Military Engineer Services Tender
Karnataka, also known as Karunadu, is a state in the southwestern region of India. Karnataka was formed originally as Mysore State on 1st November 1956 and currently is the biggest state in south India. Its capital and largest city is Bengaluru. It covers an area of 191,791 km2 (74,051 sq mi) and is the sixth largest state by area comprising 31 districts. Karnataka is also a state of multiple languages; Kannada being the official and most widely spoken language in Karnataka. Other languages spoken in the state include Tamil, Telugu, Malayalam, Kodava, Konkani and much more.Karnataka tenders are issued by the government of Karnataka, public & private sector organisations. The state government issues majority of the Karnataka tenders, which are for goods and services including construction, road and bridge construction, IT services, engineering services, medical services, educational services amongst many others. Bidassist is one of the largest eprocurement portals, which offers all government tenders from across the world in one place. Bidassist offers information on all Karnataka tenders and other state and authority tenders in no time. Bidassist is a platform where users can look for various Karnataka tenders as well as other tenders.
Military Engineer Services - MES Tender
Security and Emergency Services
Eprocure
Opening Date25 Nov 2024
Closing Date16 Dec 2024
Tender Amount₹ 49,99,000
Costs
EMD
₹ 1,00,000Document Cost
₹ 500Tender Fee
Refer Documents
Summary
Comprehensive Repair/maint Of Fire Fighting Fire Alarm System Lift Servo Voltage Stabilizer
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_684486_1Bid Award Id
ViewTender No
8979/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
COMPREHENSIVE REPAIR/MAINT OF FIRE FIGHTING FIRE ALARM SYSTEM LIFT SERVO VOLTAGE STABILIZERS FOR BALANCED UNBALANCED LOAD APFC PANEL SECURITY PERIMETER LIGHTS AND OTHER MISC EM WORKS AT AFTC 2DC AREA AND AFS JALAHALLI
COMPREHENSIVE REPAIR/MAINT OF FIRE FIGHTING FIRE ALARM SYSTEM LIFT SERVO VOLTAGE STABILIZERS FOR BALANCED UNBALANCED LOAD APFC PANEL SECURITY PERIMETER LIGHTS AND OTHER MISC EM WORKS AT AFTC 2DC AREA AND AFS JALAHALLI
PS COMPREHENSIVE REPAIR/MAINT OF FIRE FIGHTING FIRE ALARM SYSTEM LIFT SERVO VOLTAGE STABILIZERS FOR BALANCED UNBALANCED LOAD APFC PANEL SECURITY PERIMETER LIGHTS AND OTHER MISC EM WORKS AT AFTC 2DC AREA AND AFS JALAHALLI
GEN CONDI COMPREHENSIVE REPAIR/MAINT OF FIRE FIGHTING FIRE ALARM SYSTEM LIFT SERVO VOLTAGE STABILIZERS FOR BALANCED UNBALANCED LOAD APFC PANEL SECURITY PERIMETER LIGHTS AND OTHER MISC EM WORKS AT AFTC 2DC AREA AND AFS JALAHALLI
BOQ Items
... More
Comprehensive maintenance passengers lift to carry 08 passengers (554 Kg) capacity of Make: Schindler to serve ground floor plus two floors, including Examining the operation, adjusting, lubricating and repairs as required to machine motor, controller parts, safety devices, governors, repair/replacement as required to alarm bell, indicators, emergency light, emergency components, including low voltage protection relay, call bell, etc complete all as specified and directed.. Location : SMC - 01 No
Note: (a) The contractor shall make AMC contract with the original manufacturer of lift and the repairs/maintenance shall be carried out through the original manufacturers only. (b) Cost of labour element towards removing of unserviceable spare parts and re-fixing of serviceable spare parts for supply only items here-in-after shall be deemed to be included in quoted rate. Supply only spare parts shall be measured and paid separately.
9
-
-
... More
Supply only transformer as per existing model suitable to 08 passenger Lift Makes Schindler India Pvt Ltd / Johnson all as specified and directed.
1
-
-
... More
Supply only transformer as per existing model suitable to 13 passenger Lift Makes Schindler India Pvt Ltd all as specified and directed.
1
-
-
... More
Supply only shaft information switch as per existing model suitable to 8/13 passenger Lift Makes Schindler India Pvt Ltd all as specified and directed.
1
-
-
... More
Supply only shaft information card as per existing model suitable to 8/13 passenger Lift Makes Schindler India Pvt Ltd all as specified and directed.
1
-
-
... More
Supply only travelling cable as per existing model and size suitable to 08/13 passenger Lift Makes Schindler India Pvt Ltd all as specified and directed.
100
-
-
... More
Dismantling the existing unserviceable hoisting motor upto 10 HP capacity 3 phase, 440 volts from site and carrying out rewinding, changing bearing and all connected parts etc. including transporting the motor to the workshop and back and fixing to its original position all as specified and directed.
1
-
-
... More
Supply only main contactors as per existing model suitable to 13 passenger Lift Makes Schindler India Pvt Ltd all as specified and directed..
1
-
-
... More
Supply only for main contactors as per existing model suitable to 08 passenger Lift Makes Schindler India Pvt Ltd/ Johnson all as specified and directed..
1
-
-
... More
Supply only Relays as per existing model suitable to 13 passenger Lift Makes Schindler India Pvt Ltd all as specified and directed.
1
-
-
... More
Supply only Relays as per existing model suitable to 08 passenger Lift Makes Schindler India Pvt Ltd/ Johnson all as specified and directed.
2
-
-
... More
Supply only Landing Floor indicators as per existing model suitable to 8/13 passenger Lift Makes Schindler India Pvt Ltd all as specified and directed.
1
-
-
... More
Supply only door contact switch as per existing model suitable to 13 passenger Lift Makes Schindler India Pvt Ltd all as specified and directed.
1
-
-
... More
Supply only infrared door sensor as per existing model and size suitable to 08/13 passenger Lift makes Schindler India Pvt Ltd / Johnson all as specified and directed..
1
-
-
... More
Supply only Rectifiers as per existing model suitable to 13 passenger Lift Makes Schindler India Pvt Ltd all as specified and directed.
1
-
-
... More
Supply only Rectifiers as per existing model suitable to 08 passenger Lift Makes Schindler India Pvt Ltd / Johnson all as specified and directed.
1
-
-
... More
Supply only OSG pulley top complete as per existing model suitable to 8/13 passenger Lift Makes Schindler India Pvt Ltd all as specified and directed.
1
-
-
... More
Supply only OSG pulley bottom complete as per existing model suitable to 8/13 passenger Lift Makes Schindler India Pvt Ltd all as specified and directed.
1
-
-
... More
Supply only Limit switch as per existing model suitable to 8/13 passenger Lift Makes Schindler India Pvt Ltd all as specified and directed.
1
-
-
... More
Supply and fixing ARD system in case of mains power failure and Lift control system failure, the Lift’s own rechargeable and maintenance free battery power shall move the car to the nearest floor and the door shall open automatically for automatic rescue of passengers. A battery run-down indicator shall be provided complete with Battery 12volts and battery charger and make the system functional all as specified and directed..
1
-
-
... More
Supply and Fix Sealed Maintenance Free (SMF) battery of capacity 12 V, upto 18 AH, suitable for passenger/ goods lift as required at locationSMC/ Gurukul bldg. including initial charging complete with inbuilt charger including electrolyte/ distilled water etc including taking down of old battery and shifting to MES store yard for deposit all as directed. by Engineer in Charge complete all as specified.
Make of battery : Exide / Amar raja / Amaron Note :- (i) The contractor shall submit full replacement warranty certificate for minimum 02 years from the date of installation.
(ii) The contractor shall supply SMF battery as per requirement given by Engineer-in-Chare throughout the currency of contract.
10
-
-
... More
Supply and fix hydrant valve 63 mm double headed type including taking down of old unserviceable one complete all as specified and directed..
2
-
-
... More
Supply and fix fire hose of 15 m length 63 mm dia with hose clamp including taking down of old unserviceable one complete all as specified and directed.
2
-
-
... More
M & L as in repair for hose box of any description and providing new hose box made of MS sheet with double door with 4mm thick glass and door frame made of MS sheet painted fire red outside and brilliant white inside yard complete all as directed.
1
-
-
... More
Supply and fix Hose reel Drum 30 m of dia 25 mm dia including taking down of old unserviceable one complete all as specified and directed.
1
-
-
... More
Supply and fix as in repair of 2mm thick transoarent Arcilary sheet for Hose reel Drum and hose box complete all as specified and directed.
2
-
-
... More
M& L for preparation to external old steel surface of pipe of various size and completely removal of existing paint by scraping or chemical and surface painted with synthetic enamel paint with help of brush complete all as specified and as directed. Note :- (i) Colour of paint shall be decided by Engr-in-Charge. (ii) Scxafolding and other safety precautions shall be taken by the contractor.
20
-
-
... More
Supply and fix in repair of MS pipe ERW Heavy (IS1239) errect, jointing complete of 150 mm dia with necessary supports and specials such as tees, bends, reducers etc including consumables and painting with one coat of red oxide primer and two coat of synthetic enamel paint including making good the disturbed surfaces of wall/ ceiling etc complete all as directed..
12
-
-
... More
Supply and fixing in replacement butterfly valve of size 150 mm dia Cl body, both ends flanged duly drilled, ISI marked with IS-14846-2000, having Stainless Steel spindle and check nut including operating wheel, fixing with new nuts, bolts, washers and rubber insertion/packing complete all specified and directed.
1
-
-
... More
Supply and fixing in replacement Non return valve (confirming to IS-5312) (NRV) of size 150 mm ISI marked, CI body suitable for 200 mm dia pipe line complete all specified and directed.
1
-
-
... More
Supply and fix in repair of MS pipe ERW Heavy (IS1239) errect, jointing complete of 100 mm dia with necessary supports and specials such as tees, bends, reducers etc including consumables and painting with one coat of red oxide primer and two coat of synthetic enamel paint including making good the disturbed surfaces of wall/ ceiling etc complete all as directed..
10
-
-
... More
Supply and fixing in replacement butterfly valve of size 100 mm dia Cl body, both ends flanged duly drilled, ISI marked with IS-14846-2000, having Stainless Steel spindle and check nut including operating wheel, fixing with new nuts, bolts, washers and rubber insertion/packing complete all specified and directed.
2
-
-
... More
Supply and fixing in replacement Non return valve (confirming to IS-5312) (NRV) of size 80 mm ISI marked, CI body suitable for 200 mm dia pipe line complete all specified and directed.
2
-
-
... More
M& L for preparation to external old steel surface of hose box/door/panel board of various size and completely removal of existing paint by scraping or by using chemical and surface painted with synthetic enamel paint with help of brush complete all as specified and as directed. Note :- (i) Colour of paint shall be decided by Engr-in-Charge.
30
-
-
... More
Supply and fix in repair of MS pipe ERW Heavy (IS1239) errect, jointing complete of 80 mm dia with necessary supports and specials such as tees, bends, reducers etc including consumables and painting with one coat of red oxide primer and two coat of synthetic enamel paint including making good the disturbed surfaces of wall/ ceiling etc complete all as directed..
12
-
-
... More
Supply and fixing in replacement butterfly valve of size 80 mm dia Cl body, both ends flanged duly drilled, ISI marked with IS-14846-2000, having Stainless Steel spindle and check nut including operating wheel, fixing with new nuts, bolts, washers and rubber insertion/packing complete all specified and directed.
2
-
-
... More
M&L for taking down defective centrifugal pump set 60 HP capacity by disconnecting the pump from motor after unscrewing nuts/ bolts of coupling, foundation, suction pipe delivery pipes and shifting of pump to workshop for repair/ servicing, comprising strip opening of pump, replacement of any defective parts, carrying out necessary lathe work, re-assembling and shifting from workshop to site, re-installation at same location as directed. by Engr-in-Charge, testing on full load capacity at least for 8 hrs, complete all as specified and as directed.. Note :- (a) The spares shall be measured and paid seperately in the relevent items given below. (b) Cost of labour for replacement of spares and transportation are deemed to be included in the quoted rate. (c) The pumpset shall be spared for one week for repair from the date of complaint given by AGE/ JE E/M regarding breakdown. The Contractor is responsible for making alternate arrangement of pump set in case of time required more than one week. (d) In case services affected due to delay in repair of pump set, a penalty of Rs 1000/- per day will be levied from the contractor.
(e) Please note that this penalty is exclusively other than the condition 67 of IAFW-2249 and shall be treated as interim condition of the contract.
(f) The decision of the Accepting Officer in this regard shall be final and binding.
1
-
-
... More
Supply only Ball bearing suitable for 60 HP capacity motor pump as per manufacturer's design complete all as specified and as directed.. Make : Tata/SKF/NBC
1
-
-
... More
Supply only coupling Rubber Bush suitable for 60 HP capacity motor pump as per manufacturer's design complete all as specified and as directed..
2
-
-
... More
Supply only split casing gaskets suitable for 60 HP capacity motor pump as per manufacturer's design complete all as specified and as directed..
1
-
-
... More
Supply only shaft sleeves suitable for 60 HP capacity motor pump as per manufacturer's design complete all as specified and as directed..
1
-
-
... More
Supply only coupling bolt with nuts suitable for 60 HP capacity motor pump as per manufacturer's design complete all as specified and as directed..
2
-
-
... More
Supply only water seal suitable for 60 HP capacity motor pump as per manufacturer's design complete all as specified and as directed..
1
-
-
... More
Supply only Air cock grease nipple suitable for 60 HP capacity motor pump as per manufacturer's design complete all as specified and as directed..
1
-
-
... More
Remetaling of shaft, turning, grinding as per the required size and polishing including provision of neck rings of impellers suitable for 60 HP capacity motor pump as per manufacturer's design complete all as specified and as directed..
1
-
-
... More
Supply only bronze impeller suitable for 60 HP capacity motor pump as per manufacturer's design complete all as specified and as directed..
1
-
-
... More
M&L for rewinding of squirrel cage induction electrical motor , 3 phase, 415 volts with suitable size of copper enameled winding wire and insulating materials incl disconnecting all electrical connections ,decoupling from pump,taking down the motor from foundation , cleaning and varnishing the stator & rotor winding, heating and drying, replacement of burnt terminals, greasing to bearings, re-assembling the motor and refixing of motor on the foundation by using new nut, bolts and washers, coupling with pump,checking alignment connecting all electrical connections,checking the vibrations, RPM and testing on full load all as directed. and specified for the 60 HP motor capacity.
1
-
-
... More
M & L for servicing fire pump panel by checking and servicing the contactor coil , over load relay coil and any other parts and replacement the burnt out wiring including any modification to fire pump panel by welding,cutting , grinding ,drilling testing the panel complete all as specified and directed..
Notes :- (i) Minor spare parts such as nuts,bolts ,washers ,indicator lamps , start,stop push button and suitable size of copper wire are deemed to be include in quoted rate.
1
-
-
... More
Servicing/ comprehensive maintenance of fire alarm system comprising of Smoke detection control panel , Smoke detector (Photoelectric detection Technology), Conventional Fire Alarm control panel, flame detector, conventional manual call point with EN 54-11 : 2001 and LPCB, conventional sounder etc by attending fault testing of system, quarterly checking of system including preventive maintenance by replacing small spare parts complete all as specified and directed.. Location : ETI, Bldg No. P-389 (Ground floor), P-389 (1st Floor), Bldg No. P-506 Lab, Immols Room 1 & 2 and SMC.
3
-
-
... More
Note for item No 52 :- (a) The repairs/ maintenance shall be carried out through the Authorised service agency only as per instructions recommended by the original manufacturer.
(b) The rate quoted shall be deemed to include for carry out all repairs noticed during the period.
(c) The authorised service agency must attend as and when called for urgent nature of repair of the fire alarm equipment's.
(d) Checking of Alarm signal should not lost when primary power failure untill the alarm signal processed.
(e) Checking of smoke detector sensibility
(f) Checking of all speaker circuit and loops.
(g) Periodicity shall be overall 3 months or as per manufacturers recommendations.
-
-
-
... More
Supply & install in replacement Addressable manual call point resettable type. Make :- Ceasefire/ Visionic/ Universal (Ravel)/ Honeywell or equivalent as per site requirement.
6
-
-
... More
Supply & install in replacement Addressable electronic sounder cum strobe. Make :- Ceasefire/ Visionic/ Universal (Ravel)/ Honeywell or equivalent as per site requirement.
2
-
-
... More
Supply & install in replacement Addressable monitor module. Make :- Ceasefire/ Visionic/ Universal (Ravel)/ Honeywell or equivalent as per site requirement.
2
-
-
... More
Supply & install in replacement smoke and heat detectors, photoelectric / optical type certified to EN 54 addressable with self built intelligent with connected accessories complying with optical chamber, cover, case moulding, photodiode (transducer), infrared LED all as specified and directed.. NOTE:- i). Metal junction box of suitable size for detector made of 16 SWG sheet steel is to be provided for mounting of detectors in the concrete mother ceiling / surface along with necessary gland and boxes duly painted with two coats of super enamelled paint over a coat of red oxide primer. ii) Rate of metal boxes shall be included in quoted rate of items. Make :- Ceasefire/ Visionic/ Universal (Rqvel)/ Honeywell or equivalent as per site requirement.
8
-
-
... More
Supply & install in replacement Addressable control module. Make :- Ceasefire/ Visionic/ Universal (Ravel)/ Honeywell or equivalent as per site requirement.
2
-
-
... More
Supply & install in replacement Fire Alarm Sounders / Sirens Electronic type horizontal single stage continuous normal operation for at least 50 minutes with sound level 65 DB to 120 DB measured at 1.5 Mtr with sound output variation of + 5 DB 500 mtrs range. Make :- Ceasefire/ Visionic/ Universal (Ravel)/ Honeywell or equivalent as per site requirement.
2
-
-
... More
Supply & install 2 core solid conductor of size 1.5 sqmm, as per IS-1554 PVC insulated & PVC sheathed, armoured cable FRLS drawn through non metallic PVC conduit of suitable size shall be properly clamped to the ceiling / surfaces including taking down of unserviceable cable and 'S' loop shall also be left where cables connect to sounders, panels and all the cables and wires shall be tagged for proper identification complete all as specified and directed..
300
-
-
... More
Taking down defective Jockey pump set 7.5 HP to 15 HP by disconnecting the pump from motor after unscrewing nuts/ bolts of coupling, foundation, suction pipe delivery pipes and shifting of pump to workshop for repair/ servicing, comprising strip opening of pump, replacement of any defective parts, carrying out necessary lathe work, re-assembling and shifting from workshop to site, re-installation at location as directed. by Engr-in-Charge, testing on full load capacity at least for 8 hrs, complete all as specified and as directed.. Note :- (a) The spares shall be measured and paid seperately in the relevent items given below. (b) Cost of labour for replacement of spares and transportation are deemed to be incl in the quoted rate. (c) The pumpset shall be spared for one week for repair from the date of complaint given by AGE/ JE E/M regarding breakdown. The Contractor is responsible for making alternate arrangement of pump set in case of time required more than one week. (d) In case services affected due to delay in repair of pump set, a penalty of Rs 500 per day will be levied from the contractor.
(e) Please note that this penalty is exclusively other then the condition 67 of IAFW-2249 and shall be treated as interim condition of the contract.
(f) The decision of the Accepting Officer in this regard shall be final and binding.
1
-
-
... More
Supply only coupling Rubber Bush suitable for 7.5 HP to 15 HP motor pump as per manufacturer's design complete all as specified and as directed..
1
-
-
... More
Supply only coupling bolt with nuts suitable for 7.5 HP to 15 HP motor pump as per manufacturer's design complete all as specified and as directed..
1
-
-
... More
Supply only Ball bearing suitable for 7.5 HP to 15 HP motor pump as per manufacturer's design complete all as specified and as directed.. Make : Tata/SKF/NBC
1
-
-
... More
Supply only Air cock grease nipple suitable for 7.5 HP to 15 HP motor pump as per manufacturer's design complete all as specified and as directed..
1
-
-
... More
Supply only shaft sleeves suitable for 7.5 HP to 15 HP motor pump as per manufacturer's design complete all as specified and as directed..
1
-
-
... More
Supply only split casing gaskets suitable for 7.5 HP to 15 HP motor pump as per manufacturer's design complete all as specified and as directed..
1
-
-
... More
Supply only water seal suitable for 7.5 HP to 15 HP motor pump as per manufacturer's design complete all as specified and as directed..
1
-
-
... More
Supply only bronze impeller suitable for 7.5 HP to 15 HP motor pump as per manufacturer's design complete all as specified and as directed..
1
-
-
... More
Remetaling of shaft, turning, grinding as per the required size and polishing including provision of neck rings of impellers suitable for 7.5 HP to 15 HP motor pump as per manufacturer's design complete all as specified and as directed..
1
-
-
... More
M&L for rewinding of induction electrical motor , 3 phase, 415 volts with suitable size of copper enameled winding wire and insulating materials incl disconnecting all electrical connections ,decoupling from pump,taking down the motor from foundation , cleaning and varnishing the stator & rotor winding, heating and drying, replacement of burnt terminals, greasing to bearings, re-assembling the motor and refixing of motor on the foundation by using new nut, bolts and washers, coupling with pump,checking alignment connecting all electrical connections,checking the vibrations, RPM and testing on full load all as directed. and specified for the 7.5 HP to 15 HP motor capacity.
1
-
-
... More
Excavation in trenches in any type of soil not exceeding 1.5 mtr in width and not exceeding 1.5 mtr in depth for laying of cables etc up to proper level complete all as specified and directed.
157.78
-
-
... More
Returning, filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm complete all as specified and directed. by Engr-in-charge.
91.65
-
-
... More
Removing surplus excavated material from excavation not exc 50 meter and depositing where directed. at a level not exc 1.5 meter above the starting point complete all as specified and directed. by Engr-in-charge.
66.13
-
-
... More
Material and labour for Spreading ribbed soil in trenches as in cable cushioning all as per IS 1255-1983 and as directed.. Note :- Excavated approved soil obtained from excavation under item No 72 shall be ribbed by using sieve to separate composite particles etc as per IS and refilling in trenches before laying of cable 8 CM and 15 CM after laying of cable. This is then gently punned down to a depth of 10 cm above the top of upper most cable. For the purpose of measurement only punned thickness shall be considered for payment.
56.8
-
-
... More
Material and labour for well burnt class ‘B’ bricks as mechanical protection to under ground cables laying with length of the bricks equal to the width of the trench complete all as specified and directed.
4.91
-
-
... More
Material and labour for Cutting existing road/PCC/Drain for laying of GI or any type of pipe including necessary earth work, excavation exc 600mm depth but not exc 1mtr depth, 800mm wide including making good existing surface with 150 mm thick PCC 1:2:4 type B1 using 20mm graded stone aggregate complete all as specified and directed.. Note :- The tenderer shall take into consideration for the following points while quoting rate for this item and the unit rate is deemed to be inclusive for :-
(i) Earth work excavation in any type of soil
(ii) Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cm thick complete all as specified and as directed..
(iii) Removing excavated material/rubbish out side MD land
(iv) Laying of any type/any bore of pipe in trenches including taking down any description. Supply of pipe will be measured and paid separately (v) 150 mm thick PCC 1:2:4 type B1 using 20mm graded stone aggregate as in road to make good existing disturbed surfaces.
35
-
-
... More
Supply and laying of GI pipe light grade for cable protection of size 100 mm bore complete with fitting complete including taking down unserviceable one all as specified and directed.
40
-
-
... More
Material and labour for 3 ½ core 240 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheatherd laying in trenches/cable ducts, fixed to wall/pole complete including taking down unserviceable one all as specified and directed. Make: Havells/ Polycab/RPG Asian
200
-
-
... More
Supply, installation, commissioning and testing of factory assembled, floor mounted, free standing type tested LT Feeder pillar panels, with canopy, as per electrical specifications for outdoor installation to be made of IP65 Polycarbonate modular enclosures. The enclosures made of polycarbonate, should be weather/vermin proof, anti -acid, anti-corrossive, UV resistance in accordance with IEC 61439-1, fire retardant and self extingushing in accordance with IEC 60695-2-11, UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties, RoHS compliant & Halogen free. The manufacturer of boards/panels shall submit a copy of type test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tightened to base with thermoplastic screws having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosure should be above 200mm for air circulation & to minimize temp rise. Panel should be fitted with one No. polycarbonate IP 65, 9 W LED translucent bulk head luminaire color temp not less than 6500K, PF 0.95 under canopy for easy maintenance. Panel should be fitted outside with one No. of 16 Amp 3 Pole IP65 industrial socket and 01 No of 32 Amp 5P IP 65 industrial socket. 3 Phase and neutral 600 Amp current carrying capacity of Aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the under mentioned swtich gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20 mm graded crused stone aggregate for bedding upto a height of 45 CM above ground level, including dismanting and taking out old U/s LT panel board of any size and description, reconnecting existing LT UG Cable with new panel board, complete all as specified and as directed. :-
1
-
-
... More
(a) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 400 Amp, 50 KA - 01 No (Incomer).
(b) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 315 Amp, 35 KA - 01 No.
(c) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 200 Amp, 35 KA - 02 Nos.
(d) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 100 Amp, 10 KA - 02 Nos.
(e) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 63 Amp, 10 KA - 01 No.
(f) Multifunction Meter (V,I,PF) with suitable capacity of CT's - 01 No
(g) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set.
(h) Space for spare feeder - 01 No. Note :-
(i) The Contractor shall submit the drawing for approval of GE before executing the work. (ii) Insulators, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (iii) Make of Switch gear : Schneider/L&T/C&S.
(iv) MCCB should be ICu =100% ICs.
(v) Make of LT Panel/FPB shall be as mentioned in list of makes (PS).
-
-
-
... More
Boring of holes under road, pavement hard standings by trenchless technology using ultra sound technique and necessary machine including HDPE pipes of 150 mm dia suitable for 0.4 Mpa working pressure complete all as specified and directed..
24
-
-
... More
Material and labour for 3 ½ core 120 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheather laying in trenches/cable ducts, fixed to wall/pole complete including taking down unserviceable one all as specified and directed. Make: Havells/ Polycab/RPG Asian
275
-
-
... More
Material and labour for 3 ½ core 95 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheather laying in trenches/cable ducts, fixed to wall/pole complete including taking down unserviceable one all as specified and directed. Make: Havells/ Polycab/RPG Asian
350
-
-
... More
Comprehensive maintenance of Automatic Power Factor Correction Panels ( APFC ) at various sub stns of capacities 250 KVAr -1 No,75 KVAr-01 No, 60 KVAr - 01 No , 40KVAr - 01 No and 35 KVAr - 02 Nos and comprising of following works :- (i) Repair / maintenance of Contactors, Relays and Capaciters , MCCBs & MCBs provided in the APFC Panel (ii) Monitoring and effective management of power factor correction near to unity as per the veriation of load in the corrrosponding transformer in terms of serviceability of MCCB/MCBs , Contactors , Capacitors and Relay and display unit including the following Technical services:- The following daily Maintenace to be carried out : (a) Check seviciablity of APFC panels , MCCBs/MCBs, Contactors, Relays etc. (b) Maintain a register to note the values of power factor from all APFC Panels and VCBs panel at MRS and that should be submitted to concerned JE (E/M) or AGE(E/M) . (c) Check the connection and serviciablity of incoming cable from Main LT Panels to APFC Panels (d) Checking and tightening control wiring and rectifying the defects if any.
9
-
-
... More
Note :(i) The Contractor shall be responsible for maintaining the power factor near to unity on induvidual APFC Panels and overhaul the value at main Receiving Stn . Contracor will responsible for, the penalty/ compensation charges which charged by BESCOM , due to Low Power factor and same amount shall be paid by the contractor from his own account. The above quoted rate is inclusive of all regarding to maintain the APFC Panel power factor. (ii ) The Capacitors, Contactors, Relays replaced will be measured and Paid separetly. However, the labour element is included for replacement of wornout/ defective components.
-
-
-
... More
Supply only three phase power capacitor duty contactors of following ratings including taking down old item all as directed. :-
-
-
-
... More
5 KVAR Make : L&T/ Siemens (Epcos)/ Schneider/ABB
2
-
-
... More
10 KVAR Make : L&T/ Siemens (Epcos)/ Schneider/ABB
6
-
-
... More
12.5 KVAR Make : L&T/ Siemens (Epcos)/ Schneider/ABB
1
-
-
... More
20 KVAR Make : L&T/ Siemens (Epcos)/ Schneider/ABB
4
-
-
... More
25 KVAR Make : L&T/ Siemens (Epcos)/ Schneider/ABB
2
-
-
... More
50 KVAR Make : L&T/ Siemens (Epcos)/ Schneider/ABB
1
-
-
... More
Supply only TP, MCB 20 to 32 Amp, 240 v, 50 Hz AC suitable for ‘C’ curve, 10 KA breaking capacity complete conforming to IS 8828 of 1996, all as specified Make : Legrand/ L&T/ Indo Asian/Schenider/ABB
10
-
-
... More
Supply only contactor suitable for 5 KVAr Capacitor Make - L&T /BCH/Schneider
2
-
-
... More
Supply only contactor suitable for 10 KVAr Capacitor Make - L&T /BCH/Schneider
2
-
-
... More
Supply only contactor suitable for 12.5 KVAr Capacitor Make - L&T /BCH/Schneider
2
-
-
... More
Supply only contactor suitable for 20 KVAr Capacitor Make - L&T /BCH/Schneider
2
-
-
... More
Supply only contactor suitable for 25 KVAr Capacitor Make - L&T /BCH/Schneider
1
-
-
... More
Supply only contactor suitable for 50 KVAr Capacitor Make - L&T /BCH/Schneider
1
-
-
... More
Supply and fixing in replacement MCB SP 6A 'C' series Make - Make - L&T/Havells/Indoasian
4
-
-
... More
Supply and fixing in replacement MCB SP 16A 'C' series Make - Make - L&T/Havells/Indoasian
3
-
-
... More
Supply and fixing in replacement MCB SP 63A 'C' series Make - Make - L&T/Havells/Indoasian
2
-
-
... More
Supply and fixing in replacement MCB SP 32A 'C' series Make - Make - L&T/Havells/Indoasian
3
-
-
... More
Supply only Electric cooling fan single phase 240 Volts suitable for APFC panel.
2
-
-
... More
Supply only APFC relay square flush type with Intelligent Power Factor Controller complete all as directed.. Make :GE/EPCOS/ABB
1
-
-
... More
Supply only Indicator lamps (RYB) complete all as specified and directed. .
18
-
-
... More
Supply and fixing in replacement of wiring of APFC panel with including copper wire ,PVC wire holder and other connected items suitable for APFC panel 30 KVAr to 250 KVAr capacity as per existing make including testing and complete all as specified and directed..
2
-
-
... More
Supply and fix smart integrated solar all in one LED solar street light fitting 12.8V, 15 watts with IP 65 protection, built-in MPPT charge controller, lithium ion battery, mono crystalline solar panel, PIR motion sensor complete with anodised reflector, toughened heat resistant glass cover, LED 12 watts white colour lamp connector block with all accessories pre wired including bracket, welding drilling, bolts, nuts and any alteration required for fixing the panel with existing pole all as specified and as directed.. Make: CG/Bajaj/ Philips
10
-
-
... More
Comprehensive maintenance of 3 phase oil cooled servo stabilizer of Make :Vinitec with input variation between 300V to 480V with output stabilized at 415 Volts of capacity 1000 KVA with all spares including isolating stabilizer from system, opening up, examining the accessories parts, cleaning, soldering as required and testing and connecting back with the system periodical maintenance as recommended by the original manufacturer complete all as specified and directed.. Location : Gurkkul
1
-
-
... More
Comprehensive maintenance of 3 phase oil cooled servo stabilizer of Make :Vinitec with input variation between 300V to 480V with output stabilized at 415 Volts of capacity 300 KVA with all spares including isolating stabilizer from system, opening up, examining the accessories parts, cleaning, soldering as required and testing and connecting back with the system periodical maintenance as recommended by the original manufacturer complete all as specified and directed.. Location : AFTC Pump House/ AFTC Power House.
2
-
-
... More
Comprehensive maintenance of 3 phase oil cooled servo stabilizer of Make :Power One with input variation between 276V to 450V with output stabilized at 415 Volts of capacity 225 KVA with all spares including isolating stabilizer from system, opening up, examining the accessories parts, cleaning, soldering as required and testing and connecting back with the system periodical maintenance as recommended by the original manufacturer complete all as specified and directed.. Location : 16 Tettra School
2
-
-
... More
Comprehensive maintenance of 3 phase oil cooled servo stabilizer of Make :Vinitec with input variation between 300V to 480V with output stabilized at 415 Volts of capacity 200 KVA with all spares including isolating stabilizer from system, opening up, examining the accessories parts, cleaning, soldering as required and testing and connecting back with the system periodical maintenance as recommended by the original manufacturer complete all as specified and directed.. Location : AFS AFNET SECTION
1
-
-
... More
Comprehensive maintenance of 3 phase oil cooled servo stabilizer of Make :Vinitec with input variation between 300V to 480V with output stabilized at 415 Volts of capacity 100 KVA with all spares including isolating stabilizer from system, opening up, examining the accessories parts, cleaning, soldering as required and testing and connecting back with the system periodical maintenance as recommended by the original manufacturer complete all as specified and directed.. Location : Telephone Exchange
1
-
-
... More
Note for Item No 110 to 114 :-
(a) Thecomprehensive maintenance shall be done through authorised person of OEM only. (b) The rate quoted shall be deemed to include for carriy out all repairs to servo stabilizer noticed during the period 09 months.
(c) Any other spare parts which have not covered in the relevant items but are required to make in functional condition are deemed to be included in the quoted unit rate.
(d) Cost of labour element towards removing of unserviceable spare parts and re-fixing of serviceable spare parts for supply only items here-in-after shall be deemed to be included in quoted rate. Supply only spare parts shall be measured and paid separately.
-
-
-
... More
Supply only Servo motor suitable for 100KVA to 300KVA all as specified and directed..
1
-
-
... More
Supply only Servo motor suitable for 1000 KVA all as specified and directed..
1
-
-
... More
Supply only Auto transformer of servo stablizer of capacity 100KVA to 300KVA all as specified and directed..
1
-
-
... More
Supply only Auto transformer of servo stablizer of capacity 1000 KVA all as specified and directed..
1
-
-
... More
Supply only Bypass switch of servo stabilizer of capacity 100 KVA to 300KVA all as specified and directed..
1
-
-
... More
Supply only Microprocessor / Microcontroller board of servo stablizer of capacity 100KVA to 300KVA all as specified and as directed..
1
-
-
... More
Supply only Microprocessor / Microcontroller board of servo stablizer of capacity 1000 KVA all as specified and as directed..
1
-
-
... More
Supply only Buck Boost transformer of servo stablizer of capacity 100KVA to 300KVA all as specified and directed..
1
-
-
... More
Supply only Buck Boost transformer of servo stablizer of capacity 1000 KVA all as specified and directed..
1
-
-
... More
Supply only Carbon Brush (100Amps to 200 Amps)
4
-
-
... More
Supply only Carbon Brush (250 Amps to 300 Amps)
2
-
-
... More
Supply and fix as in repair 9/10 watt LED holder type (E27) Bollard light energy saving environment friendly with decorative clear opal arcylic diffuser including 9/10 watt LED bulb with IP 65 protection complete all as specified and as directed.. Make: Havells/ CG/Bajaj/ Philips
10
-
-
... More
Supply and fixing LED flood light fitting of 120 watts pressure die cast housing with IP66 protection with efficient high output emitter LED for better distribution with all accessories pre wired including necessary electric connection and bracket for fixing the fitting all including taking down unserviceable old fitting ,complete all as specified and directed..Make : Bajaj/Philips/CG/Halonix.
12
-
-
... More
Supply, fabricating, installation, testing and commisioning Feeder Pillar Box out Supply, installation,commissioning and testing of factory assembled ,floor mounted ,free standing type tested LT Feeder pillar panels,with canopy ,as per electrical specifications for outdoor installation to be made of IP65 Polycarbonate modular enclosures. The enclosures made of polycrabonate,should be weather, vermi proof, anti -acid,anti-corrossive,UV resistance in accordance with IEC 61439-1,fire retardant and self extingushing in accordance with IEC 60695-2-11 ,UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties ,RoHS compliants & Halogen free. The manufacturer of boards/panels shall submit a copy of type test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tight to base with thermoplastic screw having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosuser should be above 200mm for air circulatiocirculation & to minimize temp rise. Panel should be fitted with one No. of polycarbonate IP 65 9 W LED transperent bulk head luminaire 6500K,PF 0.95 under canopy for easy maintenance . Panel shall be fitted outside with one No. of 16 A 3 Pole IP65 industrial socket and 01 No of 32A 5P IP 65 industrial socket. 3 Phase and neutral 600 A current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the under mentioned switch gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20mm graded aggregate for bedding upto a height of 45 CM above ground level ,including dismanting and taking out U/s LT panel board and reconnecting existing LT UG Cable with new panel board, complete all as specified and directed. :-
1
-
-
... More
(a) MCCB with thermal magnetic release 4 Pole ,415 V of capacity 315 Amps ,36 KA - 01 No (Incomer).
(b) MCCB with thermal magnetic release 4 Pole ,415 V of capacity 200 Amps , 25 KA - 01 No.
(c) MCCB with thermal magnetic release 4 Pole ,415 V of capacity 63 Amps ,10 KA - 03 Nos.
(d ) Multifunction Meter (V,I,PF) with suitable capacity of CT's - 01 No.
(e) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set.
(f) Space for spare feeder -01 No.
Note :-
(i) The Contractor shall submit the drawing for approval of GE before executing the work. (ii) Insulators, wiring, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (iii) Make of Switch gear : Schenider/L&T/C&S.
(vi) MCCB should be ICu = 100 % ICs .
(v) Make of LT Panel /FPB shall be as mentioned in list of makes (PS).
-
-
-
... More
Supply, installation, testing & commissioning of maintenance free chemical earthing system comprising of 17mm dia copper bonded rod 3 mtr long horizontally pre welded T-terminal rod with provision for connection size of 50 x 150mm long, 6mm thickness with equal space either side, with 12mm dia hole of 02 numbers each on either side of the terminal clamp with 250 microns (average) coating thickness, tested and certified by CPRI India alongwith 50 Kg earth energizer compound and 10 litres earth resistance reducing liquid. The earthing energizer compound and resistance reducing earthing liquid shall be tested as per IEC-62561-7 read with ASTM G57-06, CI 3.4 A by any NABL accredited lab. The above mentioned rod shall be installed in 4-6 inch bore, 12 feet depth with a distance of minimum 3 meters between each installation including taking down existing one, complete all as specified and directed..
Make : Model HTSP 317 of safeTrode or equivalent in OBO Betterman/ FURSE/ERICO.
25
-
-
... More
The quoted rate shall also deemed to be included the following :- (i) Prior to installation of maintenance free chemical earthing, soil resistivity test to be carried out at the location where earthing work to be done in presence of Engr-in- Charge/JE (E/M),user and the report has to submit to Garrison Engineer with recommendation of manufacturer, if required additional interconnection of earthing (not more than 04 number of earthing) to achive earth result less then 1 Ohms. The arrangement done for soil resistivity testing and submission of report with recommendation deemed to be included in the quoted rate.
-
-
-
... More
(ii) The description/ size/ qty of items mentioned in above are for indicating only however qty/ size may vary at site condition to maintain the earth resistance 1 ohm. The contractor shall quote rate by considering all factors.
-
-
-
... More
(iii) Rate of earth energizer compound of 25 Kg of 02 bags and earth resistance reducing liquid 10 litre per cane for each pit deemed to be included in the quoted rate.
-
-
-
... More
(iv) Resistivity of earth energizer compound and resistance reducing earthing liquid shall be certified by any NABL accredited lab carried out as per IEC-62561-7 read with ASTMG57-06, CI-3.4A and the certificate of same shall be submitted by the contractor before commencement of work.
-
-
-
... More
(v) Earth enhancing material should not leach into the adjacent soil or underground water channels and its PH value should be in neutral range complete all as specified and as directed. It should solidify when mixed with water and set like concrete.
-
-
-
... More
(vi) Copper strip of size 20 x 3 mm shall be fixed on proper post insulator at the instrument end ( copper strip upto 7.5 RM shall be considered in unit quoted rate and extra will be measured and paid separately).
-
-
-
... More
(vii) Testing of earth shall be carried out in presence of departmental and user representative and report shall be submitted to Garrison Engineer duly signed by all concerned.
-
-
-
... More
(viii) Earth resistance tester will be provided by the contractor. Tester should be calibrated from authorised company/ lab.
-
-
-
... More
(ix) Earthing shall be tested after completion of work by the contractor in presence of Engr-in-charge, user and proper record shall be maintained duly signed by all concerned. After testing if the desired earth resistance of less than 1 Ohm is not obtained, the earthing will be redone at no extra cost to Govt. till desired result is obtained.
-
-
-
... More
(x) The contractor shall give a written guarantee of minimum three years for maintaining the earth resistance less than 1 Ohm after certified date of completion.
-
-
-
... More
(xi) No further maintenance or periodic watering or recharge shall be required in earthing during its guarantee period of over 03 years in all type of soil including soft/ disintegrated or hard rock.
-
-
-
... More
(xii) During the guarantee period, if earth resistance is not maintained less than 1 ohm the contractor has to redo or rectify at no extra cost to Govt till desired result is maintained.
-
-
-
... More
(xiii) A security deposit of value equal to 2.5 % of the rate quoted for chemical earthing for each earthing shall be retained from payment due to the contractor from final bill for the guarantee period.
-
-
-
... More
(xiv) The electrode shall carry manufacturer's name .
-
-
-
... More
(xv) The connection clamp shall be permanentlly welded to the copper bounded rod to avoid any kind of connectivity loss,.The pre-welded copper bounded rod shall not need any additional clamp for termination.
-
-
-
... More
(xvi) The acceptable earth resistance at earth busbar/ test point shall not be more than 0.1 ohm.
-
-
-
... More
(xvii) Earth work such as auguring and making good the surrounding area shall carried out in any type of soil.
-
-
-
... More
(xviii) The contractor shall submit CPRI India certified document for copper bounded rod to ensure genuineness of material.
-
-
-
... More
(xix) Sign board of mild steel sheet 2 mm thick duly painted with two coats of synthetic enamel paint over a coat of red oxide Zinc chrome primer showing result of earthing shall be fixed near the earth pit after completion as directed by engr -in- charge.
-
-
-
... More
Material and labour for Earth pit cover made of heavy duty poly plastic of high grade polypropylene tested and certified by any NABL accredited lab for load bearing capacity not less than 7.2 tonnes with top dia not less than 250mm, bottom dia not less than 330 mm and height not less than 260 mm dia for each electrode pit complete including taking down all as specified and directed.
Make : Model SEPC 250 of SAFE TRODE/ Electrogrip Model/ EGTEK3LC of ISG Global or equivalent in OBO Betterman/ ERICO.
Note :- The contractor shall submit load bearing capacity certificate from the manufacturer.
25
-
-
... More
S&F in repair copper strip 20 x 3mm thick as earthing lead fixed to wall/roofs etc including taking down existing one, complete all as specified and directed. Note : - All Joints should be joined by Exothermic Welding or Brazing.
20
-
-
... More
Supply, installation, commissioning and testing of factory assembled, floor mounted, free standing type tested LT Feeder pillar panels, with canopy, as per electrical specifications for outdoor installation to be made of IP65 Polycarbonate modular enclosures. The enclosures made of polycarbonate, should be weather/vermin proof, anti -acid, anti-corrossive, UV resistance in accordance with IEC 61439-1, fire retardant and self extingushing in accordance with IEC 60695-2-11, UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties, RoHS compliants & Halogen free. The manufacturer of boards/panels shall submit a copy of type test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tightened to base with thermoplastic screws having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosure should be above 200mm for air circulation & to minimize temp rise. Panel should be fitted with one No polycarbonate IP 65, 9 W LED translucent bulk head luminaire color temp not less than 6500K, PF 0.95 under canopy for easy maintenance. Panel should be fitted outside with one No. of 16 A 3 Pole IP65 industrial socket and 01 No. of 32A 5P IP 65 industrial socket. 3 Phase and neutral 400 A current carrying capacity of Alluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the under mentioned swtich gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20 mm graded crushed stone aggregate for bedding upto a height of 45 CM above ground level, including dismanting and taking out U/s LT panel board and reconnecting existing LT UG Cable with new panel board all as directed. :-
1
-
-
... More
(a) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 160 Amps 36 KA - 01 No (Incomer).
(b) On Load Change over front operated of capacity 250 Amp, 4 Pole, 415 V - 01 No.
(c) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 100 Amps 25 KA - 02 Nos.
(d) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 63 Amps 10 KA - 02 Nos.
(e) MCB SPN of 240 V of capacity 40 Amps 10 KA - 04 Nos.
(f) Multifunction Meter (V,I,PF) with suitable capacity of CT's - 01 No.
(g) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set.
(h) Space for spare feeder - 01 No. Note :-
(i) The Contractor Shall submit the drawing for approval of GE before executing the work. (ii) Insulators, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (iii) Make of Switch gear : Schneider/L&T/C&S.
(iv) MCCB should be ICu =100% ICs.
(v) Make of LT Panel/FPB shall be as mentioned in list of makes (PS). Note :- An amount of Rs 34283.00 on account of credit schedule for schedule 'A' part II shall be deducted from the total amount of BOQ to arrive at the contract sum.
-
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements