Military Engineer Services Tender

Search from the latest JKtenders and find a business opportunity fitting your SME on the online platform of BidAssist. If you're wondering how to find the latest JK tenders or from where to get all the documents without the hassles, this is what we explain here. Find the best opportunities coming to the surface via the JK government, PSUs and state corporations.

Military Engineer Services - MES Tender

Works
Electrical and Electronics
Electrical Works
Eprocure
Opening Date15 Oct 2024
Closing Date21 Nov 2024
Tender Amount₹ 48,00,000 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Taking up cast iron water mains bore of pipe 100 mm (including all fittings), with spigot and socket ends and lead joints including burning out joints and recovering lead complete all as specified and directed.

10

-

-

... More
Supply and laying Cast iron pipes with spigot and sockets ends centrifugally, Class LA in 100 mm size laid in trenches complete all as specified and directed.

10

-

-

... More
Supply & fixing bends (any type radius and angle tapers any type straight, bend, increasing decreasing or double sockets etc ) Tee pieces single branch 'Y' Junction, double branch, cross (all sockets or sockets and spigot) collars caps and plugs upto 150mm bore complete all as specified and directed. .

36

-

-

... More
M&L for run lead joint for CI pipe spigot and socket pipes and fittings of 100 mm dia bore complete all as specified and directed.

5

-

-

... More
Taking up or down steel tubing of 20mm dia bore pipe and connection laid in trenches or floors or fixed to walls and including cleaning for refixing or removal to credit complete with all fittings & valves etc complete all as specified and directed.

102

-

-

... More
All as per description of ser item No-8 above but 25mm.

84

-

-

... More
All as per description of ser item No-8 above but 40mm.

60

-

-

... More
All as per description of ser item No-8 above but 50mm.

36

-

-

... More
All as per description of ser item No- 8 above but 80mm.

24

-

-

... More
S&F GI water tubing 20mm bore 'medium grade', galvanized, with all fittings like socket, union, elbow, bend, tees etc jointed and laid in trenches complete all as specified and as directed.

102

-

-

... More
All as per description of ser item No-14 above but 25mm.

84

-

-

... More
All as per description of ser item No-14 above but 40mm.

60

-

-

... More
All as per description of ser item No-14 above but 50mm.

36

-

-

... More
All as per description of ser item No-14 above but 80mm.

24

-

-

... More
S&F gun metal, globe or gate valve with iron wheel head, screwed both ends for iron pipe and fixed of bore of 20mm complete all as specified and directed.

14

-

-

... More
All as per description of ser item No-18 above but 25mm.

14

-

-

... More
All as per description of ser item No-18 above but 40mm.

4

-

-

... More
All as per description of ser item No-18 above but 50mm.

3

-

-

... More
Taking down old unserviceable old sluice valve and supply and fixing ball valve having SS ball with both CI end flanged, ISI marked, with nuts, bolts and washer and rubber gasket with stainless steel handle over PVC coating complete all as specified and directed for 80 mm bore pipe complete all as specified and directed.

2

-

-

... More
Taking down old unserviceable old sluice valve and supply and fixing sluice valve cast iron ISI marked with flanged ends drilled with iron wheels head shuts and open direction cast on it class PN 1.6 confirming to IS 14846-2000 including necessary fixing arrangement such as rubber insulation, packing rings, jointing materials nuts, bolts washer, gasket and packings material etc all as specified and directed for 100 mm dia complete all as specified and directed.

2

-

-

... More
Supply and fixing in replacement CI Non return valve of size 100mm bore without bypass arrangement swing type confirming to IS 5312-1 flanged end, pressure rating PN 1.6 complete all as specified and directed.

1

-

-

... More
Supply and Fixing in replacement CI Non return valve of size 80mm bore without bypass arrangement swing type confirming to IS 5312 flanged end pressure rating PN 1.6 complete all as specified and directed.

1

-

-

... More
M&L for lagging to pipes used in internal water supply or plumbing all round with, 25min thick bonded mineral wool preformed ‘SNAP ON’ pipe sections of density 144 Kg/cum conforming to IS 9842 for 20 mm dia pipe line complete all as specified and directed.

80

-

-

... More
M&L for lagging to pipes used in internal water supply or plumbing all round with, 25min thick bonded mineral wool preformed ‘SNAP ON’ pipe sections of density 144 Kg/cum conforming to IS 9842 for 25 mm dia pipe line complete all as specified and directed.

60

-

-

... More
Supply and replacement of 10 Sqmm 3 Core submersible copper conductor flat type for submersible pump complete all as specified and directed.

90

-

-

... More
Supply and replacement of 6 Sqmm 3 Core submersible copper conductor flat type for submersible pump complete all as specified and directed. .

180

-

-

... More
M&L for dewatering and taking out sludge from tank of size and capacity (10000 to 40000Gln), removing the same to a distance not exceeding 50m with & including, cleaning the sump by wire brushing including ,including brooming down complete including white washing internally, complete all as directed.

5

-

-

... More
Material and labour for repair of centrifugal motor pump set 50 HP including removing the motor pump from the foundation, disconnecting from the motor and transporting to the work shop for repair including replacement of worn out impellers-01 set with bronze impellers, replacing bearing No 6308-02 Nos, replacement of worn out bearing housing, replacement of gland bush, unserviceable nut bolts and washers and bringing back the pump to the pump house and coupling the pump with motor and fixing on foundation and testing, complete all as specified and directed. Note:- Rewinding job will be measured and paid separately.

1

-

-

... More
Material and labour for repair of centrifugal motor pump set 15/ 20 HP including removing the motor pump from the foundation, disconnecting from the motor and transporting to the work shop for repair including replacement of worn out impellers-01 set with bronze impellers, replacing bearing No 6307-02 Nos, replacement of worn out bearing housing, replacement of gland bush , unserviceable nut bolts and washers and bringing back the pump to the pump house and coupling the pump with motor and fixing on foundation and testing complete all as specified and directed. Note:- Rewinding job will be measured and paid separately.

2

-

-

... More
Material and labour for rewinding of 50 HP centrifugal motor by uncoupling the motor from the pump, removing the motor from the foundation and transportation of the motor to the workshop, opening the motor , taking out burnt out winding, preparing the slot for winding and rewinding of motor with super enamelled copper winding wire of appropriate size and gauge as existing to make the same cap of motor, varnishing and heat drying including scrapping of old paint & repainting with one coat of grey tinted synthetic enamel paint after motor is reassembled and testing complete all as specified and directed.

2

-

-

... More
Material and labour for rewinding of 15/20HP centrifugal motor by uncoupling the motor from the pump, removing the motor from the foundation and transportation of the motor to the workshop, opening the motor , taking out burnt out winding, preparing the slot for winding and rewinding of motor with super enamelled copper winding wire of appropriate size and gauge as existing to make the same cap of motor, varnishing and heat drying including scrapping of old paint & repainting with one coat of grey tinted synthetic enamel paint after motor is reassembled and testing complete all as specified and directed.

2

-

-

... More
Material and labour for rewinding of 7.5 HP to 10 HP centrifugal motor by uncoupling the motor from the pump, removing the motor from the foundation and transportation of the motor to the workshop, opening the motor , taking out burnt out winding, preparing the slot for winding and rewinding of motor with super enamelled copper winding wire of appropriate size and gauge as existing to make the same cap of motor, varnishing and heat drying including scrapping of old paint & repainting with one coat of grey tinted synthetic enamel paint after motor is reassembled and testing complete all as specified and directed.

1

-

-

... More
Material and labour for taking out the submersible pump set and motor assembly of capacity 5 HP to 10 HP from the borewell, by taking out the column pipes with chain pulley block and tripod stand, complete using skilled and experienced labour and transporting the same to workshop for repair and replacement of worn impellers -01 set , replacement of worn out bushings and bearings and transport back repaired pump set back to site after repair and Lowering the same in the bore well after testing complete all as specified and directed.

2

-

-

... More
Material and labour for rewinding of submersible motor 5 to 7.5HP by taking out the burnt out winding from the strater with PVC insulated copper winding wire of same gauge and size as per existing, replacement of thrust bearing and bushes and testing complete all as specified and directed.

2

-

-

... More
Supply and fixing of 1 HP Centrifugal Motor Pump, of head and throughput output as mentioned at site, complete with all related accessories for installation and operation complete all as specified and directed.

2

-

-

... More
Supply and fixing of 0.5 HP Centrifugal Motor Pump, of head and throughput output as mentioned at site, complete with all related accessories for installation and operation complete all as specified and directed.

2

-

-

... More
S&F manually operated Direct On line oil immersed starter (Heavy duty) ISI Marked suitable for 50 HP motor 3 phase 415 Volt AC 50 Hz complete all as specified and directed.

2

-

-

... More
S&F in replacement starter for submersible pump 5/7.5 HP complete all as specified and directed.

2

-

-

... More
S&F in replacement rubber Star coupling of size L-190 for 50HP Centrifugal pump set complete all as specified and directed.

15

-

-

... More
S&F in replacement gland packing of suitable size for 50 HP pump complete all as specified and directed.

6

-

-

... More
M&L for Construction of brick masonry valve pit of size 600 x 600 x 600 mm (Internal dimensions of chamber from top of PCC to bottom of cover) including excavation in any type of soil returning, filling around foundation and removal of surplus soil to a distance not exceeding 50m PCC 1:4:8 type D2 in foundation brick work in cement mortar 1:6, 10mm thick plaster in cement mortar 1:4 to internal surface covered pit with MS sheet cover 3.15 mm thick with locking arrangement handle fixing arrangement and painting with oil paint two coat over a coat of red oxide primer complete all as specified and directed.

1

-

-

... More
M&L for lagging to pipes used in water supply or plumbing all round with, 40 mm thick bounded mineral wool preformed 'SNAPON' pipe section of density 144 Kg/cum conforming is IS 9842 on pipe of internal dia 20 mm with chicken mesh wire netting 25 mm gauge,20mm mesh complete all as specified and directed.

60

-

-

... More
All as per description of ser item No-45 above but 25mm dia bore.

60

-

-

... More
S&F non-return valve heavy duty of size 80 mm bore, ISI Marked, flanged ends including suitable nut bolts, washers, packing sheet, etc complete with necessary arrangements for fixing complete all as specified and directed.

1

-

-

... More
S&F non-return valve heavy duty of size 50 mm bore, ISI Marked, flanged ends including suitable nut bolts, washers, packing sheet, etc complete with necessary arrangements for fixing complete all as specified and directed.

1

-

-

... More
M&L for dewatering of sump by pump from clean water sump of size and capacity (30000 to 50000Gln), and taking out sludge, removing the same to a distance not exceeding 50m with & including, cleaning the sump by wire brushing, including brooming down complete including white washing internally, complete all as specified and directed.

2

-

-

... More
M&L for disconnecting and taking out unserviceable 3 phase electric motor of 5 HP capacity, taking to work shop, dismantling carefully, cutting out burnt out windings, cleaning the slots. And rewinding with super enamelled copper winding wire of appropriate gauge and weight including all insulating materials, varnishing, drying, heating etc, and reassembling, transportation to site and refixing at original position and testing complete all as specified and directed.

1

-

-

... More
M&L for disconnecting and taking out unserviceable 3 phase electric motor of 15- 20 HP capacity, taking to work shop, dismantling carefully, cutting out burnt out windings, cleaning the slots. And rewinding with super enamelled copper winding wire of appropriate gauge and weight including all insulating materials, varnishing, drying, heating etc, and reassembling, transportation to site and refixing at original position and testing complete all as specified and directed.

1

-

-

... More
M&L for disconnecting and taking out unserviceable 3 phase electric motor of 30 HP capacity, taking to work shop, dismantling carefully, cutting out burnt out windings, cleaning the slots. And rewinding with super enamelled copper winding wire of appropriate gauge and weight including all insulating materials, varnishing, drying, heating etc, and reassembling, transportation to site and refixing at original position and testing complete all as specified and directed.

1

-

-

... More
S&F after testing at site fully automatic star delta starter for 10 HP motor /submersible pump provide with protection degree IP 54, Extended wide band coil, Starter type Air Break, FRLS internal Wiring Over load relay Range 8.0A to 12 A. complete all as specified and directed.

1

-

-

... More
S&F manually operated Direct On line oil immersed starter (Heavy duty) ISI Marked suitable for 15-20 HP motor 3 phase 415 Volt AC 50 Hz complete all as specified and directed.

1

-

-

... More
S&F (after testing at site) fully automatic star delta starter for 15 HP motor /submersible pump provide with protection digree IP 54, Extended wide band coil, Starter type Air Break, FRLS internal Wiring complete all as specified and directed.

1

-

-

... More
S&F in replacement of manually operated Direct On line oil immersed starter (Heavy duty) ISI Marked suitable for 30 HP motor 3 phase 415 Volt AC 50 Hz complete all as specified and directed.

1

-

-

... More
Supply and fixing in replacement foot valve of size 80mm complete all as specified and directed.

1

-

-

... More
Supply and fixing in replacement foot valve of size 50 mm complete all as specified and directed.

2

-

-

... More
S & F cast iron sluice valve 80 mm bore, ISI marked flanged ends drilled pressure rating PN-1.0 PD short body confirming to IS- 14846-2000 having stainless steel spindle with cast iron operation wheel at top complete all as specified and as directed. Note :- Flanged joints with jointing material shall deemed to be included in the quoted rate .

1

-

-

... More
S & F cast iron sluice valve 50 mm bore, ISI marked flanged ends drilled pressure rating PN-1.0 PD short body confirming to IS- 14846-2000 having stainless steel spindle with cast iron operation wheel at top, complete all as specified and as directed. Note :- Flanged joints with jointing material shall deemed to be included in the quoted rate .

1

-

-

... More
Material and labour for taking out the submersible pump motor assembly of capacity 20 HP from the borewell by taking out column pipe of any dia and length complete using skilled labour, T &P and transporting the same to workshop for repair, getting back and lowering the pump set in the borewell and providing electric connections complete all as specified and directed.

1

-

-

... More
M&L for rewinding of 25/20 HP submersible motor by taking out burnt winding from stator with PVC insulated copper winding of same gauge and size as per existing, replacing bushes and testing and commissioning complete all as specified and directed.

2

-

-

... More
M&L for dismantling of submersible pump assembly of capacity 25/20 HP and carry out repair including replacement of defective impellers, bushes, keys, CI bodies, unserviceable nuts, bolts and washers including testing and commissioning complete.

2

-

-

... More
Taking down carefully copper/ aluminium unserviceable/ perished point wiring (light, fan, socket or power complete including fixture and fittings such as switches, ceiling roses, pandents, regulators, sockets, light fittings, removing material from site for taking credit etc and making good disturbed surfaces of wall, floors, complete all as specified and directed.

279

-

-

... More
M & L for point wiring with PVC insulated unsheathed single core multistranded copper conductor 1.5 sqmm, 1100 volts grade cable, FRLS, drawn through PVC casing caping including accessories and providing of PVC boxes for mounting switches, switch socket, fan regulator, provision of modular terressa plate Irene stripes, No of modules as required on site or as directed by Engineer-in-Charge including one run of PVC insulated unsheathed multistranded copper conductor cable 1.5 sqmm (green colour) earth wire and connected to earth dolly complete all as specified and directed for one light /one fan/one bell point controlled by one switch.

201

-

-

... More
All as per item No 65 herein before but for one socket outlet 5 pins 5 amps controlled by one switch on same board.

16

-

-

... More
All as per item No 65 herein before but for one socket outlet 5 pins 5 amps controlled by one switch on independent board.

30

-

-

... More
All as per item No 65 herein before but wiring with 2.5 sqmm copper wire (FRLS) and 2.5 sqmm earth wire for socket outlet 6 pin 15 amps on independent board.

32

-

-

... More
S&F Modular switch 1 way 6A, single pole, one module complete all as specified and directed.

35

-

-

... More
S&F Modular switch 1 way 16A, single pole, one module complete all as specified and directed.

13

-

-

... More
S&F switch piano flush button single pole, one way 5 amps complete all as specified and directed.

188

-

-

... More
S&F Bell Push Flush Type single pole, one way 5 amps complete all as specified and directed.

4

-

-

... More
S&F socket outlet multi 3 pins 5 amp modular, complete all as specified and directed.

18

-

-

... More
S&F socket outlet multi 5 pins 5 amp, complete all as specified and directed.

16

-

-

... More
S & F switch socket combination 2 in 1, 5A flush type all as specified and directed by Engr-in-Charge

22

-

-

... More
S&F switch piano flush button single pole, one-way 15amps complete all as specified and directed.

10

-

-

... More
S&F socket outlet 2 in 1, 2/3 pins 15-amp, modular socket complete all as specified and directed.

13

-

-

... More
S&F socket outlet 2 in 1, 6 pins 15 amp, complete all as specified and directed.

8

-

-

... More
S & F switch socket combination 3 pin 16A, flush type , complete all as specified and directed.

24

-

-

... More
S&F ceiling rose, PVC/poly carbonate, isolated body three terminal complete all as specified and directed.

80

-

-

... More
S&F lamp holder angle type PVC/Poly carbonate type insulated body with back plate suitable for batten/wall fitting complete all as specified and directed.

43

-

-

... More
S&F LED bulb 5W suitable for fixing in PVC angle holder complete all as specified and directed.

23

-

-

... More
S&F LED bulb 9W suitable for fixing in PVC angle holder complete all as specified and directed.

20

-

-

... More
S&F sheet metal enclosure for DBs (single door type) when MCBs to be used single pole and neutral 4 way including blanking plate as required with 200 amps rated busbar 240V fixed sunk/flush to the wall or niche complete all as specified and directed.

5

-

-

... More
S&F sheet metal enclosure for DBs (Double door type) when MCBs to be used single pole and neutral 4 way including blanking plate as required with 200 amps rated busbar 240V fixed sunk/flush to the wall or niche complete all as specified and directed.

2

-

-

... More
S&F sheet metal enclosure for DBs (single door type) when MCBs to be used single pole and neutral 8 way including blanking plate as required with 200 amps rated busbar 240V fixed sunk/flush to the wall or niche complete all as specified and directed.

9

-

-

... More
S&F sheet metal enclosure for DBs (Double door type) when MCBs to be used single pole and neutral 8 way including blanking plate as required with 200 amps rated busbar 240V fixed sunk/flush to the wall or niche complete all as specified and directed.

2

-

-

... More
S&F sheet metal enclosure for DBs (single door type) when MCBs to be used single pole and neutral 12 way including blanking plate as required with 200 amps rated busbar 240V fixed sunk/flush to the wall or niche complete all as specified and directed.

5

-

-

... More
S&F single pole and neutral enclosure with two pin and earth plug and socket complete with one single pole MCB 6-32 amp complete all as specified and directed.

8

-

-

... More
MCB single pole & neutral 40 to 63 Amps 230 Volts 'C' series, 10 KA complete all as specified and directed.

8

-

-

... More
S&F MCB's single pole 240 volts 6 to 32Amps 10 KA 'C' series, complete all as specified and directed.

70

-

-

... More
S&F 1100 volt grade heavy duty cable PVC insulated multistranded aluminium stranded conductor served with PVC tape and overall PVC sheathed in service connection suspended by insulating hangers not more than 1 mtr apart including 4mm dia GI suspension ire one twin core flat cable of circular of size 10 sqmm complete all as specified and directed.

90

-

-

... More
S&F 1100 volt grade heavy duty cable PVC insulated multistranded aluminium stranded conductor served with PVC tape and overall PVC sheathed in service connection suspended by insulating hangers not more than 1 mtr apart including 4mm dia GI suspension ire one twin core flat cable of circular of size 16 sqmm complete all as specified and directed.

90

-

-

... More
M & L for sub main wiring with two single core 2.5 sqmm PVC insulated and unsheathed 1100 volts grade, stranded copper conductor FRLS ISI marked drawn into & including medium grade PVC conduit/ casing caping 25 mm dia with all fittings and accessories and one continuous run of 2.5 sqmm copper conductor PVC insulated (green colour) as earth wire fixed into PVC casing / conduit (not less than 25mm outer dia) with all fittings and accessories fixed concealed/ surface including taking down old unserviceable submain wiring and making good disturbed surface complete all as specified and directed.

65

-

-

... More
M & L for sub main wiring with two single core 4 sqmm PVC insulated and unsheathed 1100 volts grade, stranded copper conductor FRLS ISI marked drawn into & including medium grade PVC conduit/ casing caping 25 mm dia with all fittings and accessories and one continuous run of 4 sqmm copper conductor PVC insulated (green colour) as earth wire fixed into PVC casing / conduit (not less than 25mm outer dia) with all fittings and accessories fixed concealed/ surface including taking down old unserviceable submain wiring and making good disturbed surface complete all as specified and directed.

78

-

-

... More
S & F in replacement LED light fitting 1x9W/1X10Wbulk head luminaires including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed.

10

-

-

... More
Supply and fixing in replacement LED lights fitting 1x 20W, 220V,AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and directed.

85

-

-

... More
Supply and fixing in replacement LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete. complete all as specified and directed.

6

-

-

... More
Supply and fixing in replacement Circular/Square (as per site Requirement) shape 6 watt 220 volts AC recessed type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed.

5

-

-

... More
Supply and fixing in replacement Circular/Square (as per site Requirement) shape 12 watt 220 volts AC recessed type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed.

13

-

-

... More
Supply and fixing in replacement Circular/Square (as per site Requirement) shape 15 watt 220 volts AC recessed type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed.

4

-

-

... More
Supply and fixing in replacement LED luminaire 600 mm x 600 mm,35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and directed.

26

-

-

... More
S&F Bed side designer lamp, 5 watts, with LED lamp, including all wiring and switches required, with terminal connection, 3 terminal/ PVC/ polycarbonate, isolated body complete all as specified and directed.

4

-

-

... More
Supply and fix in replacement decorative gate light made up of high grade unbreakable polycarbonate material suitable for retrofit LED 20W B22 base with 1x20 watt LED lamp complete all as specified and directed.

4

-

-

... More
M&L for rewinding of exhaust fan with super copper enamelled wire with suitable gauge, varnishing, oiling and greasing of any make of size 450 mm sweep by dismantling its parts, capacitor 4 Mfd by replacing petty items such as nuts & bolts bearing & washers, cleaning of exhaust fan body and its blade by cleaning agent, assembling, and connecting and testing complete all as specified and directed.

8

-

-

... More
S&F of heating element with new one capacity of 1500 Watts (triangle type) for 25 Ltr geysers complete all as specified and directed.

8

-

-

... More
S&F of heating element with new one capacity of 2000 Watts for 25 Ltr geyser(triangle type) complete all as specified and directed.

8

-

-

... More
S&F of Thermostat 7''/9" suitable for 25/50 ltrs capacity water geyser with automatic thermal cut out fixed in repair and including testing, complete all as specified and directed.

7

-

-

... More
S&F of copper Geyser Assembly with rubber packing for 25/50 ltrs capacity water geyser with automatic thermal cut out fixed in repair and including testing, complete all as specified and directed.

7

-

-

... More
Supply and fixing in replacement Exhaust fan AC single phase, 1200 rpm 230/240V of size 250mm sweep with louvre heavy duty complete all as specified and directed.

1

-

-

... More
Supply and fix in replacement, water heater storage type , electric capacity 25 ltr along with all acessories BEE 5 star rated, complete all as specified and directed.

1

-

-

... More
Supply and fix in replacement, water heater storage type , electric capacity 10 ltr along with all accessories BEE 5 star rated, complete all as specified and directed.

1

-

-

... More
S&F Motion Sensor 10 Watt Light circular/Square shape 6500K Neo surface white radar Polycarbonate downlighter , Auto on off ceeling light , surface mounted no false ceiling required , Flicker Free Instant start operate on AC current , voltage range 100V-300V , input Voltage-220V complete all as specified and directed.

4

-

-

... More
M&L for earthing complete with galvanized steel earth plate electrode 60cmx 60cmx6mm thick buried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5m below normal ground level, connected to galvanized iron wire 4.0mm dia by means of bolts, nuts and washers of galvanized iron or steel, protected by GI light grade pipe 15mm bore including GI light grade water pipe 20mm dia with funnel all as shown in electric plate No. 03 of 2009 SSR Pt-I and testing on complete including earth work in any type of soil, PCC 1:2:4 type B-0 as in earth pit and cover 40mm thick reinforced with XPM (weight not less than 4.0Kg/Sqm) and frame of angle iron 25x25x3mm with lugs 2 Nos and with 6mm dia MS bar handle made to shape, common salt, charcoal and testing on completion, complete all as specified and directed.

20

-

-

... More
S&F MCB single pole & neutral 32 Amps 230 Volts 'C' series, 10 KA complete all as specified and directed.

12

-

-

... More
M & L for sub main wiring with two single core 6 sqmm PVC insulated and unsheathed 1100 volts grade, stranded copper conductor FRLS ISI marked drawn into & including medium grade PVC conduit/ casing caping 25 mm dia with all fittings and accessories and one continuous run of 6 sqmm copper conductor PVC insulated (green colour) as earth wire fixed into PVC casing / conduit (not less than 25mm outer dia) with all fittings and accessories fixed concealed/ surface including taking down old unserviceable submain wiring and making good disturbed surface complete all as specified and directed.

30

-

-

... More
Supply and fixing 1100 volts grade heavy duty cable PVC insulated stranded aluminium conductor, served with inner sheathed of PVC tape overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4 mm suspension wire, one twin core cable of size 16 Sqmm complete all as specified and directed

90

-

-

... More
Supply and fixing 1100 volts grade heavy duty cable PVC insulated stranded aluminium conductor, served with inner sheathed of PVC tape overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4 mm suspension wire, one twin core cable of size 10 Sqmm complete all as specified and directed

90

-

-

... More
Supply & Laying with commissioning and testing XLPE insulated, armoured heavy duty electric cable with multistrandd aluminium conductor, 1100 volts grade, laid in trenches, passing through pipes, fixed on walls complete including connecting properly by means of thimbles and taking out old unserviceable damaged cables of size (a) 50 sq mm, 3.5 core

1300

-

-

... More
All as per item No 119 herein before but for 35 sq mm, 3.5 core cable.

840

-

-

... More
All as per item No 119 herein before but for 25 sq mm, 3.5 core cable.

390

-

-

... More
All as per item No 119 herein before but for 16 sq mm, 4 core cable.

240

-

-

... More
All as per item No 119 herein before but for 16 sq mm, 2 core cable.

280

-

-

... More
All as per item No 119 herein before but for 95 sq mm, 3.5 core cable

445

-

-

... More
Excavation in trenches exceeding 1.5 Mtr wide and not exceeding 3 mtr depth and getting out in any type of soil complete all as specified and directed.

1.29

-

-

... More
Sand cushioning to underground cables 8 cm below the cable before laying and 15cm above the cable after laying, complete all as specified in clause 19.75 of SSR Part-I, complete all as specified.

56.8

-

-

... More
M&L sub class 'B' brick old size brick covering laid dry, flat equal to width of bricks, perpendicular to UG cable over the dry sand cushioning, for cable protection as directed by Engineer-in-Charge.

5067.04

-

-

... More
M&L for mild steel cross arms bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminium paint after preparation of surface, including taking down unserviceable/old cross arms, complete all as specified and directed.

2.48

-

-

... More
M&L in replacement of ACSR conductor of any size and any type (as required on site) including stretching, fixing and binding to insulator on OH LT/HT line service feeders all as specified including aluminium binding wire or aluminium tapes complete all as specified and directed.

9.5

-

-

... More
M & L for pin type, porcelain, vitreous, white or brown insulator including one galvanised mild steel spindle, one galvanised iron washers and one galvanised iron nut, 150mm height, 150mm dia for 11000(HT) volts grade. Including taking down old unserviceable pin insulator complete all as specified and directed.

45

-

-

... More
M & L for pin type, porcelain, vitreous, white or brown insulator including one galvanised mild steel spindle, one galvanised iron washers and one galvanised iron nut, 100 mm height, 65mm dia for 1100 (LT) volts grade. Including taking down old unserviceable pin insulator complete all as specified and directed.

45

-

-

... More
M&L in replacement of Shackle type, porcelain, vitreous, white, brown or green insulators for working pressure 1100 volts grade, 90 mm dia 75 mm height including galvanized mild steel straps of 31 x 3 mm size, 12 mm dia insulator bolts, washers and nuts complete all as specified and directed.

45

-

-

... More
S & F in replacement steel tubular swaged poles erected truly vertical or planted as strut complete with 300 x300x 6 mm thick mild steel base plate, welded to pole, B-118 final, taper cap, bolts, nuts & screws, poles made out of ERW MS tubing conforming to IS-2713 Part-II. type 410 SP-55 (11.0 metres long) including drilling of holes of required size for fixing of cross arms, painting the exposed surfaces of pole with two coats of aluminium paint over a coat of red oxide zinc chrome primer and with two coats of black bituminous paint internally & portion embedded in concrete, making five black & red bands at lower portion of pole each 300mm wide alternately, and making pole No. with black paint at suitable height complete all as specified and directed.

6

-

-

... More
S&F of on load changeover switch 415 volt in sheet metal enclosure 3/4 pole of capacity from 63 Amp to 250 Amp complete all as specified and directed.

17

-

-

... More
Supply and fix cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination, heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE /(ABC), armoured, Al conductor cable of size 50 to 95 sqmm (as required on site) complete all as specified and directed.

15

-

-

... More
M&L for Stright through joint of size 25 Sqmm to 95 Sqmm Sqmm 3½ core regin cast complete heat shrink outdoor type LT PVC / XLPE cable upto 1.1 KV complete with all accessories and generally conforming to IS 8438/1977 complete all as specified and directed.

16

-

-

... More
M&L for Straight through joint of size 120 Sqmm to 240 Sqmm Sqmm 3½ core regin cast complete heat shrink outdoor type LT PVC / XLPE cable upto 1.1 KV complete with all accessories and generally conforming to IS 8438/1977 complete all as specified and directed.

15

-

-

... More
Supply and fixing copper thimble of size 50 to 120 Sqmm, complete all as specified and directed.

60

-

-

... More
Supply and fixing Aluminium thimble of size 25 to 70 Sqmm, complete all as specified and directed.

60

-

-

... More
Supply and fixing Aluminium thimble of size 95 to 150 Sqmm, complete all as specified and directed.

60

-

-

... More
Supply and fixing Aluminium thimble of size 185 to 240 Sqmm, complete all as specified and directed.

60

-

-

... More
Material and Laying for Cement concrete 1:4:8 (using 40mm graded stone aggregate) as in sub base of poles / Strut including necessary frame work complete all as specified and directed.

0.96

-

-

... More
Material and Laying for Cement concrete 1:3:6 (using 40mm graded stone aggregate in foundation filling and mass concrete including necessary frame work complete all as specified.

3.45

-

-

... More
Material and Laying for Cement concrete 1:2:4 type B-2 using 40 mm graded crushed stone aggregate as in pole coping complete all as specified and directed.

1.13

-

-

... More
Supply, installing, testing and commissioning of Air-break, gang operated, triple pole switch, outdoor, horizonal mounting type (ISI marked), mechanically operated with ertical isolation , mounted on insulators and steel frame with operating mechanism worked from ground level and including operation rod of 25mm dia medium grade GI pipe with and with locking arrangement including Godrej pattern 65mm pad locks with two keys for current rating 200 amp HT 11 KV with and including drop fuse set with 12 insulators and making all incoming/outgoing connections including two coats of aluminium paint over a coat of red oxide primer on steel surfaces , complete all as specified and directed.

9

-

-

... More
M&L for re stretching of LT/HT ACSR conductor and GI wire of any size and on any type of poles carrying up to six conductors in a span including disconnecting from insulator and rewinding to insulator after stretching with and including aluminium wire including refixing /re-adjusting line spans , line separators, cross arm on poles complete all as specified and directed.

180

-

-

... More
M&L for cutting/Trimming/choping of tree trenches along the overhead line upto 3m from electric line clearance on both side of HT/ LT lines and disposing off the cut tree / Branches site to a distance not exc. 50m and clearing the site complete all as specified and directed.

220

-

-

... More
M&L for painting to HT/LT poles, 11/9 mtr with cross arms, bracing and clamps with one coat of synthetic enamelled paint over one coat of red oxide primer including scrapping the old paint carefully to make smoothen complete and painting strips of red and black from foot of pole upto 5 feet each strip of 30 cm height complete all as specified and directed.

282

-

-

... More
S&F of MCCB 400 Amp 4 Pole 415 Volt breaking capacity 36kA complete all as specified and directed.

6

-

-

... More
S&F of MCCB 250 Amp 4 Pole 415 Volt breaking capacity 36kA complete all as specified and directed.

10

-

-

... More
S&F of MCCB 200 Amp 4 Pole 415 Volt breaking capacity 25kA complete all as specified and directed.

17

-

-

... More
S&F of MCCB 125 Amp 4 Pole 415 Volt breaking capacity 16kA complete all as specified and directed.

15

-

-

... More
S&F of MCCB 63-100 Amp 3/4 Pole ( as per site Requirement) 415 Volt breaking capacity 16kA complete all as specified and directed.

14

-

-

... More
S & F in replacement steel tubular swaged poles erected truly vertical or planted as strut complete with 300 x300x 6 mm thick mild steel base plate, welded to pole, B-118 final, taper cap, bolts, nuts & screws, poles made out of ERW MS tubing conforming to IS-2713 Part-II. type 410 SP-31 (9.0 metres long) including drilling of holes of required size for fixing of cross arms, painting the exposed surfaces of pole with two coats of aluminium paint over a coat of red oxide zinc chrome primer and with two coats of black bituminous paint internally & portion embedded in concrete, making five black & yellow bands at lower portion of pole each 300mm wide alternately, and making pole No. with black paint at suitable height all as specified and directed.

6

-

-

... More
M&L for painting of any type of size of LT Panel Indoor/outdoor type cubical panel board painted with two coats synthetic enamelled spray painting outside of panel upto 3 Sqmm of LT panel complete all as specified and directed.

8

-

-

... More
M&L for painting of any type of size of LT Panel Indoor/outdoor type cubical panel board painted with two coats synthetic enamelled spray painting outside of panel above 3 Sqmm and upto 6 Sqmm of LT panel complete all as specified and directed.

8

-

-

... More
M&L for cutting existing road/hard standing not exc 45x45 cm in wide & depth getting out excavated material for laying cable/GI tube, returning filling & well ramming watering finish surface 10 cm from top using PCC 1:3:6; including removal of surplus soil complete all as specified and directed.

16

-

-

... More
Taking down the existing un serviceable distribution panel board with conventional type switches, unserviceable MCCBs from Panel boards, controls and removing from site for further disposal and complete all as specified and directed.

3

-

-

... More
M&L preparing old painted surfaces by scraping and removing old paints, rust, etc. from Steel Tubular Poles (above the Planting Depth and PCC Copings of 9.0/11 Metre length Pole) and Mild Steel Cross Arms, Cable Protection Pipe, Brackets, etc. and applying one Coat of alternate Yellow & Black Strips Painting (4 No. Each Strip 300 mm wide) and remaining portion of Pole and Cross Arms, Cable Protection Pipe, Brackets, etc. treated with One Coat of Aluminium Paint, including writing of pole numbers with black synthetic enamel paint, complete all as specified and as directed.

40

-

-

... More
Supply install commissioning and testing floor mounted Outdoor cubical type LT Feeder Pillar Box (CPRI tested) of suitable size fabricated out of 3.15 mm thick CRCA Sheet and angle iron 60 X 60 X 6 mm frame factory made totally enclosed dust and vermin proof both side hinge opening arrangement on front and back centre openable double door with locking arrangement cable entry and exit from bottom with cable glands and gaskets, Digital VAF + PF Meter- 01 Set, including LED indicating lamps- 03 Nos, internal wiring of suitable size to be used for incoming and outgoing connection of all switches/MCCB's & Bus-bar. The TPN bus bars shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator, connected with Aluminium lugs, including painting on the surfaces externally & internally with powder coating (RAL-7032) incl. necessary PCC (1 : 3 : 6) type C2 as in foundation all as specified and as directed, comprising of the following :-

1

-

-

... More
Note: 1. Internal Wiring with single core copper conductor cable/ PVC Insulated Strip of suitable size incoming busbar and busbar to out going MCCB/MCB - 1 Job.

-

-

-

... More
2. Fine wiring with single core copper conductor cable for instruments/ indicating lamps - 1 Job.

-

-

-

... More
INCOMING

-

-

-

... More
(a) Bus bar chamber comprising 04 Nos Tin-plated Copper strip bus bar mounted on DMC (Dough moulding compound) insulator and PVC sheathed capacity 400 Amps with colour coding for RYB & N - 01 Set

-

-

-

... More
(b) MCCB 250 Amps, 4pole, 415 Volts rating with overload short circuit fault protection 3 phase with neutral link specially fixed for incoming supply ( Breaking capacity 25 KA) , Ics=100% of Icu - 01 No

-

-

-

... More
OUT GOING

-

-

-

... More
(c) MCCB 160 Amps, 4pole, 415 Volts rating with overload short circuit fault protection 3 phase with neutral link specially fixed for outgoing supply (Breaking capacity 25 KA) , Ics=100% of Icu - 01 No

-

-

-

... More
(d) MCCB 100 Amps, 4pole, 415 Volts rating with overload short circuit fault protection 3 phase with neutral link specially fixed for outgoing supply (Breaking capacity 25 KA) , Ics=100% of Icu - 01 No

-

-

-

... More
(e) MCCB 63 Amps, 4pole, 415 Volts rating with overload short circuit fault protection 3 phase with neutral link specially fixed for outgoing supply (Breaking capacity 16 KA) , Ics=100% of Icu - 01 No

-

-

-

... More
(f) MCCB 40 Amps, 4pole, 415 Volts rating with overload short circuit fault protection 3 phase with neutral link specially fixed for outgoing supply (Breaking capacity 16 KA) , Ics=100% of Icu - 01 No

-

-

-

... More
Note - Fixing arrangement diagram and line diagram of the panel shall be got approved by accepting officer before panel fabrication.

-

-

-

... More
Supply install commissioning and testing floor mounted Outdoor cubical type LT Feeder Pillar Box (CPRI tested) of suitable size fabricated out of 3.15 mm thick CRCA Sheet and angle iron 60 X 60 X 6 mm frame factory made totally enclosed dust and vermin proof both side hinge opening arrangement on front and back centre openable double door with locking arrangement cable entry and exit from bottom with cable glands and gaskets, Digital VAF + PF Meter- 01 Set, including LED indicating lamps- 03 Nos, internal wiring of suitable size to be used for incoming and outgoing connection of all switches/MCCB's & Bus-bar. The TPN bus bars shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator, connected with Aluminium lugs, including painting on the surfaces externally & internally with powder coating (RAL-7032) incl. necessary PCC (1 : 3 : 6) type C2 as in foundation all as specified and as directed, comprising of the following :-

1

-

-

... More
Note: 1. Internal Wiring with single core copper conductor cable/ PVC Insulated Strip of suitable size incoming busbar and busbar to out going MCCB/MCB - 1 Job.

-

-

-

... More
2. Fine wiring with single core copper conductor cable for instruments/indicating lamps - 1 Job.

-

-

-

... More
INCOMING

-

-

-

... More
(a) Bus bar chamber comprising 04 Nos Tin-plated Copper strip bus bar mounted on DMC (Dough moulding compound) insulator and PVC sheathed capacity 200 Amps with colur coding for RYB & N - 01 Set

-

-

-

... More
(b) MCCB 100 Amps, 4pole, 415 Volts rating with overload short circuit fault protection 3 phase with neutral link specially fixed for incoming supply ( Breaking capacity 25 KA) , Ics=100% of Icu - 01 No

-

-

-

... More
OUT GOING

-

-

-

... More
(c) MCCB 63 Amps, 4pole, 415 Volts rating with overload short circuit fault protection 3 phase with neutral link specially fixed for outgoing supply (Breaking capacity 16 KA) , Ics=100% of Icu - 02 No

-

-

-

... More
(d) MCCB 40 Amps, 4pole, 415 Volts rating with overload short circuit fault protection 3 phase with neutral link specially fixed for outgoing supply ( Breaking capacity 15 KA) , Ics=100% of Icu - 01 No

-

-

-

... More
Note - Fixing arrangement diagram and line diagram of the panel shall be got approved by accepting officer before panel fabrication

-

-

-

... More
Supply install commissioning and testing floor mounted Outdoor cubical type LT Feeder Pillar Box (CPRI tested) of suitable size fabricated out of 3.15 mm thick CRCA Sheet and angle iron 60 X 60 X 6 mm frame factory made totally enclosed dust and vermin proof both side hinge opening arrangement on front and back centre openable double door with locking arrangement cable entry and exit from bottom with cable glands and gaskets, Digital VAF + PF Meter- 01 Set, including LED indicating lamps- 03 Nos, internal wiring of suitable size to be used for incoming and outgoing connection of all switches/MCCB's & Bus-bar. The TPN bus bars shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on DMC/epoxy insulator, connected with Aluminium lugs, including painting on the surfaces externally & internally with powder coating (RAL-7032) incl. necessary PCC (1 : 3 : 6) type C2 as in foundation all as specified and as directed, comprising of the following :-

1

-

-

... More
Note: 1. Internal Wiring with single core copper conductor cable/ PVC Insulated Strip of suitable size incoming busbar and busbar to out going MCCB/MCB - 1 Job.

-

-

-

... More
2. Fine wiring with single core copper conductor cable for instruments/indicating lamps - 1 Job. ( Location Trehgam) INCOMING

-

-

-

... More
(a) Bus bar chamber comprising 04 Nos Tin-plated Copper strip bus bar mounted on DMC (Dough moulding compound) insulator and PVC sheathed capacity 400 Amps with colour coding for RYB & N - 01 Set

-

-

-

... More
(b) MCCB 250 Amps, 4pole, 415 Volts rating with overload short circuit fault protection 3 phase with neutral link specially fixed for incoming supply ( Breaking capacity 25 KA) , Ics=100% of Icu - 01 No

-

-

-

... More
OUT GOING

-

-

-

... More
(c) MCCB 100 Amps, 4pole, 415 Volts rating with overload short circuit fault protection 3 phase with neutral link specially fixed for outgoing supply ( Breaking capacity 25 KA) , Ics=100% of Icu - 04 No

-

-

-

... More
(d) MCCB 63 Amps, 4pole, 415 Volts rating with overload short circuit fault protection 3 phase with neutral link specially fixed for outgoing supply ( Breaking capacity 16 KA) , Ics=100% of Icu - 03 No

-

-

-

... More
Note - Fixing arrangement diagram and line diagram of the panel shall be got approved by accepting officer before panel fabrication.

-

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.