Search from the latest JKtenders and find a business opportunity fitting your SME on the online platform of BidAssist. If you're wondering how to find the latest JK tenders or from where to get all the documents without the hassles, this is what we explain here. Find the best opportunities coming to the surface via the JK government, PSUs and state corporations.

Military Engineer Services - MES Tender

Works
Civil And Construction
Civil Works Others
Eprocure
Opening Date20 Feb 2025
Closing Date27 Mar 2025
Tender Amount₹ 5,28,25,000 
Notes
Download

AI Insights

Class Of Bidder
... View More
Class 'A' and Category '(a) (i) BUILDING WORKS'
Technical Capacity
... View More
The required prior work experience for the bidder is in similar nature of works, which means Building works. The bidder needs to have completed similar works satisfactorily, and provide details of three highest valued similar nature of works executed during the last seven years, financial year-wise, in a tabular form. This includes name of work, Accepting Officer's details, date of acceptance of tender, and actual date of completion. The value and percentage of similar works completed are not explicitly mentioned. However, the bidder needs to meet the enlistment criteria of 'A' Class MES contractors and category '(a) (i) BUILDING WORKS', which includes satisfactorily completing requisite value works with Central/ State Govt/ Central/ State PSUs/ AWHO/ AFNHB/ CGEWHO/ DGMAP. The bidder should have an annual turnover certificate from CA/ Income tax deduction at source (TDS) certificates (26AS) in support of annual turnover during the last 5 years, and a balance sheet of the last 5 years in case of Limited Companies. Additionally, the bidder should have a solvency and working capital certificate from a scheduled bank, indicating that the bidder is solvent up to Rs. 2.00 Crores OR financially sound for engagement up to Rs. 7.50 crores, and having working capital not less than Rs. 30.00 Lakhs. For contractors one class below the eligible class, they should have previously completed similar works satisfactorily and meet the criteria of upgradation in respect of past experience of completed works (individual work experience and average annual turnover) and financial soundness (solvency/financial soundness and working capital). Contractors one class/two class below the eligible class shall not be considered if their present residual work in hand is more than FIVE TIMES their present tendering limit.

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Lump sum price worked out by the contractor for INTERNAL ELECTRIFICATION WORKS carried forward from Pre-Priced Schedule 'A' Part-II.

1

443247

-

... More
Lump sum price worked out by the contractor for AREA DRAINAGE WORKS carried forward from Pre-Priced Schedule 'A' Part-III.

1

1777637

-

... More
Lump sum price worked out by the contractor for ROAD/ PATH/ HARD STANDING AND CULVERT WORKS carried forward from Pre-Priced Schedule 'A' Part-IV.

1

16349388

-

... More
Lump sum price worked out by the contractor for SEWAGE DISPOSAL WORKS carried forward from Pre-Priced Schedule 'A' Part-V.

1

375617

-

... More
Lump sum price worked out by the contractor for RETAINING WALL WORKS carried forward from Pre-Priced Schedule 'A' Part-VI.

1

2204812

-

... More
Lump sum price worked out by the contractor for FENCING, SECURITY WALL AND GATE WORKS carried forward from Pre-Priced Schedule 'A' Part-VII.

1

15990340

-

... More
Lump sum price worked out by the contractor for EXTERNAL ELECTRIFICATION WORKS carried forward from Pre-Priced Schedule 'A' Part-VIII.

1

764344

-

... More
Lump sum price worked out by the contractor for SITE CLEARANCE & EARTHWORKS carried forward from Pre-Priced Schedule 'A' Part-IX.

1

4681036

-

... More
Lump sum price worked out by the contractor for INTERNAL WATER SUPPLY WORKS carried forward from Pre-Priced Schedule 'A' Part-X.

1

99220

-

... More
INTERNAL ELECTRIFICATION WORKS (SCHEDULE 'A' PART-XI)

-

-

-

... More
Supply & Fixing of LED light fitting 1 x 20 Watt, 220V, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conuctor cable of suitable size from ceiling rose complete all as specified & directed.

80

-

-

... More
Supply & Fixing of LED Lamp 9 Watt , 'T' type, complete all as specified & directed.

20

-

-

... More
Supply & Fixing of LED street light fitting 25 Watt, 230V, AC outdoor type with high pressure die cast aluminium hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics, IP 65/66 protection complete all as specified & directed.

30

-

-

... More
SEWAGE DISPOSAL WORKS (SCHEDULE 'A' PART-XII)

-

-

-

... More
M&L for construction of 10 users LLPDE Septic Tank with upflow filter including media designed to carry sewage and sullage water, including excavation in any type of soil in foundation in PCC (1:2:4) type B-1 (using 20 mm graded crushed stone aggregate) brick masonry in CM (1:4) RCC (M-30 design Mix) slab including cast iron manhole cover having 6mm embeded plate embeded all around with angle iron frame vent shaft etc. complete all as specified, directed and shown on drawing.

5

-

-

... More
M&L for construction of soakage well of 1.8m internal dia and 3.00m deep below inlet level including necessary earth work filling with brick bats of guage 40 to 60mm, SWG inlet pipe junction 150mm bore including all other relevent works, complete all as specified, directed and shown on drawing.

5

-

-

... More
EXTERNAL ELECTRIFICATION WORKS (SCHEDULE 'A' PART-XIII)

-

-

-

... More
Supply, fixing and erect steel tubular swaged poles, ISI marked, complete with cast iron base plate, finial taper plug, bolts, nuts & screws drilling of holes for continous GI earth wire as specified type 410 SP-31 (9 metres long) including applying two coats of black bituminous paint internally throughout and externally upto embedded portion and applying two coats of synthetic enamel paint over one coat of red oxide primer with nblack and white strip of 30cm each upto 1.50 metre height and two coats of aluminium paint over a coat of red oxide primer externally on remaining exposed surface after preparation of surfaces and erection in position complete all as specified and directed. (NOTE : Excavation, Earthwork, PCC, channel, clamps, nuts, bolts shall be measured and paid separately under respective items)

30

-

-

... More
Supply and fixing GI pipe, bracket for street light fittings made out of GI pipe medium grade 1.20 m long bent to required angle/shape including necessary clamps, nuts, bolts and washers of suitable size and applying two coats of aluminium paint with a base coat of red oxide primer complete all as specified and directed.

30

-

-

... More
Supply and fixing PVC insulated unshealthed copper cable of size 1.50 sqmm 3 Core FR PVC for service connections from junction box to light fitting complete all as specified and directed.

250

-

-

... More
Supply and fixing loopin loopout fuse junction box made of thermo plastic polycarbonate with IP 66/67 weather proof for outdoor installation of size 155x210x92 mm (with knockouts of cable entry) protection with terminals and locking screw fitted with 3 phase with neutral copper Bus Bar, 415 Volts, 50 Hz and 6A MCB SP, suitable for cables off sizes and fixing on steel tubular pole at height not less than 1.5m above ground level with the help of clamps two Nos. of F1 20 x 3mm and suitable nuts and bolts, complete all as specified and directed.

30

-

-

... More
M&L for Earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6 mm thick buried directly in gound (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr below normal ground level, connected to galvanised iron strip 32 x 6mm as earthing lead by means of bolt, nuts check nuts and washers of galvanised iron and 4 mm dia GI earth wire with 40 mm dia GI pipe "light grade" for protection of earth lead and connected to control board or main switch or as directed including earthing pit in PCC (1:3:6) type C1 for chamber and pre-cast RCC cover of size 380 x 380 x 40 mm, frame of angle iron 25mmx25mmx3mm with lugs 02 Nos and with 8 mm dia MS bar handle made to shape, 20 mm dia GI light grade pipe for watering perforated at bottom 1.75 mtr long placed on top edge of earth plate, common salt and charcoal filling, test point made out of Bronze/Gun metal with fixing arrangement, funnel, wire mesh and excavation/earth work in hard/dense soil, returning filling in and removal of surplus soil to a distance not exceeding 50 metre, all as per electrical plate No 3 of SSR -2009 Part -I and connecting to earth test point all as specified or indicated including testing on completion, complete all as specified and directed.

8

-

-

... More
Note : (a) The quoted rate shall be deemed to include the cost of excavation & earth work in any type of soil. (b) The quoted rate shall be deemed to include the cost of charcoal and salt in alternate layers; GI strip and GI light grade protection pipe and GI medium grade watering pipe. (c) The quoted rate shall be deemed to include the cost of funnel, wire mesh, lugs, PCC, RCC, frame work and including provisions of testing of test point, connecting to test point and all the tests on completion. (d) Any variation in length shall be adjusted through deviation order.

-

-

-

... More
M&L for Earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6 mm thick buried directly in gound (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr below normal ground level, connected to galvanised earth lead wire 4.0mm dia as earthing lead by means of bolt, nuts check nuts and washers of galvanised iron and 4 mm dia GI earth wire with 20 mm dia GI pipe "light grade" for protection of earth lead and connected to control board or main switch or as directed including earthing pit in PCC (1:3:6) type C1 for chamber and pre-cast RCC cover of size 380 x 380 x 40 mm, frame of angle iron 25mmx25mmx3mm with lugs 02 Nos and with 8 mm dia MS bar handle made to shape, 20 mm dia GI light grade pipe for watering perforated at bottom 1.75 mtr long placed on top edge of earth plate, common salt and charcoal filling, test point made out of Bronze/Gun metal with fixing arrangement, funnel, wire mesh and excavation/earth work in hard/dense soil, returning filling in and removal of surplus soil to a distance not exceeding 50 metre, all as per electrical plate No 3 of SSR -2009 Part -I and connecting to earth test point all as specified or indicated including testing on completion, complete all as specified and directed. NOTE:- For Internal Electrification Works = 5 Nos. For External Electrification Works = 6 Nos.

11

-

-

... More
Note : (a) The quoted rate shall be deemed to include the cost of excavation & earth work in any type of soil. (b) The quoted rate shall be deemed to include the cost of charcoal and salt in alternate layers; galvanised wire 4 mm dia and GI light grade protection pipe and GI light grade watering pipe. (c) The quoted rate shall be deemed to include the cost of funnel, wire mesh, lugs, PCC, RCC, frame work and including provisions of testing of test point, connecting to test point and all the tests on completion. (d) Any variation in length shall be adjusted through deviation order.

-

-

-

... More
Supply installation Testing & Commissioning of ECO friendly Diesel Engine driven generating set outdoor type of capacity 10 KVA not less than 16 BHP, latest CPCB-IV norms nearest higher side 400/440 volts, AC 3 phase, 50 HZ, 4 wire, 0.8 PF directly coupled alternator and engine Water cooled with AMF Panel common steel base fixed on cement concrete in foundation as per OEM recommendation DG set of 10 KVA platform with inbuilt AMF panel with 2 Nos suitable size of contactors as 01 no for main supply and 01 No for DG supply as per manufacturer's recommendation and other accessories comprising of following and complete all as specified and directed:- Notes :- 1. The DG Set should be design considering the derating factor of altitude 5204 ft above sea level (Bandi (J&K)) extreme cold climate in winters. The ambient temp varies from (-) 5 degree C (in winter) to (+) 35 degree C (in summer). 2. After considering of derating factor by manufacturer on above mentioned location, the net output is required of 10 KVA DG set. 3. The Plinth should be as per Manufacturer's recommendation and the rate of plinth is deemed to be included in quoted rate. (A) ENGINE- ECO friendly for emisson and noise (PCB NORM COMPLIACE) 4 stoke diesel Engine confirming to BS standard developing, 1500 RPM turbocharged watercooled complete with a provision for 10% overload for one hour on 10 KVA and with following accessories:-

1

-

-

... More
i) Fly wheel with starter ring for generating set. ii) Dry type Air filter. iii) Lub oil cooler assembly with accessories. iv) Exhaust air manifold. v) Exhaust silencer. vi) Expansion bellow. vii) Exhaust gas turbocharger. viii) Fuel filter (pre micro). ix) Lubrication oil filter. x) 12V electrical starting system with starting motor & battery charging alternator with self-starter and other auto electric accessories as recommended by manufacturer. xi) Centrifugal by-pass filter. xii) Front & rear engine mounting supports. xiii) Engine control panel consisting of OFF/ON/START keys lub oil pressure gauge, Ammeter, electronic Hour meter, speedometer. xiv) Safety against low lub oil pressure. xv) Engine operation/Maintenance, spare parts Manual. xvi) Engine test certificate. xvii) Cold starting kit

-

-

-

... More
(B) ALTERNATOR - Salient pole brushless copper wound type suitable for direct couple to engine self-excited, self-regulated with fast response thermistor type electronic automatic voltage withhold output voltage with in desired limit (+1%) Dynamically balanced 400/415 volts AC 3 phase 50 HZ, 4 wire 0.8 PF lagging 10 KVA 1500 RPM star connected (4 wire) screen protected drip proof enclosures with radial fan mounted on rotor with insulation class- H suitable for ambient temperature varies from (-) 5 degree C in winter to (+) 35 degree C in summer with following accessories:- i) One MS frame suitable for mounting of Engine & alternator. ii) Fuel tank of suitable capacity as per Manufacturer recommendation complete with fuel gauge inlet/outlet connections drain valve with plug etc. iii) Battery of suitable capacity as per manufacturer recommendation with copper leads and terminals of suitable size iv) One set of AVM pads fitted on base frame.

-

-

-

... More
(C) Acoustic enclosure - It shall be suitable for 10 KVA DG set the degree of protection IP-42 conforming to IS - 2147 as under:- i) Fabricated out of CRCA sheet of suitable thickness as per manufacture design. Polyester based powder coated internally and externally with lockable type door handle. All nuts and handles shall be zinc coated. ii) The doors are gasketed with EPDM gaskets. iii) Sound proofing with high quality rock wool/mineral wool confirming to IS 8183 of 50mm thickness and density at 96 Kg /M3 covered with fiber glass cloth and perforated powder coats sheet specially designed alienators (Sound controller) at air entry and exit of the container noise level shall be not exceed 75 Db at 1 meter distance as per latest CPCB norms. iv) Adequate ventilation to meet air requirement for combustion and heat removal with provn of a blower. v) Emergency stop push button outside the container. vi) Provn of light inside the canopy 20W LED fitting with wiring and control switch.

-

-

-

... More
Supply, install and commissioning Servo controlled oil cooled voltage stabilizer 10 KVA for automatic operation, three phase output, naturally oil cooled, indoor type & designed for the following parameters :- Input voltage range : 300V to 480V Output voltage : 415V + 2.5% phase to phase, 230V + 2.5% (phase to neutral) Duty cycle : Continuous (24 Hours) Suitability : All power factor loads Load type : Unbalanced Environmental Protection : IP-30 Class of Insulation : Class E No load Loss : Less than 0.4% Correction Speed : 25V/sec Correction Motor : Heavy Duty synchronous motor 3 Nos Winding : Copper IS : 9815, 5142 Mounting : Preferably on Wheels Indication : 1. LED for input on (Yellow) 2. LED for output healthy (Green) 3. LED for output Trip (Red)

1

-

-

... More
Supplying and fixing LT End termination joint 1100 V Grade suitable for XLPE cable of size 25 x 4 core complete all as specified and directed.

68

-

-

... More
Supplying and fixing of GI wire 4mm dia for earthing complete all as specified and directed.

1

-

-

... More
Supply, installation, testing and commissioning of LT Panel board (Main Panel) Outdoor type suitable for 440 Volts, 50 Hz AC outdoor type fabricated out of 3.15 mm thick CRCA sheet, dust and vermin proof, totally enclosed metal clad, double door type accessible from front and rear side both with locking arrangement 3 phase 1.5 sqmm single core copper wire system with colour coded aluminium bus bar of rated current 200 Amp complete applied with two coat of synthetic enamelled paint over a coat of anti corrosion primer and mounted on angle iron of size 50x50x6 mm grouted in PCC foundation including earth work and excavation complete including accomodating the following gears and accessories :- (a) Aluminium bus bar of capacity 200 Amp for three phases 4 strip coloured R, Y, B and 100 Amp for neutral of size 32x6 mm (b) Digital Ammeter 0 to 400 Amps digital type with built in selector switch, CT's of suitable ratio (set of three) = 01 Set (c) Digital voltmeter 0 to 500 Volt digital type with built in selector switch = 01 No. (d) Indication Lamps LED Type (RYB) = 01 Set (e) Internal wiring of suitable size of copper conductor cable (f) Angle iron for frame work of size 50x50x6 mm thick for panel mounting (g) Street light Panel with all connected accessories ASTRONOMICAL timer with contactor 32 Amp TP and 40 Amp TPN = 02 Nos.

1

-

-

... More
INCOMING TPN: (h) TPN, 32 Amp, 50 Hz, 415 V = 01 No. OUTGOING TPN: (j) TPN 16 Amp = 02 Nos. Note : The Cost of MCCB, TPN, Ammeters, Voltmeters, Bus Bar, Indication Lamps, Copper wiring, street light panel, spare slot, construction of platform for panel of brick masonary work in CM 1:6 with foundation PCC 1:4:8 type D-2 including plaster work, PCC coping 1:2:4 (40mm thick crushed stone aggregates) and earthwork to be included in quoted rate. Drawings shall be approved by Accepting Officer.

-

-

-

... More
Supply & Fixing of 100 Watt LED New Generation energy saving and environmently friendly long life versatile pressure die-cast aluminium IP66 roadway luminaire with high power LED as light source and electronic drive suitable for pole, dia upto 58mm complete all as specified & directed.

30

-

-

... More
FENCING, SECURITY WALL AND GATE WORKS (SCHEDULE 'A' PART-XIV)

-

-

-

... More
Supply & Fixing of Punched Tape Concertina Coil (including spike and handle) with 56 loops and dia 600mm, Max covered length 8 RM, having a core wire of high carbon spring steel of high tensile strength. The punched tape and copper wire (2.5 + 0.35mm dia) shall be heavy galvanized (IS-1730) (Wire-275GSM & strip-200 GSM) to provided protection against outdoor exposure. The punched tape shall mechanically crimped over the core wire and then formed into a coil at various parts of the periphery of coil. The width of strip as 19mm and spacing of blades 24.00 + 0.5 mm c/c. The weight of each coil shall be 8 + 5% Kgs without packing material and coil lenth of 8 Mtr (maximum) when opened up each coil would with bituminzed hessian cloth for providing protective packing Ref specification No CQAE/5660/1620/a for raw material and drawings IMGA-0112/B (Sheet 1 of 2), IMPD-1821, IMPD-1822 complete all as specified & directed.

840

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements

Past Bidders
This list is curated from the bidders of the similar tenders in the past

Unlock the Tender details for free
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.