Karnataka, also known as Karunadu, is a state in the southwestern region of India. Karnataka was formed originally as Mysore State on 1st November 1956 and currently is the biggest state in south India. Its capital and largest city is Bengaluru. It covers an area of 191,791 km2 (74,051 sq mi) and is the sixth largest state by area comprising 31 districts. Karnataka is also a state of multiple languages; Kannada being the official and most widely spoken language in Karnataka. Other languages spoken in the state include Tamil, Telugu, Malayalam, Kodava, Konkani and much more.Karnataka tenders are issued by the government of Karnataka, public & private sector organisations. The state government issues majority of the Karnataka tenders, which are for goods and services including construction, road and bridge construction, IT services, engineering services, medical services, educational services amongst many others. Bidassist is one of the largest eprocurement portals, which offers all government tenders from across the world in one place. Bidassist offers information on all Karnataka tenders and other state and authority tenders in no time. Bidassist is a platform where users can look for various Karnataka tenders as well as other tenders.

Military Engineer Services - MES Tender

Works
Electrical and Electronics
Electrical Works
Eprocure
Opening Date7 Sep 2024
Closing Date7 Oct 2024
Tender Amount₹ 30,00,000 
Notes
Download

Costs

Summary

Repairs To Internal Electrification Including Meters Ceiling Fans Geysers And External Electrification Including Fps Dbs Lt Panel Cabels Street Light And Apfc At Sdi And Akash Vihar Camp Under Ge Af Marathahalli

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
M & L point wiring with 1.5 sqmm nominal cross sectional area, single core, 1100 Volts FRLS grade, stranded, PVC insulated, unsheathed copper conductor cable drawn through PVC concealed conduit of suitable size, complete with all PVC conduit accessories/ fittings, brass screws, washers etc, including metal flux boxes of suitable size and modular white plate with frame for mounting modular switches, sockets and regulators etc, including all cutting/chases etc in walls and including continuous earth wire of size 1.5 Sqmm nominal cross sectional area, single core, PVC insulated copper conductor cable, unsheathed and connected to common earth and earth dolly complete all as specified and directed by Engr -in -charge for One light point / one bell point controlled by one, one way switch.

70

-

-

... More
All as per Item No.04 above but One fan point controlled by one, one way switch.

30

-

-

... More
All as per Item No.04 above but one light point controlled by 2 way switch.

8

-

-

... More
All as per Item No.04 above but for One 3 pin, 05 /06 Amps socket outlet point on same board controlled by one , one way 05/06 Amps switch

32

-

-

... More
All as per Item No.04 above but for One 3 pin, 05 /06 Amps socket outlet point on independent board controlled by one , one way 05/06 Amps switch

32

-

-

... More
All as per Item No.04 above but capping cassing wiring One Light/fan point controlled by one, one way switch.

30

-

-

... More
All as per Item No.04 above but capping cassing wiring for One 3 pin, 05 /06 Amps socket outlet point on independent board controlled by one , one way 05/06 Amps switch

34

-

-

... More
M & L point wiring with 2.5 sqmm nominal cross sectional area, single core, 1100 Volts grade, stranded, PVC insulated, unsheathed copper conductor cable in and including PVC concealed conduit of 25 mm dia or higher, medium grade complete with and including all PVC conduit accessories/fittings, brass screws, washers etc,including metal flux boxes of suitable size and modular white plate with frame for mounting modular switches, sockets and regulators etc, including all cutting/chases etc in walls and including continuous earth wire of size continuous earth wire of size 2.5 Sqmm nominal cross sectional area, single core, PVC insulated copper conductor cable, unsheathed and connected to common earth and earth dolly complete all as specified and directed by Engr -in -charge for one 15 /16 Amps socket outlet point on independent board.

28

-

-

... More
All as per Item No.11 above but capping cassing wiring for One 3/5 pin, 15 /16 Amps socket outlet point on independent board with 2.5 sqmm cables.

15

-

-

... More
Supply & fixing modular switch 06 Amps 1 module complete all as specified & directed

228

-

-

... More
Supply & fixing modular switch2 way , 06 Amps 1 module complete all as specified & directed

16

-

-

... More
Supply & fixing bell push modular type 6 Amps module complete all as specified & directed.

19

-

-

... More
S & F modular socket 06 Amps 2/3 pin combined 2 module complete all as specified & directed.

98

-

-

... More
Supply & fixing modular switch 1 way 16 Amps 1 module complete all as specified & directed

43

-

-

... More
S & F modular socket 06/16 Amps 2/3 pin combined 2 module complete all as specified & directed.

43

-

-

... More
S & F electronic fan step regulator modular type, 2 module, 120W including complete all as specified and directed.

50

-

-

... More
S & F in repair switch piano flush type, 05/06 Amps single pole, one way 240 volts in replacement of old u/s complete all as specified & directed

40

-

-

... More
Supply & fixing in repair of socket outlet 3 pin, 05/06 Amps (2-in-1 Multipurpose) flush type 240 volts in replacement of old u/s complete all as specified & directed.

41

-

-

... More
Supply & fixing in repair of socket outlet 3 pin, 6 and 16 Amps (2 -in-1 Multipurpose) flush type 240 volts in replacement of old u/s complete all as specified & directed.

41

-

-

... More
Supply & fixing in repair switch piano flush type, 15 /16 Amps single ploe, one way 240 volts in replacement of old u/s complete all as specified & directed

31

-

-

... More
Supply & fixing in repair of ceiling rose surface three terminals in replacement of old u/s complete all as specified & directed.

165

-

-

... More
Supply & fixing in repair bell push flush type 5 Amps in replacement of old u/s complete all as specified & directed.

38

-

-

... More
S & F in repair Door bell AC, 230 volts, single pole in replacement of old u/s bell/ buzzer complete.

31

-

-

... More
Supply & fixing in repair Switch socket combination 2-in-1, 3 pin, 6 and 16 Amp flush type in replacement of old u/s complete.

42

-

-

... More
Supply & fixing in repair Switch socket combination 2-in-1, 3 pin, 6 Amp flush type in replacement of old u/s complete.

42

-

-

... More
S & F in repair electronic fan regulator stepped, socket type 400W including removing the switch board panel and making the provision for fixing the electronic type regulator and refixing the same complete all as specified and directed.

31

-

-

... More
S & F in repair MCB DB SPN 4Way with 200 Amps rated busbar, Double door, flush to wall including all cutting etc on wall and making good the disturbed surfaces to match the existing complete all as specified and directed. Make - L&T/ABB/Legrand/ Schneider/C&S

4

-

-

... More
S & F in repair MCB DB SPN 8Way with 200 Amps rated busbar, Double door, flush to wall including all cutting etc on wall and making good the disturbed surfaces to match the existing complete all as specified and directed. Make - L&T/ABB/Legrand/ Schneider/C&S

3

-

-

... More
S & F in repair MCB DB SPN 12Way with 200 Amps rated busbar, Double door, flush to wall including all cutting etc on wall and making good the disturbed surfaces to match the existing complete all as specified and directed. Make - L&T/ABB /Legrand/Schneider/C&S

3

-

-

... More
S & F in repair MCB DB TPN 4Way, 415 volts Double Door flush to wall including all cutting etc on wall including making good the disturbed surfaces to match the existing in replacement of old U/s complete all as specified and directed. Make - L&T/ABB/ Legrand/ Schneider/C&S

3

-

-

... More
S & F in repair MCCB DB Vertical TPN 8 Way 'A' Frame,Including MCCB TPN 125 Amp Beaking capacity 25Ka -01 nos, Double Door flush to wall including all cutting etc on wall including making good the disturbed surfaces to match the existing in replacement of old U/s complete all as specified and directed. Make - L&T/ABB/Legrand/ Schneider/C&S

2

-

-

... More
M & L for sub main wiring complete with two runs of 2.5 Sqmm single core FRLS grade PVC insulated unsheathed cable 1100Volt grade multistranded copper conductor drawn through and including PVC conduit and accessories surface on wall, roofs etc with one run of PVC insulated solid copper conductor 2.5 Sqmm single core as earth continuity conductor connected with earth dolly and mains complete all as specified and directed.

135

-

-

... More
M & L for sub main wiring complete with four runs of 4 Sqmm single core FRLS grade PVC insulated unsheathed cable 1100Volt grade multistranded copper conductor drawn through and including PVC conduit and accessories surface on wall, roofs etc with one run of PVC insulated solid copper conductor 4 Sqmm single core as earth continuity conductor connected with earth dolly and mains complete all as specified and directed.

130

-

-

... More
M & L for sub main wiring complete with four runs of 10 Sqmm single core FRLS grade PVC insulated unsheathed cable 1100Volt grade multistranded copper conductor drawn through and including PVC conduit and accessories surface on wall, roofs etc with one run of PVC insulated solid copper conductor 10 Sqmm single core as earth continuity conductor connected with earth dolly and mains complete all as specified and directed.

40

-

-

... More
Material and labour for Cutting, chases, pinning in making good to facing where required and pointing in cement mortar 1:3 to ends or edges of landing, steps, chills, sunshades shelves, lintels etc, and cutting chases for concealed water tubing or concealed conduit wiring etc; and making good, cutting not exc 10 cm girth complete all as specified and directed. Stone concrete or slab walls.

18

-

-

... More
S & F in repair MCB SPN 40 Amps, 'C' series, 240 V complete incl making conections all as specified and directed. Make - L&T/ABB/Legrand/Schneider/C&S

24

-

-

... More
S & F in repair MCB SP 6-32 Amps, 'B' series, 240 V complete incl making conections all as specified and directed. Make - L&T/ABB/Legrand/Schneider/C&S

42

-

-

... More
S & F in repair MCB TPN 63 Amps incl B curve making connections all as specified and directed. Make - L&T/ABB/Legrand/Schneider/C&S

16

-

-

... More
S & F in repair MCB TP 63 Amps incl B curve making connections all as specified and directed. Make - L&T/ABB/Legrand/ Schneider/ C&S/Havells

18

-

-

... More
S&F in repair LED PC batten light fitting of 2 feet 10 watt, with energy efficient LED and integrated electronic driver of 10W fitting including connecting up with three core flexible copper conductor upto ceiling rose complete all as specified and directed. Make : Bajaj /CG/Philips/Havells

120

-

-

... More
S&F inverter emergency LED batten 20 W which provides the uninterrupted back up of upto 3hrs during power cut,with guarantee of more lumens with 4 KV surge protection to keep the product safe in any condition ,color temperature 6500 K,brightness 2000 Lm connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed. Make : Bajaj /CG/Philips/Havells

40

-

-

... More
S&F in repair S&F in repair LED PC batten light fitting of 4 feet 20 watt, with energy efficient LED and integrated electronic driver of 20W fitting including connecting up with three core flexible copper conductor upto ceiling rose complete all as specified and directed. Make : Bajaj /CG/Philips/Havells

270

-

-

... More
Supply & Fix in repair linear LED T8 tubular lamp 18W with extruded aluminium/PC body and PC diffuser complete with inbuilt driver incl making necessary connections in the existing fittings to suit the LED tube complete all as specified and directed. (Make : Bajaj /CG/Philips/Havells)

10

-

-

... More
S & F in repair LED fitting of 6 watts - Round surface mounted LED flat panel down light, PDC aluminum housing and PMMA diffuser makes it a robust Luminaire alongwith 6W LED lamp complete all as specified. (Make: Bajaj /CG/Philips/Havells

19

-

-

... More
Supply and fixing new LED lamp 9 watt complete all as specified and directed. (Make : Bajaj /CG/Philips/Havells

20

-

-

... More
Supply and fixing in repair LED lamp 5 watt complete all as specified and directed. (Make : Bajaj /CG/Philips/Havells

42

-

-

... More
S&F in repair energy saving new generation 10W LED IP65 bulkhead luminaire with opal diffuser complete with and incl 10W LED all as specified and directed. (Make : Bajaj /CG/Philips/Havells

10

-

-

... More
Taking down ceiling fan/Exhaust fan, sealing the cable ends dismantling the fan blade kept in safe costody complete all as specified. Note: (a) Servicing and Spares will be measured and paid seperately .

70

-

-

... More
M & L for painting of ceiling fan/ exhaust fan complete, at site with synthetic enamel paint by spraying including filling cavities with filler,one coat after cleaning all dust all as specified.

70

-

-

... More
Hanging only ceiling fan/exhaust fan and connecting up including provision of cable from ceiling rose or connector to fan all as specified ,and any addn/alteration /threading if required to down rod shall be done by contractor with out any extra cost.

70

-

-

... More
Labour for servicing the ceiling / exhaust fan of any make including greasing /oiling /repairs and replacing the spares such as cater pin unserviceable / rusted bolts, split pins, rubber wheel, bearing, washers, bush all as specified and directed .

60

-

-

... More
Supply only GM bush of ISI marked suitable for ceiling fan of size 1200 / 1400mm sweep.

52

-

-

... More
Supply only ball bearing suitable for ceiling fan of 1200 /1400mm sweep. Make : SKF, bearing No 6202 or equivalent in NBC.

46

-

-

... More
Replacement of old unserviceable capacitors 2.5 MFD of the fan in position as directed by Engr - in - Charge

140

-

-

... More
Replacement of old unserviceable capacitors 4.0 MFD of the fan in position as directed by Engr - in - Charge

36

-

-

... More
M & L for dismantling the defective exhaust fan motor by taking out the burnt copper winding, rewinding the motor with super enamelled copper winding wire of existing gauge and weight including replacement of all insulation material, "O" rings and other petty items required for making motor functional and checking the winding leak proof complete all as specified and directed.

30

-

-

... More
M & L for dismantling the defective Ceiling fan motor by taking out the burnt copper winding, rewinding the motor with super enamelled copper winding wire of existing gauge and weight,warnishing , including replacement of all insulation material, and other petty items required for making motor functional and checking the winding leak proof complete all as specified and directed.

60

-

-

... More
M&L for straight through joints (epoxy) heat shrinkable type for UG cable including joint kit and all accessories complete for making joints suitable for LT UG Cable of Aluminium conductor upto 16 Sqmm to 10 sqmm 4 core cable complete all as specified and directed. (Make : 3M /Densons).

4

-

-

... More
All as per ser item no. 61 here-in-before but of size upto 25 to 50 sqmm x 3.5 core complete all as specified and directed. (Make : 3M /Densons).

4

-

-

... More
All as per ser item no. 61 here-in-before but of size upto 70 to 150 sqmm x 3.5 core complete all as specified and directed. (Make : 3M /Densons).

2

-

-

... More
All as per ser item no. 61 here-in-before but of size upto 185 to 300 sqmm x 3.5 core complete all as specified and directed. (Make : 3M /Densons).

2

-

-

... More
All as per ser item no. 61 here-in-before but of size upto 400 sqmm x 3.5 core complete all as specified and directed. (Make : 3M /Densons). Note for ser item nos 61 to 65 : Excavation and earth work shall be measured and paid seperately.

2

-

-

... More
M & L for Fault locating of LT UG cables by using measuring instruments and rectification of the same by using epoxy cable joints of suitable size of cables and testing the phase contuinity of the cable complete all as specified and directed. Note : Cable joint kit and Excavation/earth work shall be measured and paid seperately.

3

-

-

... More
Taking down unsv 400 Amps MCCB and Supply & Fix MCCB TPN 415 Volts 400 Amps rating with breaking capacity of 36 kA with adjustable thermal & magnetic release complete with making all connections as per site requirement as specified and directed. Make - L&T/ABB/Legrand/Schneider/C&S

1

-

-

... More
All as per ser item no.67 here-in-before but MCCB TPN 415 Volts 250 Amps, 36 kA complete with making all connections as specified and directed. Make - L&T/ABB/Legrand/Schneider/C&S

2

-

-

... More
All as per ser item no.67 here-in-before but MCCB TPN 415 Volts 200 Amps, 25 kA complete with making all connections as specified and directed. Make - L&T/ABB/Legrand/Schneider/C&S

2

-

-

... More
All as per ser item no.67 here-in-before but MCCB TPN 415 Volts 160 Amps, 25 kA complete with making all connections as specified and directed. Make - L&T/ABB/Legrand/Schneider/C&S

2

-

-

... More
All as per ser item no.67 here-in-before but MCCB TPN 415 Volts 100 Amps, 16 kA complete with making all connections as specified and directed. (Make : Havells / L&T/ Legrand)

2

-

-

... More
All as per ser item no.67 here-in-before but MCCB TPN 415 Volts 63 Amps, 16 kA complete with making all connections as specified and directed. (Make : Havells / L&T/ Legrand)

4

-

-

... More
Supply and fixing four pole changeover switch disconector with advance neutral 415 volt 50 Hz 100/125 amps in sheet steel enclosure and Conforming to IS / IEC : 60947 - 3 including dismantling old one complete all as directed. Make - L&T/SIEMENS/Legrand/Schneider/CG

2

-

-

... More
Supply and fixing in repair for swich disconnector fuse unit in sheet steel enclosure TPN current rating 200 Amp with HRC Fuse including disconnecting and taking out unserviceable one complete all as directed. Make - L&T/SIEMENS/Legrand/Schneider/CG

1

-

-

... More
Supply and erecting steel tubular pole, swaged, complete with cast iron base plate, finial taper plug, bolts, nuts, washer and screws including painting with two coats of aluminium paint over one coat of red oxide primer on all exposed surfaces and tarring with black bituminous paints to portion embedded in PCC including numbering of poles with two coats of synthetic enamel paints, type 410-SP-22 (8.5 meter long) complete, Including disconnecting and taking out old damage PCC pole all as directed. (Note Excavation & Earth work and PCC foundation/base shall be measured and paid separately under relevant items of this BoQ)

1

-

-

... More
M & L for Cross arms, bracing, supports, clamps and back plate, fabricated from structural steel section including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as directed including two coats of synthetic enamel paint over a coat of red oxide primer, complete all as directed .

0.3

-

-

... More
Dismantling and taking out servicable cross arms, bracings, supports, clamps and back plates from existing poles / dismantled poles / pole structures complete all as directed. Reuse within 50m

0.3

-

-

... More
M & L for painting the surface of post top poles of size 50mm dia and 3 mtr length by applying two coats of synthetic enamel paint complete all as specified and directed by Engr-in-charge.

50

-

-

... More
M & L for Painting of steel pole/PCC pole with cross arms, clamp of any length and shape for LT overhead line with single coat of aluminium paint including preparation of the existing surface including marking pole numbers in a 20 cm dia yellow circle & marking six black & four yellow bends width 15 cm by fluorescent paint, from bottom of pole to 1.5 Mtr height and providng three nos of Red ,Yellow & Blue of reflecting strip of 25 mm width adhesive PVC tape around the pole at suitable height complete all as specified and directed.

60

-

-

... More
Excavation in trenches in soft /loose soil not exceeding 1.5 metre wide and not exceeding 1.5 metre deep for laying of cables etc, getting out and forming bottom surface to required gradient complete.

216

-

-

... More
Excavating in trenches exceeding 1.5 m wide and not exceeding 3 m depth and not less than 1.5 m in depth for laying of cables & foundation of poles , stay assembly and getting out in any type of soil complete all as specified and directed .

0.5

-

-

... More
Returning filling including spreading levelling watering and well ramming to excavated soil in layers not exc 25 cm thick complete all as specified.

118

-

-

... More
Removing excavated material not exc 50m and depositing where directed at a level not exc 1.5m above the starting point in soils complete all as specified.

96

-

-

... More
Supply, laying riddled earth soil conformed IS-1255, cushioning to cables with a layer of riddle earth soil 15cm deep before laying the cable and 8 cm depth after laying of cable, complete all as specified.

83

-

-

... More
Brick protection cover on cable with sub class 'B' brick, laid dry and flat adjacent to each other complete all as specified.

6.4

-

-

... More
M & L for G.I. tubing light grade of size 50mm bore for protection of cables to be laid under roads, crossings/culverts complete all as specified and directed.

36

-

-

... More
Ditto All as per Srl item No 86 here in above but GI pipe of size 80 bore

24

-

-

... More
Taking up underground unservicable cable of any size from existing trench including bricks, etc and removing of materials from work site all as directed by Engr-in-charge.

1060

-

-

... More
Supply, laying, jointing & testing in trenches or passing through pipe, 1100 volts grade, XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured LT electric power under ground cables, heavy duty with aluminium conductor of cross sectional area 240 sqmm 3.5 core with all fixing & connecting accessories such as Alluminium cable lugs, cable gland, nut, bolts, washer etc complete as specified and as directed. Make: Havells/ Polycab/CCI/GLOSTER/RR/ KEI

30

-

-

... More
Ditto All as per Srl item No 89 here in above but size of cable 150 Sqmm 3.5 core

45

-

-

... More
Ditto All as per Srl item No 89 here in above but size of cable 25 Sqmm 4 core

115

-

-

... More
Ditto All as per Srl item No 89 here in above but size of cable 16 Sqmm 4 core

160

-

-

... More
Ditto All as per Srl item No 89 here in above but size of cable 10 Sqmm 4 core

230

-

-

... More
Ditto All as per Srl item No 89 here in above but size of cable 95 Sqmm 3.5 core

110

-

-

... More
Ditto All as per Srl item No 89 here in above but size of cable 50 Sqmm 3.5 core

140

-

-

... More
Laying only cable any sizes obtained from item No 86 of Sch ‘A’ with all fixing & connecting accessories such as Aluminium cable lugs, cable gland, nut, bolts, washer etc complete as specified and as directed

230

-

-

... More
S&F in replacement single pole and neutral enclosure with two pin and earth plug and socket including 1 No. MCB 20 Amp capacity complete all as specified and as directed. Make - HAVELLS/POLYCAB

6

-

-

... More
Supply and fixing in replacement of 1100 Volts grade heavy duty cable 10 Sqmm 2 core with PVC insulated stranded aluminium conductor served with inner sheathing of PVC tape and over all PVC sheathed in service connection suspended by insulated hanger not more than 1 mtr a part including 4mm suspension wire, one twin core cable flat or circular complete all as specified and directed by Engr-in-Charge. Make : Finolex/Plaza/Kalinga/ Paragon

130

-

-

... More
Material and labour for boring of holes under road, pavement hard standing by trenchless technology using ultra sound technique and necessary machine including HDPE pipe upto 150 mm dia suitable for 0.4 mpa working pressure.

6

-

-

... More
M & L for Earthing complete with galvanized iron or steel plate electrode 600 mm x 600 mm x 6.0 mm buried directly in ground vertically in pit of depth not less than 2.25 metre below normal ground level with top edge of the earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides with mixture of charcoal and common salt in alternate layers and electrode connected to galvanized iron strip 32 x 6mm dia as earthing lead by means of GI bolts, nuts, check nuts and washers, earth wire protected by galvanized steel pipe 15 mm bore (light grade) connected to machinery/ equipment all as shown in electrical plate No. 5 of SSR-2009 Part I and including necessary excavation and earth work in any type of soil, 20 mm bore light grade GI pipe for watering funnel wire mesh, PCC (1:3:6), type C-1 chamber, RCC (1:2:4), type B-1, reinforced with 6 mm dia MS round bars @ 15 cm c/c both way for cover and MS frame etc., complete all as specified.

2

-

-

... More
Material & labour for fixing of Earth continuity conductor GI strip of size 25X 4 mm with nut bolts at joints , fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles,equipments or any other indicated situation for loop earthing etc, strip fixed on with epoxy insulatorof suitable size all as specified and directed by Engineer-in-Charge.

15

-

-

... More
Taking down the u/s post top lantern from position by disconnecting the electrical connection carefully and replacement with New generation, post-top of 40 Watts, 240V, energy saving, environmental friendly, long life aesthetically designed with symmetrical light distribution, spun aluminium landscape luminaire with high power LEDs as light source including making all necessary wiring, provn of suitable fitments and connecting upto control box complete all as specified and directed. Make : Bajaj /CG/Philips/Havells

14

-

-

... More
Supply and fix in repair CELESTA LED post top made in cast aluminium with decorative opal polycarbonate di user with IP 65 protection of cap 40 watt complete all as specified and directed. (Make : Bajaj /CG/Philips/Havells

2

-

-

... More
S&F PVC Junction box of size 255X200X100mm inside dimension fixed on pole by means of mild steel clamps with hinged door, bolt and nuts, provn for cable entry for incoming and outgoing including MCB 2.5 amps-1 No and 4 way connector-1nos neccessary connection duly fixed with clamps on pole and including cable glands threaded type IP55/IP65 made of polymide with lock nut complete all as specified. Make : Sintex GSJB2520 or equivalent in POLYCAB/HAVELLS.

28

-

-

... More
M&L for PCC (1:4:8) type D-2 using 40mm graded stone aggregate as in foundations for electric poles, filling and mass concrete complete all as specified and directed.

3

-

-

... More
M & L for PCC (1:3:6) type C-1 using 20mm graded stone aggregate as in coping of the LT poles including form work complete all as specified

2

-

-

... More
Supply and fixing of Endura Citylite Platinum, 35 W Street Light fittingpressure die cast aluminium housing, heat resistance toughened glass, IP-66 protection in replacement of old UNSV 70W HPSV light fittings complete all as specified and directed. (Make : Bajaj /CG/Philips/Havells

16

-

-

... More
Supply and fixing of Endura Cityliner Neo, 70 W LED Street Light fitting pressure die cast aluminium housing, heat resistance toughened glass, IP-66 protection in replacement of old UNSV 150W HPSV light fittings complete all as specified and directed. (Make : Bajaj /CG/Philips/Havells

7

-

-

... More
Supply and fixing LED flood light 120 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp complete all as specified and directed. (Make : Bajaj /CG/Philips/Havells

4

-

-

... More
Taking out the u/s Street light fitting driver and S&F LED Driver unit suitable for 70 to 150 watt capaity complete all as specified and directed. Make - Bajaj /CG/Philips/Havells

2

-

-

... More
Taking out the u/s Street light fitting driver and S&F LED Driver unit suitable for 30 to 45 watt capaity complete all as specified and directed. Make - Bajaj /CG/Philips/Havells

5

-

-

... More
Maintenance for APFC panel Out door/indoor Type APFC panel (out door Type) 100 (8x12.5) KVAR -02No,APFC panel (out door Type) 125 (5x20,2x12.5) KVAR -01No capacitors, internal wiring,inrush current limiting coil, auxilary contactor, indicating lamps, auto-manual selector switch, MCCB ,axial flow fan and replace the unserviceable parts. The following checking will be carried out to ensure smooth and effective operation all the time all as specified and directed. (a) Checking of the control panel,power supply, fuses ,circuits etc and tighten to any loose contact. (b) Checking of the helthiness of capacitors,contactors and APFC relays. (c) Cleaning of the panel by using blower without any distrubance/damages. (Note:- Spares will be measure and paid seperately )

3

-

-

... More
Capacitor (MPP, Heavy duty) 440 volts with inrush current limiting coil, 20 KVAR

3

-

-

... More
Capacitor (MPP,Heavy duty) 440 volts with inrush current limiting coil, 10/12.5 KVAR

1

-

-

... More
Supply and fixing Capaitor duty contactor 25 KVAR

2

-

-

... More
Supply and fixing automatic power factor relay (APFCR) 8 stage complete all as specified and directed.

1

-

-

... More
Supply and fixing capacitor duty contactor 20 KVAR

1

-

-

... More
Supply and fixing capacitor duty contactor 12.5 KVAR

1

-

-

... More
Maintenance of storage type electric water heaters(Geyser) of storage capacity 25 ltrs comprising of the following tasks and all as per specified and directed by Engr-in-Charge. (a) Inspection taking down, opening (dismantling),descaling, brushing cleaning of storage tank and painting internally with one coat of proprietary bituminous compositions not liable to impart taste or or odour or otherwise contaminate the water. (a) Examine water tightness of storage tank after cleaning. (b) Carry out operation of all stop cocks,pressure reducing valves etc to ensure free movement of the working parts. (c) Replacement washers and glands of all taps and ball valves to ensure water tightness. (d) Visual examination of fusible plug to (e) Descaling of the immersion type heating element and cleaning with diluted hydrochloric acid or "clear pedette" solution and testing before refitting. (f) Replacement/repair of neon lamp/indicator lamp. (g) Replacement of the rubber/PVC gaskets to ensure water tightness.. Note : (i) Attending complaint during the currency contract period on phone call and rectification with in 24 Hrs. (ii) The spares will be measured and paid seperately.

25

-

-

... More
All as per Item No-119 above, but of 50 ltrs storage capacity.

9

-

-

... More
Supply only new heating element suitable to existing model and make 2 KW Dual clip type/tri angle type and round type with rubber gasket suitable for geysers up to 25/50 Ltr capacity. Make: Theeta /Elteck or equivalent

45

-

-

... More
Supply only new heating element suitable to existing model and make 1.5 KW Dual clip type/tri angle type and round type with rubber gasket suitable for geysers up to 25/50 Ltr capacity . Make: Theeta /Elteck or equivalent

15

-

-

... More
Supply only thermostat clip type (Range 30 C to 80 C and acting at 70 C) for geysers up to 50 Lts. range 30 C to 80 C and acting at 70 C all as specified . Make: Elcon or eq

34

-

-

... More
Supply only PVC connections up to 600 mm in length suitable to connect GI pipe 15 mm dia to hot water outlet of geyser. Make: Kohinoor or eqivalent

39

-

-

... More
Supply only PVC connections up to 650 mm in length suitable to connect GI pipe 15 mm dia to cold water inlet of geyser. Make: Kohinoor or eqivalent

35

-

-

... More
Supply only pressure release valves suitable for geyser up to 50 ltrs capacity

13

-

-

... More
Supply only indicating lamps green / red suitable for geysers up to 50 Ltrs

30

-

-

... More
Supply only HRFR PVC insulated copper flexible cable 3 core 2.5 Sqmm and PVC sheathed 1100 volts grade

60

-

-

... More
Taking down unserviceable plug top and supply and fixing plug top 3 pin 15 amps 230 volts complete all as specified and directed.

24

-

-

... More
M&L for arresting the leakage in inner tank of any size/make of geyser complete with brazing work and leak test, servicing etc

10

-

-

... More
S& F Non return valve of size 1/2"

15

-

-

... More
Material and labour for painting of storage type electric water heaters(Geyser) of storage capacity 25/50 ltrs painting with one coat of synthetic enamel paint ( as per exsisting colour) all as per specified and directed by Engr-in-Charge.

32

-

-

... More
Supply and fixing in replacement digital type Ampere meter range 0 – 400/300/200 Amps, with built in selector switch including CTs with proper ratio, square type, flush mounted of size 96 mm x 96 mm including making connection with copper conductor cable of suitable size complete all as specified and as directed by Engineer-in-charge. Make- AE/HAVELLS/L&T

4

-

-

... More
Supply and fixing in replacement digital type Volt meter with built in selector switch, range 0 – 500 volts, square type, flush mounted of size 96 mm x 96 mm including making connection with copper conductor cable of suitable size complete all as specified and as directed by Engineer-in-charge. Make- AE/HAVELLS/L&T

5

-

-

... More
S&F Celing Fan complete with blades , down rods ,elcetrinic regulator and acessories , 230 volts, 1200 mm sweep , min air delevery 210 CFM with service value 6.00 BEE five star rated with brushless direct current motor complete all as specified and directed. Make- PHILIPS/HAVELLS/ BAJAJ

21

-

-

... More
Material and labour for Cleaning and preparation of old painted surface of LT panel board complete and painting with one coat of synthetic enamel paint (exsisting colour) on surfaces of panel board all as specified and directed by Engineer-in-Charge.

20

-

-

... More
Supply and fix exhaust fan, steel body AC single Phase. 230V of size 300m sweep with, blades, and frame and louvers complete all as specified and directed. (Make : Bajaj /CG/Philips/Havells

10

-

-

... More
Supply and fix exhaust fan made of sturdy Engineering plastic complete with louvers shutter, voltage 230V, 50 Hz, RPM 1200, Copper winding of 250 mm sweep complete all as specified and directed. (Make : Bajaj /CG/Philips/Havells

10

-

-

... More
Supply and fixing wall fan of single phase 230/240V of size 400 mm sweep and grouting with nut , bolts & Fastenar on the wall and make good the disturbed surface and electric connection with 1.5 Sqmm three core PVC insulated round flexible copper conductor and sheathed cable complete all as specified and directed .

4

-

-

... More
Supply and fix electric water heater,storage type steel body with copper inner tank and heating element upto2 KW capacity 25 litre, BEE 5 Starrated complete with all accessoriessuch as safety valve, thermostate,NRV, connection piece etc. Make- Bajaj/ RACOLD/ USHA/ HAVELLS

6

-

-

... More
Disconnection ,Supply and Fixing Air conditioning Changeover Timer Complete all as specified and directed. Note: (a) Timer should suitable for two Ac load upto 20 A. (b) Timer should available in two modes. (c) In Auto mode gap time 30 Minute, 1hr, 2hr,3 hrs, 4hrs. (d) Din channel mounting for easy installation.

3

-

-

... More
S&F in repair LED Spot light 5 watt Innova Neo Surface mounted spotlight in matt finish for premium aesthetics complete all as specified.

2

-

-

... More
S&F in repair LED bollard in cylindrical shape with opal acrylic di user and IP 66 protection of cap 9 watt including necessary form work/PCC work complete all as specified and directed.

3

-

-

... More
Supply and fixing in repairs 36W LED Fitting, 2 x 2 600 x 600mm recess / Surface PMMA LED flat panel with high brightness LED for glare free homogenous illumination including LED driver complete all as specified including taking down old unserviceable fittings. Make : Bajaj /CG/Philips/Havells

6

-

-

... More
Maintenance for APFC panel Out door/indoor Type APFC panel (In door Type) 150 (6x25) KVAR -01No,APFC panel (In door Type) 200 (6x25,4x12.5) KVAR -01No, APFC panel (In door Type)150 (4x25,4x12.5) KVAR -01No, capacitors, internal wiring,inrush current limiting coil, auxilary contactor, indicating lamps, auto-manual selector switch, MCCB ,axial flow fan and replace the unserviceable parts. The following checking will be carried out to ensure smooth and effective operation all the time all as specified and directed. (a) Checking of the control panel,power supply, fuses ,circuits etc and tighten to any loose contact. (b) Checking of the helthiness of capacitors,contactors and APFC relays. (c) Cleaning of the panel by using blower without any distrubance/damages. (Note:- Spares will be measure and paid seperately )

3

-

-

... More
Capacitor (MPP, Heavy duty) 440 volts with inrush current limiting coil, 5 KVAR

3

-

-

... More
Capacitor (MPP,Heavy duty) 440 volts with inrush current limiting coil, 10 KVAR

2

-

-

... More
Capaitor duty contactor 7 KVAR

3

-

-

... More
Add on Auxiliary contact Block 4 NO

3

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.