Military Engineer Services Tender
Karnataka, also known as Karunadu, is a state in the southwestern region of India. Karnataka was formed originally as Mysore State on 1st November 1956 and currently is the biggest state in south India. Its capital and largest city is Bengaluru. It covers an area of 191,791 km2 (74,051 sq mi) and is the sixth largest state by area comprising 31 districts. Karnataka is also a state of multiple languages; Kannada being the official and most widely spoken language in Karnataka. Other languages spoken in the state include Tamil, Telugu, Malayalam, Kodava, Konkani and much more.Karnataka tenders are issued by the government of Karnataka, public & private sector organisations. The state government issues majority of the Karnataka tenders, which are for goods and services including construction, road and bridge construction, IT services, engineering services, medical services, educational services amongst many others. Bidassist is one of the largest eprocurement portals, which offers all government tenders from across the world in one place. Bidassist offers information on all Karnataka tenders and other state and authority tenders in no time. Bidassist is a platform where users can look for various Karnataka tenders as well as other tenders.
Military Engineer Services - MES Tender
Security and Emergency Services
Eprocure
Opening Date20 Nov 2024
Closing Date11 Dec 2024
Tender Amount₹ 27,40,000
Costs
EMD
₹ 54,800Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_684743_1Tender No
8295/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Servicing and repairs to motorised siren "Dual Tone" of range 2 KM with driving unit installed at technical hangars complete all as specified and directed by Engr-in-charge.
Note
(i) Servicing and cleaning of the item complete.
(ii) Checking of all internal components/accessories for their serviceability.
4
-
-
Supply and refilling of NOVEC-1230 fluid in cylinders of fire suppression system installed at various technical buildings all as specified and directed by Engr-in-Charge.
60
-
-
Supply and refilling of FM-200 fluid in cylinders of fire suppression system installed at various technical buildings all as specified and directed by Engr-in-Charge.
30
-
-
Maintenance and repairs of fire alarm panels Qty 13 Nos installed at various technical buildings once in a qtr complete all as specified and directed by Engr-in-charge.
Note : (i) The work includes 01 service per month and all the break down during the contract period to be rectified by the contractor. (ii) Servicing and cleaning of complete fire alarm panels.
(iii) Checking of complete internal wiring and carrying out necessary repairs/soldering/lugs etc.
(iv) Checking of all internal components/accessories for their serviceability.
3
-
-
Supply only addressable single loop card for connecting inside panel
Make : Morley IAS - Honeywell/Seimens/Notifier/Bajaj Securiton
2
-
-
Supply only 12V 7AH lead acid battery for connecting inside panel.
Make : Morley IAS - Honeywell/Seimens/Notifier/Bajaj Securiton
6
-
-
Supply, installation, testing and commissioning in repairs Micro processor based loop driven Intelligent addressable sounders cum strobe inbuilt. The addressable sounder cum strobe shall form part of loop device such that, no additional separate wiring is required. The sounder shall have audible range of 75 dB when heard at a distance of 1 Mtr. The sounder shall be suitable for wall / ceiling mounting shall operate on 24 Volt DC each sounder shall meet the specifications all as specified and as directed. Make:Morley IAS- Honeywell / Seimens / Notifier/Bajaj Securiton, UL / FM/ CE/ LPCB certified all as specified and directed.
5
-
-
Supply and fix in repairs Addressable manual call point with built in adressable monitor module, restorable type which is suitable for external mounting on polycarbonate box or concealed in metallic box with suitable covering plate . The manual call point will be of 'Pull down' type all as specified and as directed. Make:Morley IAS- Honeywell / Seimens / Notifier/Bajaj Securiton, UL / FM/ CE/ LPCB certified all as specified and directed.
35
-
-
Supply, installation, testing and commissioning in repairs Intelligent addrressable Short Circuit Isolator (Fault Isolation Module) shall be suitable for DIN rail mounting and mounted external device shall display status of Tri colour with Open, short circuit LED status indication for normal, The Device shall be suitable for Loop connectivity. (The FIM shall be cosidered for every 20/22 devices as the site condition). Make:Morley IAS- Honeywell / Seimens / Notifier/Bajaj Securiton, UL / FM/ CE/ LPCB certified all as specified and directed.
15
-
-
Supply, installation, testing and commissioning in repairs Response Indicator for multisensor type heat and smoke detetor with LED indication enclosed in sturdy box and inscribed as "FIRE". Make:Morley IAS- Honeywell / Seimens / Notifier/Bajaj Securiton, UL / FM/ CE/ LPCB certified all as specified and directed.
50
-
-
Supply, installation, testing and commissioning in repairs Microprocessor based Intelligent Addressable multisensor type Heat & Smoke detectors (Combination of Photio electric & thermal sensor) with bases.including fixed on metal junction of size 75x75x50 mm with metal glands and gasket. The detector shall sense fire / smoke and generate alarm if any Fire / smoke occurred in the building. The detectors shall have Two built in LEDs for 360 degree viewing all as specified and as directed.
Make:Morley IAS- Honeywell / Seimens / Notifier/Bajaj Securiton, UL / FM/ CE/ LPCB certified all as specified and directed.
25
-
-
Supply and fix in repair two core PVC cable, FRLS with copper conductor round cable 1.5 Sqmm for including 25mm dia metallic conduit FRLS/FR including all fittings and accessories complete all as directed by Eng-in-Charge.
Make : Havells/Finolex/ Polycab/KEI
180
-
-
Supply and fix in repair four core PVC cable, FRLS with copper conductor round cable 2.5 Sqmm for including 25mm dia metallic conduit FRLS/FR including all fittings and accessories complete all as directed by Eng-in-Charge.
Make : Havells/Finolex/ Polycab/KEI
132
-
-
Supply and fix in repair mannual call point breakable glass complete all as specified and directed by Engr in charge.
100
-
-
Supply and fix in repairs of Active repeater panel of DIMENSIONS [MM] (H X W X D) 165 x 254 x 50,OPERATING TEMPERATURE +5°C to +45°C,RELATIVE HUMIDITY 5% - 95% non-condensing,Compatible with all Morley-IAS intelligent multiprotocol fire alarm control panels
• Connects to RS485 peripheral bus
• Active or Passive options
• Backlit adjustable alphanumeric display
• General status LEDs
• Controls for system reset, accept, mute, silence
alarms, and self test (active repeater only)
• “Access Enable” key-switch on active repeater
Morley IAS- Honeywell / Seimens / Notifier
1
-
-
Supply and fix in repairs of Duct detector Photoelectric, integrated low-flow technology having Air velocity rating from1.5m/s to 20.3m/sec, Versatile mounting options, square or rectangular configuration, Broad ranges for operating temperature −20°C to 70°C and humidity,0% to 95% Complete all as specified and directed. Make:Morley IAS- Honeywell / Seimens / Notifier
4
-
-
Material and Labour for servicing of package type AC indoor/outdoor of capacity 5/5.5 TR of make Blue star/ Voltas including following item of works all as specified and directed by Engr-in-Charge :
(a) Cleaning of complete unit including cooling coil condenser, Fan (Outdoor unit), blower etc. (b) Checking of Electrical wiring and carrying out necessary repairs/replacement along with lugs, clamps, soldering etc. (c) Checking of refrigerant piping and carrying out necessary repairs/replacement to copper tubing and insulation to copper tubing. (d) Checking of all components/accessories for their serviceability and replacement of defective components/accessories. (e) Greasing and oiling of fan motor. Note: (i) Replacement of unserviceable items wrt (d) above shall be measured and paid separately under relevant items of BOQ. (ii) Servicing of each Pakage type AC should be done once during the contract period. Servicing done once to be measured as one job. (iii) Servicing of Plant/ Package AC should be carried out through OEM or auth service centre/ Vendor by OEM.
7
-
-
All as per item 20 above but packaged type AC capacity 11 TR of make Blue Star/ Voltas with one No indoor and 2 Nos outdoor units.
3
-
-
All as per item 20 above but packaged type AC capacity 16.5 TR of make Blue Star/ Voltas with one No indoor and 3 Nos outdoor units.
4
-
-
All as per item 20 above but Ductable type AC capacity 8.3 Ton of make Blue Star/ Voltas complete all as specified and directed by Engr-in-Charge.
2
-
-
Topping up / Replacement of compressor oil with new compressor oil of make Frizol 68 or equivalent all as specified and directed by Engr-in-Charge.
30
-
-
Supply and Charging of Freon gas-22 for ACs complete all as specified and directed by Engr-in-Charge.
95
-
-
Supply and replacement of flexible Core PVC insulated with stranded copper conductor 2.5 Sqmm 4 core 600/1100 V ISI Marked complete all as specified and directed by Engr-in-Charge.
90
-
-
Supply and fix in repair new filter drier for 5/5.5TR Split type AC having same features as per existing old unserviceable at site complete all as specified and directed by Engr-in-Charge. Make : Blue Star/ Voltas/ Sanyo
2
-
-
Supply and fix in repair of contactor for compressor contactor (LT, MN-16 for 5/5. 5TR Split type AC) complete all as specified and directed by Engr-in-Charge.
2
-
-
Supply and fix in repair of new Single phase preventer (SM-101) for 5/5.5TR Split type AC complete all as specified and directed by Engr-in-Charge. Make : Blue Star/ Voltas/ Sanyo
1
-
-
Supply and fixing in repair of LP/HP cut out for 5/5.5TR Split type AC complete all as specified and directed by Engr-in-Charge. Make : Blue Star/ Voltas/ Sanyo
2
-
-
Supply and fix in repairs to PCB board with corded remote for 5/5.5 TR Split type AC complete all as specified and directed by Engr-in-Charge. Make : Blue Star/ Voltas/ Sanyo
2
-
-
Supply and fix in repairs to PCB board for 8.2 TR Ductable AC complete all as specified and directed by Engr-in-Charge.Make : Blue Star/ Voltas/ Sanyo
1
-
-
Supply and fix in repair new Compressor scroll type of capacity 5.5 TR suitable for package type AC of capacity 5.5TR/11TR/16.5 TR having same features as per existing old unserviceable compressor at site complete all as specified and directed by Engr-in-Charge. Make : Blue Star/ Voltas
6
-
-
Supply and fix in repair new Compressor scroll type of capacity 8.2 TR suitable for package type AC of capacity 16.5 TR having same features as per existing old unserviceable compressor at site complete all as specified and directed by Engr-in-Charge. Make : Blue Star/ Voltas
1
-
-
Supply and fix in repair thermal insulation for external ducts using 19mm thick closed cellnitrile rubber with adhesive and covered with UV protection cloth and finished with FRP painting complete all as specified and directed by Engr-in-Charge.
125
-
-
Supply and fix in repair Canvas clothes for duct flanges complete all as specified and directed by Engr-in-Charge.
4
-
-
Supply and fix in repair volume control Dampers with operating handle and TDF Flange for duct branches of size 520mm x 400mm complete all as specified and directed by Engr-in-Charge.
4
-
-
M&L for servicing and maitenance of Dehumidifier of 8.3 TR capacity Ductable AC complete all as specified and directed by Engr-in-Charge. Make : Blue Star/ Voltas/ Sanyo
10
-
-
S&F in repairs including brazing of copper tube size 5/8 suitable for ductable / package ACs complete all as specified & directed.
30
-
-
S&F in repair including brazing of copper tube size 3/8 suitable for ductable / package ACs complete all as specified & directed.
30
-
-
S&F in repair insulation with heatlon or Superlon insulation material of thickness 6mm on existing copper tubing complete all as specified & directed.
40
-
-
Dismantling & taking out old unserviceable earthing pits including connected materials all as specified and directed.
15
-
-
M&L for earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25 M deep below ground level) with top edge of the plate not less than 1.5 M below normal ground level connected to galvanised earth lead wire of size 4.0mm dia up to a length of 7.5 mtr long by means of nuts, bolts, checknuts, washers of galvanised iron or steel all as shown in electrical plate No. 3 of SSR Part I of 2009 connected to earthing test point or disconnecting / testing link including excavation/ earth work in any strata, removal of surplus soil, GI pipe medium grade 20mm dia for watering and funnel, GI Pipe medium grade 15mm dia for earth lead protection, PCC 1:3:6 type C2 bed and chamber in PCC 1:2:4 type B1 including necessary form work, 10mm thick CI chamber cover with hinge, etc. complete all as specified and directed.
4
-
-
M&L for earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25 M deep below ground level) with top edge of the plate not less than 1.5 M below normal ground level connected to galvanised strip of size 25x4 mm up to a length of 7.5 mtr long by means of nuts, bolts, checknuts, washers of galvanised iron or steel all as shown in electrical plate No. 3 of SSR Part I of 2009 connected to earthing test point or disconnecting / testing link including excavation/ earth work in any strata, removal of surplus soil, GI pipe medium grade 20mm dia for watering and funnel, GI Pipe medium grade 40mm dia for earth lead protection, PCC 1:3:6 type C2 bed and chamber in PCC 1:2:4 type B1 including necessary form work, 10mm thick CI chamber cover with hinge, etc. complete all as specified and directed by Engr-in-charge.
4
-
-
All same as per item No 44 here-in-before but galvanised strip of size 32 x 6mm complete all as specified and directed.
3
-
-
M&L for earthing complete with copper earth plate electrode 600mm x 600mm x3.15mm thick buried directly in ground (earth pit not less than 2.25 M deep below ground level) with top edge of the plate not less than 1.5 M below normal ground level connected to copper strip of 20x3 mm up to a length of 7.5 mtr long by means of nuts, bolts, checknuts, washers of galvanised iron or steel all as shown in electrical plate No. 3 of SSR Part I of 2009 connected to earthing test point or disconnecting / testing link including excavation/ earth work in any strata, removal of surplus soil, GI pipe medium grade 20mm dia for watering and funnel, GI Pipe medium grade 40mm dia for earth lead protection, PCC 1:3:6 type C2 bed and chamber in PCC 1:2:4 type B1 including necessary form work, 10mm thick CI chamber cover with hinge, etc. complete all as specified and directed.
Note for item Nos 43 to 46 :
(a) Earthing value should be less than 5 ohms for Ser item No 2 to 4 and less than 1 ohms for ser item No 5.
(b) If desired value of earth resistance not achieved during testing, the earthing work shall be redone by the contractor at free of cost to achieve the desire value of earthing resistance. The rate quoted by the contractor deemed to be inclusive of the provision.
4
-
-
Supply and fix in repairs GI strip of size 25mmx4mm as earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing using clamps & nut bolt as required complete all as specified and directed.
110
-
-
All same as per item No 47 here-in-before but 4mm dia galvanised iron wire complete all as specified and directed.
120
-
-
Supply and fix in repairs aluminium strip 25 mm x 3 mm complete with saddles and fixing screws etc for roof conductors and down conductors above ground level and fixing upto 20 mtr height including removing u/s strips complete all as specified and directed.
150
-
-
Supply and fix in repairs copper strip 20mm x 3 mm complete with saddles and fixing screws etc for roof conductors and down conductors above ground level and fixing upto 20 mtr height including removing u/s strips complete all as specified and directed.
50
-
-
All same as per item No 50 here-in-before but Galvanised iron strip 32 x 6mm complete all as specified and directed.
30
-
-
Supply and fix in repairs single pointed air termination aluminium rod, 12 mm dia, 300 mm long and fixing upto 20 mtr height complete all as specified and directed.
20
-
-
S&F in repair porcelain strip holder on wall and roof of suitable size including removing broken u/s one complete all as specified and directed. Note for item Nos 47 to 53 : (a) Repairing/replacing/fixing work shall be carried out upto 20 mtr height on hangars/tech buildings/Over Head Water Tanks. (b) Necessary T&P such as Ladder/Crane and like as required for execution of work shall be borne by the contractor. (c) The rate quoted by the contractor deemed to be inclusive of all the above provision.
60
-
-
M&L for earth indicators made of 2 mm thick MS sheet of oval/Triangular/ Rectangular shape of size 30 cm x 20 cm duly fixed over MS angle iron of size 25 x 25 x 3mm in size 0.9 metre in total length and 30 cm embedded in below ground level and 60 cm above ground level and angle iron embedded in cement concrete of 1:3:6 type C-2, of size 30 cm x 30 cm x 30 cm painting the steel surfaces with two coats of red paint for chemical earpits and yellow paint for Lightening Arrester( LA), Power Supply(PS) earth pits over coat of red oxide and writing the earth pit indication in alphabets with black colour of one inch height and marking all as per the direction of Engr -in-Charge and including necessary earth work and returning filling and removal etc complete all as specified and directed.
20
-
-
M&L for providing earthing chambers made up of PCC 1:2:4 type B1,(using 20mm graded stone aggregate) including necessary formwork over 75mm thick PCC bed, 1:3:6 type C2 (using 40mm graded stone aggregate) with provision of 10mm thick CI chamber cover with hinge all as per electrical plate no.3 of SSR part-I including demolition of old unserviceable earthing chamber complete all as specified and directed.
15
-
-
S&F in repair earthing 10mm thick CI chamber cover with hinge suitable for existing earthing chambers at site including taking down old unserviceable chamber cover complete all as specified and directed.
20
-
-
M&L for Test point terminal box made of gun metal or phosphorous bronze, size 75x75x25 mm drilled and screwed including 3 Nos 8 mm dia 25 mm long hexagonal head screw including removing the existing u/d test point terminal block complete all as specified and directed.
22
-
-
M & L for recharging of normal earth pits by excavating the earth at a radius of 600mm from the centre from the earth pit and at a depth of 900mm after removing the earth chambers and accessories carefully and keeping aside for reuse including adding and spreading Charcoal 10 Kg and Salt 10 Kg in 75mm layers each at ground level and watering, refixing the earth chambers and accessories after allowing the soil to settle down complete all as specified and directed.
20
-
-
M&L for Testing of existing earthing resistance with suitable digital Earth tester and recording the readings obtained including making the earthing good by pouring the salt water complete up to the satisfaction of the Engr-in-Charge.
Note :
(a) Value of earth resistance should be less than 1 Ohms for equipments earthing and less than 5 ohms for LA & Power Supply earthings.
(b) A register will be maintained for building/establishment/ section wise (for Equipment earthing, LA, Power etc) duly obtaining the sign of the user.
110
-
-
M&L for Testing of existing earthing resistance with suitable digital Earth tester and recording the readings obtained.
Note:
(a) A register will be maintained for building/establishment/ section wise (for Equipment earthing, LA, Power etc) duly obtaining the sign of the user.
1000
-
-
Supply and fix in replacement 10 mm dia and 1000 mm length solid aluminium blunt tip Air termination with Base plate (Vertical air terminal with accessories providing of Air terminals as per IS-IEC -62305) along with concrete block for fixing AT on Terrace with all mounting accessories complete all as specified and directed.
6
-
-
Supply and fix in repair 8 mm dia solid Aluminium Conductor for roof top mesh grid meets the requirement of IS IEC 62305 (As specified in Drawing) complete all as specified and directed.
50
-
-
Supply and fix in repair conductor holding clamp suitable for mesh grid Conductor holder each at 1 meter distance to meets the requirement of IS IEC 62305 complete all as specified and directed.
50
-
-
Supply and fix in repair cross universal connector for T and cross connection, to route vertical down conductor /mesh formation meet the requirement complete all as specified and directed.
15
-
-
Supply and fix in repair Expansion Piece with connector to compensate the expansion and contraction of Solid Round Al. Conductor during temperature variations to be provided on conductors length over 20 meters with Expansion Piece Connector for to connect Solid Round Al. Conductor at both ends to meet the requirements of IS/IEC 62305 complete all as specified and directed.
8
-
-
Supply and fix in repair Straight Splicers for Aluminium Conductor meet the requirement of IS IEC 62305 tested as per IS IEC 62561-7 Standard complete all as specified and directed.
10
-
-
Supply and fix in repair test link in order to disconnect the earth termination system for enabling measurements. to connect Aluminium round conductor to Ring Earthing complete all as specified and directed.
15
-
-
Supply and fix in repair 10 mm copper bonded Round steel solid Conductor in compliance with IS/ IEC 62305 and IEC 62561-2. The coating shall be smooth, continuous & free from flux stains(Ring Earthing) should be tested and use exclusively for lightning protection ,earthing system and ring equipotential bonding complete all as specified and directed.
25
-
-
Supply and fix repair conductor holding clamp suitable for 10mm Cu. Bonded Steel Conductor complete all as specified and directed.
40
-
-
Supply and fix in repair SS Straight Connector for connecting Ring Conductor suitable for 10mm Cu. Bonded Steel Conductor to meet the requirement for IS/IEC-62305 complete all as specified and directed.
8
-
-
Supply and fix repair SS Cross Splicer -Providing of cross universal connector For T and cross connection, to route vertical down conductor with stud connection meets the requirements of IS / IEC 62305 complete all as specified and directed.
15
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements
Past BiddersThis list is curated from the bidders of the similar tenders in the past
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%