Karnataka, also known as Karunadu, is a state in the southwestern region of India. Karnataka was formed originally as Mysore State on 1st November 1956 and currently is the biggest state in south India. Its capital and largest city is Bengaluru. It covers an area of 191,791 km2 (74,051 sq mi) and is the sixth largest state by area comprising 31 districts. Karnataka is also a state of multiple languages; Kannada being the official and most widely spoken language in Karnataka. Other languages spoken in the state include Tamil, Telugu, Malayalam, Kodava, Konkani and much more.Karnataka tenders are issued by the government of Karnataka, public & private sector organisations. The state government issues majority of the Karnataka tenders, which are for goods and services including construction, road and bridge construction, IT services, engineering services, medical services, educational services amongst many others. Bidassist is one of the largest eprocurement portals, which offers all government tenders from across the world in one place. Bidassist offers information on all Karnataka tenders and other state and authority tenders in no time. Bidassist is a platform where users can look for various Karnataka tenders as well as other tenders.
Military Engineer Services - MES Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date18 Sep 2024
Closing Date16 Oct 2024
Tender Amount₹ 49,99,000
Costs
EMD
₹ 1,00,000Document Cost
₹ 500Tender Fee
Refer Documents
Summary
Special Repair To Strengthening Of Power Supply At Various Locations Provn Of
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_675144_1Bid Award Id
ViewTender No
8967/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
SPECIAL REPAIR TO STRENGTHENING OF POWER SUPPLY AT VARIOUS LOCATIONS PROVN OF STANDBY POWER SUPPLY AND FLAME PROOF LIGHTS AT AFS JALAHALLI AND AFTC
SPECIAL REPAIR TO STRENGTHENING OF POWER SUPPLY AT VARIOUS LOCATIONS PROVN OF STANDBY POWER SUPPLY AND FLAME PROOF LIGHTS AT AFS JALAHALLI AND AFTC
PS SPECIAL REPAIR TO STRENGTHENING OF POWER SUPPLY AT VARIOUS LOCATIONS PROVN OF STANDBY POWER SUPPLY AND FLAME PROOF LIGHTS AT AFS JALAHALLI AND AFTC
GEN CONDI SPECIAL REPAIR TO STRENGTHENING OF POWER SUPPLY AT VARIOUS LOCATIONS PROVN OF STANDBY POWER SUPPLY AND FLAME PROOF LIGHTS AT AFS JALAHALLI AND AFTC
BOQ Items
Excavation in trenches for laying under ground cable, errection of poles and stays etc. in any type of soil not exceeding 1.5 meter wide and not exceeding 1.5 meter deep and getting out complete all as specified and directed.
650.3
-
-
Returning, filling in including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick complete all as specified and directed.
369.72
-
-
Removing surplus excavated material to a distance not exceeding 50 meter and depositing where directed at a level not exc. 1.50 M above the starting point complete all as specified and directed by Engr in charge.
280.58
-
-
Material and labour for Spreading ribbed soil in trenches as in cable cushioning all as per IS 1255-1983, complete all as specified and directed.
Note :- (i) Excavated approved soil shall be ribbed by using sieve to separate composite particles etc. as per IS and refilling in trenches before laying of cable 8 CM and 15 CM after laying of cable. This is then gently punned down to a depth of 10 cm above the top of upper most cable (ii) For the purpose of measurement only punned thickness shall be considered for payment.
232.96
-
-
M & L for Bricks covering with width equal to length of brick as mechanical protection to cable with well burnt sub class ‘B’ bricks laid dry flat complete all as specified and directed.
20.74
-
-
Material and labour for Cutting existing road/PCC/Drain for laying of GI or any type of pipe including necessary earth work, excavation exc 600mm depth but not exc 1mtr depth, 800 mm wide including making good existing surface with 150 mm thick PCC 1:2:4 type B1 using 20mm graded stone aggregate, complete all as specified and directed. Note :- The tenderer shall take into consideration for following points while quoting rate for this item and the unit rate is deemed to be inclusive for :-
(i) Earth work and excavation in any type of soil
(ii) Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cm thick complete all as specified and as directed.
(iii) Removing excavated material to out side MD.
(iv) Laying of any type/any bore of pipe in trenches including taking down. Supply of pipe shall be measured and paid separately (v) 150 mm thick PCC 1:2:4 type B1 using 20mm graded stone aggregate as in road to make good existing disturbed surfaces.
42
-
-
M& L for GI tubing light grade of size 100 mm dia fixed on walls / laid in trenches as protection pipe for under ground cable including provisioning of specials and clamps etc complete all as speified and directed.
Note - Excavation to be paid separately in respective items.
12
-
-
Material and labour for 3 ½ core 185 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed laying in trenches/cable ducts, fixed to wall/pole, complete all as specified and directed. Make:- Havells/ Polycab/ RPG Asian Note - Earthwork and bricks to be paid separately in respective items.
200
-
-
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 100 mm dia suitable for 0.4 mpa working pressure complete all as speified and directed
24
-
-
Material and labour for 3 ½ core 95 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed laying in trenches/cable ducts, fixed to wall/pole, complete all as specified and directed. Make:- Havells/ Polycab/ RPG Asian Note - Earthwork and bricks to be paid separately in respective items.
800
-
-
Supplying, installing ,testing and commisioning of factory made,outdoor type LT cubical panel board,440 Volts,50 Hz,3 phase,4 wire, indoor compartmental type including busbar chamber in centre( vertically) and cable alley either side,outer shell made out of 3.15 mm thick CRCA sheet duly powder coated finishing and completely weather,vermin & dust proof ,adequate air ventilation at sides & back,outer door shall be provided with double door,hinges,self door closing system and FPB locking arrangements,CPRI approved,IP 66 protection etc.,suitable to accomodate the following mentioned fittings,inner shell shall be made out of 2 mm thick CRCA sheet duly powder coated & compartmentalized for each control gear including front openable single door with half knob type locking,taking out incoming and outgoing cables and making connections with suitable chromium plated cable glands and lugs,duly marked with rivetted letter plates of appropriate size for each feeder/block ,danger board etc including necessary PCC (1:3:6) type C-1 using 20 mm graded stone aggregate for foundation extending 300 mm above GL and 60 cm wide platform infront of the panel complete all as specified and directed and comprising of the following :-
INCOMING
(a) Aluminium busbar of capacity 400 Amps with epoxy insulated supports 3 phase and neutral -1 set
(b) MCCB 250 Amps 4 pole 25 KA adjustable type - 01 No (c ) Volt meter digital type 96 x 96 mm with in built selector switch - 01 set
(d) Amps meter digital type 96 x 96 mm with CT's 300/5 -03 Nos and in built selector switch - 01 Set
(e) Indicating lamp RYB LED type - 01 set
OUTGOING
(a) MCCB 160 Amps, 4 Pole 25 KA adjustable type - 04 Nos ( 1 No Spare )
1
-
-
Supply, installation,commissioning and testing of factory assembled ,floor mounted ,free standing type tested LT Feeder pillar panels,with canopy ,as per electrical specifications for outdoor installation to be made of IP65 Polycarbonate modular enclosures. The enclosures made of polycrabonate,should be weather vermin proof, anti -acid,anti-corrossive,UV resistance in accordance with IEC 61439-1,fire retardant and self extingushing in accordance with IEC 60695-2-11 ,UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties ,RoHS compliants & Halogen free. The manufacturer of boards/panels shall submit a copy of type test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tight to base with thermoplastic screw having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosuser should be above 200mm for air circulation & to minimize temp rise. Panel shall be fitted with one No. of polycarbonate IP 65 9 W LED transperent bulk head luminaire 6500K,PF 0.95 under canopy for easy maintenance . Panel should be fitted outside with one No. of 16 Amp 3 Pole IP65 industrial socket and 01 No. of 32 Amp 5P IP 65 industrial socket. 3 Phase and neutral 250 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following swtich gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20mm graded stone aggregate for bedding upto a height of 45 CM above ground level ,including dismanting and taking out old U/s LT panel board and reconnecting existing LT UG Cable with new panel board, complete all as specified and directed :-
1
-
-
(a) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 160 Amp, 25 KA - 01 No. (Incomer). (b) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 40 Amp,10 KA - 07NoS (OG).
(c) Multifunction Meter (V,I,PF) with suitable capacity of CT's - 01 No
(d) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set.
Note :-
(i) The Contractor shall submit the drawing for approval of GE before executing the work. (ii) Insulators, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (iii) Make of Switch gear : Schneider/L&T/C&S.
(iv) MCCB should be ICu =100% ICs.
(v) Make of LT Panel/FPB shall be as mentioned in list of makes (PS).
-
-
-
Material and labour for Plain cement concrete 1:4:8 type D-2 using 40 mm graded stone aggregate as in foundation filling and mass concrete complete all as specified and as directed.
1.5
-
-
Material and labour for PCC 1:3:6 type C1 using 20 mm graded stone aggregate for stay and coping for poles including necessary form work to exposed surfaces finished smooth and even all as specified and as directed.
4.5
-
-
Supply & Erecting of Mild steel tubular swaged poles of 9.0 meter long 410, SP-31 complete with cast iron base plate, bracket, finial taper plug, bolt, nuts & screws and painted on both side (internally & externally), external surface painted with two coat of aluminum paint over a coat of red oxide primer and painting with black up to 1.5 meter from top of PCC coping white colour paint as in strips of equal width including marking pole numbers with one coat of synthetic enamel paint including taking down old U/S poles of any description complete all as specified and as directed.
10
-
-
Supply and fix street light fitting bracket made out of 40 mm bore GI pipe, light grade, tubing bent to shape, 1.2 metre long, fixed to pole/wall with and including two sets of clamps made out of flat iron of size 25 x 6 mm with bolts, nuts and washers, complete, all as specified and directed.
10
-
-
Supply and fix weather proof PVC junction box approved by CPRI street light control box made out of not less than 2mm thick of size 250mm x 200 mm x 105mm (approx) complete with hinged door locking arrangement and consisting of 2 Nos of suitable size cable glands consisting of 01 No. panel mounted connector 4 pole MCB 6A 10KA 01No, including connecting up with the electrical connections and fixing and clamping complete all as specified and as directed.
45
-
-
Supply and fix of LED street light fittings 70 watts pressure die cast aluminium housing with toughened glass and high power LEDs with option of secondary optic with IP-66 ingress protection with 4/5KV surge protection device, Manufacturers logo embossed on the housing for traceability (stickering/ printing not acceptable), system level efficacy of the luminarie is 110lm/W at L70. The color temparature is arround 6500K with a color rendering index of 70. The luminaire if IP:66 protected with impact rasistence IK05 impact resistance, electronic driver compliant to IEC safety standards with power factor is greater than 0.9, voltage variation range 120-270V, THD less than 20%, high and LED with individual peanut lens and lena plate for better optics. The product should be tested for IEC60598 safety standards, LM80 report for LED, entire product one complete all as specified and directed. Make : Philips/Bajaj/CG/Halonix
10
-
-
Supply and laying 1.5 Sq.mm (nominal area) PVC unsheathed multi strandard copper conductor PVC insulated 1100 volt FRLSH grade three core cable drawn through PVC Pipe not less than 20 mm dia for connecting the street light fittings including aluminium clamp complete all as specified and as directed.
200
-
-
Supply, installation, testing and commissioning LT Feeder pillar box CPRI Tested of Size 800x600X450 mm suitable for 3 phase 415 Volts of suitable size out door made out of 3.15mm thick CRCA sheet of outdoor of panel with angle iron frame of size 50x50x6mm cubical type complete with aluminium bus bar 600 Amp and including PCC foundation as per site requirement to accomodate the following:-
INCOMING
(a) MCCB 4 pole 320 Amp 36 KA - 01 No. (b) LED indicating lamp R-Y-B - 03 Nos.
(c) Multifunction Meter (V,I,PF) with suitable capacity of CT's - 01 No OUTGOING
(a) Through Bus Bar
Note :- 1. Make of Switch gear : Schneider/L&T/C&S. 2.MCCB should be ICU = 100 % ICS 3. Bus Bar Make Should be Hindalco Alumina.
1
-
-
Supply and fix Time light DB 110 Amp 3 pole with incoming MCCB 100 Amp 4 pole ,16 KA , 115 Amps AC 3 pole duty contactor ,analog timer 1 module 24 hours program, programmable every 15 minutes and selector switch complete with encloser along with fixing arrangement including taking down old unserviceable one , complete all as specified and directed. Make : Indo Asian/ L&T/Legrand
2
-
-
Supply, installation, commissioning and testing of factory assembled, floor mounted, free standing type tested LT Feeder pillar panels, with canopy, as per electrical specifications for outdoor installation to be made of IP65 Polycarbonate modular enclosures. The enclosures made of polycarbonate, should be weather/vermin proof, anti -acid, anti-corrossive, UV resistance in accordance with IEC 61439-1, fire retardant and self extingushing in accordance with IEC 60695-2-11, UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties, RoHS compilaints & Halogen free. The manufacturer of boards/panels shall submit a copy of type test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tightened to base with thermoplastic screws having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosure shall be above 200mm for air circulation & to minimize temp rise. Panel shall be fitted with one No polycarbonate IP 65, 9 W LED translucent bulk head luminaire color lamp not less than 6500K, PF 0.95 under canopy for easy maintenance. Panel should be fitted outside with one No. of 16 Amp 3 Pole IP65 industrial socket and 01 No of 32 Amp 5P IP 65 industrial socket. 3 Phase and neutral 150 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following swtich gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20 mm graded aggregate for bedding upto a height of 45 CM above ground level, including dismanting and taking out old U/s LT panel board of any size and description, reconnecting existing LT UG Cable with new panel board, complete all as specified and as directed :-
1
-
-
(a) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 100 Amp, 25 KA - 01 No. (Incomer). (b) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 40 Amp,10 KA - 04Nos
(c) MCB SPN of 240 V of capacity 40 Amps 10 KA - 01No.
(d) Multifunction Meter (V,I,PF) with suitable capacity of CT's - 01 No.
(e) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set
(f) Space for spare feeder - 01 No. Note :-
(i) The Contractor shall submit the drawing for approval of GE before executing the work. (ii) Insulators, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (iii) Make of Switch gear : Schneider/L&T/C&S.
(iv) MCCB should be ICu =100% ICs.
(v) Make of LT Panel/FPB shall be as mentioned in list of makes (PS).
-
-
-
Material and labour for 4 core 25 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed laying in trenches/cable ducts, fixed to wall/pole, complete all as specified and directed. Make:- Havells/ Polycab/ RPG Asian Note - Earthwork and bricks to be paid separately in respective items.
450
-
-
Material and labour for 4 core 16 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed laying in trenches/cable ducts, fixed to wall/pole, complete all as specified and directed. Make:- Havells/ Polycab/ RPG Asian Note - Earthwork and bricks to be paid separately in respective items.
1000
-
-
M& L for GI tubing light grade of size 80 mm dia fixed on walls / laid in trenches as protection pipe for under ground cable including provisioning of specials and clamps etc complete all as speified and directed.
Note - Excavation to be paid separately in respective items.
18
-
-
Supplying, installing ,testing and commisioning of factory made,outdoor type LT cubical panel board,440 Volts,50 Hz,3 phase,4 wire, indoor compartmental type including busbar chamber in centre( vertically) and cable alley either side,outer shell made out of 3.15 mm thick CRCA sheet duly powder coated finishing and completely weather,vermin & dust proof ,adequate air ventilation at sides & back,outer door shall be provided with double door,hinges,self door closing system and FPB locking arrangements,CPRI approved,IP 66 protection etc.,suitable to accomodate the following mentioned fittings,inner shell shall be made out of 2 mm thick CRCA sheet duly powder coated & compartmentalized for each control gear including front openable single door with half knob type locking,taking out incoming and outgoing cables and making connections with suitable chromium plated cable glands and lugs,duly marked with rivetted letter plates of appropriate size for each feeder/block ,danger board etc including necessary PCC (1:3:6) type C-1 using 20 mm graded stone aggregate for foundation extending 300 mm above GL and 60 cm wide platform infront of the panel complete all as specified and directed and comprising the following :-
(a) On load change over switch 4P,440V,200 Amps - 03 Nos
(b ) Volt meter digital type 96 x 96 mm with in built selector switch - 01 set
(c) Amps meter digital type 96 x 96 mm with CT's 200/5 -03 Nos and in built selector switch - 01 Set
(d) Indicating lamp RYB LED type - 01 set
1
-
-
M&L for point wiring using approved colour coding as per IS for one flame proof light point controlled by one flame proof switch with PVC insulated, unsheathed FRLS multi stranded copper conductor 2.5 Sqmm (nominal area) 1100 volt grade cable for phase & neutral drawn in and including ERW steel conduit (25mm) with and including new MS/ cast iron sunken boxes duly painted with two coats of anticorrosive paint over a coat of red oxide primer on surface in touch with wall and synthetic enamel paint over a coat of red oxide on other side, PVC unsheathed FRLS multi stranded copper conductor 2.5 Sqmm (nominal area) insulated, unsheathed, multi stranded FRLS cable as earth wire and connected to earth dolly, complete all as specified and as directed.
6
-
-
S & F LED tube light fitting flameproof type suitable for single tube 20 W LED integral built in control box made of aluminium alloy LM6 , IP65 with all accessories, complete all as specified and as directed. Make- Bajaj/Sudhir/ Shyam Switchgear/Baliga
6
-
-
S&F factory made powder coated distribution board SPN 8 way double door, including bus bar, Neutral bar, standard DIN rail, earth bar complete all as specified and conforming to IS: 8623, Make : Legrand/ L&T/ Indo Asian
1
-
-
S&F SP MCB 6-32 Amp, 240 v, 50 Hz AC suitable for ‘C’ curve, 10 KA breaking capacity conforming to IS 8828 of 1996, all as specified and directed. Make : Legrand/ L&T/ Indo Asian
6
-
-
S&F SPN MCB 32 Amp, 240 v, 50 Hz AC suitable for ‘C’ curve, 10 KA breaking capacity conforming to IS 8828 of 1996, all as specified and directed. Make : Legrand/ L&T/ Indo Asian
1
-
-
M&L for Sub main wiring with PVC insulated unsheathed FRLS cable 1100 volts grade multi stranded copper conductor cable 2 runs of 4 Sqmm drawn through in and incl suitable size PVC casing capping and all accessories fixed to wall/floors along with 4 Sqmm PVC insulated unsheathed copper conductor multi stranded cable 1100V grade as earth continuity conductor and connected to common earth dolly complete all as specified and directed.
Note: (a) 2 runs of 4 Sqmm cable along with one run of 4 Sqmm cable for earth conductor shall be measured as one length.
Make:- Havells/ Polycab/ Plaza.
6
-
-
Supply, installation, testing and commissioning LT Feeder pillar box CPRI Tested of Size 800x600X450 mm suitable for 3 phase 415 Volts of suitable size out door made out of 3.15mm thick CRCA sheet of outdoor of panel with angle iron frame of size 50x50x6mm cubical type complete with aluminium bus bar 400Amp and including PCC foundation as per site requirement to accomodate the following:-
INCOMING
(a) MCCB 4 pole 125 Amp 25 KA - 01 No. (b) LED indicating lamp R-Y-B - 03 Nos.
(c) Multifunction Meter (V,I,PF) with suitable capacity of CT's - 01 No OUTGOING
(a) Through Bus Bar
Note :- 1. Make of Switch gear : Schneider/L&T/C&S. 2.MCCB should be ICU = 100 % ICS 3. Bus Bar Make should be Hindalco Alumina.
2
-
-
Supply, installation, testing & commissioning of maintenance free chemical earthing system comprising of 17mm dia copper bonded rod 3 mtr long horizontally pre welded T-terminal rod with provision for connection size of 50 x 150mm long, 6mm thickness with equal space either side, with 12mm dia hole of 02 numbers each on either side of the terminal clamp with 250 microns (average) coating thickness, tested and certified by CPRI India alongwith 50 Kg earth energizer compound and 10 litres earth resistance reducing liquid. The earthing energizer compound and resistance reducing earthing liquid shall be tested as per IEC-62561-7 read with ASTM G57-06, CI 3.4 A by any NABL accredited lab. The above mentioned rod shall be installed in 4-6 inch bore, 12 feet depth with a distance of minimum 3 meters between each installation including taking down existing one, complete all as specified and directed.
Make : Model HTSP 317 of safeTrode or equivalent in OBO Betterman/ FURSE/ERICO.
30
-
-
The quoted rate shall also deemed to be included the following :- (i) Prior to installation of maintenance free chemical earthing, soil resistivity test to be carried out at the location where earthing work to be done in presence of Engr-in- Charge/JE (E/M),user and the report has to submit to Garrison Engineer with recommendation of manufacturer, if required additional interconnection of earthing (not more than 08 number of earthing) to achive earth result less then 1 Ohms. The arrangement done for soil resistivity testing and submission of report with recommendation deemed to be included in the quoted rate.
-
-
-
(ii) The description/ size/ qty of items mentioned in above are for indicating only however qty/ size may vary at site condition to maintain the earth resistance 1 ohm. The contractor shall quote rate by considering all factors.
-
-
-
(iii) Rate of earth energizer compound of 25 Kg of 02 bags and earth resistance reducing liquid 10 litre per cane for each pit deemed to be included in the quoted rate.
-
-
-
(iv) Resistivity of earth energizer compound and resistance reducing earthing liquid shall be certified by any NABL accredited lab carried out as per IEC-62561-7 read with ASTMG57-06, CI-3.4A and the certificate of same shall be submitted by the contractor before commencement of work.
-
-
-
(v) Earth enhancing material should not leach into the adjacent soil or underground water channels and its PH value should be in neutral range complete all as specified and as directed. It should solidify when mixed with water and set like concrete.
-
-
-
(vi) Copper strip of size 20 x 3 mm shall be fixed on proper post insulator at the instrument end ( copper strip upto 7.5 RM shall be considered in unit quoted rate and extra will be measured and paid separately).
-
-
-
(vii) Testing of earth shall be carried out in presence of departmental and user representative and report shall be submitted to Garrison Engineer duly signed by all concerned.
-
-
-
(viii) Earth resistance tester will be provided by the contractor. Tester should be calibrated from authorised company/ lab.
-
-
-
(ix) Earthing shall be tested after completion of work by the contractor in presence of Engr-in-charge, user and proper record shall be maintained duly signed by all concerned. After testing if the desired earth resistance of less than 1 Ohm is not obtained, the earthing will be redone at no extra cost to Govt. till desired result is obtained.
-
-
-
(x) The contractor shall give a written guarantee of minimum three years for maintaining the earth resistance less than 1 Ohm after certified date of completion.
-
-
-
(xi) No further maintenance or periodic watering or recharge shall be required in earthing during its guarantee period of over 03 years in all type of soil including soft/ disintegrated or hard rock.
-
-
-
(xii) During the guarantee period, if earth resistance is not maintained less than 1 ohm the contractor has to redo or rectify at no extra cost to Govt till desired result is maintained.
-
-
-
(xiii) A security deposit of value equal to 2.5 % of the rate quoted for chemical earthing for each earthing shall be retained from payment due to the contractor from final bill for the guarantee period.
-
-
-
(xiv) The electrode shall carry manufacturer's name .
-
-
-
(xv) The connection clamp shall be permanentlly welded to the copper bounded rod to avoid any kind of connectivity loss,.The pre-welded copper bounded rod shall not need any additional clamp for termination.
-
-
-
(xvi) The acceptable earth resistance at earth busbar/ test point shall not be more than 0.1 ohm.
-
-
-
(xvii) Earth work such as auguring and making good the surrounding area shall carried out in any type of soil.
-
-
-
(xviii) The contractor shall submit CPRI India certified document for copper bounded rod to ensure genuineness of material.
-
-
-
(xix) Sign board of mild steel sheet 2 mm thick duly painted with two coats of synthetic enamel paint over a coat of red oxide Zinc chrome primer showing result of earthing shall be fixed near the earth pit after completion as directed by engr -in- charge.
-
-
-
Earth pit cover made of heavy duty poly plastic of high grade polypropylene tested and certified by any NABL accredited lab for load bearing capacity not less than 7.2 tonnes with top dia not less than 250mm, bottom dia not less than 330 mm and height not less than 260 mm for each electrode pit, complete including taking down, old U/S pit cover complete all as specified and directed.
Make : Model SEPC 250 of SAFE TRODE/ Electrogrip Model/ EGTEK3LC of ISG Global or equivalent in OBO Betterman/ ERICO.
Note :- The contractor shall submit load bearing capacity certificate from the manufacturer.
30
-
-
Material and labour as for Earth pit indicator for existing earthing pit made out of 16 mm dia and 60 cm long MS Square Bar embeded in PCC (1:3:6) type C-1 using 20 mm graded stone aggregate in PCC block of size 30 X30 X30 cm including CI/MS plate of size 250X300X 3 mm thick fixed on side of earth pit cover complete painting and writing over the plate ie. Type , Result, Date of measurement and pit number with Black backround with white complete all as specified and as directed.
2
-
-
S&F Copper strip 20 x 3mm thick (99.99% molecularly copper) as earthing lead fixed to wall/roofs etc including taking down existing one all as directed. NOTE : All Joints should be joined by Exothermic Welding or Brazing.
35
-
-
Supply, installation, commissioning and testing of factory assembled, floor mounted, free standing type tested LT Feeder pillar panels, with canopy, as per electrical specifications for outdoor installation to be made of IP65 Polycarbonate modular enclosures. The enclosures made of polycarbonate, should be weather/vermin proof, anti -acid, anti-corrossive, UV resistance in accordance with IEC 61439-1, fire retardant and self extingushing in accordance with IEC 60695-2-11, UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties, RoHS compilaints & Halogen free. The manufacturer of boards/panels shall submit a copy of type test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tightened to base with thermoplastic screws having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosure shall be above 200mm for air circulation & to minimize temp rise. Panel shall be fitted with one No polycarbonate IP 65, 9 W LED translucent bulk head luminaire color lamp not less than 6500K, PF 0.95 under canopy for easy maintenance. Panel should be fitted outside with one No. of 16 Amp 3 Pole IP65 industrial socket and 01 No of 32 Amp 5P IP 65 industrial socket. 3 Phase and neutral 400 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following swtich gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20 mm graded stone aggregate for bedding upto a height of 45 CM above ground level, including dismanting and taking out old U/s LT panel board of any size and description, reconnecting existing LT UG Cable with new panel board, complete all as specified and as directed :-
1
-
-
(a) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 250 Amp, 36 KA - 01 No. (Incomer). (b) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 200 Amp,25 KA - 01No.
(c) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 125 Amp,25 KA - 02 Nos.
(d) Multifunction Meter (V,I,PF) with suitable capacity of CT's - 01 No
(e) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set.
(f) Space for spare feeder - 01 No. Note :-
(i) The Contractor shall submit the drawing for approval of GE before executing the work. (ii) Insulators, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (iii) Make of Switch gear : Schneider/L&T/C&S.
(iv) MCCB should be ICu =100% ICs.
(v) Make of LT Panel/FPB shall be as mentioned in list of makes (PS).
-
-
-
Material and labour for 4 core 10 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed laying in trenches/cable ducts, fixed to wall/pole, complete all as specified and directed. Make:- Havells/ Polycab/ RPG Asian Note - Earthwork and bricks to be paid separately in respective items.
850
-
-
Supply, laying, jointing & testing, XLPE insulated, armoured, heavy duty electric LT UG cable with multi stranded aluminium conductor, 1100 volts grade laid in trenches or in duct/passed through pipes or fixed to wall/poles etc cross sectional area of size 70 sqmm 3.5 core complete all as specified and directed.
81
-
-
M& L for GI tubing light grade of size 50 mm dia fixed on walls / laid in trenches as protection pipe for under ground cable including provisioning of specials and clamps etc complete all as speified and directed.
Note - Excavation to be paid separately in respective items.
22
-
-
M & L for UG cable route indicator made out of 100 mm dia MS plate with 20 mm dia 50cm long MS bar as legs for writing LT and name of feeder fixing with and including necessary PCC 1:2:4 type B-1 using 20 mm graded stone aggregate in grouting route indicator complete all as specified and directed.
32
-
-
Supply and fixing MCCB 4P 250 Amps, 36 KA breaking capacity, adjustable thermal and magnetic range,415 V, 50 Hz AC supply including making all connections complete all as specified . Note :- Make:Indo Asian/ Legrand / L&T.
1
-
-
Supply, installation, testing and commissioning LT Feeder pillar box CPRI Tested of Size 800x600X450 mm suitable for 3 phase 415 Volts of suitable size out of door made out 3.15mm thick CRCA sheet of outdoor of panel with angle iron frame of size 50x50x6mm cubical type complete with aluminium bus bar 600 Amp and including PCC foundation as per site requirement to accomodate the following:-
INCOMING
(a) MCCB 4 pole 160 Amp 25 KA - 01 No. (b) LED indicating lamp R-Y-B - 03 Nos.
(c) Multifunction Meter (V,I,PF) with suitable capacity of CT's - 01 No OUTGOING
(a) Through Bus Bar
Note :- 1. Make of Switch gear : Schneider/L&T/C&S. 2.MCCB should be ICU = 100 % ICS 3. Bus Bar Make Should be Hindalco Alumina.
1
-
-
Supply, installation, commissioning and testing of factory assembled, floor mounted, free standing type tested LT Feeder pillar panels, with canopy, as per electrical specifications for outdoor installation to be made of IP65 Polycarbonate modular enclosures. The enclosures made of polycarbonate, should be weather/vermin proof, anti -acid, anti-corrossive, UV resistance in accordance with IEC 61439-1, fire retardant and self extingushing in accordance with IEC 60695-2-11, UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties, RoHS compilaints & Halogen free. The manufacturer of boards/panels shall submit a copy of type test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tightened to base with thermoplastic screws having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosure shall be above 200mm for air circulation & to minimize temp rise. Panel shall be fitted with one No polycarbonate IP 65, 9 W LED translucent bulk head luminaire color lamp not less than 6500K, PF 0.95 under canopy for easy maintenance. Panel should be fitted outside with one No. of 16 Amp 3 Pole IP65 industrial socket and 01 No of 32 Amp 5P IP 65 industrial socket. 3 Phase and neutral 400 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following swtich gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20 mm graded aggregate for bedding upto a height of 45 CM above ground level, including dismanting and taking out old U/s LT panel board of any size and description, reconnecting existing LT UG Cable with new panel board, complete all as specified and as directed :-
1
-
-
(a) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 250 Amp, 36 KA - 01 No. (Incomer). (b) Change over switch 250 Amp, 4P front operated-01 No.
(c) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 125 Amp, 25 KA - 02 Nos (O/G).
(d) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 63 Amp, 10 KA - 01 No (O/G)
(e) MCB TPN of 415 V of capacity 40 Amps 10 KA - 01 No.
(f) Multifunction Meter (V,I,PF) with suitable capacity of CT's - 01 No.
(g) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set
(h) Space for spare feeder - 01 No. Note :-
(i) The Contractor shall submit the drawing for approval of GE before executing the work. (ii) Insulators, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (iii) Make of Switch gear : Schneider/L&T/C&S.
(iv) MCCB should be ICu =100% ICs.
(v) Make of LT Panel/FPB shall be as mentioned in list of makes (PS).
Note :- An amount of Rs 119490.00 on account of credit schedule for schedule 'A' part II shall be deducted from the total amount of BOQ to arrive at the contract sum.
-
-
-