Military Engineer Services Tender

Search from the latest JKtenders and find a business opportunity fitting your SME on the online platform of BidAssist. If you're wondering how to find the latest JK tenders or from where to get all the documents without the hassles, this is what we explain here. Find the best opportunities coming to the surface via the JK government, PSUs and state corporations.

Military Engineer Services - MES Tender

Works
Electrical and Electronics
Electrical Works
Eprocure
Opening Date22 Nov 2024
Closing Date19 Dec 2024
Tender Amount₹ 43,90,000 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Taking up or down steel tubing with connections for cleaning for refixing or removing to storeyard complete of bore 15mm, complete, all as specified and directed.

160

-

-

... More
Description all as per item No. 4 above but 20mm bore, complete, all as specified and directed.

550

-

-

... More
Description all as per item No. 4 above but 25mm bore, complete, all as specified and directed.

400

-

-

... More
Description all as per item No. 4 above but 40mm bore, complete, all as specified and directed.

180

-

-

... More
Description all as per item No. 4 above but 50mm bore, complete, all as specified and directed.

160

-

-

... More
Description all as per item No. 4 above but 80mm bore, complete, all as specified and directed.

24

-

-

... More
Description all as per item No. 4 above but 100mm bore, complete, all as specified and directed.

18

-

-

... More
Laying only GI water mains after removal of scalling, cleaning and flushing etc including supply and fixing of new fittings for 15mm bore pipe, complete, all as specified and directed.

10

-

-

... More
Description all as per item No. 11 above but 20mm bore, complete all as specified and directed.

60

-

-

... More
Description all as per item No. 11 above but 25mm bore, complete all as specified and directed.

50

-

-

... More
Description all as per item No. 11 above but 40mm bore, complete all as specified and directed.

20

-

-

... More
Description all as per item No. 11 above but 50mm bore, complete all as specified and directed.

20

-

-

... More
Description all as per item No. 11 above but 80mm bore, complete all as specified and directed.

6

-

-

... More
Description all as per item No. 11 above but 100mm bore, complete all as specified and directed.

6

-

-

... More
Supply and laying GI water tubing, medium grade, galvanised (ISI marked as IS-1239), with all fittings including short lengths, fixed to walls, concealed in wall and ceiling or laid in floor trench complete with all fittings (such as bends, elbows, Tee, short pieces, connectors, back nuts, diminishing pieces, caps and plugs, unions etc), complete, all as specified and directed for 15 mm bore.

150

-

-

... More
Description all as per item No. 18 above but 20mm bore, complete all as specified and directed.

490

-

-

... More
Description all as per item No. 18 above but 25mm bore, complete all as specified and directed.

350

-

-

... More
Description all as per item No. 18 above but 40mm bore, complete all as specified and directed.

160

-

-

... More
Description all as per item No. 18 above but 50mm bore, complete all as specified and directed.

140

-

-

... More
Description all as per item No. 18 above but 80mm bore in trenches, complete all as specified and directed.

18

-

-

... More
Description all as per item No. 18 above but 100mm bore in trenches, complete all as specified and directed.

12

-

-

... More
Supply and fixing in repair Gun metal globe or gate valves, with iron wheel head screwed both ends for iron pipe of 15mm bore and fixed, complete, all as specified and directed. Make:- Shakti/Jaypee/SEIKO

25

-

-

... More
Description all as per item No. 25 above but 20mm size, complete all as specified and directed.

35

-

-

... More
Description all as per item No. 25 above but 25mm size, complete all as specified and directed.

30

-

-

... More
Description all as per item No. 25 above but 40mm size, complete all as specified and directed.

15

-

-

... More
Description all as per item No. 25 above but 50mm size, complete all as specified and directed.

10

-

-

... More
S&F in replacement of cast iron sluice valve of 80mm dia with flanged ends class PN 1 .6 with iron wheel, stainless steel spindle and check nut confirming to IS :14846 incl all jointing materials such as nuts, bolts, washers and gaskets etc complete all as directed.

2

-

-

... More
Description all as per item No. 30 above but 100mm size, complete all as specified and directed.

2

-

-

... More
Repair/maint of water leakage from DI pipe joint in ground and open carefully the joint portion of the of the pipe line duly excavated the trench and burning out the defective run lead joint in existing of CI pipe/fitting and provision of new lead joint in site using the retrieved lead as obtaining from burning out of joint and adding of fresh lead if required to make the joint 100% water leak proof including returning, filling and ramming the excavated materials after satisfactory, joint/leak chacking all as directed for following bore of CI pipe line :- (a) 100 mm bore pipe line.

20

-

-

... More
Description all as per item No. 32 above but 80mm bore, complete all as specified and directed.

25

-

-

... More
M&L Lagging on pipes of internal dia 20 mm, used in external water supply or plumbing all round with, 40mm thick bonded mineral wool preformed ‘SNAP ON’ pipe sections of density 144 Kg/cum conforming to IS 9842, provided with chicken mesh wire netting 25 gauze 20mm mesh and finally covering with plaster of pairs including taking down old, complete, all as specified and directed.

400

-

-

... More
Description all as per item No. 34 above but 25mm bore tubing, complete all as specified and directed.

350

-

-

... More
Description all as per item No. 34 above but 40mm bore tubing, complete all as specified and directed.

90

-

-

... More
Description all as per item No. 34 above but 40mm thick bonded and for 50mm bore tubing, complete all as specified and directed.

40

-

-

... More
Description all as per item No. 34 above but GI/DI pipe of 40mm thick bonded and for 80mm bore tubing.

30

-

-

... More
Description all as per item No. 34 above but GI/DI pipe of 40mm thick bonded and for 100mm bore tubing.

40

-

-

... More
Disconnectiong existing defective electric motor of any make upto 20 HP from electric mains isolating the necked connections, removing from foundation by unscrewing the nuts, bolts etc, discouple from pump, opening of motor for inspection in presence of Engr-in-Charge and carry out minor repairs at site or transporting to workshop and back, reassembling the motor after repair, refixing in position reconnecting same as prior to removing from foundation including replacement of nuts, bolts washers of suitable size, testing and commissioning complete all as specified and directed. Note :- (a) Replacement of defecting parts shall be measured and paid separately as S&F here after. (b) In case of major repairs not possible at site, the motor shall be shifted to Civil workshop, and cost of shifting to wksp and back to site included in the rates. The spares are as follows:-

8

-

-

... More
(a) Gland Packing of any size

10

-

-

... More
(b) Impeller (brass) for 20 HP Pump.

2

-

-

... More
(c) Impeller (brass) for 15 HP Pump.

1

-

-

... More
(d) Impeller (brass) for 10 HP Pump.

1

-

-

... More
(e) Impeller (brass) for upto 7.5 Pump

4

-

-

... More
(f) Pump shaft with nut for 20 HP Pump.

2

-

-

... More
(g) Pump shaft with nut for 15 HP Pump.

1

-

-

... More
(h) Pump shaft with nut for 10 HP Pump.

1

-

-

... More
(j) Pump Shaft with nut for upto 7.5 Pump

4

-

-

... More
(k) Bearing for 20 HP Pump

4

-

-

... More
(l) Bearing for 15 HP Pump

4

-

-

... More
(m) Bearing for upto 10 Pump

2

-

-

... More
(n) Bearing for upto 7.5 Pump

2

-

-

... More
(o) Tyre coupling set for 10/15/20 HP Pumping Set

2

-

-

... More
(p) Neck ring for pump set capacity of 10/15/20 HP

4

-

-

... More
Carrying out rewinding and overhauling of motor assembly after cutting burnt winding wire, cleaning of core slots and re- winding by using super enameled copper winding wire of appropriate gauge and turn as per existing incl providing all insulation materials & varnishing heating, replacement of worn out bearing bushing etc incl lubrication, and assembling the complete motor assembly, testing complete for following capacity motor. NOTE :- (a) All new spares/components will be measured and paid separately under respective items. (b) Replacement of bolts/nuts/washers are deemed to be included in the items. The following capacity of motors :

-

-

-

... More
(a). Motor of capacity 20 HP.

2

-

-

... More
(b). Motor of capacity 15 HP.

1

-

-

... More
(c) Motor of capacity 10 HP.

1

-

-

... More
(d) Motor of capacity upto 7.5 HP

4

-

-

... More
Supply and fixing in replacement Automatic star delta starter for 5 HP submersible pump 3 Phase 415 volts, as per existing complete all as specified and directed. Make: Havell's/L&T/Siemens.

1

-

-

... More
Taking out old unsv chnage over switch of nay capacity and supply & fixing connecting off load change over switch 4 pole 200 Amp 440 volts conforming to relevant IS including all connecting and jointing material complere, complete all as specified and directed.

1

-

-

... More
Supply and laying rubber matting electrical grade of size 2m x1m x 10mm ISI marked, laid in front of the LT panel, complete all as specified and directed.

5

-

-

... More
Earthing complete with GI earth plate 60cmx60cmx6mm thick electrode and 32 x 6 mm GI strip as earthing lead. buried directly in ground ( earth pit not less then 2.25 metres deep below ground level ) with top edge of the plate not less then 1.5 metres below normal ground level. connected to GI strip 32 x 6 mm as earth lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No. 3 and incl earth work, PCC pit and RCC cover, atering pipe 20 mm dia light grade, funnel, wire mesh, charcoal dust and salt etc and connected to earthing test point, complete, all as specified and directed. Note:- Item of earthing includes cost of 7.5m long GI earth lead 32x6mm and protection of 40mm bore GI light grade including testing

10

-

-

... More
Supply and fixing in replacement of Ampere meter 0 to 200 Amps Digital type with selector switches, CTs etc. complete all as specified and directed. Make- AE/L&T/ABB

3

-

-

... More
Supply and fixing in replacement of volt meters 0 to 500 Volts Digital type 415 volts with selector switches etc., complete all as specified and directed.Make- AE/L&T/ABB

3

-

-

... More
Supply and fixing in replacement single phase preventor, complete all as specified and directed.Make- AE/L&T/ABB

3

-

-

... More
Supply and fix in replacement of CIDFS wing type NRV size 100 mm dia bore as per IS-5312 of PN-1.6 type including nuts, bolts and jointing materials complete all as specified and directed. Make:- Kirloskar/BIR/BVI

2

-

-

... More
Supply and fix in replacement of CIDFS wing type NRV size 80 mm dia bore as per IS-5312 of PN-1.6 type including nuts, bolts and jointing materials complete all as specified and directed. Make:- Make :Kirloskar/BIR/BVI

2

-

-

... More
Supply and fix in replacement foot valve of size 80 mm dia bore flanged end drilled type including nuts, bolts and jointing materials complete all as specified as per IS -4038. Make :Kirloskar/ Normex/BIR/BVI

2

-

-

... More
Supply and fix in replacement foot valveof size 100 mm dia bore flanged end drilled type including nuts, bolts and jointing materials complete all as specified as per IS -4038. Make :Kirloskar/ Normex/BIR/BVI

2

-

-

... More
Supply and fixing in replacement of Automatic star delta starter suitable for 10 HP Centrifugal pump Sets 415 volt, 3 Phase, 50 Hz, including single phase preventer, complete all as specified and directed. MAKE-Siemens CAT PT NO-3TE 0497-2A or equivelant to Havells /L&T

2

-

-

... More
Supply and fixing in replacement of Automatic star delta starter suitable for 20 HP Centrifugal pump Sets 415 volt, 3 Phase, 50 Hz, including single phase Preventer, complete all as specified and directed. MAKE-Siemens CAT PT NO-3TE 0497-2A or equivelant to Havells /L&T

2

-

-

... More
M & L for cleaning of overhead reservoir by draining out water below supply level, removing all internal sludge by washing. Cleaning the surface of the reservoir using wire brushes and other scraping tools to remove dirt and scale to make it free from deposits. Washing the reservoir with high pressure compressor nozzle thoroughly and removing dirty water from the tank to make it clean. Also two coats of Distempering (White colour) both inner and outer surface of the OHT/Undrground Sump. Disinfecting the sump surface using disinfectent complete all as specified and directed for 15000 gallons capacity (Note:- The work of cleaning and disinfection will be carried out by expert in the field of the work. The work is to be carried out in such a way that the water supply is not disrupted.)

1

-

-

... More
M & L for cleaning of underground water sump by pumping out water below suction level, removing all internal deposited sludge by non clogging submersible pump, cleaning the surface of the sump using wire brushes and other scraping tools to remove dirt and scales to make it free from all deposits, washing the sump with high pressure compressor nozzle thoroughly and removing dirty water from the pump to make it clean including repair to the internal surfaces by plastering with cement mortar 1:3,15mm thick and providing fillers at cracks using chemical (Doctor fixit) as required to prevent any seepage of water including disinfecting the sump surfaces, complete, Painting one coat of anti bacteria water proof paint all as specified and directed of 50000 gallons capacity. (Note:- the work of cleaning and disinfection will be carried out by expert in the field of the work. the work will be carried out in such a way that the water supply is not interupted; necessary bypass arrangement to be done).

2

-

-

... More
Collecting the water samples in the sterilised container from the different locations at Haft Chinar pump houses in the sealed container in presence of concerned dept rep and transport to National / State Govt Authorised laboratory such as PHE/NTH or any Govt approved agenises and carrying out the Physical / Chemical / Biological analysis i.e PH, Chloride (CL), Total Hardness as Ca CO₃, Total dissolved solids and submitting the details report as per standard parameters in duplicate to this office, complete all as specified and directed.

10

-

-

... More
M&L for construction of Brick Masonry valve chamber of size 900x900x600mm (Internal dimensions) with PCC 1:4:8 foundation 150mm thick, brick work built in CM 1:6, PCC 1:3:6 coping 50mm thick, plastering 15mm thick in CM 1:6 to all internal and exposed surfaces including excavation earthwork in hard/dense soil, MS sheet cover 4mm thick and MS equal angle iron 50mmx50mmx6mm frame as per existing size with locking arrangement embedded in PCC suitable for 25/40/50mm gate valve and painting to MS cover with two coats of synthetic enamel paint over one coat of red oxide primer etc complete all per Drg. No HQ/136/TD/96 V and ground requirement including dismantling old/damaged valve pits.

5

-

-

... More
M&L for fixing of Air release valve matching with existing make complete with brass spindle, coller neack nuts all as per existing type of sluice valves for the following size including dismentling old worn-out spindle (Note : Brass spindle shall be fabricated from solid round bar having dia not less than the dia of the dia of the largest section of the spindle and not using anyriveting for expended coller of the spindle or by casting and machining to make the spindle a single piece for the following of sizes:-

-

-

-

... More
(a) 80 mm bore pipe line.

2

-

-

... More
(b) 100 mm bore pipe line.

2

-

-

... More
Repairs/rectification of GI Pipe leakage by replacing short piece length up to 0.50 mtr in wall/floors etc and excavation upto 1 cum as in trenches and including providing unions, reducers,nipples etc and making necessary connections to make it functional complete all as specified and as directed for the following sizes:-

-

-

-

... More
(a) 15 mm bore pipe

30

-

-

... More
(b) 20 mm bore pipe

50

-

-

... More
(c ) 25 mm bore pipe

40

-

-

... More
(d) 40 mm bore pipe

20

-

-

... More
(e) 50 mm bore pipe

25

-

-

... More
Supply and fixing in repairs GI/ DI mechanical joints, non extendable type with rings, nuts , bolts & washers etc complete all as specified and as directed for the following sizes:-

-

-

-

... More
(a) 80 mm bore

2

-

-

... More
(b) 100 mm bore pipe

2

-

-

... More
Taking down in repair of high mast light, Hot dip galvanised Mast 15/20Mtr high and Luminaires carriage duly opening of nut & bolts at bottom with the help of Hydra/Crane for repair /replacement of old UNSV Winch and steel ropes (as per existing 6/8mm) complete with ratchet, limit switches etc as per standerd engineering practice to avoid falling of carrier during raising or lowering and re-installation, testing at site and commissioning after satisfactorily repair complete all as specified and directed.

4

-

-

... More
Annual maintenance/servicing and replacement of unserviceable consumable items of Reverse Osmosis water purifier of capacity 20/25/50 Ltrs/hrs installed at various location, required rectifying any type of blockage,loose connection in electric and electronic components of plants, servicing of the plant to be carried as directeded by Engr-in- charge. Note-:(i ) All the spares/components required for the repair and servicing shall be measured and paid separately here-in- after as supplied only.

8

-

-

... More
(i) Supply only new sediment filters 20 inch long . Make- Kent/Aquafresh or as existing make.

16

-

-

... More
(ii) Supply only new Activated carbon filters 20 inch long . Make- Kent/Aquafresh or as existing make.

16

-

-

... More
(iii) Supply only new Carbon block granule 20 Inch . Make- Kent/Aquafresh or as existing make.

16

-

-

... More
(iv) Supply only new RO membrane set (open/Closed) Make- Kent/Aquafresh or as existing make .

16

-

-

... More
(v) Supply only new solenoide valve . Make-; Make- Kent/Aquafresh or in equaivalent

8

-

-

... More
(vi) Supply only new AC/DC Adepoter 48 Volts ultera violet lamp . Make- Kent/Aquafresh or in equaivalent

5

-

-

... More
(vii) Supply only low pressure switch . Make- Kent/Aquafresh or as existing make.

5

-

-

... More
(viii) Supply only new TDS valve. Make- Kent/Aquafresh or as existing make.

5

-

-

... More
(ix) Supply only new Booster pump 150 SPD . Make- Kent/Aquafresh or as existing make.

5

-

-

... More
M&L for replacement old unserviceable PVC pipe of suitable size with all fittings for 15/25/50 Ltrs RO plant , complete all as specified and directed. Make-: Kent/Aquafresh or in equaivalent.

35

-

-

... More
Annual maintenance/servicing and replacement of unserviceable consumable items of Reverse Osmosis water purifier of capacity 2000LPH installed Pump House Haft Chinar, required rectifying any type of blockage,loose connection in electric and electronic components of plants, servicing of the plant to be carried, complete all as specified and directed. Note-: (i) All the spares/components required for the repair and servicing shall be measured and paid separately here-in- after as supplied only and complete all as specified and directed at site by Engr-in-charge. The relevant following spares are as bellow:-

1

-

-

... More
(i) Supply only Iron Removal Chemical

80

-

-

... More
(ii) Supply only treatment media as required for existing media container Salt Tablets (for water softner), Activated carbon, Sand, Pebbles, Gravel media for RO plant of 2000LPH

1

-

-

... More
(iii) Supply only sediment flter 20'' big blue cylindrical Housing

18

-

-

... More
(iv) Supply only Antiscalant chemical

50

-

-

... More
(v) Supply only Ph balance 15 ltr

50

-

-

... More
(vi) Supply only UPVC tubing upto 40mm high strength with necessary accessories like Unior/Gate valve/ elbo/socket/tee, fitting/pipes working temperature 5°C to 60°C Note: All UPVC Fittings/accessories should be brass grooved.

1

-

-

... More
(vii) Supply only UPVC flow meter with float switch

2

-

-

... More
(viii) Supply only pressure guage with Pressure Switch

2

-

-

... More
M&L for rewinding of unserviceable booster pumps capacity 01 to 02 HP, complete all as specified and directed.

4

-

-

... More
Supply only granular Chlorine (60% of chlorine content) disinfectant superior quality of approved make for mixing with drinking water for water treatment, complete all as specified and directed.

680

-

-

... More
Material & Labour for overhauling of monoblock/centrifugal pump sets 1 HP to 5 HP capacity and reassembling the same after replacement of the following unserviceable/defective parts including testing of pump sets, complete all as specified and as directed with the connected items of shaft, Impeller, coupling, gunmetal bush, bearings nuts, bolts and gland etc.

3

-

-

... More
Taking out old unserviceable/burnt winding from the monoblock/centrifugal motors 1 HP to 5 HP and rewindinig the same with insulated winding wire as per existing gauge as approved by Engr-in Charge and testing after repair, complete all as specified and as directed.

2

-

-

... More
M&L, Construction of Brick Masonry valve chamber of size 600x600x600mm (Internal dimensions) with PCC 1:4:8 foundation 150mm thick, brick work built in CM 1:6, PCC 1:3:6 coping 50mm thick, plastering 15mm thick in CM 1:6 to all internal and exposed surfaces including excavation earthwork in hard/dense soil, MS sheet cover 4mm thick and MS equal angle iron 50mmx50mmx6mm frame as per existing size with locking arrangement embedded in PCC suitable for 25/40/50mm gate valve and painting to MS cover with two coats of synthetic enamel paint over one coat of red oxide primer, complete all per Drg. No HQ/136/TD/96 V and ground requirement including dismantling old/damaged valve pits. etc complete all as specified.

5

-

-

... More
M&L for fabrication and fixing of brass/stainless steel spindle for sluice valve matching with existing make complete with coller neack nuts all as per existing type of sluice valves for the following size including dismentling old worn-out spindle (Note : Brass spindle shall be fabricated from solid round bar having dia not less than the dia of the dia of the largest section of the spindle and not using anyriveting for expended coller of the spindle or by casting and machining to make the spindle a single piece):

-

-

-

... More
(a) 100 mm bore pipe line.

3

-

-

... More
(b) 80 mm bore pipe line.

3

-

-

... More
M & L for straight plain brass ferrules (or connecting screws) screwed both ends and fixied bore diameter of pipe in 20 mm on cast iron / ductile iron water mains, in position, for branch connections complete all as specified and directed.

5

-

-

... More
Description all as per serial item No. 71 above but bore of pipe in 25 mm, complete all as specified and directed.

5

-

-

... More
Supply, connecting, testing and commissioning submersible cable with copper conductor, stranded of size 6 sqmm 3 core, complete, all as specified and as directed.

30

-

-

... More
Supply & laying underground cable in trenches/existing cable duct/ cable tray, PVC heavy duty electric cable with copper conductor sizes of 25 sqmm single core confirming to IS : 7098 (Pt-I) 1988 and copper lugs for connecting cable at end of motor & starter, complete all as specified and directed.

137

-

-

... More
Supply & laying of GI perforated cable tray 1 mm thick and size of 400 x 75 x 10 mm for PVC heavy duty electric cable with copper conductor from motor to starter, complete all as specified and directed.

15

-

-

... More
Taking down ceiling fan any size or sweep after disconnecting, dismantling and removal to trade workshop for repair, complete all as specified and directed.

135

-

-

... More
M& L for Opening the unserviceable/burnt ceiling fan 1200/1400 mm sweep and cutting of old burnt copper winding and rewinding the same with super enamelled copper winding wire of suitable gauge including insulating material such as paper cotton sleeves, varnish, reassembling, testing and connecting for satisfactory run, complete all as specified and directed.

48

-

-

... More
Supply and replacing of Ball bearing of the ceiling fan (any sweep) as per existing size incl greasing/oiling, complete all as specified and directed. Make:- SKF/ NBC or Equivalent

60

-

-

... More
Supply and replacenment gun metal bushes of surface size for ceiling fan/ceiling fan incl necessary mechanical work, complete all as specified and directed.

45

-

-

... More
Supply and replacing of cord cable, three core 0.5 Sqmm PVC insulated copper conductor cable for connecting ceiling fan, complete all as specified and directed. Make:- Plaza/Havells.

50

-

-

... More
Supply and Fix in repair Capacitor of of 3.15 MFD for ceiling fan, complete all as specified and directed.

45

-

-

... More
Supply and fixing in replacement ceiling fan blade set of three heavy duty suitable for 1200/1400mm sweep of suitable approved make as direcetd by Engr-in-Charge.

10

-

-

... More
Supply and Fix in replacement of PVC canopy for ceiling fan 1200/1400mm sweep complete for various makes/model of fan, complete all as specified and directed.

20

-

-

... More
Disconnecting and taking down exhaust fan and blades any size or sweep after dismantling and removal to trade workshop for repair, complete all as specified and directed.

35

-

-

... More
M&L for Strip opening and cutting of old burnt copper winding of exhaust fan and rewinding of exhaust fan motor of sweep 450mm with super enamelled copper winding wire of suitable gauge including insulating material such as paper cotton sleeves, varnish, re-assembling, testing and connecting for satisfactory run, complete all as specified and directed.

21

-

-

... More
Description all as per item No 77.01 above but of 300mm sweep, complete all as specified and directed.

10

-

-

... More
Supply and Fix in repair Capacitor of 4 Mfd for exhaust fan, complete all as specified and directed.

10

-

-

... More
Supply and fixing in replacement of Ball bearing of exhaust fan of any size/make as per the existing, complete all as specified and directed. Make: SKF/NBC or equivalent.

22

-

-

... More
Painting the exhaust fan including louvers of size 300/450mm sweep with two coats of synthetic enamel paint after cleaning and making the surface of oil/dust free, complete all as specified and directed.

10

-

-

... More
Servicing of Geyser by disconnecting the electric and water supply connections, dismantling the geysers of any size, type & capacity and opening the top and bottom cover, thermostat, heating element, safety valve, vent pipe, separating inner & outer tank, removing glass wool insulation complete and keeping aside for re-use after de-scaling of inner tank by liquid chemical and with pressure water jet and assembling back the geyser including re-installation on wall with studs, nuts & bolts complete and testing after reconnecting electric and water connections, complete all as specified and directed. Note- Spares will be measured and seperately under respictive items of Sch 'A'.

22

-

-

... More
Supply and fiixing in replacement of Heating element for geyser of cap 1.5KW, AC 230 Volts, 50 Hz (as per sample), complete all as specified and directed. Make:- Micron/ Bajaj/ Havells

35

-

-

... More
Supply and fixing in replacement of Heating element for geyser of cap 2.0KW, AC 230 Volts, 50 Hz (as per sample), complete all as specified and directed. Make:- Micron/Bajaj/havells

25

-

-

... More
Supply and fixing in replacement of Thermostat for Geyser of capacity 25/35/50 ltr (long size) with temperature setting adjustment range from 40 to 85°C, ISI Marked, complete all as specified and directed. Make:- Philips/ Bajaj/ Venus

20

-

-

... More
Supply and fixing in replacement of Geyser Syphon Assembly Set suitable for 25 ltr capacity geyser, fixed in replacement, complete all as specified and directed.

10

-

-

... More
Descrition all as per Srl item No. 78.04 above but for 35 Ltr capacity, complete all as specified and directed.

5

-

-

... More
Descrition all as per Srl item No. 78.04 above but for 50 Ltr capacity, complete all as specified and directed.

2

-

-

... More
Supply and fixing in replacement of Rubber gasket for water heater/Geyser storage type of any capacity fixed, in replacement and suitable as per the existing, complete all as specified and directed

5

-

-

... More
Supply and fixing in replacement of PVC insulated sheathed three core copper conductor flexible wire of size 2.5 Sqmm for electric connection of geyser, complete all as specified and directed.

35

-

-

... More
Supply and fixing of Sheet Metal Enclosure with socket, plug top and MCBs single pole and neutral enclosures with a two pin and earth plug and socket complete with one single pole MCB 20 Amps 240 Volts, complete all as specified and directed.

5

-

-

... More
Supply and Fixing in replacement of safety valve for geyser of 25/35/50 litre capacity, complete all as specified and directed

10

-

-

... More
Supply and and fixing in replacement of non return valve 15mm dia for geyser of 25/50 litre capacity, complete all as specified and directed.

10

-

-

... More
Supply and fixing in replacement of heavy duty PVC connector 600mm long 15mm dia with PTMT nut for geyser of 25/35/50 litre capacity, complete all as specified and directed. Make- Prayag or equivalent

15

-

-

... More
Disconnecting and taking out geyser of capacity 25 litre and replacement of copper/SS inner tank and refilling of glass wool, refixing, connecting and testing, complete all as specified and directed.

18

-

-

... More
Description all as per ser item Srl No. 78.13 above but for 35 Ltr capacity, complete all as specified and directed.

5

-

-

... More
Description all as per ser item Srl No. 78.13 above but for 50 Ltr capacity, complete all as specified and directed.

5

-

-

... More
Preparation of surface of Geyser of capacity 25/35/50 Ltr by scarping, removing old paint etc and applying two coats of synthetic enamel paint over one coat of red oxide primer,complete all as specified and directed.

20

-

-

... More
Supply and fixing inreplacement of geyser Bolt 100 mm Long with nut & washers, complete all as specified and directed.

30

-

-

... More
Taking out the burnt/ unserviceable compressor from the refrigerator of 165 to 200 ltr capacity and supply & fixing IN replacement of the same as per the existing, complete all as specified and directed.

5

-

-

... More
Servicing and overhauling of refrigerator of 165 to 200 ltr capacity of various make and model incl transporting to workshop & back, complete all as specified and directed.

5

-

-

... More
Supply and fixing in replacement of thermostat for refrigerator of 165 to 200 ltr capacity, complete all as specified and directed.

5

-

-

... More
Supply and fixing in Replacement of thermal relay for refrigerator of 165 to 200 ltr capacity, complete all as specified and directed.

5

-

-

... More
Charging refrigerant R134A and testing for proper cooling and leakage before charging of new refrigerant etire system will clean with nitrogen and check the leakage with leakage indicators complete for refrigerator of 165 to 200 ltr capacity, complete all as specified and directed.

5

-

-

... More
Taking out the burnt/ unserviceable compressor from the refrigerator of 210 to 335 ltr capacity and supply & fixing the same as per the existing complete all as specified and directed.

5

-

-

... More
Servicing and overhauling of refrigerator of 210 to 335 ltr capacity of various make and model incl transporting to workshop & back, complete all as specified and directed.

4

-

-

... More
Supply and fixing in Replacement of thermostat for refrigerator of 210 to 335 litre capacity, complete all as specified and directed.

4

-

-

... More
Supply and fixing in Replacement of thermal relay for refrigerator of 210 to 335 litre capacity, complete all as specified and directed.

4

-

-

... More
Charging refrigerant R134A and testing for proper cooling and leakage before charging of new refrigerant etire system will clean with nitrogen and check the leakage with leakage indicators complete for refrigerator of 210 to 335 ltr capacity, complete all as specified and directed.

4

-

-

... More
Taking out the burnt/ unserviceable compressor from the deep freezer of 210 to 400 ltr capacity and replacing & fixing the same as per the existing complete all as specified and directed.

4

-

-

... More
Servicing and overhauling of deep freezer of 210 to 400 ltr capacity of various make and model incl transporting to workshop, complete all as specified and directed.

4

-

-

... More
Supply and fixing in Replacement of thermostat for deep freezer of 210 to 400 litre capacity, complete all as specified and directed.

4

-

-

... More
Supply and fixing in Replacement of thermal relay for deep freezer of 210 to 400 litre capacity, complete all as specified and directed.

4

-

-

... More
Charging refrigerant R134A and testing for proper cooling and leakage before charging of new refrigerant etire system will clean with nitrogen and check the leakage with leakage indicators complete for Deep freezer of 210 to 400 ltr capacity, complete all as specified and directed.

4

-

-

... More
Disconnecting the electric supply from the mains, transporting the window/split type air conditioner any capacity from original location to workshop to carry out the servicing complete and re-fixing at the original position after repairs and making the ACs fully functional and testing for satisfactory working, complete all as specified and directed.

4

-

-

... More
Taking out old burnt/unserviceable compressor from the air conditioner any capacity and replacing new compressor the same as per the existing, re-fixing in position including testing for satisfactory working, complete all as specified and directed.

4

-

-

... More
Charging refrigerant gas R22/R32/R410A required 60 to 120 PSI in any capacity window /Split type air conditioner complete including testing for satisfactory working after flushing out and cleaning the surface with nitrogen gas for checking the leakage, complete all as specified and directed.

4

-

-

... More
Supply and fixing in replacing as per existing AC blower motor suitable for any capacity air conditioner, complete all as specified and directed.

4

-

-

... More
Supply and fixing in replacing thermostat suitable for any capacity air conditioner, complete all as specified and directed. Make:- Ranutrol / Sriram / Hitech / Classic

4

-

-

... More
Supply and fixing in replacement of sensor relay suitable for any capacity air conditioner, complete all as specified and directed.

4

-

-

... More
Supply and fix in repair of running condenser 36 Mfd, complete all as specified and directed.

4

-

-

... More
Supply and fix in repair of starting condenser 100/120 Mfd, complete all as specified and directed.

4

-

-

... More
Repair to unserviceable/burnt stabilizer of 3 KVA to 5 KVA capacity, rewinding the same with super enamelled copper winding wire of suitable gauge including insulating material such as paper cotton sleeves, varnishing, reassembling, replacement of knobs, LED's etc. and making fully functional on load as connected to Refrigerator/Deep freezer/AC, complete all as specified and directed.

4

-

-

... More
Descrition all as per ser item no 82 above but for stablizer of 0.5/1 KVA capacity, complete all as specified and directed.

2

-

-

... More
Dismantling the complete fuel injector pump of water heating plant of various capacity upto 2000 ltrs, transporting to trade workshop for repairs and complete servicing and refixing the same after satisfactory repairs, reinstallation, testing and commissioning complete, all as specified and directed.

2

-

-

... More
Material and labour for Calibration and complete repair of fuel injection pump of water heating plant of various capacity upto 2000 ltrs, on work bench for fine spray and machining work and refixing the same for satisfactory functioning, complete, all as specified and directed.

2

-

-

... More
Supply and fixing in replacement of nozzle of hot water plant as per existing size and testing after repairs, complete, all as specified and directed.

2

-

-

... More
Supply and fixing in replacement pressure meter suitable for hot water generator as per existing size and testing after repairs, complete, all as specified and directed.

2

-

-

... More
Supply and fixing in replacement fuel filter suitable for hot water generator as per existing size and testing after repairs, complete, all as specified and directed.

2

-

-

... More
Supply and fixing in replacement solenoid switch for hot water generator as per existing size and testing after repairs, complete, all as specified and directed.

2

-

-

... More
Dismentling of burner gasket suitable for hot water generator as per existing size and testing after repairs, complete, all as specified and directed.

2

-

-

... More
Supply and fixing in replacement burner gasket suitable for hot water generator as per existing size and testing after repairs, complete, all as specified and directed.

2

-

-

... More
Supply and fix in repair indicator assembly, , complete all as specified and directed.

2

-

-

... More
Supply and fix in repair bimetallic overload relay 4.0 - 6.5 Amps type ML , complete all as specified and directed.

2

-

-

... More
Supply and fix in repair electromagnetic rod combined with positive/ negative terminals suitable for hot water generator of any capacity as per existing size and testing after repairs , complete all as specified and directed.

2

-

-

... More
Supply and fixing in replacement photo censor suitable for hot water generator/plant as per existing size and testing after repairs, complete, all as specified and directed.

2

-

-

... More
Supply and fixing in replacement Diesel/fuel pipe with internal and outer threads suitable for hot water generator/plant as per existing size and testing after repairs, complete, all as specified and directed.

4

-

-

... More
Dismantling fuel tank of water heating plant, servicing, decarboning of complete water plant and reassembling the same after cleaning properly by removing all deposited particles, dust, carbon etc, complete, all as specified and directed.

1

-

-

... More
Supply and fixing in replacement of new digital type electronic temperature gauge with thermostat control relay suitable for 2,00,000 K Cal/hr capacity hot water generator Complete all as specified.

1

-

-

... More
Disconnecting and taking out burnt hot water plant blower motor, transporting to workshop, dismantling carefully, cutting out burnt windings, cleaning the slots and rewinding with super emamelled copper winding wire of appropriate gauge & weight incl all insulating materials, varnishing, drying, heating etc and incl replacement of ball bearings as per existing, reassembling and refixing at original site and testing, complete, all as specified and directed.

1

-

-

... More
M&L for disconnectiong existing defective 500Ltr capacity Heating plant/ Hamam from electric mains, water mains and fuel pump isolating the necked connections, removing from foundation by unscrewing the nuts, bolts etc, discouple from pump and motor, opening of Heating plant/ Hamam and motor for inspection in presence of Engr-in-Charge and to carry out major repairs transporting to workshop and back, reassembling the Heating plant/ Hamam after repair, refixing in position reconnecting same as prior to removing from foundation including replacement of nuts, bolts washers of suitable size, testing and commissioning complete all as specified and directed. Disconnecting the Heating plant and remove the SS inner and outer tank carefully, carry to trade workshop for necessory repairs such as :- (a) Cut the rust out parts of 500 Ltr capacity Heating plant/ Hamam. (b) Moulding of inner tank of 500 Ltr capacity Heating plant/ Hamam and welding work. (c) Moulding of outer tank of 500 Ltr capacity Heating plant/ Hamam and welding work. (d) Supply and filling in replacement of Glass wool between the inner and outer tank. (e) Supply and fixing in replacement upper and lower aluminium strap for suitable size. (f) Supply and fixing in replace ment of necessory quanty and size of nut,bolt and washer. (g) Supply and fixing in replacement of Base plate of 500 Ltr capacity Heating plant/ Hamam of existing size with GI plate of minimum 5 mm thick.

1

-

-

... More
BOQ item No 85.00 Contd.... (h) Supply and fixing in repair of water connection arrangement of water Heating plant/Hamam i.e, Nipple,socket, reducer socket and Gate valve/ ball valve etc. (j) Repair/ replacement of Top and bottom cover. (k) Other miscellanious Repairs. (l) Supply and eplacement of inner (Dollaky) Plates 5 mm thick. (m) Supply and replacement of Vertical MS tubes size of 50 mm. Note :- (i) Replacement of defecting parts is included in the Quated rate. (ii) major repairs are not possible at site, the Heating plant/ Hamam shall be shifted to Civil workshop, and cost of shifting to workshop and back to site included in the rates.

-

-

-

... More
M&L filling of dry sand under and around LT cable to provide sand cushioing and in sub stn ducts/trenches complete all as directed.

12.5

-

-

... More
M/L for brick well burnt locally available sub class 'B' laid over sand cushioning to cable in trenches keeping width of brick parallel to the length of cable complete all as specified and directed.

1.2

-

-

... More
M&L PCC 1:4:8 type D 2 using 40 mm graded stone aggregate for foundation of pole, complete all as specified and directed.

0.08

-

-

... More
M&L PCC 1:3:6 type C 2 using 40 mm graded stone aggregate for filling of pole & stay , complete all as specified and directed.

0.5

-

-

... More
M&L PCC 1:2:4 type B1 using 20 mm graded stone aggregate for copining of pole, complete all as specified and directed.

0.08

-

-

... More
Taking out old UNSV and Supply, laying, jointing and testing of XLPE insulated, armoured, heavy duty LT under ground cable 1100 Volts grade with aluminium conductor laid in trenches, on poles, through pipes, fixed to walls etc cross sectional area for following sizes, including taking down old, complete, all as specified and directed :-

-

-

-

... More
(a) 25 Sqmm 4.0 Core.

220

-

-

... More
(b) 16 Sqmm 4 core

190

-

-

... More
Supply and fixing of MCCB 4P 100 Amps 16 KA capacity 415V 50Hz with adjustable thermal and fixed magnetic relay incl taking out the old unserviceable complete all as specified and directed by Engr-in-Charge.

4

-

-

... More
Supply and installation of on load change over switch in sheet metal enclosure of capacity 100 Amps FP, 415 Vac, 50 Hz, complete all as specified and directed.

1

-

-

... More
Taking down existng unserviceable street/security light fittings HPSV/HPMV/MH/Tube light fittinsgs of any capacity any type from pole/wall after disconnection the connecting wires and supply and fixing in replacement of integral LED street light luminaries complete comprising of epoxy powder coated housing, enclosed with glass cover in front 35 Watts made up of pressure die cast housing of IK07 with symmetrical light distribution all accessories complete suitable for 50 mm dia pipe in gress preotection IP-66 complete all as specified and directed by Engr-in-Charge.

20

-

-

... More
Taking down existng unserviceable street/security light fittings HPSV/HPMV/MH/Tube light fittinsgs of any capacity any type from pole/wall after disconnection the connecting wires and supply and fixing in replacement of integral LED street light luminaries complete comprising of epoxy powder coated housing, enclosed with glass cover in front 60 Watts made up of pressure die cast housing of IK07 with symmetrical light distribution all accessories complete suitable for 50 mm dia pipe in gress preotection IP-66 complete all as specified and directed by Engr-in-Charge.

21

-

-

... More
S & F in replacement of 120W LED flood light of die cast aluminium body, IP-66 including all accessories as required complete all as specified and as directed.

3

-

-

... More
S & F in replacement of 210W LED flood light of die cast aluminium body, IP-66 including all accessories as required complete all as specified and as directed.

2

-

-

... More
S&F in replacement of street light terminal boxes made out with SMC material, shock and dust proof of inside size 295x195x100 mm as per IS and including 100 amp TPN busbar fixed on insulators, 01 No 06 amp SP MCB, earth termination with nuts and bolts and including 02 sets of flat iron 25x6 mm clamps of suitable size with nuts,bolts and washers complete all as specified and as directed.

24

-

-

... More
Taking out old unserviceable PCC/steel tubular pole 9 mtrs long and supply and fixing steel tubular swaged poles with cast iron base plate, finial taper plug, bolts, nuts, screws as specified type 410 SP-31 (9.0 mtr long) and erecting in position all as specified and directed with shifting of conductors and insulators including painting the exposed portion with two coats of aluminium paint over a coat of red oxide primer and internally through out plus embedded portion with two coats of black bituminous paint over a coat of red oxide primer with and including marking of pole number with black paint in yellow circle, complete, all as specified and directed.

2

-

-

... More
Taking down and replacement of existing unserviceable street light fitting bracket with new brackets made out of 40mm bore GI pipe, light grade, tubing bend to shape, 1.2 metre long, fixed to pole/wall with and including two sets of clamps made out of flat iron of size 50 x 6 mm with bolts, nuts and washers, complete, all as specified and directed.

10

-

-

... More
Taking down and replacement of existing unserviceable clamps with new clamps made out of 40x6 mm bending to shape, drilling holes for bolts suitable for fixing GI pipe bracket to steel pole, made in two halves, including nuts, bolts, washers and painting with two coats of aluminium paint over a coat of red oxide primer, complete, all as specified and directed.

8

-

-

... More
M&L for painting steel tubular pole 9 mtrs long alongwith bends with two coats of aluminium paint over a coat of red oxide primer and internally through out plus embedded portion with two coats of black bituminous paint over a coat of red oxide primer with and including marking of pole number with black paint in yellow circle, complete, all as specified and directed.

12

-

-

... More
Supply and laying pipe galvanized, “light grade” of size 50 MM to be used on road crossing/ culverts for laying of cable complete all as directed by Engr-in-Charge

6

-

-

... More
S&F in repair of 1.5 sqmm 3 core pvc insulated flexible copper conductor wire from street light terminal box to fittings of required length drawn through and including PVC conduit of suitable size or as indicated and directed.

50

-

-

... More
S&F in repair MCB SP 16 amp, 'C' curve, 10 KA, 240V complete inside existing postion of street light terminal boxes including taking down old unserviceable all as specified and as directed.

15

-

-

... More
S&F in repair of 20 watt LED decorative post top light fitting of aesthetically designed with symmetrical light distrubution, IP-65, 230/240V, 50 Hz AC supply and with all accessories and incl lamp etc prewired

10

-

-

... More
Disconnecting electric supply and dismantling old unsv LT cubical electric panel/box of any type/ size including and all connected MCCB/MCBs, CT, Volt & Ammeter and control wiring, etc at various locations of Haft Chinar Mil Stn, complete all as specified and directed.

5

-

-

... More
Supply, fixing and fabricate LT cubical electric panel/box of any type/ size and commissioning of MS sheet box 2 mm thick double door with locking arrangement of size/ dimention not less than 130 x 75 x 30 cm with suitable thickness of hylem sheet including provision of new MCCB 100 Amp -01 No, MCB SPN 32 Amp-07 Nos with suitable size of copper busbar for phase & neutral, CTs, Volt meter, Ammeter selector switch internally prewired copper conductor through PVC conduit concealed with all connection of required size and applied with powder coated synthetic enameled paint and making good to the distrubed wall surface and making good to the distrubed wall surface etc , complete all as specified and directed.

5

-

-

... More
Supply and fixing of moulded case circuit breaker Four pole 160Amps 25 KA capacity 415V 50Hz with adjustable thermal and fixed magnetic relay incl taking out the old unserviceable, complete all as specified and directed.

2

-

-

... More
Supply and fixing of moulded case circuit breaker Four pole 125 Amps 35 KA capacity 415V 50Hz with adjustable thermal and fixed magnetic relay incl taking out the old unserviceable, complete all as specified and directed.

2

-

-

... More
Supply and fixing of moulded case circuit breaker Four pole 100 Amps 25 KA capacity 415V 50Hz with adjustable thermal and fixed magnetic relay incl taking out the old unserviceable, complete all as specified and directed.

2

-

-

... More
Supply and fixing of moulded case circuit breaker Four pole 63 Amps 25 KA capacity 415V 50Hz with adjustable thermal and fixed magnetic relay incl taking out the old unserviceable, complete all as specified and directed.

8

-

-

... More
Supply and fixing of digital voltmeter 0 to 500 volts 96 x96mm flush type in LT Panels incl taking out the old unserviceable, complete all as specified and directed.

5

-

-

... More
Supply and fixing of digital ammeter range as per existing 96 x96mm flush type in LT panels incl taking out the old unserviceable complete all as specified and directed.

5

-

-

... More
Supply and fixing selector switch of voltmeter/ammeter in LT panel boards incl taking out the old unserviceable complete all as specified and directed. Make : AE/L&T

8

-

-

... More
Supply and fixing indicator assembly (RYB) LED type in LT panel boards incl taking out the old unserviceable complete all as specified and directed.

15

-

-

... More
Taking down old and unserviceable, distribution board any type including/ sheet metal enclosures, after removing all connection and make good the disturbed surface, complete all as specified and directed.

64

-

-

... More
Supply and fixing in Sheet Metal enclosure double door for DBs when MCBs to be used TPN-4 Way with 200 Amp rated bus bar complete all as specified and directed.

4

-

-

... More
Supply and fixing Sheet Metal enclosure double door for DBs when MCBs to be used SPN- 8 Way with 200 Amp rated bus bar complete all as specified and directed.

32

-

-

... More
Descrition all as per ser Item No 119 above but SPN - 12 Way complete all as specified and directed.

22

-

-

... More
Supply and fixing in replacement 415V 10KA 'B' curve miniature circuit breaker (MCB) TPN and current carrying capacity 63 Amp in the DB complete with connection testing and commissioning, complete all as specified and directed.

20

-

-

... More
Supply and fixing in replacement amp rating 240V, 10KA 'B'curve miniature circuit breaker (MCB) SPN and current carrying capacity 40 Amps in the MCB DB complete with connection, testing and commissioning, complete all as specified and directed.

89

-

-

... More
Supply and fixing in replacement amp rating 240V, 10KA 'B' curve miniature circuit breaker (MCB) SP and current carrying capacity 5-32 Amps in the MCB DB complete with connection testing and commissioning, complete all as specified and directed.

210

-

-

... More
Taking down old and unserviceable submain wiring any size of two core including earth wire complete including batten/ conduit and make good the disturbed surface to match the existing surface, complete all as specified and directed.

1815

-

-

... More
M&L for sub main wiring power/circuit using PVC insulated unsheathed, stranded copper conductor cable 2 Single core of size 4 Sqmm, earth continuity conductor of size 4.0 Sqmm to be drawn through in PVC casing caping in walls/roof/floors including taking down the old submain wiring , complete all as specified and directed. Notes:- (i) Two wires of 4 sqmm and one wire of 4.0 sqmm and one run of PVC conduit shall be measured as one unit.

730

-

-

... More
M&L for sub main wiring power/circuit using PVC insulated unsheathed, stranded copper conductor cable 2 Single core of size 6 Sqmm, earth continuity conductor of size 6 Sqmm to be drawn through in PVC casing caping in walls/roof/floors including taking down the old submain wiring, complete all as specified and directed. Notes:- (i) Two wires of 6 sqmm and one wire of 6 sqmm and one run of PVC conduit shall be measured as one unit.

635

-

-

... More
M&L for sub main wiring power/circuit using PVC insulated unsheathed, stranded copper conductor cable 2 Single core of size 10 Sqmm, earth continuity conductor of size 10 Sqmm to be drawn through in PVC casing caping in walls/roof/floors including taking down the old submain wiring, complete all as specified and directed. Notes:- (i) Two wires of 10 sqmm and one wire of 10 sqmm and one run of PVC conduit shall be measured as one unit.

450

-

-

... More
Taking down old and unserviceable alumunium/copper point wiring in batten/ conduit and make good the disturbed surface to match the existing surface, complete all as specified and directed by Engr-in-charge.

450

-

-

... More
Material & Labour for point wiring for one light / Fan point controlled by one, one way switch complete with 1.5 Sqmm multi-stranded copper conductor PVC insulated, unsheathed, fire retardant low smoke cable 1100 volts grade ISI marked drawn through and including in PVC casing & caping on surface of wall, not less than 25mm width confirming to IS 9537 (Part-III) 1983, including all accessories like bend, tees, junction boxes etc., 1.5 Sqmm multi-stranded copper conductor PVC insulated, unsheathed, fire retardant low smoke cable as a earth wire connected to common earth dolly, etc and including sunken type pressed steel terminal box with 1.8 mm wall thickness, of suitable size for flush type switch with cover plate, cost of cable provided from sub main DB to respective switch board in rooms shall be included in the quoted point wiring rate, complete all as specified and directed. Note - Colour code of cable Phase-Red Neutral- Black and Earth -Green)

240

-

-

... More
Description all as per ser item No 129 above but One 3 pin 5 amps socket outlet point on same board complete all as specified and directed.

90

-

-

... More
As per item No 129 above but One 3 pin 5 amps socket outlet point on independent board complete all as specified and directed.

120

-

-

... More
Description all as per ser item No 129 above but wiring with cable 2.5 Sqmm multi-stranded copper conductor PVC insulated, unsheathed fire retardant low smoke, cable as earth wire connected to common earth dolly for 15 Amps multipurpose socket outlet on independent board, controlled with one way switch.complete all as specified and directed.

40

-

-

... More
S&F Socket outlet 2 in 1, 3 pin, 5 amp flush type ISI marked for the same board complete all as specified and directed.

90

-

-

... More
S&F switch socket combination 5 Amps 2 in 1 flush type multipurposes for independent board complete all as specified and directed.

120

-

-

... More
S&F Switch piano, flush type single pole, one way 5 Amps 3 pin, ISI marked for the same board complete all as specified and directed.

330

-

-

... More
S&F Socket outlet 3 pin, 15 Amp, flush type , ISI marked complete all as specified and directed.

40

-

-

... More
S&F Switch piano 15 Amp, flush type single pole, ISI marked 16 Amps One Way switch complete all as specified and directed.

40

-

-

... More
S&F Ceiling rose, 3 phase/PVC/polycarbonate, isolated body type complete all as specified and directed.

240

-

-

... More
Supply and fixing in repair stepped type electronic fan regulator flush type on the existing phenolic laminated sheet etc. as reqd at site complete all as per specified and directed.

10

-

-

... More
Supply & Fixing in repair only LED lights fitting 22 W LED 6000K (4Ft),(Warm/ Warm White) 220V,AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose,complete all as specified and directed.

250

-

-

... More
Supply and fixing in repair LED light fitting 2 feet, 10 watt 220 V AC (Warm/ White) decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size,complete all as specified and directed.

120

-

-

... More
Supply and fixing in repair round shape slim fit down light LED 15 Watt round recess (Warm/ Warm White) 220 volts AC recessed type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size, complete all as specified and directed.

20

-

-

... More
Supply and fixing in repair square shape 36 watt 220 volts AC recessed mounting type low depth aesthetically designed LED 2x2 feet flat (Warm/ Warm White) panels, with high efficiency PMMA diffuser soft glare free light (Warm/ Warm White) suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed.

22

-

-

... More
Supply and fixing in repairs witch socket combination 5 Amps 2 in 1 flush type multipurposes for independent board, complete all as specified and directed.

127

-

-

... More
Supply and fixing in repair switch socket combination out let 5/16 Amps 5 in 1 flush type, complete all as specified and directed.

50

-

-

... More
Supply & fix in repair Bulk head fitting energy saving 10 W LED with opal diffuser light fitting including necessary fixing arrangements including LED bulb, complete all as specified and directed.

20

-

-

... More
Supply and fixing in repairs Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 Amp, 240 Volts complete all as specified and directed.

18

-

-

... More
Renewal of Earthing complete with galvanized street earth plate electrode 600x600x6mm thick buried directly in ground (earth plate not less than 2.25mtr deep below normal ground level) with top edge of the plate not less then 1.50 mtr. below the normal ground level connected to galvanized earth lead wire 4.00 mm dia by means of bolts nuts check nuts & washer of galvanized iron or steel all as shown in electrical plate No 3 connected to earthing test point all as specified and testing on completion including the material and labou, rcomplete all as specified and directed. for :- (a) Excavation and earth work or drilling hole for electrode in any type of soil (b) PCC pit in cement concrete 1:2:4 TYPE B-1 (c) CI cover with suitable handle (d) Funnel with watering pipe of GI 20mm nominal bore medium grade and Aluminum lugs etc all as specified. (e) 15mm nominal bore medium grade GI protection pipe up to 7.50 meter long for protection of earthing lead. (f) Requisite quantity of charcoal and common salt (g) Connection to earthing test point and testing on completion.

4

-

-

... More
Notes :- An amount of ` 1,86,378.50 on account of Credit Schedule for Schedule 'A' Part-ll shall be deducted from total quoted amount of BOQ to arrive at the contract sum

-

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.