Military Engineer Services Tender
Karnataka, also known as Karunadu, is a state in the southwestern region of India. Karnataka was formed originally as Mysore State on 1st November 1956 and currently is the biggest state in south India. Its capital and largest city is Bengaluru. It covers an area of 191,791 km2 (74,051 sq mi) and is the sixth largest state by area comprising 31 districts. Karnataka is also a state of multiple languages; Kannada being the official and most widely spoken language in Karnataka. Other languages spoken in the state include Tamil, Telugu, Malayalam, Kodava, Konkani and much more.Karnataka tenders are issued by the government of Karnataka, public & private sector organisations. The state government issues majority of the Karnataka tenders, which are for goods and services including construction, road and bridge construction, IT services, engineering services, medical services, educational services amongst many others. Bidassist is one of the largest eprocurement portals, which offers all government tenders from across the world in one place. Bidassist offers information on all Karnataka tenders and other state and authority tenders in no time. Bidassist is a platform where users can look for various Karnataka tenders as well as other tenders.
Military Engineer Services - MES Tender
Building Construction
Eprocure
Opening Date21 Nov 2024
Closing Date10 Jan 2025
Tender Amount₹ 11,30,18,000
Costs
EMD
₹ 8,90,500Document Cost
₹ 3,000Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_685021_1Tender No
801640/AF/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Lumpsum price worked out by the contractor for “Internal Water Supply” as listed in Schedule ‘A’ Part–II
1
99180
-
... More
Lumpsum price worked out by the contractor for “Internal Electric Supply" as listed in Schedule ‘A’ Part–III
1
2991769
-
... More
Lumpsum price worked out by the contractor for “Road / Hardstanding ” as listed in Schedule ‘A’ Part – IV.
1
1752033
-
... More
Lumpsum price worked out by the contractor for “Area Drainage" as listed in Schedule ‘A’ Part V .
1
928560
-
... More
Lumpsum price worked out by the contractor for "Sewage Disposal" as listed in Schedule ‘A’ Part VI .
1
388780
-
... More
Lumpsum price worked out by the contractor for “Rain Water Harvesting” as listed in Schedule ‘A’ Part – VII.
1
169869
-
... More
Lumpsum price worked out by the contractor for “External Water Supply” as listed in Schedule ‘A’ Part – VIII.
1
576352
-
... More
Lumpsum price worked out by the contractor for “External Electric Supply” as listed in Schedule ‘A’ Part – IX.
1
1365739
-
... More
Lumpsum price worked out by the contractor for “Air Conditioning / Water Cooler” as listed in Schedule ‘A’ Part – X.
1
290836
-
... More
Lumpsum price worked out by the contractor for “Fire Fighting” as listed in Schedule ‘A’ Part – XI.
1
1608830
-
... More
Lumpsum price worked out by the contractor for “Demolition of Buildings” as listed in Schedule ‘A’ Part – XII.
1
501657
-
... More
Sch 'A' Part - XIII : Fittings, Fixtures & Misc items : INTERNAL WATER SUPPLY
Supply and fix 15mm bore two way bib tap cast copper alloy chromium plated with crutch or butterfly handle, screwed down, screwed to PPR / galvanised iron pipe providing aerated flow of water complete all as specified and as directed.
49
-
-
... More
Supply and fix 15mm bore angle cock cast copper alloy fancy type chromium plated fancy type, screwed down, screwed for PPR pipe complete all as specified and as directed.
82
-
-
... More
INTERNAL ELECTRIC SUPPLY
Supply and fix Reading in bed side light 3/5 watt white with this collection of adjustable LED bedside lights ,220 Volts, Total 150 Lumens,PF 0.95, CRI 80 colour temperature 2700 to 6500K, high voltage protection, easy installation clips for user-friendly installation, AC decorative box type with driver, holder including retrofit LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and as directed.
32
-
-
... More
Supply and fix VTPN distribution boards, Vertical type, protection class IP-43, Double door, 4 Way, suitable for mounting MCCB as incomer and MCB SP, TP as outgoing with min 400 Amps rating bus bar, concealed in wall all as specified and directed by engineer in charge.
2
-
-
... More
Supply and fix Modular TV Socket, one module etc complete in all respect all as specified and as directed by engineer in charge .
2
-
-
... More
Supply and fix Modular Telephone socket, RJ-11, one module etc complete in all respect all as specified and as directed by engineer in charge .
4
-
-
... More
Supply and fix Telephone Wiring with unarmoured Solid annealed bare copper industrial cable in concealed of size 0.5 mm, 3 pair with PVC Conduit 25 mm dia etc complete in all respect all as specified and as directed by engineer in charge .
40
-
-
... More
Supply and fix TV Wiring with unarmoured coaxial cable, RG-11 in concealed with PVC Conduit 25 mm dia etc complete in all respect all as specified and as directed by engineer in charge.
20
-
-
... More
Supply and fix Mild steel Box for Telephone wiring including blocks , Suitable for 35 Pair etc complete in all respect all as specified and as directed by engineer in charge.
1
-
-
... More
ROAD: Material and labour for bituminous premix semi dense asphaltic concrete 40mm consolidated thickness with 5.5% binder content of paving bitumen VG-30 (by weight of total mix) using 6 to 8% waste plastic by weight of bitumen content (only plastic conforming to Low Density Polyethylene (LDPE), High Density Polyethylene (HDPE), PET and Polyurethane conform to the size passing 2.36 mm sieve and retained on 600 micron sieve shall be used) and not to be heated more than 180°C while mixing. Waste plastic mixing should be done using dry process as per para 6.1 of IRC:SP:98-2013. The waste plastic will not be provided by the department and the contractor to refer IRC:SP:98-2013 before quoting the rates. The mix shall be laid with mechanical paver, rolled and compacted to required camber and gradient with 8 to 12 ton power roller and tandem vibratory roller complete all as specified and as directed.
90
-
-
... More
Material and labour for preparing bituminous surfaces of road and applying 2.5mm thick marking strips/lines, dashes, arrows, (retro reflective) of white or yellow colour using hot thermo plastic material by fully/ semi automatic thermoplastic paints applicator machine fitted with profile shoe glass beads dispencer, propan tank heater and profile shoe heater drive by operator on existing/ new road surfaces complete all as specified and as directed. (Note : Glass beads shall not be less than 300 gms per sqm).
32
-
-
... More
EXTERNAL WATER SUPPLY
Material and labour for extension of existing CI/DI pipe of any dia bore/size in position for insertion of 01 No of CI/DI TEE of required size and bore connecting pieces/flanged/socketed/spigoted of suitable bore and making run lead/flanged joint complete all as speciffied and as directed.
1
-
-
... More
Material and labour for Construction of new valve chamber of size 900x900x900mm with foundation cement concrete brick / bricks in cement mortar 1:6 , with PCC 1:4:8 type D2 sub base plaster internally and exposed external surface in cement mortar 1:4 (15 mm thick and provision of valve chamber cover made out of MS sheet 3.0 mm thick welded on angle iron frames 40 x 40 x 5 mm made out of double door type with hinges and locking arrangement duly painted with 2 coats of synthetic enamel paint over a coat of red oxide primer all as directed complete with good finishing.
1
-
-
... More
EXTERNAL ELECTRIC SUPPLY
Material and labour for returning and filling of trenches in two parts:-
(i) using riddled soil obtained from excavated soil up to depth of 30cm (8cm below cable and remaining above cable) for cushioning of cable and (ii) refilling the trench of remaining depth with normal excavated soil all as specified and as directed.
Note: Excavated soil shall be riddled by using sieve to separate composite particles etc as per IS-1255-1983 and refilling in trenches as in cable cushioning
59.54
-
-
... More
Supply, Installing & testing and commissioning factory made and tested (incl CPRI type test certified) LT feeder pillar box (KIOSK) out door type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminium bus bar 400 Amps rating installed on porcelain insulators. The panel shall be dust and vermin proof. IP 65 class protection and made of CRCA MS sheet not less than 1.8x1.2x.5 thick 3.15mm and 50 x 50 x 6 mm thick angle iron frame work, powder coated finish over one coat of red oxide primer out side and two coats of red oxide primer inside, front opening type with aprons for cable entry with double door shutter and locking arrangement (including provn of 65mm Godrej Freedom) lock with 2 keys, internal wiring with PVC insulated solid copper conductor FRLS cable IS 694 marked of adequate size but not less than 4 Sqmm. The scope of work includes the following
1
-
-
... More
(a) INCOMING
(i) MCCB 4 Pole 415 volts grade 250 Amps rating and 35 KA rupturing capacity -01 No
(ii) Voltmeter 0-500 volts, Square 96 mm, flush pattern with 3 way rotary selector switch-01 No
(iii) Ammeter size 96 mm, square dial flush pattern having dual range 500 Amps
(iv) CTs ratio 300/5 class ISI marked set of three each
(v) Indicating lamp - 01 set of three
(b) OUTGOING
(i) MCCB 415 volts grade 125 Amps rating and 35 KA rupturing capacity -02 Nos
(ii) MCCB 415 volts grade 100 Amps rating and 35 KA rupturing capacity -03 Nos
(iii) MCCB 3 Pole, 415 V, fixed type, 40 Amps with breaking capacity 16 KA - 01 No
(Iv) Time Switch (Multi function time switch)
(v) On load switch with enclosure 250 A - 01 No
-
-
-
... More
Supply and fix vertical type VTPN including FP MCCB up to 100 Amps DB, 8 ways, Double door type complete all as specified and as directed
2
-
-
... More
Supply and fix vertical type VTPN including FP MCCB up to 125 Amps DB, 8 ways, Double door type complete all as specified and as directed
2
-
-
... More
Supply and fix bracket suitable for street light, made out of 40 mm dia 1.5 mtr length GI pipe medium grade bend to shape fixed with 40 x 6mm MS flat iron clamp, bolts, nuts and washers incl painting MS clamp with one primer coat and two coat of aluminium paint complete all as specified and directed by Engineer-in-Charge.
22
-
-
... More
Earthing complete with Galvanised steel earth plate electrode 600mmx600mmx6mm thick buried directly in the ground vertically to a depth not less than 3 metre below the ground level with top edge of the earth plate not less than 2.25 metre below the ground level connected to GI earth strip of 32mmx6mm size by means of bolts, nuts and washers protected by GI tubing light grade 40mm dia upto test point and GI watering pipe medium grade20mm dia with funnel and wire mesh, PCC pit in PCC 1:2:4 type B-1 (using 20mm graded crushed stone aggregate) chamber 40mm thick RCC cover slab (1:2:4) type B-1 (using 20mm graded crushed stone aggregate) complete all as specified and shown in electrical plate No. 3 of SSR 2009 Part-I including earth work in any type of soil removal of surplus soil and providing charcoal dust and salt layers all around the earth plate upto 15cm and testing on completion complete all as specified and as directed by Engineer-in-Charge. NOTE: (i) GI pipe of 40 mm dia upto 7.5 mtr length and GI strip of 32X6 mm shall deem to be included in the quoted rate.
12
-
-
... More
DG SET
Supply and installation, commissioning and testing totally enclosed silent operation with canopy, pollution/emission confirming to CPCB-IV+ norms, static type Diesel Engine driven, liquid cooled, Generating set of Turbo Charge Air Cooled 6 in line cylinder of 125KVA/100KW capacity, with Outdoor type AMF Panel, IoT enabled and remote monitoring system, QR Code enabled , 415, 50 Hz 3 Phase 4 wire system, 0.80 lagging P.F & 0.85 load factor with following details specifications
(a) Diesel Engine
Diesel Engine shall be 4 stroke liquid cooled, electric start, of suitable BHP at 1500 RPM confirm to IS 10001/10002 ISO 8528-1 suitable for specified capacity of alternator, turbo charged, Governing class as per ISO 8528 Part V, engine capacity of 10% overload for one hour in every 12 hours of continuous operation, shall have noise limit of 75DB at 1 metre compiled with CPCB-IV+ norms complete engine and alternator mounted on anti vibration pads.
(A1) Air Intake system
(i) Air intake manifold
(ii) Dry type air cleaner
1
-
-
... More
(A2) Exhaust System
(i) Turbocharger system
(ii) Dry Exhaust monifold with Residential silencer and catalytic converted
(A3) Cooling System
(i) Engine water coolant pump
(ii) Radiator with Fan
(iii) Coolant additive concentrate
(A4) Lubricating System
(i) Oil pan
(ii) Engine mounted lubrication oil pump
(iii) Lubrication oil filter
(A5) Starting System
(i) 12/24V DC Starter Motor, Voltage regulators
(ii) 12/24v DC Dynamo for Battery charging
(iii) 12 v suitable maintenance free battery of suitable numbers / capacity
-
-
-
... More
(A6) Engine mounted control Panel
(i) Microprocessor based (preferably) instrument panel with digital display (ii) LED indicating lamps- for Genset running, remote start, shutdown, warning, manual auto and stop
(iii) Controller Data Logs with date and time
(iv) Start/ Stop switch with Key
(v) Indication / Display of for water temp, lub oil pressure, Lub Oil temp, Battery charging, RPM, Over speed, Low lub oil trip, Engine hours, fuel level,, KWH generated, frequency, PF, KW,KVA,volt, Amp.
(vi) Engine and alternator Data - Starting battery voltage, Engine running Hrs, Engine temp, Engine Oil pressure, Alternator Voltage, current, KVA, frequency KWH shall be displayed
(B) Protection to GenSet
(i) Low lube oil pressure warning / shutdown
(ii) High engine temp warning . shutdown
(iii) Low coolant temp warning
(iv) Low/ High battery voltage warning
-
-
-
... More
(C) Alternator
Sycgribiys alternator copper wounded above rated capacity, 415 Volts,1500 RPM, 3 Phase 4 wire system, 50 Hz AC Supply with 0.8 lagging power factor at 50 degree c, 50 % RH and at 1000 m MSL, brushless type, self excited continuous duty self regulated through AVR conforming to IS 4722 with Class F/H insulation as per IS : 13364. The salient feature are as under : (i) Permanent lubricating bearing
(ii) Permissible overloading of 10% for one hours in every 12c Hrs of continuous operation
(iii) Permissible unbalancing capability minimum 25 % per phase
(D) AMF Panel (OURDOOR TYPE 3MM CRCA SHEET)
(i) Digital AMF controller with control relay such as mains failure, relay, under/over voltage protection relay, under.over frequency relay, Reverse power protection relay
(iii) Switch gears such as FP MCCB 200 A - 02 NOS, Power contactor, Fuse
(iii) Metering, Control switches
(iv) Weak battery warning
(v) Fail to start shutdown
(vi) Cranking lockout
-
-
-
... More
(D) Acoustic Enclosure For DG Set
Supply and fixing acoustic enclosures suitable for specified capacity diesel Generator set duly fabricated of channel and CRCA Sheet of required size having doors, insulation sides and top by mineral rock wool confirming to IS -8183 of adequate thickness acoustic louvers/outlet. ventilation system etc. complete as per manufactures instructions with wiring and lighting arrangements duly painted synthetic enameled paint over primer coat or as directed of suitable size all as require at site and comprising of the following:
(i) Base : MS Channel fabricate MS Channel made out of 5 mm thick MS Sheet (ii) Structure heavy duty rectangular MS Box channel
(iii) Door fabricated from MS CRCA Sheet with air tight with neoprene rubber gasket and gun metal heavy duty spring loaded locks.
(iv) Out side cover : Made out CRCA Sheet
(c) Acoustic insulation (side & Top) sound proofing mineral rock wool slat confirming to IS 8183, covered by fire Resistant fiber tissue as per manufacturer recommendation
(vi) Inside cover : CRCA perforated sheet powder coated
(vii) Inspection port : Aluminium frame with double walled glass fixed type sealed with neoprene rubber gasket for viewing instrument panel including earth work etc complete all as directed.
-
-
-
... More
(E) FUELTANK
One No of sheet tank made out of 3.0 mm thick MS Sheet of suitable capacity of hold diesel sufficient for 8 house running at full load or as standard capacity of manufacturer, tank shall be fitted with in canopy as per manufactures' design including the following.
(i) Level indicator to indicate level of diesel in tank
(ii) Drain plug with pipe for drain oil
(iii) Fuel strainer
(iv) Pipe for fuel
(v) Air Vent
(vi) Manually operated one no fuel pump
NOTE : -
(a) Generating set will be placed on suitable foundation as recommended by manufactures and cost thereof shall be included on the prices quoted
(b) Tools shall be supplied with DG Set Unit as per manufacturer's, instructions and cost thereof shall be included in the price quoted
(c) DG Set shall be placed at the site directed by Engr-in- charge
(d) Testing of DG Set shall be done as per relevant clause of Ps
(e) Type tested pollution / notice lever certificate shall be deemed to be included in the rate quoted.
(f) 3 mm thick Rubber mat of size 1mx2m with chequered finish ISI marked suitable for using in electrical installations Confirming with IS15652/2006 (BIS,CPRI, NTH, ERDA approved) with test copy.
-
-
-
... More
Earthing complete with galvanised steel earth plate electrode 60×60cm× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised earth strip 25x4 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion complete all as specified and as directed.
NOTE: (i) GI pipe of 40 mm dia upto 7.5 mtr length and GI strip of 25x4 mm shall deem to be included in the quoted rate.
6
-
-
... More
LIGHTNING PROTECTION
Supply and fix Air termination, single pointed aluminium rod 12mm dia 300mm long extended with GI Pipe 25mm medium grade 1.5 mtr with insulator and PCC pit 1:2:4 B1 for fixing purpose of Air termination rod including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed by Engr-In-Charge.
18
-
-
... More
AIR CONDITIONING
Supply and install inverter type hi wall split AC units indoor & outdoor complete with cordless remote control unit and with Alexa and Hey Google with in built air ioniser and Plasma filter for better indoor air quality with 5 star rating of capacity 2.0 TR, anti freeze thermostat, self diagnosis, 7 in 1 convertible with additional AI mode, 4 way swing, anti microbial self clean tech, blue fin anti corrosive, condenser coil and connected pipe are made of 100% copper, anti dust filter, with zero ozone depletion potential and low global warming potential all as specified and directed by Engr-In-Charge
12
-
-
... More
Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled wall mounted, copper wound with digital display indoor type for AC & designed for input variation between 140 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 3 % and of capacity 5 KVA complete all as specified and directed by Engr-In-Charge
12
-
-
... More
Supply and fix jointing and testing copper tubing with nominal diameter 1/4 inch of suitable thickness for liquid line to connect with outdoor unit complete all as specified and directed by Engr-in-Charge
36
-
-
... More
Supply and fix jointing and testing copper tubing with nominal diameter 3/8 inch of suitable thickness including expanded polythene for external insulation of suction line for connecting with outdoor condensing unit complete all as specified and directed by Engr -in- Charge
36
-
-
... More
Supply and fix PVC non metallic flexible pipe of size of 20mm dia alongwith fixing accessories such as saddles, pip hook etc, for draining out the water from indoor unit complete all as specified and directed by Engr -in- Charge
36
-
-
... More
Material and labour for fabrication of base stand from MS Angle iron of size 50x50x6mm thick including necessary nuts, bolts & washers for mounting of outdoor unit 1.5/2.0 TR capacity split AC complete all as specified and directed by Engr-in-Charge.
12
-
-
... More
FIRE FIGHTING SYSTEM:- Supply and fix hose box for keeping 2 Nos hose pipe of length 15 meter each, branch pipe, nozzle, coupling etc of MS sheet of Thickness 2.0 mm complete all as specified and as directed.
NOTE :-
Each hydrant shall be housed in a Hose cabinet of suitable size. The Hydrant Cabinet shall hold single headed hydrant 2 hoses and one branch pipe as required. Internal hydrants shall normally fit the niche made for it or shall be suitable for wall mounting. The cabinet shall be of minimum 14 SWG M.S. sheet double coated with P.O. Red paint after single coat of Red Oxide primer with center opening glazed doors (clear glass of 4 mm thickness). The glass shall be firmly fixed by means of steel clips and screws with rubber beading. Hinges shall also be screwed and not welded. The corner members (frame) shall be of 25 x 25 x 3 mm thick angle. The hose box shall be firmly fixed to the wall / support by means of brackets and dash fasteners. The steel work shall have one coat of primer and two coats of red paint. The words "Yard Hydrant", "Hydrant' etc., should be painted in white or red on the glass in 75 mm high letters, The Hose Box shall be lockable.
12
-
-
... More
Supply and fix Manual Swing Type for Fire hose reel of 20 mm dia and 30 meter length conforming to IS 5132 Hose real arrangement shall confirm to IS 884 complete all as specified and as directed.
NOTE : Fire Hose Reel consists of 20 mm dia. High pressure rubber hose of 30 mtr. Length with Gun Metal nozzle of 5 mm bore. Rubber Hose is connected with wall mounted circular hose reel of heavy duty Mild Steel construction and Cast Iron brackets. Hose Reel shall conform to IS: 884 -1969. The Hose Reel shall be connected directly to the M.S. pipe riser through an independent connection with 25 mm dia. ball valve.
12
-
-
... More
Supply and fix branch pipe with nozzle of 20 mm dia for hose reel conforming to IS 8090 complete all as specified and as directed.
12
-
-
... More
Supply and fix hose reel of 20 mm size of 30 meter length complete with coupling branch pipe and nozzle, Rubber hose pipe Type I W.P 10.2Kgf/cm2 IS 444 complete all as specified and as directed.
12
-
-
... More
Supply and fix Gun metal fire brigade in let connection for connecting to external fire hydrant ring main consisting of two nos 63mm dia instantaneous type male coupling with built in check valves and 100mm dia, flanged outlet complete with all accessories. a Two way gun metal inlet connection as per IS 904-1983 shall be provided at the Fire Storage Tank for filling of the tank by the fire Brigade, through a 100mm dia. inlet Pipe. The connection will have the option to pressurize the building Fire System (by the Fire Brigade directly) by provision of sluice valves, tee and bend complete all as specified and as directed.
3
-
-
... More
Supply and fix MS cabinet (approx 750mm x 600mm x 450mm) to encl fire brigade inlet connections fabricated from 16 gauge sheet with full front glass door and locking arrangement painted and mounted on masonry platform complete all as specified and as directed.
3
-
-
... More
Supply and Air Cushioning tank (Air Vessel) 250mm dia x 1000mm high with dished top made of minimum 6mm thick MS Pipe / plate complete with 20 mm dia. Brass air valvee (ball type), 20mm dia stop valve, pressure gauge wiht brass stop cock, nipple tees elbows and all accessoried complete all as specified and as directed.
1
-
-
... More
Supply and fix Strainer Y type and Foot Valve conforming to IS, size 80 mm (3”) dia complete all as specified and as directed.
2
-
-
... More
Supply and install Booster pump Terrace Pump is employed of capacity 900 LPM and 35 MWC head. 12.5 HP totally enclosed fan cooled squirrel cage induction motor suitable to operate at 415 ± 5%, 3 Phase, 50 c/s ± 3%, A.C. Supply with combined voltage variation of ± 5% having ‘E’ class insulation suitable for an ambient temperature of 45 Deg Cen. The motor shall be provided by IP – 44 Degree as per IS : 4691. 36 and pressure 3.5 Kg/cm2 at terrace level alongwith Control Panel for motor consisting incomer 4P MCCB 40 A ,Out going 4P MCCB 63 A, DOL Starter, Single Phase Preventor with digital Ammeter & Vol Meter, Indication lamp for RYB and Motor Trip, ON and Push Button for ON/OFF and Over Laod Relay For Over Voltage, Under Voltage, Short Circuit etc complete all as specified and as directed.
2
-
-
... More
Supply and fix Dry Chemical Powdrer (ABC) type fire extinguisher conforming to IS 15683 6 Kg Capacity complete all as specified and as directed.
1
-
-
... More
Supply and fix Light weight squeeze grip type confirming to IS 15683 3 Kg complete all as specified and as directed.
4
-
-
... More
Supply and fix Water type fire Extinguisher confirming IS 15683 6 Kg capacity complete all as specified and as directed.
2
-
-
... More
Supply and fix Dry Chemical Powdrer (ABC) Extinguisher Trolly Mounted cofiriming to IS 16018 25 Kg Capacity complete all as specified and as directed.
1
-
-
... More
Supply and fix CO2 Type Fire Extinguisher Trolley Mounted 22.5 Kg confirming to IS 16018 complete all as specified and as directed.
1
-
-
... More
Supply and fix Fire Buckets stand with 2 Bucket (Dry Sand) confirming IS 2546 complete all as specified and as directed.
1
-
-
... More
Supply, commisioning and testing Electrical Panel Flooding System shall be provided with Co2/Inert gas local flooding system with a cylinder located beside the panel including all pipes, fittings and fixtures confirming to clause No 3.3.6.3 of NBC of India 2016 Part IV complete all as specified and as directed.
1
-
-
... More
Supply and fix Pressure Relief Valve 50mm complete all as specified and as directed.
1
-
-
... More
Supply and fix Fire fighting Unbreakable and sturdy Exit Light Box, Long life and energy efficient, 2D light boxes, safe low voltage LEDs, Easy to install and Ligh weight including MS Conduit suitable size of cable complete all as specified and as directed.
16
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements
Past BiddersThis list is curated from the bidders of the similar tenders in the past
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%