Military Engineer Services Tender
Search from the latest JKtenders and find a business opportunity fitting your SME on the online platform of BidAssist. If you're wondering how to find the latest JK tenders or from where to get all the documents without the hassles, this is what we explain here. Find the best opportunities coming to the surface via the JK government, PSUs and state corporations.
Military Engineer Services - MES Tender
Electrical and Electronics
Eprocure
Opening Date16 Dec 2024
Closing Date22 Jan 2025
Tender Amount₹ 44,60,000
Costs
EMD
₹ 89,200Document Cost
₹ 500Tender Fee
Refer Documents
Summary
Ca No. Ge (af)/sgr-60/2024-25 Provn Of High Mast Light At 45 Weu Mt Section, Pcc Foundation For Two, Four And Six Pole Structure And Three Phase Power Supply, Geysers, 02 Nos Ac, Ceiling Fans And Exhaust Fans At Certain Locations
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_688872_1Bid Award Id
ViewTender No
GE (AF)/SGR-60/2024-25Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
M&L for PCC 1:4:8, type D- 2, (using 40 mm graded crushed stone aggregate) as in foundation, filling and mass concrete, complete all as specified and directed.
5
-
-
... More
S&F mild steel work in post and struts in fencing including cuttings tops to shape as directed, drilling holes, notching for wire etc. flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting and similar work conforming to Fe-290 Gde E-165, complete all as specified and directed.
220
-
-
... More
S&F mild steel screw bolts of dia 11 to 15 mm (machine made) with hexagonal or square heads at one end and screwed the other or screwed both ends, each screwed end to be fitted with washer and one hexagonal or square nut, of length exc 5 cm but not exc 10 cm, complete all as specified and directed.
15
-
-
... More
Supply only chain link fencing 4 mm dia galvanized steel wire aperture of size as directed, made up into mattresses or cages lapped wired conforming to is 2721, complete all as specified and directed.
Note:- Fixing only fencing will be measured and paid separately.
500
-
-
... More
Fixing only chain link fencing of description fixed to steel post with mild steel flat & nut bolt etc., complete all as specified and directed.
Note:- (i) Fixing only fencing will be measured and paid separately.
(ii) Supply and fix mild steel nut bolt, and flat will be measured and paid separately.
250
-
-
... More
Surface dressing n exc 15 cm deep in any type of soil, including trimming of ground, to remove vegetation and / or small inequalities, complete all as specified and directed.
620
-
-
... More
M&L for cleaning of surrounding area of E&M installation around the bldg , transformer, GOD LT panel by grass cutting manually or mechanically (Bush cutter) as per requirement basis and trimming as directed by Engr-in-Charge, including taking out all shrubs, saplings with bushes and any type of vegetation and removing from site, complete all as specified and directed.
450
-
-
... More
Supply & laying HT rubber insulating mate of size 1000 mm x 2000 mm x3 mm thick suitable for HT 11 KV supply, for safety of worker in all kind of HT installation for operating HT switch gear, control panel, transformer room and busbar panel etc., complete all as specified and directed.
118
-
-
... More
S&F Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95 sqmm, complete all as specified and directed.
5
-
-
... More
S&F Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 Sqmm, complete all as specified and all as directed.
7
-
-
... More
S&F Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95 Sqmm, complete all as specified and directed.
7
-
-
... More
S&F Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 to 185 Sqmm complete all as specified and directed.
4
-
-
... More
S&F Anti climbing devices spikes type fabricated out of MS bars (round, square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole, complete all as specified and directed.
0.3
-
-
... More
S&F HT Danger notice plate of size 250 mm x 200 mm x 1.6 mm thick of mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed to pole with MS clamps, bolts and nuts of approved size, complete all as specified and directed.
50
-
-
... More
Preparation of old painted surface of steel tubular poles height approximately 9.5m above GL including cross arms and bracings and applying two coats of aluminium paint and including re-writing pole number with synthetic enamel paint, complete all as specified and directed.
90
-
-
... More
Excavating in post holes, in soft/ loose soil, (or similar holes) each not exc. 0.5 cum, getting out, returning filling in and ramming earth or broken rubble mixed with earth around, in layers n.exc 25 cm, watering and removing surplus soil to be a distance n.exc 50m and making good surfaces, complete all as specified and directed.
57
-
-
... More
Excavating in trenches not exc. 1.5m wide and not exc.1.5m in depth for laying of cable etc. and getting out in any type soil, complete all as specified and directed.
305
-
-
... More
Returning, filling in including spreading, levelling, watering and well ramming in layers not exc. 25 cm thick, using excavated soil, complete all as specified and directed.
184
-
-
... More
Removing of excavated soil to a distance n. exc. 50m and deposited where directed at a level not exceeding 1.5m above the starting point, complete all as specified and directed.
80.26
-
-
... More
M&L for dry & clean sand cushioning in trenches spreading and consolidation 8 cm thick before laying the cable and 15 cm of sand after laying the cable and punned the same up 18 cm, complete all as specified and directed. (Note:- Only punned thickness shall be measured and paid.)
81.9
-
-
... More
M&L for providing of new sub class 'B' bricks, old size, well burnt laid flat dry for protection of under ground cable, complete all as specified and directed.
6.47
-
-
... More
Supply, fixing, jointing and testing, LT cable 1100 volts grade of cross sectional area 95 sqmm 4 core as per IS- 7098 (part-I) 2011, XLPE insulated aluminium conductor heavy duty served with an inner sheathing PVC tape, galvanised steel strip or wire armoured with an overall PVC sheathing laid in trench, fixed along the poles or passed through GI pipe using clamp wherever required laid under floors, road etc. fixed concealed in walls encased in GI pipe connecting with suitable size of lugs and cable glands etc., each cable termination is to be made with suitable size of cable glands and aluminium thimble ( for junction boxes, security light, LT panels etc.) for incoming and outgoing cables, complete all as specified and directed. Note:- MS clamp with nuts, bolts washer etc. shall be measured and paid separately under relevant items.
610
-
-
... More
All as per Ser item No 24.00 here in above but cross sectional area 25 sqmm 3 core.
140
-
-
... More
All as per Ser item No 24.00 here in above but cross sectional area 16 sqmm 3 core.
140
-
-
... More
S&F 80mm dia bore mild steel galvanized iron tubes, light grade, with all fitting and laid in trenches or fixed to pole or laid in floors for protection of cable, complete all as specified and directed.
10
-
-
... More
Supply, installation, testing and commissioning of factory made LT Panel suitable for 415 Volts ,3 Phase 4 Wire, 50 Hz AC supply system confirming to IS:8623/93, outdoor type floor mounting, weather proof, vermin proof, fully ventilated and fabricated out of MS CRCA sheet of 3.15mm thick having copper bus bar of rating 200 Amps, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeves. The panel shall be front and back openable including powder coating internally and externally the entire steel surfaces. All doors shall be provided with suitable locking arrangements. The size of the outer shell should not be less than 600mm x 500mm x 350mm, mounted on angle iron stand made out of angle iron 40 X 40 X 6 mm and grouted in PCC 1:3:6, including the following control gears:-
(a) MCCB, 4 pole, 160 Amps capacity, 25 KA breaking capacity - 01 No. (Incoming)
(b) MCCB, 4 pole, 63 Amps capacity, 16 KA breaking capacity - 02 No. (Outgoing)
(c) Indicating Lamp RYB - 01 Set
(d) Digital Voltmeter & ammeter including phase sequence indicators- 01 No
1
-
-
... More
S&F epoxy powder coated or polystyrene insulated material sheet metal enclosure, factory made ( double door) 4 way VTPN suitable for MCCB DB's 415 Volts 200 Amps rated busbar, neutral & earthing link bar, flush mounted, complete all as specified and directed.
2
-
-
... More
S&F MCCB 3 pole, 100 Amps with breaking capacity 16 KA, 415 volts, complete all as specified and directed.
2
-
-
... More
S&F MCB SPN 40-63 Amps 10 KA working on 240 Volts 'C' curve 50 HZ AC supply, complete all as specified and directed.
2
-
-
... More
S&F MCB SP 5 Amp to 32 Amps 10 KA working on 230 Volts 'C' curve 50 HZ AC supply, complete all as specified and directed.
24
-
-
... More
S&F ON load change over switch in sheet metal enclosure 3 phase 4 pole 415 Volt 50 Hz of capacity 100 Amps complete side handle and accessories, complete all as specified and directed.
1
-
-
... More
Supply & laying un-reinforced precast concrete cable cover confirming to IS:5820 with minimum average breaking load capacity 200 Kgs for unreinforced covers, class LV type 1, flat size 250mm x 150mm x40mm, complete all as specified and directed.
1333
-
-
... More
Supply, laying & testing cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 1100 volts cross sectional area 35 sqmm 4 core, complete all as specified and directed.
200
-
-
... More
M&L for earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6mm buried directly in ground vertically to a depth not less than 2.25 m below normal ground level (with top edge of earth plate not less than 1.5 metre below ground level) connected to galvanized iron earth strip 25x 4 mm (main earthing lead) by means of galvanized bolts, nuts and washers all as shown in electrical plate No 3 of MES Schedule Part-I (2009) connected to earth test point & to main switch board with & including adequate quantity of charcoal dust and common salt around earth plate & 40 mm dia GI pipe medium grade for earth lead protection pipe for suitable length and GI pipe 20 mm dia medium grade for watering pipe with funnel & wire mesh including necessary earth work and PCC (1: 3 : 6) type C-1 for earth pit , internal surface of concrete shall be given 10mm thick plaster in CM 1:4 and 40 mm thick precast RCC cover 1 : 2 : 4 ,type B-1( using 20 mm graded crushed stone aggregate ) reinforced with 8 mm dia TMT bars @ 75 mm c/c both ways with 12mm dia round bar as in handle including taking down of existing earthing, complete all as specified and directed. NOTE : (i) The cost of earth lead and its protection pipe upto and including 7.5 m only from the top of earth electrode are deemed to be included under this item and additional earth lead , if any, required at site shall be measured and paid for separately under appropriate item of Schedule `A’/BOQ.
(ii) Any joint in earth lead from earth electrode to test point shall not be allowed/permitted.
2
-
-
... More
Design, fabrication, supply, errection, testing and commissioning of 20 metre High Mast, Galvanized, suitable for and including 09 (Nine) Nos LED Flood light 1x200 watt (LED Floodlight carriage shall have arrangement to rotate 360 degree manually). Material for pole shaft as per ASTM A572 Grade 50/BSEN 10025 S355 or equivalent and aerodynamic shape and mechanically strong to face wind speed up to 180 Km/hrs , Material for Base plate -As per IS 2062 and Metal Protection treatment - Hot dip Galvanized as per IS 4759 or robust door opening and locking system with weather proof facilities to increase the life of internal accessories and Double Drum Winch system motorized with manual option including design and construction of foundation with RCC (M-25) grade concrete for the high mast as approved by OEM, GI single spike of length 2m for Lightening protection, complete all as specified as under:-
1
-
-
... More
(a ) 20 metre High Mast Fabricated Part:-
(i) Top dia 200 mm , bottom Dia-460 mm section-2 section Thickness- 5 mm base ,4 mm top. Base Plate 670 mm x 30 mm.
(ii) Foundation Bolt dia - M30, Length of bolt - 850 mm ( 8 Nos) with template and anchor plate with following items -High Mast Section sections with base plate, lantern carriage suitable to fix 09 Nos of luminaries (2 x 250 W) symmetrical loading ,foundation accessories.
(b) Winches - Motorized with manual option:-
Motorized Double Drum Winches shall be self sustaining with out need for break spring or clutch required to adjustment and lubricant system the Gear ratio shall be 50:1. The Winch shall be salt lubricating system by means of an oil winch and lubricant recommended.
(c ) Steel Wire Rope:-
Steel wire rope dia 8 mm shall be fabricated 'Marine Grade"-AISI Stainless Steel 316 of 7/19 of construction, 5 wire Rope system .thimbles and terminal combustible material .Steel Wire Rope Shall be factory cut terminated and pre-rigged for case for installation.
-
-
-
... More
(d) Mast Head Assembly:-
The pulley shall be large diameter appropriate to the multy core flexible cable being used. They shall be of non-corrosive and run of self lubricant bearing with stainless steel spindle. arrangement shall be provided the Electric Cable and steel wire rope are separated before passing over the respect pulleys grooves. The complete chassis shall be hot dip galvanized after fabrication.
(e) Lantern Carriage:-
The lantern carriage shall be of durable steel tube designed to act as electric conduit . It shall be fitted at junction box mounting strips and two segments joints by bolted flange to permit removal from the erected must. Material of lantern carriage 40 NB ERW class B - M.S. pipe and dia of carriage ring 600 mm (ID).Load carrying capacity 9 luminaries, Symmetrically.
(f) Cable and Cable Connection:-
4 Sqmm 5 core CU flexible round/flat EPR insulated & PCP sheathed power cable shall be provided terminating in the base compartment of the Mast fitted with plug or socket and all mast cable shall be connected to a weatherproof junction box on the lantern ring equipt with suitable PVC glands
-
-
-
... More
Supply, installation, testing and commissioning, factory made LT Panel, outdoor type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated copper bus bars 400 Amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15mm CRCA MS sheet and 40x40x6mm thick angle iron frame work, externally powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front & rear opening type, with aprons for cable entry, with double door shutter and locking arrangement (including provn of 65mm Godrej (Freedom) lock with 2 keys, internal wiring 2.5 Sqmm with PVC insulated, solid copper conductor, FRLS cables, IS-694 marked of adequate size. The scope of work includes the following:- (i) MCCBs four pole, 63 Amps rating and 16 KA rupturing capacity : 01 No.
(ii) Indicating lamps 01 set of three. (iii) Astronomical Timer Switch (Digital Type), Legrend Cat No- Astrorex - 01 No. (iv) Contractor 40 Amps four pole - 01 Nos
(v) Ammeter Digital type -01 Nos
(vi) Voltmeter digital type -01 Nos
(vii) Push button control starter for motorized winch - 01 No
Note : - The rate quoted by the contractor is inclusive of Excavation, PCC Foundation , plastering etc. for erecting the Panel complete.
1
-
-
... More
S&F ceiling fans complete with blades, down rods, electronic regulator and accessories 230V, 1200 mm sweep, minimum air delivery 210 CFM with service value 6.00, BEE 5 star rated with brushless direct current motor (BLDC), complete all as specified and directed.
86
-
-
... More
S&F of Exhaust fan, made of sturdy Engineering steel body, complete with louvers shutter, 450mm sweep, voltage 230V, 50 Hz, RPM 1200, copper winding, including connection with 1.5 sqmm mutistrand copper conductor flexible wire from ceiling rose, including outside louvers with proper hole, and necessary fixing arrangement and making good to disturbed surfaces, complete all as specified and directed .
19
-
-
... More
S&F of Exhaust fan, made PVC body, complete with louvers shutter, 200mm sweep, voltage 230V, 50 Hz, RPM 1200, copper winding, including connection with 1.5 sqmm mutistrand copper conductor flexible wire from ceiling rose, including outside louvers with proper hole, and necessary fixing arrangement and making good to disturbed surfaces, complete all as specified and directed .
19
-
-
... More
M&L for Modular fan step regulator 100 watt, 2 Module, complete all as specified and directed.
86
-
-
... More
Supply, installation, commissioning and testing high wall with cordless remote with inbuilt Heating and Cooling arrangement split type air conditioner of capacity 1.5 TR suitable for non CFC refrigerant gas including material and labour for the following works involved for smooth functioning & installation of outdoor/indoor for split type AC all as directed by Engr-in-charge:-
(a) Fixing the heating & cooling unit with grounting nuts, cutting groove to wall for gas pipe and water drainage pipe complete.
(b) S&F cutting, bent to shape copper pipe of appropriate size from outdoor unit to indoor unit by cutting holes to wall including brazing the copper pipe, fixing union all as required at site.
(c) S&F 20mm dia PVC pipe transparent flexible heavy duty for drainage pipe (approx-3.0 M).
(d) Insulation of both the copper pipe with insulating material and covering the complete pipes with PVC casing & capping of size 75x75mm for mechanical protection of copper pipe complete.
2
-
-
... More
(e) Charging of correct quantity non CFC refrigerant gas after necessary brazing/fixing of both the outdoor/indoor unit and testing complete on load up to satisfaction of EIC.
(f) S&F MS bracket factory made, fixed on wall through fastener of appropriate size and gauge for installation of out door unit (condensing unit) complete all as directed.
(g) M&L for provision of shed for outdoor unit made of MS sheet 2.0 mm thick and MS angle 30x30x5mm complete.
Note - (i) All other connected civil works and other miscellaneous works required for installation of split AC & copper functioning as directed by Engr-in-charge shall deemed to be included with the quoted rate.
-
-
-
... More
S&F industrial single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole 'B' series MCB of capacity 20 Amp, 10 KA 230 V etc., complete as specified and directed
10
-
-
... More
S&F copper tubing of following size special annealed pressure copper purity min 99.9% and making flairing at both ends for connection including brass nut and testing in existing split type air conditioner of any description/ capacity/make and in any position including insulating with suitable size insulation, complete as specified and as directed.
-
-
-
... More
(a) size 3/8"
20
-
-
... More
(b) size 5/8"
20
-
-
... More
(c) size 1/2"
15
-
-
... More
(d) size 1/4"
20
-
-
... More
S&F Voltage stabilizer for automatic operation single phase naturally air cooled, indoor type, and designed for input variation between 180V to 250V with output voltage stabilized at 230 V with accuracy of +/-2.5% and of capacity of 5 KVA, complete as specified and as directed.
2
-
-
... More
M&L for Point wiring for 15 amp socket outlets point controlled by one switch on Independent socket outlet using 2.5 Sqmm PVC insulated and unsheathed fire retardant low smoke and halogen (FR-LSH) copper conductor single core multi stranded copper cable confirming to IS:694(2010) using approved colour code for phase and neutral as per IS code drawn through non metallic PVC rigid surface conduit heavy mechanical stress (HMS) grade in accordance with IS:9537 (Part 3) having wall thickness not less than 2.0 mm thick and minimum 20 mm external dia but shall be increased as per actual site requirement in accordance with clause No 19.125 of SI Part I (ISI marked) including conduit accessories like bends, tees, junction boxes etc. fixed concealed with all accessories suitable for modular type fitment, provision for fixing of modular flush boxes of appropriate size and dimensions for fixing of piano switches/sockets/regulator etc. including PVC insulated and unsheathed FRLSH 2.5 Sqmm multi stranded copper conductor cable (green colour) as continuous earth lead wire connected to common earth and earth dolly, complete all as specified and directed.
6
-
-
... More
S&F 50 Litre capacity storage type water heater (Geyser), BEE 5 Star rated, vertical wall mounting type made out of CRCA outer body stainless steel storage tank, titanium enamelled heating element thermostat, thermal cutout, glass wool including 15 mm, 450 mm long (cold water pipe ), 15 mm, 450 mm long armoured pipe (hot water pipe) etc. complete including making necessary electrical and water connections with 2.5 sqmm 3 core copper multistandred cable with top indicator plug top 15 amp from geyser connection to socket including hold fast for fixing of new geyser and writing the MES No., complete as specified and directed.
2
-
-
... More
S&F 25 Litre capacity storage type water heater (Geyser), BEE 5 Star rated, vertical wall mounting type made out of CRCA outer body stainless steel storage tank, titanium enamelled heating element thermostat, thermal cutout, glass wool including 15 mm, 450 mm long (cold water pipe ), 15 mm, 450 mm long armoured pipe (hot water pipe) etc. complete including making necessary electrical and water connections with 2.5 sqmm 3 core copper multistandred cable with top indicator plug top 15 amp from geyser connection to socket including hold fast for fixing of new geyser and writing the MES No., complete as specified and directed.
4
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements