Military Engineer Services Tender
Search from the latest JKtenders and find a business opportunity fitting your SME on the online platform of BidAssist. If you're wondering how to find the latest JK tenders or from where to get all the documents without the hassles, this is what we explain here. Find the best opportunities coming to the surface via the JK government, PSUs and state corporations.
Military Engineer Services - MES Tender
Civil And Construction
Pipe Line Project
Eprocure
Opening Date21 Jun 2024
Closing Date19 Jul 2024
Tender Amount₹ 33,84,000
Costs
EMD
₹ 67,680Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_661316_1Bid Award Id
ViewTender No
GE/U- /2024-25Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete panel height 800, width 800, depth 600, base frame of 50x50x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following panel should be 61439part I7II and should be foem 3B. MCCB should be extendable rom will speady teeeming will on/off trip.
Incoming:-
(a) MCCB 160 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 35 KA-01 No.
(b) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 240 Amp,4 pole, not less than 75 cm long mounted on insulators 01 set.
1
-
-
Outgoing:-
(a) MCCB 125 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 35 KA-01 No.
(b) MCB TPN 63 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 10 KA-04 No. Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level.
(iii) Outgoing MCCBs shall be fed with solid busbar connectors.
(iv) Cables shall be terminated using gun metal /SS glands.
(v) Including suitable thimbles/lungs, nut bolts, washers fitted the cables.
(vi) cable glands for incoming LT cable 95sqmm -01 Nos and out going cables 70 sqmm -02 Nos, 50 Sqmm-1Nosand 25 sqmm - 04 Nos are including rate quated by vendor.
-
-
-
Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete panel height 800, width 800, depth 600, base frame of 50x50x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following panel should be 61439part I7II and should be foem 3B. MCCB should be extendable rom will speady teeeming will on/off trip.
Incoming:-
(a) MCCB 160 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 35 KA-01 No.
(b) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators mounted on insulators 240 Amp, 4 pole, not less than 75cm long mounted on insulatros - 01 set.
1
-
-
Outgoing:-
(a) MCB TPN 40 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 10 KA-04 No. Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level.
(iii) Outgoing MCCBs shall be fed with solid busbar connectors.
(iv) Cables shall be terminated using gun metal /SS glands.
(v) Including suitable thimbles/lugs, nut bolts, washers fitted the cables.
(vi) Cable glands for incoming LT cable 95sqmm -01 Nos and out going cables 70 sqmm -02 Nos, 50 Sqmm-1 Nos and 25 sqmm -4 Nos are including rate quated by vendor.
-
-
-
Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete panel height 800, width 800, depth 600, base frame of 50x50x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following panel should be 61439part I7II and should be foem 3B. MCCB should be extendable rom will speady teeeming will on/off trip.
Incoming:-
(a) MCCB 200 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 35/36 KA-01 No.
1
-
-
Outgoing:-
(a) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 240 Amp,4 pole - 01 set.
Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level.
(iii) Outgoing MCCBs shall be fed with solid busbar connectors.
(iv) Cables shall be terminated using gun metal /SS glands.
(v) Including suitable thimbles/lugs, nut bolts, washers fitted the cables.
(vi) Cable glands for incoming LT cable120sqmm -01 Nos and out going cables95 sqmm -02 Nos ,50 sqmm -01 Nos and 35 sqmm 5 is including rate quated by vendor.
-
-
-
Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete panel height 800, width 800, depth 600, base frame of 50x50x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following panel should be 61439part I7II and should be foem 3B. MCCB should be extendable rom will speady teeeming will on/off trip.
Incoming:-
(a) MCCB 200 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 35/36 KA-01 No.
1
-
-
Outgoing:-
(a) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 240 Amp,4 pole, not less than 75 cm long mounted on insulators 01 set.
Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level.
(iii) Outgoing MCCBs shall be fed with solid busbar connectors.
(iv) Cables shall be terminated using gun metal /SS glands.
(v) Including suitable thimbles/lugs, nut bolts, washers fitted the cables.
(vi) Cable glands for incoming LT cable 95 sqmm -01 Nos and out going cables 70 sqmm -02 Nos and 50 sqmm - 01 Nos and 25 sqmm -04 Nos is including rate quated by vendor.
-
-
-
Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete panel height 800, width 800, depth 600, base frame of 50x50x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following panel should be 61439part I7II and should be foem 3B. MCCB should be extendable rom will speady teeeming will on/off trip.
Incoming:-
(a) MCCB 100 A 4 pole, with thermal adjustable and fixed magnetic setting with extended 50Hz ,415 V with rupturing capacity 25/26 KA-01 No.
6
-
-
Outgoing:-
(a) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 150 Amp,4 pole, not less than 75 cm long mounted on insulators 01 set.
Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level.
(iii) Outgoing MCCBs shall be fed with solid busbar connectors.
(iv) Cables shall be terminated using gun metal /SS glands.
(v) Including suitable thimbles/lugs, nut bolts, washers fitted the cables.
(vi) Cable glands for incoming LT cable 95 sqmm -01 Nos and out going cables 70 sqmm -02 Nos, 50 sqmm - 01Nos and 25 Sqmm -04 Nos are including rate quated by vendor.
-
-
-
Supply, install, testing and commissioning and testing factory made and tested CPRI type test certified) LT feeder pillar box (KIOSK) out door type, floor mounted,compertmantalised suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, dust and vermin proof, made of 3.15mm CRCA MS sheet with digital Volt meter, Ammeter, with CTs ,Led lamps RYB for all incomers & outgoings MCCBs are to busbar spadles to fitted complete panel height 800, width 800, depth 600, base frame of 50x50x6mm angle iron , powder coated, having front and rear openeable hinged double door shutters with aprons for cable entry and locking arrangement complete with following panel should be 61439part I7II and should be foem 3B. MCCB should be extendable rom will speady teeeming will on/off trip.
Incoming:-
(a) MCCB 125 amps,4 pole,25/26 KA , with adjustable thermal over load release 50 Hz, 415 volts grade - 01 Nos.
1
-
-
Outgoing:-
(a) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 200 Amp,4 pole, not less than 75 cm long mounted on insulators 01 set.
Note- (i) Rate quoted is deemed to be inclusive of PCC foundation/pedestal and connected earth work. (ii) Panels shall be placed above 0.6 mtr from ground level.
(iii) Outgoing MCCBs shall be fed with solid busbar connectors.
(iv) Cables shall be terminated using gun metal /SS glands.
(v) Including suitable thimbles/lugs, nut bolts, washers fitted the cables.
(vi) Cable glands for incoming LT cable 95 sqmm -01 Nos and out going cables 70 sqmm -01 Nos and 35 sqmm - 04 Nos is including rate quated byvendor.
-
-
-
S&F in replacement MCCB 4 pole, Ics=100%Icu- 35/36 KA, 415 Volts, 200 Amps , with thermal adjustable and fixed magnetic setting with extended terminals complete all as specified and directed by Engr-in-Charge.
1
-
-
S&F in replacement MCCB 4 pole, Ics=100%Icu- 35/36 KA, 415 Volts, 160 Amps , with thermal adjustable and fixed magnetic setting with extended terminals complete all as specified and directed by Engr-in-Charge.
1
-
-
S&F in replacement MCCB 4 pole, Ics=100%Icu- 35/36 KA, 415 Volts, 315/320 Amps ,with thermal adjustable and fixed magnetic setting with extended terminals complete all as specified and directed by Engr-in-Charge.
1
-
-
S&F in replacement MCCB 4 pole, Ics=100%Icu- 25/26 KA, 415 Volts, 100 Amps, with thermal adjustable and fixed magnetic setting with extended terminals complete all as specified and directed by Engr-in-Charge.
3
-
-
S&F LED Street light 60 watt made uppressure diecast aluminium housing with toughned glass and high power leds and secondary lens with IP 66 protection system of efficasy 110 LPW including 10 KV SPD including taking down old UNSV Street lights complete all as specified and directed by Engr-in-Charge.
63
-
-
S&F thermoplastic, polystyrene unbreakable junction box size 260 x 210 x 116 mm suitable for pole mounted outdoor type IP 65 insulated complete with FI clamp & nut, bolts, washers and including phase seperator between R, Y, B terminals and one MCB SP 6 amp 10 KA, all duly mounted on din cannel, cable glands for cable entry complete all as specified and directed by Engr-in-Charge.
15
-
-
Material and labour in replacement of PVC insulated multi stranded copper conductor PVC cable sheathed 2.5 sqmm 3 core and making connections of street light fittings and bollards lights complete all as specified and directed by Engr-in-Charge.
150
-
-
GI pipe bracket Suitable size of light single swan neck shape suitable to fix on top of tubular pole complete with clamps, nuts, bolts and washers complete all as specified and directed by Engr-in-Charge.
15
-
-
S&F of Steel tubular swaged poles erected to truly vertical or planted as strut complete with 6 mm thick mild steel base plate, welded to Pole, B-118 finial taper cap, bolts, nuts and screws, poles made out of ERW MS tubing conforming to IS-2713 Part-II type 410-SP-31 (9m long) including drilling of holes of required size for fixing of cross arms, painting the exposed surfaces of pole with two coats of aluminum paint over a coat of red oxide zinc chrome primer and with two coats of black bituminous paint on the and portion embedded in concrete, making five black and white bands at lower portion of pole above ground level/coping each 300 mm wide alternately and marking pole number. with black paint at suitable height complete all as specified and directed by Engineer-in-Charge. Note:- The earthwork, PCC foundation, steel clamps, MS Cross arms & bracing of angle iron etc will be measured and paid separately under relevant items of Sch ‘A’.
15
-
-
S&F in replacement of automatic street light control switch of 8 KW three phase using Infrared sensor based Nature Switch for automatic switching of street light. Nature switch operation should be based on Natural Light Lux*level. Reqd illuminance level also have part night operation facility for min 4 hrs to max 12 hrs. The sensor along with suitabe rating power contractor (s), one Incoming and three Outgoing MCBs rating of 20-32 Amps & main load circuit wiring (copper) of min 10 sqmm should be enclosed in a pole/wall mountable rust proof, electric shock proof, termite proof and FR grade thermoplastic polycarbonate enclosure conforming to IP66 protection class-2 (Hansel make). The circuit should be also have provision for manual operation (i.e. sensor by pass option) complete all as specified and directed by Engr-in-Charge.
2
-
-
Supply and Laying and fixing in replacement of along the poles or passing through pipes or laid under floor of through walls etc jointing and testing LT Cross Linked Polythene Insulated (XLPE insulated) galvanized steel strip armoured electric cable 1100 volt grade heavy duty ISI marked with aluminium conductor and overall served with an outer sheath of PVC, of cross sectional area as under including taking out old UNSV LT cables complete all as specified and directed by Engr-in-Charge. Note : Excavation, earthwork, Pipe for cable protection to be measured and paid for separately.
-
-
-
All as per serial item No 20.00 here-in-before but of size 185 sqmm 3.5 core complete all as specified and directed by Engr-in-Charge.
235
-
-
All as per serial item No 20.00 here-in-before but of size 150 sqmm 3.5 core complete all as specified and directed by Engr-in-Charge.
100
-
-
All as per serial item No 20.00 here-in-before but of size 120 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge.
1100
-
-
All as per serial item No 20.00 here-in-before but of size 95 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge.
825
-
-
All as per serial item No 20.00 here-in-before but of size 70 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge.
300
-
-
All as per serial item No 20.00 here-in-before but of size 50 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge.
200
-
-
All as per serial item No 20.00 here-in-before but of size 25 Sqmm 3.5 core complete all as specified and directed by Engr-in-Charge.
690
-
-
All as per serial item No 20.00 here-in-before but of size 16 Sqmm 4 core complete all as specified and directed by Engr-in-Charge.
650
-
-
All as per serial item No 20.00 here-in-before but of size 16 Sqmm 2 core complete all as specified and directed by Engr-in-Charge.
1375
-
-
Supply & fixing or laying galvanised steel tubing light grade 80 mm dia (ISI marked) for protection of under ground cable on poles / walls under road crossing etc of following sizes including dismantling & taking down existing pipe complete all as specified and directed by Engr-in-Charge.
40
-
-
M&L for boring of existing road/path for laying of GI pipe protection for UG cable including making good distrurbed area/surface all as specified and directed by Engr-in-Charge.
40
-
-
M & L for providing earthing with GI earth plate electrode 600 X 600 X 6mm buried directly in ground (earth pit not less than 2.25M deep below ground level ) with top edge of the earth plate not less than 1.5M below ground level connected to GI strip 25 x 4 mm thick for earthing lead fixed by means of nuts,bolt,washers etc connected to earth test point complete all as specified in electrical plate NO 3 of SSR1996 part 1 ,including necessary excavation and earth work in any strata of soil,comman salt, charcoal dust, 40 mm dia light grade GI pipe for protection to earth lead, GI water pipe 20mm dia with funnel &wire mesh , PCC pit with CI cover and frame etc complete all as specified and directed by Engineer-in-charge. Note:- All the joints shall be made with welding to get proper conductivity.Note: On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction of Engineer-in-charge.
12
-
-
.M&L for ACSR conductor of required size for Over head lines on poles including streching, tightining of poles insulator with winding wire of suitable size with insulator/streching of ACSR conductor including Taking down the unserviceable conductor from OH structures, complete all as specified and directed by Engr-in-Charge.
1.5
-
-
S&F double walled corrugated (DWC) pipe of size 77 mm including snap fit coupler conforming to IS14930 (Pt-II)/IS16205 Pt-II for protection of HT cable in under ground complete all as specified and directed by Engr-in-Charge.
2000
-
-
S&F double walled corrugated (DWC) pipe of size 50 mm including snap fit coupler conforming to IS14930 (Pt-II)/IS16205 Pt-II for protection of HT cable in under ground complete all as specified and directed by Engr-in-Charge.
2550
-
-