Military Engineer Services Tender
Search from the latest JKtenders and find a business opportunity fitting your SME on the online platform of BidAssist. If you're wondering how to find the latest JK tenders or from where to get all the documents without the hassles, this is what we explain here. Find the best opportunities coming to the surface via the JK government, PSUs and state corporations.
Military Engineer Services - MES Tender
Electrical and Electronics
Electrical Works
Eprocure
Opening Date11 Jan 2025
Closing Date30 Jan 2025
Tender Amount₹ 27,50,000
Costs
EMD
₹ 55,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2025_MES_692911_1Tender No
8070/NIT-77/2024-25Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://mes.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
PCC (1:4:8) type D-2 using 40mm graded aggregate as in foundation for filling in, mass concrete for foundation of Pole, Transformer, Panel board, stay, post lantern, repairs to road cutting, drain, path etc complete all as specified and directed.
0.2
-
-
... More
PCC (1:3:6) type C-2 using 40mm graded aggregateas in foundation for filling in, mass concrete for foundation of pole, Transformer Panel board, stay, Post lattern, repairs to road cutting, drain, path etc complete all as specfied and directed.
1.1
-
-
... More
PCC (1:2:4) type B-1 using 20mm graded aggregate as in coping of new pole /reconstruction old damaged copings etc, including necessary from work complete all as specified and directed.
0.2
-
-
... More
M&L for dry Sand cushoning in trenches for protection of cable including watering and consolidation all as specified and directed Note: Punned thickness shall be considered for measurement purpose.
15
-
-
... More
M&L for well burnt brick sub class B old size laying in trenches perpendicular to axis of the cable complete all as specified and directed.
1.3
-
-
... More
Relaying in trenches/Floor or fixed to Pole/Wall GI pipe light grade with fitting of size 40 mm bore for protection of cable including dismantling existing pipe complete all as specified and directed by the Engineer-in-Charge.
10
-
-
... More
Relaying in trenches/Floor or fixed to Pole/Wall GI pipe light grade with fitting of size 50 mm bore for protection of cable including dismantling existing pipe complete all as specified and directed by the Engineer-in-Charge.
10
-
-
... More
Relaying in trenches/Floor or fixed to Pole/Wall GI pipe light grade with fitting of size 80 mm bore for protection of cable including dismantling existing pipe complete all as specified and directed by the Engineer-in-Charge.
10
-
-
... More
M&L cutting of PCC/Hard standing/WBM road not exceeding 20cm in width not exceeding 30cm in depth for passing of LT cable and making good of disturbed surface to match with the existing surfaces by using old and new material i.e. bitumen/PCC (1:3:6) type C-1 complete all as specified and directed.
20
-
-
... More
Taking out existing workn out/old PVC insulated cable in 3.5 core of 120 sqmm to 95 sqmm size of 1100 Volt grade in pieces for trenches making loop for transportation and removal from site after taking proper shut down from MES compitent staff complete in all respecrt and as directed at site.
225
-
-
... More
Taking out existing workn out/old PVC insulated cable in 3.5 core of 70 sqmm to 35 sqmm size of 1100 Volt grade in pieces for trenches making loop for transportation and removal from site after taking proper shut down from MES compitent staff complete in all respect and as directed at site.
300
-
-
... More
Taking out of old serviceable / unserviceable PVC under ground LT or HT Cable of any size and type fixed on pole, wall or laid in floors, tranches, across road crossing etc, including taking out of cable covers of precast PCC/RCC slab or brick cover etc Note: Excavation/Removal/Returning filling in/Sand Cushioning/New Bricks to be paid separately.
200
-
-
... More
Supply and fixing in repairs or replacement ISI mark aluminium Lugs/thimbles suitable for under ground LT cables of following sizes
-
-
-
... More
10 Sqmm
100
-
-
... More
16 Sqmm
100
-
-
... More
25 Sqmm
100
-
-
... More
35 Sqmm
100
-
-
... More
50 Sqmm
100
-
-
... More
70 Sqmm
100
-
-
... More
95 Sqmm
100
-
-
... More
120 Sqmm
50
-
-
... More
Matrial and labour for fixing or passing through pipe, laid in trenches or fixed to pole/wall or fixed to LT panel board, 100 volts grade heavy duty cable with XLPE insulated stranded aluminium conductor served with inner sheathing of PVC tape, armoured with galvanised steel wire or tape and overall PVC sheathed 35 Sqmm 3.5 core with required aluminium cable lugs all as specified and directed.
150
-
-
... More
Do as per item no. 17 above but size 120 sq mm 3.5 core.
50
-
-
... More
Do as per item no. 17 above but size 95 sq mm 3.5 core.
75
-
-
... More
Do as per item no. 17 above but size 70 sq mm 3.5 core.
100
-
-
... More
Do as per item no. 17 above but size 50 sq mm 3.5 core.
100
-
-
... More
Do as per item no. 17 above but size 35 sq mm 3.5 core.
100
-
-
... More
Do as per item no. 17 above but size 25 sq mm 3.5 core.
100
-
-
... More
Do as per item no. 17 above but size 16sq mm 4 core.
100
-
-
... More
Supply & laying XLPE insulated screened aluminium stranded conductor cable PVC bedded galvanized strip armoured heavy duty 11 KV cross sectional area 95 Sqmm 3 Core (Earthed) conforming to IS 7098 lead in duct/tranches complete all as specified and directed.
100
-
-
... More
S & fix LT cable End termination joining kit heat shrinkable complete with jointing materials suitable for LT Armoured cable of size 10 to 35 Sqmm complete all as specified amd directed by Engr in charge.
20
-
-
... More
S & fix LT cable End termination joining kit heat shrinkable complete with jointing materials suitable for LT Armoured cable 3.5 core of size 50 to 95 Sqmm complete all as specified amd directed by Engr in charge.
20
-
-
... More
S & fix LT Cable joining kit heat shrinkable complete with jointingmaterials suitgable for LT Armoured cable 3.5 core of size 50 to 185 Sqmm complete all as specified and directed by Engr in charge.
30
-
-
... More
Supply and fixing cable jointingkit for 11 KV (earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 Sqmm to 95 Sqmm.
5
-
-
... More
Supply and fixing cable jointingkit for 11 KV (earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 Sqmm to 95 Sqmm.
5
-
-
... More
Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6.0 mm thick buried directly in ground, (Earth pit not less than 2.25 mtr deep below gound level) with top edge of plate not less than 1.5mtr below normal gound level, connected to and including galavanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised standard iron or steel all as specified or indicated in electrical plate no 3 of MES part-I, including testing on completion. Including Taking Down material and labour of the following:
(a) Excavation and earth work for drilling hole for electrode in any type of soil.
(b) Earth pit cover square type of size internal size not less than 300 x 300mm with top openable cover with handle and one side hinges.
(c) Funnel with watering pipe of GI 20 mm nominal bore medium grade and copper lugs etc all as specified.
(d) Relaying old 40mm nominal bore light grade GI protection pipe 5mtr long for protection of earthing lead form mechanical injury or tempering.
(e) Requisite quantity of common salt and charcoal.
(f) Testing of earthing.
Note: (a) On testing after completion of earthing, if the desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk and cost to the entire satisfaction of the Engineer-in-Charge.
(b) The Contractor shall quote his rate considering taking down cost of existing unserviceable earthing.
(c) GI Wire Beyond 7.5mtr will bemeasured and paid for separately.
5
-
-
... More
Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6.0 mm thick buried directly in ground, (Earth pit not less than 2.25 mtr deep below gound level) with top edge of plate not less than 1.5mtr below normal gound level, connected to and including 32x6 mm galavanised earth earth strip by means of bolts, nuts, check nuts and washers of galvanised standard iron or steel all as specified or indicated in electrical plate no 3 of MES part-I, including testing on completion. Including Taking Down material and labour of the following:
(a) Excavation and earth work for drilling hole for electrode in any type of soil.
(b) Earth pit cover square type of size internal size not less than 300 x 300mm with top openable cover with handle and one side hinges.
(c) Funnel with watering pipe of GI 20 mm nominal bore medium grade and copper lugs etc all as specified.
(d) Relaying old 40mm nominal bore light grade GI protection pipe 5mtr long for protection of earthing lead form mechanical injury or tempering.
(e) Requisite quantity of common salt and charcoal.
(f) Testing of earthing.
Note: (a) On testing after completion of earthing, if the desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk and cost to the entire satisfaction of the Engineer-in-Charge.
(b) The Contractor shall quote his rate considering taking down cost of existing unserviceable earthing.
(c) GI Strip Beyond 7.5mtr will bemeasured and paid for separately.
5
-
-
... More
Supply and fixing of earth continuity conductor or main earthing lead fixed to wall on batten or recess or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc., as required 32x6 mm galvanised iron strip for earthing in case the distance exceeds the value as specified and directed incl taking down.
30
-
-
... More
Supply and fixing of earth continuity conductor or main earthing lead fixed to wall on batten or recess or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc., as required 4 mm dia galvanised iron or steel wire as specified and directed incl taking down.
30
-
-
... More
Taking down old UNSV pannel any type and shape/size and supply, installation, testing and commissioning as repair Outdoor type LT pannel board made out of CRCA MS sheet of size 0.90 M x 0.9 M x 0.40 M not less than 3.0 mm thick, front & back openable (CPRI approved) including cutting, shearing, shaping, bending, welding, drilling, threading etc., supported on base frame made out of MS angle of size 50 mm x 50 mm x 6 mm welded with & including 4 Nos MS angle legs of size 50 mm x 50 mm x 6 mm not less 900mm high, grouted in PCC 1:3:6 type C-1 factory made out of duly painted internally and externally with two coats of synthetic enamel paint over a coat or red oxide primer, with suitable locking arrangements with & including Aluminium Bus Bar duly encased in & including colour coded FRP Sleeves of size 40 mm x 10mm mounted on SMC/DMC red insulators Insulator (RYBN) complete all as specified and as directed by Engr-in-Charge comparising of the following accessories:-
(a) Voltmeter flush mounted 0-500 V square digital type -01 No
(b) Ammeter flush mounted 0-250A, with & including CTs 400/5 type -01 Set
(c) Phase indicating lamp set (RYB) industrial LED type-01 Set.
(d) MCCB 200 AMP FP 25 KA MCCB with adjustable thernal setting-1No (as incoming)
(e) MCCB 4 Pole 100 Amp 16 KA- 03 Nos.
(f) MCB SPN 63 Amp -01 Nos (g) Space for provision of 4 pole MCCB 63 Amps 16 KA-01 Nos
1
-
-
... More
Taking down old UNSV pannel any type and shape/size and supply, installation, testing and commissioning as repair Outdoor type LT pannel board made out of CRCA MS sheet of size 0.90 M x 0.9 M x 0.40 M not less than 3.0 mm thick, front & back openable (CPRI approved) including cutting, shearing, shaping, bending, welding, drilling, threading etc., supported on base frame made out of MS angle of size 50 mm x 50 mm x 6 mm welded with & including 4 Nos MS angle legs of size 50 mm x 50 mm x 6 mm not less 900mm high, grouted in PCC 1:3:6 type C-1 factory made out of duly painted internally and externally with two coats of synthetic enamel paint over a coat or red oxide primer, with suitable locking arrangements with & including Aluminium Bus Bar duly encased in & including colour coded FRP Sleeves of size 40 mm x 10mm mounted on SMC/DMC red insulators Insulator (RYBN) complete all as specified and as directed by Engr-in-Charge comparising of the following accessories:-
(a) Voltmeter flush mounted 0-500 V square digital type -01 No
(b) Ammeter flush mounted 0-250A, with & including CTs 400/5 type -01 Set
(c) Phase indicating lamp set (RYB) industrial LED type-01 Set.
(d) MCCB 4P 160 Amps, 25 KA, 415 Volts-01 No. (as incoming)
(e) MCCB 4P 100 Amp, 16 KA, 415 Volts-04 No. (outgoing)
(f) MCB SPN 63 Amp -01 Nos (g) Space for provision of 4 pole MCCB 100 Amps 16 KA-01 Nos
2
-
-
... More
Taking down old UNSV starter and S&F in replacement DOL starter suitable in sheet metal enclosur for 10 HP 415 Volt, 3 phase electric motor including connection.
1
-
-
... More
Taking down old UNSV starter and S&F in replacement fully Aujtomatic star delta motor starter in sheet metal enclosure with SPP feature 415 Volt 3 Phase 50 HZ suitable for motor rating 15 to 50 HP including connection with coper thimbless and tsting complete all as specified and directed.
6
-
-
... More
Supply and fixing in replacement MCCB of following ratings complete all as specified and directed by Engr-incharge.
-
-
-
... More
MCCB 63 Amps 4 pole, 415 V, breaking capacity 16 KA
3
-
-
... More
MCCB 100 Amps 4 pole, 415 V, breaking capacity 16 KA
5
-
-
... More
MCCB 125 Amps 4 pole, 415 V, breaking capacity 16 KA
2
-
-
... More
MCCB 160 Amps 4 pole, 415 V, breaking capacity 25/36 KA, adjustable type
4
-
-
... More
MCCB 200 Amps 4 pole, 415 V, breaking capacity 25/36 KA, adjustable type
4
-
-
... More
MCCB 250 Amps 4 pole, 415 V, breaking capacity 35/36 KA, adjustable type
3
-
-
... More
MCCB 320 Amps 4 pole, 415 V, breaking capacity 35/36 KA, adjustable type
2
-
-
... More
MCCB 400 Amps 4 pole, 415 V, breaking capacity 35/36 KA, adjustable type
1
-
-
... More
MCCB 630 Amps 4 pole, 415 V, breaking capacity 50 KA, adjustable type
1
-
-
... More
S&F in replacement single phase priventer.
15
-
-
... More
M&L for reparing, dismantling defective LT Panel / Bus Bar Chamber, indoor after opening of all incoming & outgoing cable connections, uprooting from foundation, cutting & setting aside burnt cable ends, opening of loop by excavating around near LT panel & refixing at suitable place but height not less than 50 cm from ground level by fixing MS angle ion legs on brick work/PCC 1:3:6 cleaning bus bars, inseting new cable lugs in cut ends of cables & connecting to bus bars/MccBs, cleaning of wholwe panel & welding at places/welding new hinges not less than 150mm long at three places in each door complete including painting with one coat of synthetic enamel paint from outside after preparation of old surfaces complete all as specified and as directed by Engr-in-Charge.
20
-
-
... More
S&F in replacement Voltmeter flush mounted 0-500 V square digital type.
15
-
-
... More
S&F in replacement Ammeter flush mounted 0-500 V square digitgal type.
15
-
-
... More
S&F in replacement CTs 400/5 type.
5
-
-
... More
S&F in replacement selecter switch square.
20
-
-
... More
S&F in replacement Phase indicating lamp (RYB) industrial LED type.
30
-
-
... More
Taking down old UNSV bus bar chamber any type and shape and supply, installation, testing and commissioning in replacement busbar chamber made out of CRCA steel sheet Minium of 3mm thick, outdoor type, double of size (0.6Mx0.6Mx0.35M) factory made, front & back openable, including cutting, shearing, shaping, bending, welding, drilling, threading etc supported on base frame made out of MS angle of Size 35x35x5 mm welded with & including 4 Nos legs not less 900mm high MS angle of size 35x35x5mm, duly panted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer, with suitable locking arrangements with & including 5 Nos Aluminium Bus Bar (3 for phases + 1 for neutral +1 for earth) duly encased in & including colour coded FRP Sleeves of size 50mm x 5mm mounted on SMC/DMC red insulators Insulator (RYBN) complete all as specified and as directed by Engr-in-Charge.
20
-
-
... More
M&L for replacement of MS box mounted covectional power factor correction system with supply, installation, testing and commissioning in replacement Autmatic power factor corrector (APFC) panel for 3-phase, 415 V 50 Hz system of capacity 20 KVAR with incomming MCCBs 4 pole of capacity 125 Amps 25 KA thermal adjustable 0.7 IN to 1.0 IN made out of CRCA steel sheet Minium of 3mm thick, outdoor type, double door of size (0.6mx0.6mx0.35m) factory made, front & back openable, including cutting, shearing, shaping, bending, welding, drilling, threading etc, supported on base frame made out of MS angle size 35x35x5 mm welded with & including 4 Nos legs not less 900 mm high MS angle of size 35x35x5mm, duly painted internally and externally with two coats of syntheticenamel paint over a coat of red oxide primer, with suitable lockng arrangemernts with suitable locking arrangements with & including suitable Aluminium Bus Bars (for Phase & for neutral) duly encased in & including colour coded FRP Sleeves of size 50mmx5mm mounted on SMC/DMC red insulators Insulator (RYBN) complete all as specified and as directed by Engr-in-charge comprisng of the following accessories:- S&F in replacement Automatic power factor corrector (APFC) panel for 3-phase, 415 V 50 HZ system of capacity 20 KVAR with imcomming MCCBs 4 pole of capacity125 Amps 25 KA complete all as specified and as directed by Engr-in-charge.
(a) Voltmeter flush mounted 0-200 V square digital type-01 No.
(b) Phase indicating malp set (RYB) industrial LED type -01 set.
(c) APFC controller minimum 8 steps type
(d) Auto mannual arrangement with push buttion and contactors.
(e) MCB TPN for each step with two spare of suitable capacity.
7
-
-
... More
Deduct Schedule of Credit of Rs. (-) 57180.00 (Minus) as listed in Schedule 'A' Part-II.
Contract Sum shall be arrived after deducting the credit amount
Note: Tenderers will not quote against this item being a firm amount.
-
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements
Past BiddersThis list is curated from the bidders of the similar tenders in the past
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%