Military Engineer Services Tender
Search from the latest JKtenders and find a business opportunity fitting your SME on the online platform of BidAssist. If you're wondering how to find the latest JK tenders or from where to get all the documents without the hassles, this is what we explain here. Find the best opportunities coming to the surface via the JK government, PSUs and state corporations.
Military Engineer Services - MES Tender
Security and Emergency Services
Coronavirus COVID 19
Eprocure
Opening Date15 Nov 2018
Closing Date10 Dec 2018
Tender Amount₹ 15,14,222 This is an estimated amount, exact amount may vary.
Costs
EMD
₹ 39,000Document Cost
Refer DocumentsTender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2018_MES_223520_1Bid Award Id
ViewTender No
GE 861EWS-65/2018-19Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
M&L for MCB single pole 240 volts 5 to 32 amps as per site requirement , with rupturing capacity 10 KA as per IS-8828-1996 (IEC-60898), biconnect upper and lower terminals , integrated label holder to ensure circuit identification, Make : Hager,Legrand , Schinder (Acti-9)/Havells
1
-
-
... More
Supply, install , testing and commissioning automatic voltage stabilizer (servo controlled ) for automatic operation 50 KVA, copper on 3 phase, 50 Hz, naturally oil cooled , unbalanced, type indoor type with micro processor based control card, digital type, relay free smooth and silent operation & designed for input voltage of 200-415 Volts per phase with output voltage stabilized at 415 with volts with (+/-) 1.0% for phase to phase and 240 volts with (+/-) 1.0% for phase Neutral of accuracy of 50 Hz and speed of correct @ 20 volts per second, having high voltage protection, overload/short circuit protections with first fill of oil (ISI Marked), having MCCB at input side of 100 amp capacity, 4 pole, 35 KA, ICS = 100 % ICU, microprocessor release, with all accessories, complete all as directed. Make : AE/Andrew/Yule/Aplab/Electric field.
1
-
-
... More
Supply laying connecting and testing 1100 volt graded heavy duty XLPE cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanized steel strip or wire and overall PVC sheathed of size 35 Sqmm normal cross section area, 3.5 core laid in trenches fixed to pole or passing through pipes incl all necessary clamps nuts, bolts and washers complete all as specified.
45
-
-
... More
Material & labour for earthling complete with galvanised cast iron earth plate electrode of size 600x600x6.3mm thick burried directly in ground not less than 3.0m deep below normal ground level as earth electrode with top edge of the earth plate not less than 2.25mtr below ground level using GI strip 25x4 mm width as earth continuity conductor connected to earth plate by means of welding, GI thimbles, nuts, bolts & washers all as directed including providing earth wire protection pipe GI light grade 32mm dia from earth plate to main switch board/panel, watering pipe 20mm dia with wire mesh and funnel at top, earth pit and RCC pit cover with handle of angle iron frame of size 40 x 40 x 6mm in PCC 1:3:6 adequate quantity of charcoal dust and salt and kalmi shore all around the earth plate, earth work in any type of soil remaining surplus excavated material all as required at site and specified in EP No 3 of SSR part I 2009 or directed by Engineer-in-charge and incl testing on completion.
26
-
-
... More
S&F LED 60 Watt security light fitting new generation energy saving & environmental friendly long life versatile pressure die cast aluminium housing with heat resistant toughened glass & IP 66 protection complete and all as specified and directed by Engineer - in - Charge Cat Part No of surya SLE UL65W IP66 LXN or equivalent Make- Bajaj/CG/Havells
11
-
-
... More
S&F LED 45 Watt security light fitting new generation energy saving & environmental friendly long life versatile pressure die cast aluminium housing with heat resistant toughened glass & IP 66 protection complete and fixing to wall/pole complete all as specified and directed by Engineer - in - Charge Cat Part No of Surya SLE UL 45W IP66 LXN or equivalent Make- Bajaj/HPL/Havells
5
-
-
... More
Supply & fix in replacement cable PVC insulated flexible aluminium conductor service cable 2 core 4 sqmm cut to pieces all as required, drawn into conduit/pipe fixed to wall or pole all as directed by Engr-in-charge. Make : Finolex/Havells/Polycab
220
-
-
... More
Excavation in trenches n.exc 1.5m wide and n.exc 1.5m deep and getting out in any type of soil for laying of cable complete all as specified and directed by Engineer-in-charge.
170
-
-
... More
Excavation in trenches beyond 1.5 m wide and n.exc. 3 m deep for foundation of poles/stay etc including getting out in any type of soil complete all as specified and directed by Engr-in-Charge.
2.37
-
-
... More
Excavation in trenches n.exc 1.5m wide and n.exc 1.5m deep and getting out in Hard/ Dense soil ( Road cutting) for laying of cable complete all as specified and directed by Engineer-in-charge.
12
-
-
... More
Returning filling in (soil) including spreading leveling, watering and well ramming in layers not exc 25cm thick all as specified and directed by Engineer -in-charge.
80
-
-
... More
Removal of excavated soil to a distance n.exc 50 m and depositing where directed at a level not exc 1.5 mtr above the ground level/starting point complete all as specified and directed.
111
-
-
... More
Sand cushioning to cable with dry fine sand in trenches 8 cm below the cable and 15 cm above the cable after laying complete all as specified. Note : Compacted thickness will be measured.
52.1
-
-
... More
M/L Sub Class 'B' brick covering protection to the electric cable laid dry flat transversally along the length of cable on sand cushioning with width equal to length of brick complete all as specified
22.05
-
-
... More
Supply and laying testing in replacement of cable XLPE insulated screened PVC bedded ,galvanized steel strip or wire armored ,electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 3.5 core 35 Sqmm Make : Havells/ Polycab/ Palaza
320
-
-
... More
Taking out old rusted outdoor panels including taking out of electric out going and incoming connections
2
-
-
... More
Taking out old unserviceable electric cable aurmored and service wire any type and any size
300
-
-
... More
PCC 1:2:4 type B-1 using 20mm graded stone aggregate as in benching including weathering slightly chamfered on edges and finished exposed surfaces even and smooth including necessary form work complete all as specified and directed. ( for road crossing)
0.5
-
-
... More
Supply and laying testing in replacement of cable XLPE insulated screened PVC bedded ,galvanized steel strip or wire armored ,electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 2 core 10 Sqmm Make : Havells/ Polycab/ Palaza
200
-
-
... More
Supply and laying testing in replacement of cable XLPE insulated screened PVC bedded ,galvanized steel strip or wire armored ,electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 2 core 16 Sqmm Make : Havells/ Polycab/ Palaza
50
-
-
... More
Supply and laying testing in replacement of cable XLPE insulated screened PVC bedded ,galvanized steel strip or wire armored ,electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 4 core 16 Sqmm Make : Havells/ Polycab/ Palaza
250
-
-
... More
Supply and laying testing in replacement of cable XLPE insulated screened PVC bedded ,galvanized steel strip or wire armored ,electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 4 core 25 Sqmm Make : Havells/ Polycab/ Palaza
250
-
-
... More
Supply and laying testing in replacement of cable XLPE insulated screened PVC bedded ,galvanized steel strip or wire armored ,electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 3.5 core 50 Sqmm Make : Havells/ Polycab/ Palaza
100
-
-
... More
S & F GI tubing Light grade ISI marked with all fittings and fixed complete to wall/ trench for passing of Cable of dia 50mm Make- Prakesh/ jindal /Tata.
6
-
-
... More
Supply installation commissning and testing of out door feeder pillar board LT floor mounted , factory assembled, outdoor type weather and vermin proof made out of 40m x 40mm x 6mm angle iron frame and 3.15 mm thick CRCA sheet with front hinged opening, rubber lining, locking arrangement, painted externally and internally with two coats of synthetic enamel paint over a coat of red oxide primer complete comprising of following:-
Incoming (a) Bus Bar chamber comprising 4 Nos aluminium strip bus bars air insulated and PVC sheathed capacity 100 Amps with colour coding.
(b) MCCB 63 amps, 433 Volts, 3 phase with neutral link specially fixed for incoming supply with over load, short circuit and earth fault protection with earth module (Breaking capacity 35KA)-1 No
(c) MCB 40 Amps, 433 volts, 3 phase 4 pole with neutral link with over load, short circuit t protection fixed for outgoing supply (Breaking capacity 16KA)- 2 Nos
(d) MCB 32 Amps, 240 volts, Single phase SPN with neutral link with over load, short circuit t protection fixed for outgoing supply (Breaking capacity 16 KA)- 12 Nos
(e) MCB 32 Amps, 240 volts, Single phase SP with neutral link with over load, short circuit t protection fixed for outgoing supply (Breaking capacity 16 KA)- 04 Nos
(f) Voltmeter 0-500V with selector switch 96mm2 flush mounted.
(g) Ampere meter CTs operated including CTs 0-150A 96mm2 flush mounted with selector switch-2 Nos
(h) Wiring with single core copper conductor cable of suitable size incoming to bus bar and bus bar to outgoing MCCB/MCB-1Job.
(j) Fine wiring with single core copper conductor cable for instruments/indicating lamps-1 Job.
(k) Indicating lamps RYB-3 Nos
4
-
-
... More
Dismantling from insulators and taking down ACSR conductor any size from LT over head lines and removing from site.
1
-
-
... More
Dismantling earth wire any size from eye hooks/insulators etc from LT over head lines and removing from site.
0.5
-
-
... More
Dismantling insulator any type and any size from LT over head lines and removing from site.
40
-
-
... More
Dismantling, cross arms, clamps, supports made of channels or angle section etc including nuts and bolts and setting aside for reuse on the same or new location or removing from site all as required at site or directed by Engr-in-charge.
1
-
-
... More
Dismantling stay assy complete including excavation for taking out PCC block breaking of PCC block for taking out MS plate and removing of PCC and iron items from site.
5
-
-
... More
Disconnecting electrically and taking out cable LT 1100 volts grade heavy duty, armoured, with alumn conductor of any size upto 50 Sqmm.
700
-
-
... More
Disconnecting electrically, dismantling from foundation and removing from site LT panel/feeder pillar box any size or type all as required at site.
9
-
-
... More
Dismantling steel tubular pole LT after disconnecting electrically complete including excavation and remove from site.
4
-
-
... More
M&L for cross arms, bracings, supports, clamps and back plates fabricated from steel section including nuts, bolts, washers, welding bending cold or hot drilling holes for bolts in any shape ors size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of alumn paint.
1
-
-
... More
S & F Pin type insulator, porcelain vitreous white or brown including one galvanised mild steel spindle, two galvanised iron washers and nuts, 100mm height, 65mm dia for 1100 volts grade complete all as specified and directed.
20
-
-
... More
S & F Shackle type porcelain vitreous white or brown insulator size 75mm height 90mm dia (maximum) including mild steel strips of section 31 x 3mm, washers, 12mm dia insulator bolt and nut suitable for working pressure 1100 volts grade all complete as specified and directed..
15
-
-
... More
S & F Loop type insulator, vitreous porcelain, white or brown small size with overall dimension 65mm x 90mm and clearance of hole 16mm complete all as specified and directed.
5
-
-
... More
Supply and laying Galvanised steel wire 4.00mm dia as continuous earth wire on over head conductor, Guard cradles on road crossing and stretching the same with required span, sag and binding the conductor with GI binding wire of approximate size all complete all as specified and directed.
0.5
-
-
... More
S & F Stay assembly complete with all accessories with stay clamps as shown in electrical plate No 1 of SSR Part-I with using stay rod 16mm dia all complete as specified and directed.[Note :- Loop type insulator, excavation and concrete foundation shall be measured and paid separately under relevant items of Sch 'A']
5
-
-
... More
M&L for Aluminium conductor steel reinforced (ACSR) on overhead electric lines and stretching the same with required span sag and binding the conductor with pin/shackle insulator and jumpers with aluminium binding wire not less than 2.00 mm dia complete all as specified and directed for any size.
1
-
-
... More
Material and labour for GI tubing light grade 80mm bore with fittings in replacement laid for protection of cable under road crossing fixed to walls or pole complete including taking down of old UNSV GI pipes all as specified and as directed
10
-
-
... More
Material and labour for GI tubing light grade 50mm bore with fittings in replacement laid for protection of cable under road crossing fixed to walls or pole complete including taking down of old UNSV GI pipes all as specified and as directed
25
-
-
... More
Material and labour for GI tubing light grade 40mm bore with fittings in replacement laid for protection of cable under road crossing fixed to walls or pole complete including taking down of old UNSV GI pipes all as specified and as directed
25
-
-
... More
Supply, Installaton,testing and commissioning of LT panel outdoor cubical, dust and vermin proof with protection class IP-55 ,CPRI approved, front and rear openable double door with locking arrangements floor mounted type made out of 3.15 mm thick CRCA Sheet duly powder coated complete with bus bar 300 amps rating made of aluminium strip duly drilled holes for connections and mounted on epoxy based post insulators for 3 phase 4 wire 415 volts 50Hz power supply system suitable for and including the following :- (a) MCCB 200 Amp 4 Pole 50 Hz 415V having thermal magnetic release with rupturing capacity 35 KA.- 01 Nos as incoming (b) MCCB 100 Amp TPN 50 Hz 415 V having thermal magnetic release with rupturing capacity 25 KA. - 03 Nos ( 02Nos in use and one stand by being an vital location ) as outgoing (c) On load change over switch front handle operative panel mounting type 4 pole 415V 50Hz AC without enclosure 200 A -01Nos
(d) Indicator set RYB 01 set of 3 pcs LED type . (e) Digital voltmeter of size 96 x 96 mm range 30 to 600 volts with in built in selector switch 01 Set. (f) Digital ammeter of size 96 x 96 mm range 0 to 200 amps with in built in selector switch complete with 3 nos CTs of appropriate ratio 01 Set.
(g) Ampere meter CTs operated including CTs 0-150A 96mm2 flush mounted with selector switch-2 Nos
All accessories prewired with suitable size copper conductor cable/strip and suitable foundation as per manufacturer's recommendation.
1
-
-
... More
Supply, Installation, ,testing and commissioning of LT panel outdoor cubical, dust and vermin proof with protection class IP-55 , of appropriate size but not less than 1.00X1.00X0.60 mtr (LXHXD) CPRI approved, front and rear openable double door with locking arrangements floor mounted type made out of 3.15 mm thick CRCA Sheet duly powder coated complete with bus bar 200 amps rating made of aluminium strip duly drilled holes for connections and mounted on epoxy based post insulators for 3 phase 4 wire 415 volts 50Hz power supply system suitable for and including the following :- (a) MCCB 100 Amp 4 Pole 50 Hz 415V having thermal magnetic release with rupturing capacity 35 KA.- 01 Nos as incoming conf to cat pt No 625348 of Legrand or equivalent make L&T(Dsine)/ABB/Siemens
(b) MCB 63 Amp TPN 50 Hz 230V having rupturing capacity 10 KA. "C" curve type - 03 Nos as outgoing Conf to cat pt No 603269 of Legrand or equivalent make L&T(Hager)/ABB prewired from bus bar to and including connection terminal for connecting out going cables without disturbing MCB connections.
(c) MCB 32 Amp single Pole 50 Hz 230V having rupturing capacity 10 KA. "C" curve type - 12 Nos as outgoing (d) MCB 16 Amp single Pole 50 Hz 230V having rupturing capacity 10 KA. "C" curve type - 4 Nos as outgoing (e)Indicator set RYB 01 set of 3 pcs LED type .
(f) Digital voltmeter of size 96 x 96 mm range 30 to 600 volts with in built in selector switch 01 Set. (g) Digital ammeter of size 96 x 96 mm range 0 to 200 amps with in built in selector switch complete with 3 nos CTs of appropriate ratio 01 Set.
(h) Ampere meter CTs operated including CTs 0-150A 96mm2 flush mounted with selector switch-2 Nos
All accessories prewired with suitable size copper conductor cable/strip and suitable foundation as per manufacturer's recommendation.
4
-
-
... More
Supply, Installation, ,testing and commissioning of LT panel outdoor cubical, dust and vermin proof with protection class IP-55 , of appropriate size but not less than 1.00X1.00X0.60 mtr (LXHXD) CPRI approved, front and rear openable double door with locking arrangements floor mounted type made out of 3.15 mm thick CRCA Sheet duly powder coated complete with bus bar 200 amps rating made of aluminium strip duly drilled holes for connections and mounted on epoxy based post insulators for 3 phase 4 wire 415 volts 50Hz power supply system suitable for and including the following :- (a) MCCB 63 Amp 4 Pole 50 Hz 415V having thermal magnetic release with rupturing capacity 40 KA.- 01 Nos as incoming (b) MCCB 32 Amp TPN 50 Hz 415 V with rupturing capacity 25 KA. - 03 Nos ( 02Nos in use and one stand by being an vital location ) as outgoing (c) MCB 10 Amp single Pole 50 Hz 230V having rupturing capacity 10 KA. "C" curve type - 6 Nos as outgoing (d) Indicator set RYB 01 set of 3 pcs LED type .
(e) Digital voltmeter of size 96 x 96 mm range 30 to 600 volts with in built in selector switch 01 Set. (f) Digital ammeter of size 96 x 96 mm range 0 to 200 amps with in built in selector switch complete with 3 nos CTs of appropriate ratio 01 Set.
All accessories prewired with suitable size copper conductor cable/strip and suitable foundation as per manufacturer's recommendation.
4
-
-
... More
Supply, installation, Testing and commissioning of servo controlled, voltage stabilizer of capacity 100 KVA, copper wound, for automatic operation 3 phase, 50Hz, naturally oil cooled, unbalanced type, indoor type with micro processor based control card, digital type, relay free smooth and silent operation & designed for input voltage of 250-415 Volts per phase with output voltage stabilizer at 415 volts with (+/-) 1.0% for phase to phase and 240volts with (+/-) 1.0% for phase to Neutral of accuracy of 50 Hz and speed of correct @ 20 volts per second, having high voltage protection, low voltage protection, single phasing & phase reversal protection, overload/short circuit protections with first fill of oil (ISI Marked), having MCCB at input side of 200 amp capacity, 3 pole, 35 KA, adjustable thermal & magnetic setting, withali accessories, complete all as directed. Make : AE/Andrew/Yule/Aplab/Electric field.
2
-
-
... More
Supply anf fix in replacement steel tubular swaged pole complete with cast iron base plate, finial taper plug , bolts, nuts and screws as specified type 410 SP-31 (9.0 m long) conforming to IS-2713 (Part I&III) including painting of pole with two coat of aluminium paint over a coat of red oxide primer from top of the pole to 1.5m above the bottom of pole and painting with two coat of black paint over a coat of red oxide primer upto 1.5m from bottom of the pole as directed complete all as specified and directed.(Note - Excavation, earthwork and PCC shell be measured and paid separately.)
4
-
-
... More
Supply and fix cable jointing kit for 1100 V grade cable for straight through joint complete with jointing material heat shrink type and accessories suitable for 3.5 or 4 core XLPE , armoured , AL conductor cable of size upto 50 sqmm indoor/outdoor type.
5
-
-
... More
M&L for PCC 1:4:8 (using 40mm graded stone aggregate ) as in foundation, filling, and mass concrete complete all as specified and directed.
0.22
-
-
... More
M&L for PCC 1:3:6 (using 40mm graded stone aggregate ) as in foundation, filling, and mass concrete complete all as specified and directed.
2.04
-
-
... More
M&L for PCC 1:2:4 (using 20mm graded stone aggregate ) as in foundation, filling, and mass concrete complete all as specified and directed.
0.23
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements