Military Engineer Services Tender
... More
Search from the latest JKtenders and find a business opportunity fitting your SME on the online platform of BidAssist. If you're wondering how to find the latest JK tenders or from where to get all the documents without the hassles, this is what we explain here. Find the best opportunities coming to the surface via the JK government, PSUs and state corporations.
Military Engineer Services - MES Tender
Civil And Construction
Building Construction
Eprocure
Opening Date2 May 2025
Closing Date6 Jun 2025
Tender Amount₹ 3,75,00,000
AI Insights
Technical
Technical
Financial
Additional Eligibility
Class Of Bidder
... View More
Class 'A' and category 'a(i)'
Technical Capacity
... View More
The required prior work experience for the bidder is not explicitly stated in terms of specific years or amount. However, it is mentioned that the bidder should have previously completed similar works satisfactorily and meet the criteria of upgradation in respect of past experience of completed works and financial soundness. The value of similar works completed is to be submitted in a specific format, but the exact values and percentages are not specified. No specific percentage of similar works completed is mentioned.
Costs
EMD
₹ 4,50,000Document Cost
₹ 2,000Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2025_MES_706200_1Tender No
Token 05/2025-26Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Total amount of Sch 'A' PART-III ( Sanitary Work)
1
45260
-
... More
Total amount of Sch 'A' PART-IV ( Sewage Disposal Works)
1
104966
-
... More
Sch 'A' PART-IV ( Section- II)( Sewage Disposal Works) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
-
-
-
... More
M&L for on site LLDPE septic tank convntional type designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below foundation, Vent shaft, connection etc., complete for 25 users.
1
-
-
... More
M&L for Soakage wells excavation, in any type of soil, foundation in PCC 1:3:6, walls of honey combed masonry with top ring of M25 concrete including intercepting chamber and screen chamber made of Brick masonary in CM, RCC cover slab in M25/ SFRC cover, interconnecting pipes of RCC/DWC complete filled with brick bats of size, complete of size 1.80 M dia X 3.00 M deep(effective depth).
1
-
-
... More
Total amount of Sch 'A' PART-V (Road/Path/Culvert Works )
1
124309
-
... More
Total amount of Sch 'A' PART-VI (SECTION-I) ( INTERNAL ELECTRICATION)
1
73126
-
... More
Sch 'A' PART-VI ( Section-II) ( INTERNAL ELECTRICATION) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
-
-
-
... More
S&F LED highbay Light fitting 200 watt, for opearting voltage between 120V to 300V system efficiency not less than 110 lumen / watt, PF-0.95 minimum, IP66 protection, 6000CCT(K), CRI between 80-85, for estimated life span of minimum 50,000 hrs, maintenance free isolated Electronic driver circuits, Low THD, PMMA grade high quality Transmittance lens, Epoxy powder coated Die Cast Aluminium housing with LED street optics LENS for uniform light distribution, weather proof gasket for lamp & driver compartment, Heat resistance toughened UV stabilized glass fitted in cast aluminium housing with SS screws, including all hanging accessories for mounting on ceiling as per OEM and connecting up with three core flexible copper conductor cable with suitable size,complete all as specified and directed.
81
-
-
... More
M&L for concealed point wiring with 1.5 Sqmm size FRLSH copper conductor cable single core multi stranded including PVC conduit medium grade with all fittings and MS terminal boxes suitable for housing modular switches, socket and regulators including modular inner plate and cover plates of suitable modules and 1.5 Sqmm size FRLSH copper conductor cable single core multi standard and connection to common earth dolly all as specified and directed for the following:-
(a) One light/fan /bell point controlled by one switch one way.
20
-
-
... More
M&L for concealed point wiring with 1.5 Sqmm size FRLSH copper conductor cable single core multi stranded including PVC conduit medium grade with all fittings and MS terminal boxes suitable for housing modular switches, socket and regulators including modular inner plate and cover plates of suitable modules and 1.5 Sqmm size FRLSH copper conductor cable single core multi standard and connection to common earth dolly all as specified and directed for the following:-
(a) One 3 pin socket outlet 5/6 Amp independent board
2
-
-
... More
M&L for concealed point wiring with 2.5 Sqmm size FRLSH copper conductor cable single core multi stranded including PVC conduit medium grade with all fittings and MS terminal boxes suitable for housing modular switches, socket and regulators including modular inner plate and cover plates of suitable modules and 2.5 Sqmm size FRLSH copper conductor cable single core multi standard and connection to common earth dolly all as specified and directed for the following:-
(a) One 16 Amp socket outlet on independent board
2
-
-
... More
Supply & fix modular switch one way 16Amp ,1 module including MS terminal boxes suitable for housing modular switches, with modular inner plate and cover plates flush in wall complete all as specified and directed.
9
-
-
... More
Supply & fix modular switch one way 6Amp ,1 module including MS terminal boxes suitable for housing modular switches, with modular inner plate and cover plates flush in wall complete all as specified and directed.
5
-
-
... More
Supply & fix modular Switch socket outlet multipurpose 3 pin, 15 amp and one pin, 5 amp controlled by one switch including MS terminal boxes suitable for housing modular switches, with modular inner plate and cover plates flush in wall complete all as specified and directed.
16
-
-
... More
S & F LED batten surface / wall mounted with specially designed powder coated aluminium housing, high optically efficient polycarbonate diffuser, in built electronic driver duly wired up to terminal block, power consumption 20W, luminaire lumen 2000 lm, system efficiency of 120 lumens/W, with LED binning as per ANSI Bin C78.377A, photo biological safety report as per IEC624718 & electrical insulation class 1, Ingress protection IP 20, colour rendering index CRI80, temp range 0 to 450C, driver efficiency85%, power factor 0.95, THD 20% as per IEC 61000-3-2, colour temp -6500K, surge protection 2.5 KV, 50,000 burning hrs (min) as per L7O criteria, two stages isolated constant current operated driver with range 150-270V AC and safety extra low voltage safe level 60 V DC as per IEC standard with LM70 & LM 80 certification.
14
-
-
... More
S&F LED Street Light fitting 35 watt, for opearting voltage between 120V to 300V system efficiency not less than 120 lumen / watt, PF-0.95 minimum, IP66 protection, 5700CCT(K), CRI between 80-85, confirming to LM79 and LM 80 standards or as per IS-16104:2012 and IS-16106:2012, for estimated life span of minimum 50,000 hrs consisting of high / low voltage cut off, maintenance free isolated Electronic driver circuits, Low THD, PMMA grade high quality Transmittance lens, Epoxy powder coated Die Cast Aluminium housing with LED street optics LENS for uniform light distribution, weather proof gasket for lamp & driver compartment, Heat resistance toughened UV stabilized glass fitted in cast aluminium housing with SS screws, including bracket made out of GI light grade pipe of suitable dia 1.5 mtr long bend to an angle of 120 degree with 02 Nos MS clamp 50mm x 5 mm and 04 sets of nuts,bolts and washers complete all as specified and as directed by Engr-in-charge.
5
-
-
... More
S&F of Exhaust fan 200 mm sweep, PVC body, AC, single phase, 230 Volts, including connection with 1.5 sqmm mutistrand copper conductor flexible wire from ceiling rose, including outside louvers with proper hole, and necessary fixing arrangement complete all as specified and directed.
2
-
-
... More
M&L Sub main wiring using four runs of PVC insulated and unsheathed fire retardant low smoke and halogen (FR-LSH) copper conductor single core multi stranded unsheathed copper cable 04.00 sqmm (for Phase and neutral) and two runs of earth continuity conductor of size 04.00 sqmm multistranded copper conductor FRLSH 1100V conforming to IS:694 (2010) using approved colour code for phase and neutral as per IS code drawn through non-metallic PVC rigid concealed conduit, 25mm outer dia (ISI marked) heavy mechanical stress (HMS) grade in accordance with IS:9537 (Part 3) having wall thickness not less than 2.0 mm thick. The external dia shall be increased as per actual site requirement in accordance with clause No 19.125 of SSR Part I (ISI marked) including conduit accessories like bends, tees, junction boxes etc fixed concealed with all accessories complete all as specified and as directed by Engineer-in-charge.
65
-
-
... More
M&L Sub main wiring using PVC insulated and unsheathed fire retardant low smoke and halogen (FR-LSH) copper conductor single core multi stranded unsheathed copper cable 04.00 sqmm (for Phase and neutral) and earth continuity conductor of size 04.00 sqmm multistranded copper conductor FRLSH 1100V conforming to IS:694 (2010) using approved colour code for phase and neutral as per IS code drawn through non-metallic PVC rigid concealed conduit, 20mm outer dia (ISI marked) heavy mechanical stress (HMS) grade in accordance with IS:9537 (Part 3) having wall thickness not less than 2.0 mm thick. The external dia shall be increased as per actual site requirement in accordance with clause No 19.125 of SSR Part I (ISI marked) including conduit accessories like bends, tees, junction boxes etc fixed concealed with all accessories complete all as specified and as directed by Engineer-in-charge.
20
-
-
... More
M&L Sub main wiring using PVC insulated and unsheathed fire retardant low smoke and halogen (FR-LSH) copper conductor single core multi stranded unsheathed copper cable 2.5 sqmm (for Phase and neutral) and earth continuity conductor of size 2.5 sqmm multistranded copper conductor FRLSH 1100V conforming to IS:694 (2010) using approved colour code for phase and neutral as per IS code drawn through non-metallic PVC rigid concealed conduit, 20mm outer dia (ISI marked) heavy mechanical stress (HMS) grade in accordance with IS:9537 (Part 3) having wall thickness not less than 2.0 mm thick. The external dia shall be increased as per actual site requirement in accordance with clause No 19.125 of SSR Part I (ISI marked) including conduit accessories like bends, tees, junction boxes etc fixed concealed with all accessories complete all as specified and as directed by Engineer-in-charge.
460
-
-
... More
M&L Sub main wiring using PVC insulated and unsheathed fire retardant low smoke and halogen (FR-LSH) copper conductor single core multi stranded unsheathed copper cable 2.5 sqmm (for Phase and neutral) and earth continuity conductor of size 2.5 sqmm multistranded copper conductor FRLSH 1100V conforming to IS:694 (2010) using approved colour code for phase and neutral as per IS code drawn through non-metallic PVC rigid conduit, 20mm outer dia (ISI marked) heavy mechanical stress (HMS) grade in accordance with IS:9537 (Part 3) having wall thickness not less than 2.0 mm thick. The external dia shall be increased as per actual site requirement in accordance with clause No 19.125 of SSR Part I (ISI marked) including conduit accessories like bends, tees, junction boxes etc fixed with all accessories complete all as specified and as directed by Engineer-in-charge.
340
-
-
... More
M&L Sub main wiring using PVC insulated and unsheathed fire retardant low smoke and halogen (FR-LSH) copper conductor single core multi stranded unsheathed copper cable 1.5 sqmm (for Phase and neutral) and earth continuity conductor of size 1.5 sqmm multistranded copper conductor FRLSH 1100V conforming to IS:694 (2010) using approved colour code for phase and neutral as per IS code drawn through non-metallic PVC rigid concealed conduit, 20mm outer dia (ISI marked) heavy mechanical stress (HMS) grade in accordance with IS:9537 (Part 3) having wall thickness not less than 2.0 mm thick. The external dia shall be increased as per actual site requirement in accordance with clause No 19.125 of SSR Part I (ISI marked) including conduit accessories like bends, tees, junction boxes etc fixed concealed with all accessories complete all as specified and as directed by Engineer-in-charge.
320
-
-
... More
S and F Sheet metal enclosure Vertical TPN distribution board Conforms to IS 8623-1 & 3, IEC 61439-1 & 3 with MCCB Incomer, 415 volts 12 way with IP-43 IK-09 protection double door complete with 200 Amp size bus bar and neutral link, fixed flush in wall including chases cutting in wall for fixing DB and making good distributed wall surfaces to match with existing specification complete all as specified and directed. Note - MCCB/ MCBs will be measured and paid separately.
1
-
-
... More
S&F MCCB with Thermal - magnetic release of 125 Amps, 4 Pole, 415V, 18 kA, Ics=100%Icu with adjustable over load setting and adjustable short circuit setting including all accessories complete all as specified and as directed
1
-
-
... More
Supply and fixing MCB Double Pole 16 Amps rating 240V, 10KA 'C' curve miniature circuit breaker complete with connection testing and commissioning complete all as specified.
1
-
-
... More
Supply and fixing MCB three pole 32 Amps rating 240V, 10KA 'C' curve miniature circuit breaker complete with connection testing and commissioning complete all as specified.
2
-
-
... More
Supply and fixing LED aviation light 10Watt with integarl driver incorporating 302nos LED comprising of aluminium housing with red polycaronate enclosure dome of opearting voltage between 100V to 270V AC,50,000 burning hrs (min),minimum IP65 protection having protection against short-circuit and protection against surge including mounting arrangement complete all as specified.
1
-
-
... More
Material & Labour for earthing with galvanised steel earth plate electrode of size 60cmx60cmx6mm thick buried directly in ground (earth pit not less than 2.25m deep below the ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to the galvanised earth lead by means of bolts, nuts check nuts and washers of galvanised iron or steel using GI or steel wire 4 mm dia as earthing lead as shown in electrical plate No.3 of SSR Part-I connected to earthing test point all as specified or indicated including testing on completion including necessary excavation and earth work in soft/loose soil, returning filling, disposal of surplus soil, earth pit in PCC 1:3:6 type C-1 using 20mm graded stone aggregate pit,funnel,20mm dia GI medium grade watering pipe, 15mm dia GI light grade earth lead protection pipe, CI frame and cover, wire, copper lugs etc mesh, chorcoal and common salt in alternatee layer complete all as specified and directed.
NOTE:
(i) Main earthing lead and GI protection pipe 15 mm dia upto 7.5 meter is included in quoted rate beyond 7.5 meters shall be measured and paid seperately under appropriate item.
(ii) Excavation and earth work or drilling hole for electrode is deemed to be included in quoted rate.
2
-
-
... More
Total amount of Sch 'A' PART-VI (Section-II) (INTERNAL ELECTRIC SUPPLY WORK)
-
-
-
... More
Total amount of Sch 'A' PART-VII (SECTION-I) (Lightening Protection Works)
1
86291
-
... More
SCHEDULE `A' PART-VII (SECTION-II) (Lightening Protection Works) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
-
-
-
... More
Earthing with galvanised steel plate elctrode 600x600x6 mm thick, burried directly in ground (earth pit not less than 2.25 mtr below GL) with the top edge of the plate not less then 1.5 mtr below the normal ground level connected to GI strip 25x4 mm dia proteted by 40 mm GI pipe( light grade) and chamber PCC (1:4:8) type D2 using 40 mm grated stone aggregate, coping shall be (1:3:6) type C1 using 20 mm stne aggregate with RCC pit cover 50mm thick in (1:2:4) type B1 using 20 mm stone aggregate reinforced with 8 mm for MS bar at 80mm c/c both way in lieu of CI pit cover with angle iron frame including excavation and earth work and removal of surplus soil complete all as shown in electrical plate No. 3 of SSR Part I and as specified including charcoal dust, common salt complete and earth lead connected to earthing test point /main board all as specified and testing of earthing complete. Note : Protection pipe and GI strip upto 7.5 mtr is included in the unit rate. contractor shall be deemed to quote the rate accordingly.
NOTE:
(i) Main earthing lead and GI protection pipe 40 mm dia upto 7.5 meter is included in quoted rate beyond 7.5 meters shall be measured and paid seperately under appropriate item.
(ii) Excavation and earth work or drilling hole for electrode is deemed to be included in quoted rate.
8
-
-
... More
Total amount of Sch 'A' PART-VII (SECTION-II) (Lightening Protection Works)
-
-
-
... More
Total amount of Sch 'A' PART-VIII(EXTERNAL WATER SUPPLY WORKS)
1
18808
-
... More
SCHEDULE `A' PART-VIII (SECTION-II) (EXTERNAL WATER SUPPLY WORKS) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
-
-
-
... More
Material and labour for construction of brick masonry valve pit of size 450mm x 450mm x 450mm (internal dimensions), using old size sub class 'B' brick, built in CM 1:6 and 10 mm thick cement plaster 1:4 both internally and externally with 75 mm thick PCC 1:3:6 type C-2 in foundation, PCC 1:2:4 type B-2 in benching complete with and including 2 mm thick mild steel sheet cover (mounted on angle iron frame of size 50 mm x 50 mm x 6 mm thick, embedded in PCC 1:2:4 type B-1 coping), fitted with proper locking arrangement, hinges and handle of suitable size and painting with two coats of black bituminous paint over a coat of red oxide zinc chrome primer on all steel surfaces, including necessary earth work ( in soft/loose soil), returning filling and removal of surplus soil to a distance n.exc 50 m complete all as specified and directed..
1
-
-
... More
Total amount of Sch 'A' PART-VIII(EXTERNAL WATER SUPPLY WORKS)
-
-
-
... More
Total amount of Sch 'A' PART-IX (Section-I) (External Electric supply)
1
782209
-
... More
SCHEDULE `A' PART-IX(SECTION-II) (External Electric supply) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
-
-
-
... More
Material & Labour for earthing with galvanised steel earth plate electrode of size 60cmx60cmx6mm thick buried directly in ground (earth pit not less than 2.25m deep below the ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to the galvanised earth lead by means of bolts, nuts check nuts and washers of galvanised iron or steel using GI or steel wire 4 mm dia as earthing lead as shown in electrical plate No.3 of SSR Part-I connected to earthing test point all as specified or indicated including testing on completion including necessary excavation and earth work in soft/loose soil, returning filling, disposal of surplus soil, earth pit in PCC 1:3:6 type C-1 using 20mm graded stone aggregate pit, funnel,20mm dia GI medium grade watering pipe, 15mm dia GI light grade earth lead protection pipe, CI frame and cover, wire, copper lugs etc mesh, chorcoal and common salt in alternatee layer complete all as specified and directed.
NOTE:
(i) Main earthing lead and GI protection pipe 15 mm dia upto 7.5 meter is included in quoted rate beyond 7.5 meters shall be measured and paid seperately under appropriate item.
(ii) Excavation and earth work or drilling hole for electrode is deemed to be included in quoted rate.
2
-
-
... More
Supply, testing and commissioning of outdoor type dust & vermin proof L.T. Panel board cubicle type totally enclosed with outer shell shall be made out of 3.15 mm thick sheet & MS angle section of suitable size for frame, factory fabricated, compartmentalized inner shell shall be made of out of 2.0 mm thick sheet .The Panels must be design and verified as per the IS/IEC 61439-01 & 2 with complete type test certificates for conformance to IS / IEC 61439 -1 and 2, with 65 KA 1 sec along with MCCB mounted in switch boards with aluminium bus bars conformed to IEC 61641 with internal arc containment fault level of 65 KA/03 Sec and shall be suitable for Seismeic Zone III/IV Zone including the type test conducted at ERDA/CPRI for seismic test.All MCCB/ ACB panel should be single Tier for easy cable termination.Cable termination space should be adequate to safely gland and terminate al/cu cables for the given current ratings with Form B seperation for Incoming MCCB / ACB feeders and For Outgoing MCCB feeders. The Switch board cubicles shall have steel frame work enclosed on all sides and top by CRCA sheet steel of Minimum 2.00 mm thickness.The panel shall have integral base frame of 100 MM ISMC base channel.removeable undrilled gland plates shall be fitted for bottom cable entry and making connections, earth work and PCC foundation complete comprising of the followings and specified herewith:- (i) Rectangular Aluminium bus bar fixed on insulated mounting arrangement of rating 1.5 times current carrying capacity of incoming switch gear or not less than 200 Amp whichever higher provided with heat shrinkable sleeve not less than one mm thick. -04 Nos (ii) Cable alley (a) INCOMING (i) MCCB 4P 125 Amps Icu =16 KA at 415 volts with microprocessor release type - 01 No (I/C) . Ics = 100 % Icu, adjustable overload setting from 0.4 to 1.0 x In ,adjustable short-circuit setting from 1.5 to 8 x Ir and class II front face, Isolation with positive break indication with double break contacts, Standard extended rotary handle,Spreaders, Phase barrier etc . (ii) 3 lines LCD display 3P, 4W, VAF + PF meter in 96 x 96 sqmm flush mounted case, accuracy class 1.0 - 01 No (iii) Suitable CTs of cast resin type with necesaary CT shortlinking should be provieded . - 1 set. (b) OUTGOING (i) MCCB 4P 100 Amps Icu =16 kA at 415 volts Thermal - Magnetic Release - 01 No (I/C) . Ics = 100 % Icu,with adjustable over load setting and adjustable short circuit setting and class II front face, Isolation with positive break indication with double break contacts, Standard extended rotary handle,Spreaders, Phase barrier etc .
2
-
-
... More
(ii) MCCB 4P 63 Amps Icu =16 kA at 415 volts Thermal - Magnetic Release - 01 No (I/C) . Ics = 100 % Icu,with adjustable over load setting and adjustable short circuit setting and class II front face, Isolation with positive break indication with double break contacts, Standard extended rotary handle,Spreaders, Phase barrier etc .
-
-
-
... More
Construction of Platform with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 mm thick in foundation, brick work in CM 1:6 with sub class "B" old size brick, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc of size 2500mm x 2000mm x 1200mm with fencing foldable upto 1.5m height, gate with locking arrangements using GI wire mesh, GI wire 4mm dia, angle iron, MS plate etc, complete all as specified and directed.
1
-
-
... More
Total amount of Sch 'A' PART-IX(SECTION-II) (External Electric supply)
-
-
-
... More
Total amount of Sch 'A' PART-X (COOLING APPLAINCE )
1
43410
-
... More
SCHEDULE `A' PART-X(SECTION-II) (COOLING APPLAINCE) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
-
39
-
... More
S & F Voltage stabilizer copper wonded wall mounted for automatic operation single phase naturally cooled indoor type and designed for input variation between 170V to 270V with Built In Thermal Overload Protection of current capacity 15 Amp ,3350 VA complete all as specified and directed.
1
-
-
... More
Total amount of Sch 'A' PART-X (COOLING APPLAINCE )
-
-
-
... More
Total amount of Sch 'A' PART-XI (SITE CLEARNACE, EXACAVATION AND EARTHWORK )
1
47389
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements
Past BiddersThis list is curated from the bidders of the similar tenders in the past
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%