Power Development Department Tender

... More
Search from the latest JKtenders and find a business opportunity fitting your SME on the online platform of BidAssist. If you're wondering how to find the latest JK tenders or from where to get all the documents without the hassles, this is what we explain here. Find the best opportunities coming to the surface via the JK government, PSUs and state corporations.

Power Development Department - PDD Tender

Works
Energy, Oil and Gas
Eprocure
Opening Date16 Jan 2025
Closing Date21 Feb 2025
Tender Amount₹ 3,61,68,000 
Notes
Download

AI Insights

Bid Capacity
... View More
The bid capacity required in the given tender includes both financial and technical requirements. Financially, the bidder must have: - A Minimum Average Annual Turnover (MAAT) of at least 30% of the estimated cost of the project, which is 0.3 * 361.68 Lacs = Rs. 108.504 Lacs. - Liquid Assets (LA) and/or evidence of access to or availability of fund-based credit facilities of not less than 10% of the estimated cost of the project, which is 0.1 * 361.68 Lacs = Rs. 36.168 Lacs. Technically, the bidder needs to have experience in similar work(s) with a total value of at least: - 70% of the estimated project cost for a single contract, which is 0.7 * 361.68 Lacs = Rs. 253.176 Lacs. - 40% of the estimated project cost for each of two contracts, which is 0.4 * 361.68 Lacs = Rs. 144.672 Lacs per contract. - 30% of the estimated project cost for each of three contracts, which is 0.3 * 361.68 Lacs = Rs. 108.504 Lacs per contract. Additionally, for electrical works at EHV Level, the bidder should have executed works with specific values: - 1 Work Equivalent to 80% of the Estimated Cost, which is 0.8 * 361.68 Lacs = 289.344 Lacs. - OR 2 Works each Equivalent to 50% of the Estimated Cost, which is 0.5 * 361.68 Lacs = 180.84 Lacs per work. - OR 3 Works each Equivalent to 40% of the Estimated Cost. Formulas provided include: - Liquid Assets = unencumbered cash (and equivalents) + bank deposits with maturity less than 365 days + securities that can be freely traded or maturity less than 365 days + receivables which has general certainty of getting received - payables which has general certainty of getting paid. - Minimum liquid assets required = 10% of the estimated cost of the project. - Joint Venture criteria: (Lead partner's capacity >= 40% of minimum criteria) AND (Each other partner's capacity >= 25% of minimum criteria).
Technical Capacity
... View More
The required prior work experience for the bidder is as follows: - 1 Work Equivalent to 80% of the Estimated Cost, which is 289.34 Lacs - 2 Works each Equivalent to 50% of the Estimated Cost, which is 2 x 180.84 Lacs - 3 Works each Equivalent to 40% of the Estimated Cost, which is 3 x 144.67 Lacs Additionally, the bidder shall meet the following minimum criteria in the past 7 years: - Experience in similar work under single contract, costing not less than the amount equal to 70% of the estimated amount of the project - Or Experience in similar works under two contracts, each costing not less than the amount equal to 40% of the estimated amount of the project - Or Experience in similar works under three contracts, each costing not less than the amount equal to 30% of the estimated amount of the project. Each JV partner should have completed at least 1 contract costing not less than the amount equal to 30% of the estimated amount of the project. The estimated amount of the project is 361.68 Lacs. The percentage of similar works completed is mentioned as 70%, 40%, and 30% for single, two, and three contracts respectively. The amount for similar works completed is not less than 70%, 40%, and 30% of the estimated amount of the project, which is 361.68 Lacs. The values are: - 70% of 361.68 Lacs = 253.17 Lacs - 40% of 361.68 Lacs = 144.67 Lacs - 30% of 361.68 Lacs = 108.5 Lacs These values and percentages are mentioned for the purposes of satisfaction of Technical Requirement, where similar works refer to commissioning, overhauling of power transformer above the rating 20 MVA and installation of C&R panels at 66KV/132 KV/ 220KV level.

Costs

Summary

Capital Maintenance Of 200 Mva 220 132kv Auto Transformer At 320mva 220 132 66kv Grid Station Hiranagar

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Inspection and Testing of Transformers including Drying/Replacement of Silica Gel Checking of buchloz relay, Surge Relay temperature sensor/Cooling system, Measurement of IR Values, BD Values of transformer oil.

4

-

-

... More
Cleaning of Transformer, Dehyderation of Transformer including use of vaccum pumps, filling of drained transformer oil, and fresh oil after filteration and obtaining aquarate BDV values.

92800

-

-

... More
Final Erection check including connection of LV & HT jumpers, Control wiring etc.

4

-

-

... More
Supply of fresh transformer oil as per IS335/193

56700

-

-

... More
DGA and PPM of Transformer oil from accredited labortaries

4

-

-

... More
Supply of paints & Painting of Transformers (Zinc chromate metal primer,Epoxy Paint of shade-IS 631 etc)

4

-

-

... More
Overhauling of OLTC of transformer including material cost.

4

-

-

... More
Supply & Fixing of Silica Gel Breather

4

-

-

... More
Supply and replacement of cooling Fans

32

-

-

... More
Supply and replacement of Gate Valves Spare for one transformer (80Nb-3 No, 50Nb-7 No,25Nb-5 No)

1

-

-

... More
Supply, installation, testing and commissioning of damaged/outlived 220KV bushing including crane/mechanical equipment

2

-

-

... More
Supply, installation, testing and commissioning of damaged/outlived 132KV bushing including crane/mechanical equipment

2

-

-

... More
Supply, installation, testing and commissioning of outlived neutral bushing including crane/mechanical equipment

4

-

-

... More
Supply & Fixing Aircell

4

-

-

... More
Supply & Replacement of O-Rings, oil seals and Gaskets of different thickness as per requirement

1

-

-

... More
Supply of WTI and OTI

4

-

-

... More
C&R Panels-Supply part: a) 220KV Control and Relay Panel for Transformer Bay completely wired including Substation automation supporting IEDs/numerical relays including Differential relay, Directional 3 O/C 1 E/F protection and numerical communicable REF protection relay

2

-

-

... More
b) 220KV Control and Relay Panel for Line/Feeder completely wired including Substation automation supporting IEDs/numerical relays with DistanceRecorder.

4

-

-

... More
c) 132KV Control and Relay Panel for Transformer bay completely wired including Substation automation supporting IEDs/numerical relays including Differential relay, Directional 3 O/C 1 E/F protection and numerical communicable REF protection relay.

2

-

-

... More
d) 132KV Control and Relay Panel for Line/Feeder completely wired including Substation automation supporting IEDs/numerical relays inlcuding Distance Recorder.

2

-

-

... More
e) 66 KV Control and Relay Panel for 66 KV Line Bay completely wired & SCADA Compatible including Substation automation supporting IEDs/numerical relays.

1

-

-

... More
f) 66 KV Control and Relay Panel for 66 KV Transformer Bay completely wired & SCADA Compatible including Substation automation supporting IEDs/numerical relays.

2

-

-

... More
C&R Panels-Replacement/erection, testing and commissioning part: a) 220KV Control and Relay Panel for Transformer Bay completely wired including Substation automation supporting IEDs/numerical relays including Differential relay, Directional 3 O/C 1 E/F protection and numerical communicable REF protection relay.

2

-

-

... More
b) 220KV Control and Relay Panel for Line/Feeder completely wired including Substation automation supporting IEDs/numerical relays with DistanceRecorder.

4

-

-

... More
c) 132KV Control and Relay Panel for Transformer bay completely wired including Substation automation supporting IEDs/numerical relays including Differential relay, Directional 3 O/C 1 E/F protection and numerical communicable REF protection relay.

2

-

-

... More
d) 132KV Control and Relay Panel for Line/Feeder completely wired including Substation automation supporting IEDs/numerical relays inlcuding Distance Recorder.

2

-

-

... More
e) 66 KV Control and Relay Panel for 66 KV Line Bay completely wired & SCADA Compatible including Substation automation supporting IEDs/numerical relays.

1

-

-

... More
f) 66 KV Control and Relay Panel for 66 KV Transformer Bay completely wired & SCADA Compatible including Substation automation supporting IEDs/numerical relays.

2

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.