INKEL Limited Tender
Everything can be found here in your one-stop destination for all types of Kerala tenders online - be it Kerala PWD tenders or an LSGD Kerala tender. Search from across the categories, cities, and authorities while having the option to download tender-related documents. Also, get to know how to register as a bidder and how to bid online for Kerala tenders.
Costs
EMD
₹ 50,000Document Cost
₹ 2,950Tender Fee
Refer Documents
Summary
Alappuzha Heritage Project - Supply, Installation, Testing And Commissioning Of Diesel Generator, Street Lighting And Balance Electrical Works For Yarn Museum, Alappuzha
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2021_INKEL_458296_1Bid Award Id
ViewTender No
NIT/INKEL/ALP/2021-22/271 dated 03/12/2021Tender Authority
INKEL Limited ViewPurchaser Address
-Website
http://etenders.kerala.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
1.14.1 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required
2x1.5 sq.mm + 1x1.5 sq.mm earth wire
50
-
-
1.14.2 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required
2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
100
-
-
1.14.3 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required
2 X 4 sq. mm + 1 X 4 sq. mm earth wire
20
-
-
1.17.3 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.
3 X 1.5 sq.mm
80
-
-
1.17.31 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.
4 x 6 sq. mm
100
-
-
1.21.1 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.
20 mm
105
-
-
1.21.2 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.
25 mm
115
-
-
1.21.3 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.
32 mm
25
-
-
1.26 : Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
50
-
-
Supplying and fixing suitable size PVC box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections etc. as required.
14
-
-
Supplying and fixing suitable size PVC box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
34
-
-
1.33 : Supplying and fixing 3 pin, 5 amp ceiling rose on the existing junction box/ wooden block
including connection etc as required.
10
-
-
1.44 : Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard
length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc.
as required.
132
-
-
Supplying and fixing of following sizes of ISI medium class Oval PVC conduit along with all accessories in surface and making good the same as required.
20 mm
50
-
-
Supplying and fixing of following sizes of ISI medium class Oval PVC conduit along with all accessories in surface and making good the same as required.
25 mm
50
-
-
DG AND EXHAUST PIPING
-
-
-
Supply, Installation, Testing and Commissioning of 62.5 kVA prime rated D.G set with acoustic enclosure and control panel, protection and digital metering, controls and interlocks, CTs and transducers for all metering and protection with suitable size breaker, including antivibration mountings, exhaust silence conforming to latest environment protection regulations for emission and noise levels, water/coolant cooled, ( radiator type) four stroke, electric start conforming to BS: 5514 , brushless, self excited, self regulated and suitable for continuous operation at 1500 RPM, generating 415 V +/- 5% Volts at 0.8 p.f (lag),50 Hz, 3Phase, 4 wire system generally conforming to IS 4722. Both Engine and alternator shall be mounted on common channel iron base frame, and with standard accessories such as maintance free batteries and engine driven battery charger along with leads, battery stand, necessary control wiring with control cables, first fill of lubricating oil, and earthing as per standards, Inbuilt Fuel tank suitable for 8 hrs continuous operation, fuel piping from fuel tank to Engine, Residential silencer, suitable size of cable termination box etc.as required and as per technical specifications
1
-
-
EXHAUST PIPES:
Supply, erection, commissioning of additional length of suitable dia exhaust pipes with long radius bend from residential silencer with necessary clamps, fixtures, civil works and painted with heat resistant, rust proof, bituminous paint of approved colors to a maximum of 10 m in stages of following sizes including suitable rain cap for top to avoid rain water entry. The distance between exhaust pipe at top and rain cap should be higher than diameter of pipe. It is also recommended that horizontal run of exhaust piping should slope downwards away from engine to the condensate trap. Silencer should be installed with drain plug at bottom. Fixing shall be done with proper clamps, expansion bolts, and all other acessories as instructed by the Engineer and the rate inclusive of all minor civil works required, bolts, clamps angle, channel, I section, necessary nut and bolt and all required accessories including cutting, hoisting, fixing in position and applying 2 coats of primer and 2 coats of enamel paint of approved quality etc as required in the steel works etc as required for istallation. Support to exhaust piping should be done in such a manner that load of exhaust piping is not exerted to turbocharger. Exhaust pipe height shall be 3m more than the top of any adjacent building within 10m radius of the exhaust.
5
-
-
MCB &DBs
-
-
-
Supply, installation, testing and commissioning of totally enclosed free standing wall mounting dust and vermin proof,indoor cubicle type , suitable for 415 V, 3 phase, 50 HZ supply, fabricated of 14 SWG CRCA sheet steel Powder coated complete with busbars having 200 A rating, indicating lamps (LED type) with 2A control MCBs & interconnections with suitable size of copper leads/solid aluminium strips/rod and having following incoming and outgoing MCCB/MCBs as per the drawing and specifications. The design should be as per the standards of the State Electrical Inspectorate.
Incoming:
160A, 25 kA, FP Thermal Magnetic Type MCCB
Busbar
160A TPN busbar chamber with Aluminium busbar Earth busbar - 25x6mm Cu.
Instruments
RYB, ON OFF TRIP Indicating lamps LED type Multifunction Meter 160/5A,10 VA CTs class 1 Outgoing:
40A TPN MCB - 5Nos.
63A TPN MCB - 2Nos.
1
-
-
Supply, erection, testing and commissioning of following capacity manual change over switch in metal enclosure suitable for vertical or horizontal mounting .
160A 4P Change Over Switch
1
-
-
2.1.5 : Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.
160 Amp TP&N
1
-
-
2.4.1 : Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
4 way (4 + 12), Double door
1
-
-
2.4.2 : Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
6 way (4 + 18), Double door
2
-
-
2.5.1 : Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (but without MCB's and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 4 way (4 + 12), Double door
1
-
-
2.13.1 : Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.
40 amps
2
-
-
2.13.2 : Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.
63 amps
1
-
-
2.15.2 : Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.
40 amps
4
-
-
2.10.1 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single pole
48
-
-
2.10.4 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Triple pole
4
-
-
2.11 : Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
20
-
-
2.21 : Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2
mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
2
-
-
MV & LT CABLE LAYING
-
-
-
7.1.1 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
Upto 35 sq. mm
205
-
-
7.1.2 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
Above 35 sq. mm and upto 95 sq. mm
80
-
-
7.5.1 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
Upto 35 sq. mm
25
-
-
7.5.2 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.
Above 35 sq. mm and upto 95 sq. mm
5
-
-
7.7.1 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.
Upto 35 sq. mm (clamped with 1mm thick saddle)
20
-
-
7.7.2 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.
Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
5
-
-
7.8.1 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.
Upto 35 sq. mm (clamped with 1mm thick saddle)
10
-
-
7.8.2 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.
Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
5
-
-
7.10 : Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with
inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing
the same in ground as required.
5
-
-
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required.
3.5c x 50 sq.mm
100
-
-
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required.
3.5c x 35 sq.mm
80
-
-
Supply of the following size 1.1kV grade XLPE insulated PVC sheathed, armoured Aluminium conductor power cable confirming to IS 7098 (part 1) ammended upto date. 4c x10 sq.mm Al Cable
180
-
-
9.1.22 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3 1/2 X 50 sq. mm (35mm)
2
-
-
9.1.21 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3 1/2X 35 sq. mm (32mm)
8
-
-
9.1.32 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
4 X 10 sq. mm (25mm)
35
-
-
Supply and laying and clamping of the following PVC sheathed unarmoured power cable conductor of best conductivity copper solid/stranded conductor, XLPE insulated, PVC inner sheathed 1.1kV grade strictly conforming to IS:1554 (Part-I) 1964 of the following sizes in meduin duty conduit / cable tray /wall using factory made heavy gauge GI/painted MS clamps. Space between clamps not exceeding 60cms amd making good the damages colour washing etc as required. and instructed by engineer at site/consultant.
1 x25 Sq.mm Copper Flexible Cable
60
-
-
Supply and termination of superior quality copper tubular cable socket and making core termination of cables of the following sizes including crimping etc. as required.
1CX25 sq.mm Cu Cable
18
-
-
EARTHING
-
-
-
5.15 : Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
10
-
-
5.19 : Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
50
-
-
5.20 : Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for connections etc. as required.
4
-
-
LIGHT &FAN FIXTURES
-
-
-
Supply and installation of internal(IP20) 4 feet tube light with thickness not more than 36mm having a minimum lumen output of 2,000 at a power consumption between 20 -; 22 W. The life time of equipment should not be less than 50,000 hours, with preferable surge protection up to 2KV(optional).The Correlated Colour Temperature (CCT) should be 2700-3000K.The colour of the light output to be yellow.
Brand: Philips / Wipro/ Bajaj or Equivalent
200
-
-
SITC of internal(IP20) 4 feet tube light with thickness not more than 50mm having a lumen output between 2,000 to 2,600 at a power consumption between 26-28W. The life time of equipment should not be less than 50,000 hours, should have surge protection up to 2KV -; 4KV. The Correlated Colour Temperature (CCT) should be 2700-3000K. The colour of light output to be yellow. Necessary support to be considered as per the site condition.
Brand: Philips / Wipro/ Bajaj
7
-
-
Supply and installation with proper support as per the site condition of LED 4 feet 40W IP20 Surface Mounted/Suspended Industrial Type Luminaire including accessories as required.
Make:Wipro LE10-491-XXX-57-XX/ Equivalent Brand Philips/ Bajaj.
18
-
-
SITC of internal(IP20) 2 feet tube light having a minimum lumen output of 900 at a power consumption between 10-14 W, with expected life time of 50,000 hours, with preferable surge protection up to 2KV(optional).The Correlated Colour Temperature (CCT) should be 2700-3000K. Including all accessories as per the site condition. The colour of light output to be yellow.
Brand: Philips / Wipro/ Bajaj.
15
-
-
Supply and Installation of internal(IP20) 1 feet tube light having a minimum lumen output of 900 at a power consumption of 5W, with expected life time of 50,000 hours, with preferable surge protection up to 2KV(optional).The Correlated Colour Temperature (CCT) should be 2700-3000K.The colour of light output to be yellow.Brand: Philips / Wipro/ Bajaj or Equivalent
364
-
-
Supply and installation of recess mount eyeball light fixture having a diameter between 102mm to 115 mm and height not exceeding 80mm with lumen output not less than 1,000 at a power consumption of 15-16W, with life time not less than 50,000 hours, with preferable surge protection up to 2KV(optional).The Correlated Colour Temperature (CCT) should be 2700-3000K. Beam angle: 38 to 40 degree.The colour of light output to be yellow. Brand: Philips / Wipro/ Bajaj or Equivalent
278
-
-
Supply and installation of recess mount eyeball fitting with aluminium casement having a diameter not more than 100mm and thickness not exceeding 50mm with lumen output not less than 660 at a power consumption of 8 W, with life time not less than 40,000 hours.The Correlated Colour Temperature (CCT) should be 2700- 3000K. Beam angle: 38 degrees. The colour of light output to be yellow.Brand: Philips / Wipro/ Bajaj or Equivalent.
5
-
-
upply and Installation of ceiling fans 1200mm sweep - 5star rated BLDC ceiling fan complete with 300mm down rod , canopies, shackeles and blades working on 230V/240V single phase A/C. The color of the fan should be brown without any ornate or decorative border finish. Brand:Crompton/ Orient/ Usha
129
-
-
Supply and instllation of 3 Metres Decortive GRP Pole in Conical/Cylindrical Shape made by CNC Filament Machine using thermo set resin having minimum 62% glass content in one piece, suitable for fixing Post top fitting with top 60mm dia, 3mm thickness, Internal Junction Box with 200mm GRP Base Plate, M12 foundation Bolt.
31
-
-
SITC of 27W ± 10% Post Top Light fixture including control wiring, Control Boxes with individual MCB, 4kA Surge Protection, Electrical fixture Connectivity with FRLS Cu Flexible Cable from Control Boxes, & other Accessories required for the effective commissioning of Light fixture Make: Philips (BGP161 LED2500/NW PSU 220-240V 7043) or Equivalent Wipro Makes.
31
-
-
Supplying and fixing extra conduit down rod of MS pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)
100
-
-
Dismantling and Rewiring of light circuit/power circuit with 1.5/2.5 /4 sq.mm FRLS PVC insulated copper conductor including conduit as required analyzing site conditions
1
-
-
Dismantling of existing vertical DB from the wall and making good of wall with necessary plastering and painting after the work.
1
-
-
Supply & fixing MS Clamps for the ceiling fans including cutting the holes with all necessary accessories as required as per the site condition.
80
-
-
Installation, testing and commissioning of ceiling fan, excluding down rod but termination of existing wires to the supplied ceiling fans.
129
-
-
CABLE TRAY
-
-
-
4.1.2 : Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.150 mm width X 50 mm depth X 1.6 mm thickness
20
-
-
MINOR CIVIL WORKS
-
-
-
2.6.1 : Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50 m and lift up to 1.5 m, disposed earth to be levelled and neatly dressed.All kinds of soil
9.11
-
-
4.1.8 : Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 nominal size)
2.19
-
-
5.1.3 : Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level:1:2:4 ( 1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size)
4.31
-
-
5.9.1 : Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete
9.09
-
-
5.22.6 : Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more
323.16
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements