earth work shall only be measured in case location is other than item No.99 above
3
-
-
... More
M & L for road cutting /removing the hard Standing/Cutting floor inside the Substation /E/M Installations / Path for laying of cables of any size complete all as specified. The item shall include cutting of road, and necessary PCC for making good all as specified and directed by engg in charge.
20
-
-
... More
Supply only driver as per sample for outdoor type LED fitting of following watt complete all as specified and as directed
-
-
-
... More
LED driver 10 Watt
6
-
-
... More
LED driver 40/45 Watt
15
-
-
... More
LED driver 150Watt
2
-
-
... More
LED driver 300Watt
2
-
-
... More
Supply, installation, testing and commissioning of street light timer control panel, frame size suitable for upto 6 Kw load on pole/wall/floor mounting made out of CRCA steel sheet duly powder coated with locking arrangement, including internal wiring complete with bypass arrangements as per manufactures recommendation and design complete all as specified and as directed. Make :Havells/Schenider/IndoAsian
1
-
-
... More
Supply and fix in replacement power contactors 3 pole, 65 Amps, for street light after dismantling existing contactors from panel and connecting new contactors and making connection with incoming and outgoing MCCB/MCB complete all as specified and as directed for following ratings . Make: L & T /Indo Asian/Legrand