Military Engineer Services Tender
Search from the latest JKtenders and find a business opportunity fitting your SME on the online platform of BidAssist. If you're wondering how to find the latest JK tenders or from where to get all the documents without the hassles, this is what we explain here. Find the best opportunities coming to the surface via the JK government, PSUs and state corporations.
Military Engineer Services - MES Tender
Civil And Construction
Eprocure
Opening Date5 Mar 2024
Closing Date25 Mar 2024
Tender Amount₹ 49,92,000
Costs
EMD
₹ 99,840Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_639180_2Bid Award Id
ViewTender No
GE/KC/NIT-79/2023-24Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
M&L for dry sand cushioning for UG cable in trenches including spreading levelling and hand paning and consolidating complete all as specified and directed.
273
-
-
Removing surplus excavated material (SOIL) to distance not exc. 50 m and depositing where directed at a level not exc. 1.50 m above the starting point complete all as specified and directed.
554
-
-
Supply and laying in trenches Sub class ‘B’bricks well burnt locally available for covering to cable laid dry flat ,with width of brick perpendicular to the length of cable complete all as specified and as directed.
34000
-
-
M&L for Cutting/Boring of road/Hard standing to a size of 30 cm in width and not exceeding 60 cm in depth for laying of protection pipe/water line/Cable including returning filling, Including spreading and providing PCC in 1:2:4 B1 using 20 mm grade stone aggregate for the top 100mm layer, complete all as specified and directed.by Engr-in-Charge
12
-
-
M&L for Steel Tubular swaged poles type 410 SP-31 (9.0 mtr long) conforming to IS : 2713 Part-I to III 1980, complete with 6 mm thick mild steel base plate, finial taper plug, MS bolts, nuts, screws and including two coats of aluminium paint over a coat of red oxide primer, erecting in truely vertical position and embedding in PCC foundation including marking pole numbers with black paint in letters / figures not less than 10 cms each including demolition and taking out the old existing unserviceable PCC pole, all as specified and as directed.
3
-
-
Material and labour for PCC ( 1:3:6 )Type C-2 (Using 40 mm grade aggregate as in foundation of pole, stay and filling and mass concrete) including providing necessary form work complete all as specified and as directed by the Engineer in charge
1.6
-
-
Material and labour for PCC (set in cement mortar 1:4) type B1 1:2:4 using 20 mm grade stone aggregate as in copping of new electric pole and old existng LT pole at site including providing necessary form work complete all as specified and as directed by the Engineer in charge
2.5
-
-
M&L for of PVC insulated weather prof flat twin core Aluminium cable of size 4 Sqmm single core including with PVC conduit of all necessary suitable iron clamp(3 nos), nut and bolts of appropriate size from junction box to street light all as specified.
300
-
-
M&L for GI tubing light grade with all necessary fittings laid in trenches under road crossing fixed on poles, walls under floor for cable protection complete all as specified and directed for 40mm dia.
60
-
-
M&L for GI tubing light grade with all necessary fittings laid in trenches under road crossing fixed on poles, walls under floor for cable protection complete all as specified and directed for 50mm dia.
6
-
-
M&L for GI tubing light grade with all necessary fittings laid in trenches under road crossing fixed on poles, walls under floor for cable protection complete all as specified and directed for 80mm dia.
12
-
-
Supply and fix XLPE insulated, screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor rating 1100 volts cross sectional area 16 Sq mm 4 core laid in trenches or passing through pipes/ducts or fixed to walls/poles including dismantling/taking down overhead ACSR conductors and depositing to MES store yard complete all as specified and as directed by the Engineer in charge.
2900
-
-
Supply and fix XLPE insulated, screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor rating 1100 volts cross sectional area 25 Sq mm 3.5 core laid in trenches or passing through pipes/ducts or fixed to walls/poles including dismantling/taking down overhead ACSR conductors and depositing to MES store yard complete all as specified and as directed by the Engineer in charge.
250
-
-
Supply and fix XLPE insulated, screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor rating 1100 volts cross sectional area 50 Sq mm 3.5 core laid in trenches or passing through pipes/ducts or fixed to walls/poles including dismantling/taking down overhead ACSR conductors and depositing to MES store yard complete all as specified and as directed by the Engineer in charge.
200
-
-
Supply and fix XLPE insulated, screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor rating 1100 volts cross sectional area 95 Sq mm 3.5 core laid in trenches or passing through pipes/ducts or fixed to walls/poles including dismantling/taking down overhead ACSR conductors and depositing to MES store yard complete all as specified and as directed by the Engineer in charge.
255
-
-
Supply and fix XLPE insulated, screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor rating 1100 volts cross sectional area 120 Sq mm 3.5 core laid in trenches or passing through pipes/ducts or fixed to walls/poles including dismantling/taking down overhead ACSR conductors and depositing to MES store yard complete all as specified and as directed by the Engineer in charge.
110
-
-
Supply and fix XLPE insulated, screened PVC bedded, galvanized steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor rating 1100 volts cross sectional area 150 Sq mm 3.5 core laid in trenches or passing through pipes/ducts or fixed to walls/poles including dismantling/taking down overhead ACSR conductors and depositing to MES store yard complete all as specified and as directed by the Engineer in charge.
150
-
-
M&L for stay assembly complete with accessories as shown in elect plate No-1, dia to stay 20mm dia 190cm long including MS galvanised stay plate of size 300mmx300mmx6mm thick and galvized thimble after dismantling of unserviceable stay set (above GL) including excavation in earth work, PCC (1:3:6) type C1 (using 20mm graded stone aggregate) foundation including dismantling of old unserviceable stay assembly complete all as specified and directed. (Note:- Cost of excavation, concrete work, removing of surplus soil, returning filling shall deemed to be included in the unit quoted rate.)
3
-
-
M&L outdoor type street light junction boxes with PVC water tight encloser, ready made type, with provision of suitable aluminium bus bars for three phases and one neutral mounted on insulators and bus bar having provision of 10 A SP MCB terminal connection and inter connection of street light from pole to pole and pole to light fittings including necessary PVC insulated waather proof twin core 2.5 Sqmm (nominal area) aluminium conductor cable, 1100 volts grade drawn and including PVC conduit of suitable size with clamps (3 Nos) , nuts, bolts etc from Junction box to street light connection, complete all as specified and as directed by Engr-in-Charge.
21
-
-
Supply and fix in replacement of Factory made flush shutter type sheet metal enclosures, double door, for MCCB DB load link, Vertical, triple pole and neutral, 4 way IP-43, Suitable for MCCB up to 160A as incommer.complete all as specified. including taking down old unserviceable DB of any type/size
3
-
-
Supply and fix in replacement of Thermal magnetic release MCCB 4 pole 415 volt rapturing capacity 16 KA of size 63 amp complete all as specified.
3
-
-
Supply and fix in replacement of MCB SPN-6-32 Amp, 240 volts 50Hz AC supply, complete all specified.
6
-
-
Supply and fix Integral LED security light luminaire 90W LED 230 volts made of pressure die cast aluminium housing with high power LED’s lens & toughned glass IP-66 including GI pipe 50mm ,medium grade ,1.7mtr long mounting bracket and providing fixing clamps ,bolts,nuts of suitable size including taking down old unserviceable security light any type from pole complete all as specified and as directed.
21
-
-
Supply and fix Integral LED security FLOOD light luminaire 120W LED 230 volts made of pressure die cast aluminium housing with high power LED’s lens & toughned glass IP-66 including GI pipe 40mm ,medium grade ,1.7mtr long mounting bracket and providing fixing clamps ,bolts, nuts of suitable sizecomplete all as specified and as directed.
20
-
-
Earthing complete with galvanized mild steel earth plate electrode size 600x600x6mm thick buried directly in ground (Preferably in vertical position) earth pit not less than 2.25 meter below normal ground level with top edge of the earth plate not less 1.5 meter (BGL) connected to galvanized iron earth lead wire 4mm dia by means of bolts, nuts, check nut and washer of galvanized iron including PCC pit in RCC 1:2:4 type B-1, precast RCC cover with suitable handle, excavation and earth work in any type of soil, 20mm bore “medium grade” galvanized iron water tubing fixed with cast iron funnel and wire mesh and 15mm bore “light grade” galvanized iron protection pipe for earth lead wire upto 5m length, charcoal, common salt, complete all as shown in EP No 3 of SSR 2009 part-I, connected to test point complete, all as specified and testing on completion.
10
-
-
M&L for preparation of old painted steel surfaces of PCC/ steel tubular/swaged/rail poles of 9m to 11m long including brackets, clamps, channels and cross arms by cleaning of oils, lubricants, grease etc. complete above PCC coping and applying two coats of aluminium paint on surfaces 1m above PCC coping, applying two coats of synthetic enamel paint in zebra pattern with Aluminium and red colour combination up to 1m height above PCC coping; writing MES No. of poles (Number size shall be 25mm and lettering shall be 40mm) complete including applying two coats of white wash on exposed concrete surfaces of coping to poles duly preparing the surfaces all as directed by Engineer-in-Charge.
72
-
-
Dismantling of ACSR conductor of any type & size from over head line or LT poles, complete all as specified & directed.
2
-
-
Material and labour for cross arms, bracings, supports clamps and back plates fabricated from structural steel sections incl. nuts, bolts, washers, welding, bending cold or hot drilling holes for bolts in any shape or size as indicated or directed and inclusive of two coat of aluminium paint over a coat of red oxide primer including preparing the surface all as specified and as directed.
0.5
-
-
Material and labour for Shackle type insulator, porcelain, vitreous white / brown including galvanized mild steel straps (of size 31 mm x 3 mm) washers, insulator bolts ( 12 mm dia) washers and nuts per size of height 75 mm and dia 90 mm for working pressure 1100 Volts all as specified and as directed.
12
-
-
Supply, installation, testing and commissioning of CPRI approved, factory made, LT Feeder Pillar Box cubical, Outdoor type, floor mounted double door, 3 phase 4 wire, 50 cycles, 415 Volts. The panel board shall be made of 3.15 thick CRCA sheet for load bearing members and 16 SWG (1.6 mm thick) for doors covers and internal partitions and shall be powder coated both side. Base frame of the panel shall be made of ICMC channel of size 50 x50 x 6mm, duly grouted on platform made of brick work in CM (1:2:4), 15mm thick plastering in CM (1:6) having minimum height of 450mm. The panel shall be provided with separate compartments for each switch gears with hinged door including interlocking with switch gears. The panel board shall be suitable for AC, 415 Volts, 50 Hz, 3 phase, 4 wire supply complete with epoxy insulated 400 Amps rated high conductivity aluminium bus bars, supported with DMC / SMC barriers and coluor coded, prewired with copper cable, the degree of protection is IP-54. the panel shall be complete with instrumentation such as LED phase indicating lamps and CT's, including extended aluminium strip of rating of Incomer (400Amps), and outgoing as per rating of MCCB’s, including aluminium lugs to connect the cable dismantled before etc., and comprising of the following:-
1
-
-
(a) MCCB 400 Amps, 4 pole with breaking capacity 36KA (Adjustable thermal & magnetic release) - 01 Nos(Incomer) (b) MCCB 160 Amps, 4 pole with breaking capacity 36KA (Adjustable thermal & magnetic release) - 05 Nos(Outgoing) (c) MCCB 63 Amps, 4 pole with breaking capacity 25KA (Adjustable thermal & magnetic release) - 01 Nos(Outgoing) (d) Digital Volt meter .Make Schneider Cat No DM3210 (e) Digital Ammeter meter .Make Schneider Cat No DM3110 (f) Indicator lamp RYB :01 Set (g) CT'S 300/5 01 Set Make-L&T
-
-
-
Supply, installation, testing and commissioning of CPRI approved, factory made, LT Feeder Pillar Box cubical, Outdoor type, floor mounted double door, 3 phase 4 wire, 50 cycles, 415 Volts. The panel board shall be made of 3.15 thick CRCA sheet for load bearing members and 16 SWG (1.6 mm thick) for doors covers and internal partitions and shall be powder coated both side. Base frame of the panel shall be made of ICMC channel of size 50 x50 x 6mm, duly grouted on platform made of brick work in CM (1:2:4), 15mm thick plastering in CM (1:6) having minimum height of 450mm. The panel shall be provided with separate compartments for each switch gears with hinged door including interlocking with switch gears. The panel board shall be suitable for AC, 415 Volts, 50 Hz, 3 phase, 4 wire supply complete with epoxy insulated 250 Amps rated high conductivity aluminium bus bars, supported with DMC / SMC barriers and coluor coded, prewired with copper cable, the degree of protection is IP-54. the panel shall be complete with instrumentation such as LED phase indicating lamps and CT's, including extended aluminium strip of rating of Incomer and outgoing as per rating of MCCB’s, including aluminium lugs to connect the cable dismantled before etc., and comprising of the following:-
3
-
-
(a) MCCB 200 Amps, 4 pole with breaking capacity 25KA (Adjustable thermal & magnetic release) - 01 Nos(Incomer)(b) MCCB 63 Amps, 4 pole with breaking capacity 25KA (Adjustable thermal & magnetic release) - 06 Nos (c) Digital Volt meter .Make Schneider Cat No DM3210 (d) Digital Ammeter meter .Make Schneider Cat No DM3110 (e) Indicator lamp RYB :01 Set, C&S (f) CT'S 200/5 01 Set Make Legrand
-
-
-
Taking out existing old unservicable pressure filtration plant of capacity 50 cubic meter per hour having vetical shell height about 3 m and filtration plant dia about 2.5 m including all connected items as CI pipe lines of diameter 150 mm of inlet, oulet, backwash, Centifugal pump with motor, sluice valves, non return valves and other fittings etc as directed and specified by Engr-In-Charge.
1
-
-
Supply, installation, testing and commissioning of vertical pressure water filteration plant fabricated at on ISO certified company from mild steel plate by joining vertical cylender with two dish ends one at top and one at bottom , having heavy duty legs provided on bottom dish to make the pressure filter self standing, one man hole at top dish and one hand/inspection hole on vertical shell of suitable size with water tight cover plate, comprising of common header with water distributor/collector, frontal piping, operating valves, back wash pipe lines, air vent pipe with air release valve, pressure guage etc complete in all respect and including with filter media comprising of assorted sizes of pebbles and sand etc suitable to remove suspended impurities like dirt, dust, mud, colloids and similar contamination from the raw water to make it potable water, achieve the specified results and to satisfy the undermentione technical specification all as specified and directed. Make-Ion Exchange (INDION) Model No MGF 2400 or equivalent model of Thermex/Zen Engg.
1
-
-
Note :- Contractor shall submit detailed specifications/design parameters constructional and functional drgs of all components of pressure filter plant as per IS standard for approval of accepting officer before execution of work. ii) The contractor shall submit a schedule of tests giving full details of testls to be carried out before installation i.e, in factory premises and after installation i.e, on site. THe factory test shall be carried ou t in virgin state i.e, without painting/polishing of pressure filter plant iii) The pressure filter plant shall be connected to 150 mm dia MS line for working. The filtered water of the filter shall be connected into one 150mm dia line for further distribution, iv) The civil work shall be measured and paid separately however, the foundation detail and the PCC work related to pressure filter plant shall be submitted by OEM thorugh contractor (v) The liternation and after filteration, obtained from any recognised laboratory. THe commisiong of pressure filter plant shall be carried out in the prssence of rep accepting office. (vii) The foundation of pressure filter plant shall be made as per OEM guidelines/specifications.
-
-
-
Techical Spedifications i) Filter plant capacity not less than 50000ltr/hour
ii) Dia of filter Not less thant 2400 mm iii) Verical shall height (HOS) Not less than 1800mm
iv) Size of frontal piping work-Not less than 150mm bore
v) Number and Size of frontal valve-Not less than 5 in numberseach 150 butter fly, heavy duty ISI marked. vi) Operating pressure-Not less than 2.0Kg /Cm2
vii) Design pressure-Not less than 3.5Kg/Cm2
ix) Thickness of mild steel sheet of vertical shell -Not less than6mm.
x) Filter media
a) Quartz pebbles of 1"-3/4 - Not less than 100mm thick layer.
b) Quartz pebbles of 3/4 to 1/2 - Not less than 100mm thick layer.
c) Quartz pebbles of 1/2 -1/4 Not less than 100mm thick layer.
d) Quartz pebbles of 1/4 to 1/10 p- Not less 100mm thick layer. e) Quartz sand of assorted sizes - Not less than 900 mm thick layer.
(xi) Back wash arrengement - Back wash arrangement shall be made through the running water hence frontal piping arrengement shall be to facilitate the back washing system.
xii) Pressure guages -2 Nos suitable rating Xiii) Air release pipe and valve- To provide as per OEM specification Xiv) Size of man hole & hand hole - To be provided as per OEM specification.
-
-
-
Supply & Fixing and testing Cast lron sluice valve, non-rising type conforming to IS-14846-2000, sutiable for 150 mm bore pipe consisting of SS spindle as per IS 6603, Cast iron Body, Dome & Wedge as per IS 210, greasy jute type gland packing, fasteners as per IS 1367, Natural rubber gasket, CI manual hand wheel etc complete double end flanged and drilled, of Class PN-1 ( ISI marked) including all jointing materials such as rubber gasket insertion sheet nut ,bolts and washers etc including taking out old unserviceable sluice valve from pipeline and removing from site complete all as specified and directed.
10
-
-
Supply & Fixing Cast iron non return valve single door confirming to IS 5312,Part-1 / BS EN 12334 (BS 5153) suitable for 150mm bore pipe class PN 1.6 gun metal sheat and flap with flanged and drilled flanged ends including having bypass arrangement complete all as specified .
4
-
-
Supply & Fixing MS ERW Pipe supplied and laid complete nominal dia 150 mm thickness not less than 5.4 mm complete all as specified and directed.
50
-
-
Taking out Cast iron water main / Ductile iron pipe line pf 150 mm dia(including all fittings) with spigot and socket ends /Flanged pipes including burning out lead joints and recovering lead and removing to store for reuse complete all as specified and as directed :-
Note : Excavation and earth work shall be measured and paid separately.
200
-
-
Supply, fixing and laying ductile iron pipe of 150 mm bore dia, socket & spigot with bulb type rubber tyton gasket and jointing material as per standard complete of class K-7 confirming to IS: 8329:2000 (latest revision) ISI marked of following sizes complete in trenches/ on pedestals etc complete mortar lining (CML) and outside black bitumen coatingetc complete all as directed. Note: ( Earth work incudes excavation, returning & filling and removal, DI fittings will be measured and paid separate where required).
200
-
-
Supply, installation, testing and commisioning pump motor set horizontal, centifugal type with all accessories having minimum discharge 400 ltr per minute (LPM) at water head 20 mtr, suction and delivery size as per OEM, bronze impeller, cast iron body, AISI stainless steel shaft, graphite water seal driven by energy efficient squirrel cage induction motor not less than 5 HP 415 Volts, 3 Phase, 50 Hz, totally enclosed, fan cooled , continous duty confirming to IS: 12615, mounted on a common base frame fabricated by suitable size of channel, grounted into PCC/RCC foundation, duly bolted, proper aligned with each other, comprising complete acessories such as terminal box with glands, shaft guard etc. Including provisioning and making electrical connections through single core multistanded copper conductor ISI marked PVC sheathed 1100 v grade of not less than 10 Sqmm nominal corss sectional area (6 runs ) laid from starter panel to pump motor assembly through cable duct/GI pipes etc, making inlet water supply connections from balancing tank to pump, outlet water supply connections from pump to fiterations plant, complete in all respect and testing for smooth functioning of pump-motor assemble all as specified and directe. Make - KIRLOSKAR/KSB/CROMPTON.
2
-
-
Note :- i) MS pipe for inlet and outlet connection shall be measured and paid seperately ii) Any fitting required for smooth operation of pump and motor assembly not covered into this schedule are deemed to be included into quoted rates. Iii) The inlet connection of water supply shall be made in such a manner that it can work for draining of water from swimming pool through diving pool and for back washing of pressure filter plant. iv)The connection for both the pumps shouls be made as backup for each other. v) The tenderer shall submit the detail technical drawings, model No, manufacturers literature for selection of pump model and approval of accepting officer.
-
-
-
Supply, install, test and commissioning of inbuilt type pool cleaner semi automatic in stainless steel material of size 100x200x800mm, fitted with special nylon brush and provided 70 mtr long poly propylene rope of 3/4" size and 50mm PVC braided transport flexible 70 mtr pipe with 24 numbers, 100 mm dia float complete with vacuum points 2 Nos., in stainless steel materials and 50 mm NB medium grade, ISI marked electrofusion welded joints grade 10Kg/sqcm upto suction point of main pumps in filter room and a plastic bucket type debris strainer and a 50mm size poly propylene ball valve including self priming pump set of not less than 1.5 HP of make Kirloskar, with trolley, starter and cable etc complete in all respect and all as specified and all as directed. Make : Ion Exchange Code SSM1.5 or equivalent in Certikin/Astral
1
-
-
Supply and install connecting, testing and commissoioning of high pressure single head adjustable aqua fit dosing system of following specifications inject pressure up to 25 LPH working pressure 10Kg/Cm squre, power input 230 Volts, 50 Hz, 40 Spm, 1/30 fractional hourse power max output 10 ltrs per hour with mandatory accessories like lead tubing, connecting ferrules, check valvel etc.
1
-
-
(i) Preparation of tank of net capacity 150 ltrs, FRP dosing tank dia 650xnet height 375+conical 300 gross height withstand 1000 mm consisting of (a) Water inlet line (b) Outlet with strainer (c) Drain (d) Over flow (e) Conical bottom for sludge desposition (f) Pot hole with cover (g) Level gauge (h) Agitator 120 Watt 900 rpm single phase glange mounted motor with plastic shaft and impleler. (ii) Service tank dia 480xheight 575 net capacity 10 Ltr consisting of (a) Water inlet line (b) Dosing pump inlet arrangment (c) Dosing pump inlet arrangement (d) Over flow (e) Level gauge (f) Inspection port (g) Agitator 120 Watt 900 rpm single phase flange mounted motor with plastic shaft and impeller (h) Provision of mounting pump on lid/wall
-
-
-
Supply only chlorine test kit with coloured sample complete with all testing fitments and OT solution in rexene finish box. Make: Rmco KOLKATA
1
-
-
Supply only OT solution for chlorine test 500 ML bottle complete all as specified and directed. Make : RMCO Kolkata
1
-
-
Supply only PH test kit with coloured ample covered under BTB (range 6.0 to 7.0) or phenol red (range 6.8 to 8.4) with necessary fitments and 100 ml testing solution in Rexene finished bo
1
-
-
Supply,laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 Sqmm 4 core all as specified and directed.
150
-
-
Supply,laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 Sqmm 4 core all as specified and directed.
20
-
-
Supply and fix in repairs factory made epoxy powder coated Distribution board SPN 8 ways (SPN MCB DB) with metal door (IP-43 protection) fabricated from minimum 1.6mm thick CRCA sheet and fixed flush to wall and suitable for universal mounting and including 100 Amp copper bus bar, neutral bar, standard DIN rail, Earth bar and cable ties for cale management, top and bottom removable gland plates with Knockouts and suitable for one SPN/DP-MCB as incomer and SP MCBs outgoing complete all as specified and confirming to IS : 8623.
1
-
-
Supply and fix in replacement MCB SP-06 to 20 Amp,10KA, 240 volts complete all as specified.
4
-
-
Supply and fix in replacement of MCB SPN 32 Amp, 240 volts 50Hz AC supply, complete all specified.
1
-
-
Material and labour for sub main wiring with two single core PVC insulated (unsheathed) multi strand copper conductor FRLS cable of size 4 sqmm and one single core PVC insulated (unsheathed) solid copper conductor FRLS cable of size 4 sqmm as in continuous earth wire drawn into and including concealed PVC conduit medium grade 25mm dia ISI marked complete with fittings and fixings accessories complete and including cutting chases pinning in making good to facing and pointing in using cement moter 1:3 and making good disturbed surface complete all as specified and as directed.
30
-
-
Material and labour for point wiring for one light controlled by one way switch with 1.5 Sqmm PVC insulated unsheathed single core multi-stranded copper conductor (FRLS) cable 1100 Volts grade drawn through and including rigid non metallic PVC concealed conduit (medium grade) of suitable dia along with 1.5 sqmm continuous PVC insulated unsheathed single core multi-stranded copper conductor (FRLS) cable for earth continuity wire, connected to earth dolly and to be terminated in and including pressed steel sunken boxes , readily available (Having wall thickness not less than 1.22 mm for boxes upto a size of 200 mmX300 mm and beyond that the wall thickness shall be not less than 1.63 mm) concealed type with 3mm thick bakelite sheet cover for mounting switches, sockets, fan regulators etc including testing on completion complete including cutting chases for concealed conduit pinning in making good to facing and pointing in using cement mortar 1:3 and making good disturbed surface all as specified and as directed.
5
-
-
Supply and fix in replacement of Tube light fitting integrated type suitable for LED 20W indoor decorative aluminium extruded T5 LED batten complete with hosing with all accessories pre wired and making connection with three core copper flexible cable of size 23/0.0076 from ceiling rose to PVC connection to light fitting complete all as specified and directed.
5
-
-
Earthing complete with galvanized mild steel earth plate electrode size 600x600x6mm thick buried directly in ground (Preferably in vertical position) earth pit not less than 2.25 meter below normal ground level with top edge of the earth plate not less 1.5 meter (BGL) connected to galvanized iron earth lead wire 4mm dia by means of bolts, nuts, check nut and washer of galvanized iron including PCC pit in RCC 1:2:4 type B-1, precast RCC cover with suitable handle, excavation and earth work in any type of soil, 20mm bore “medium grade” galvanized iron water tubing fixed with cast iron funnel and wire mesh and 15mm bore “light grade” galvanized iron protection pipe for earth lead wire upto 5m length, charcoal, common salt, complete all as shown in EP No 3 of SSR 2009 part-I, connected to test point complete, all as specified and testing on completion.
2
-
-
Supply,install,commissioning and testing of indoor type weather proof cubical panel board made out of 3.15mm thick CRCA sheet duly powder coated, CPRI tested,locking arrangement on front side and rear side opening,mounted over 50x50x6mm angle iron stand at the bottom of height less than 45 cm above ground level and not less than 30cm in ground / floor mounted duly grounted in PCC 1:3:6 type C1( using 20mm graded stone aggregate) factory made duly powder coated and including aluminium bus bar of capacity 1.5 times of incomer MCCB rating, panel wiring and termination of all cables with suitable size of thimples and gland complete comprising of following :-(a) Incoming MCCB 63 A 25 kA 4 pole - 01 No (b) Out going MCCB 40 A , 16 kA 3 pole - 02 No(c) MCB DP 32 A- 02 No(d) RYB indicator for each incoming and outgoing supplies -01 Set (e) Volt meter,Ammeter with CTs and selector switch-01Set.(f) Soft starter for re-circulating pump set of cap upto10 HP-02 nos
1
-
-