Military Engineer Services Tender

Bidassist allows us to explore new opportunities across the whole world so as to support the growth of the business. It is designed in such a manner that if we need any kind of information about any government e-tender the Himachal Pradesh government has posted on its website, Bidassist provides the same in a very hassle-free manner. As BidAssist is designed as a very user-friendly website which helps us find the specific Himachal Pradesh etender we are looking for.

Military Engineer Services - MES Tender

Works
Electrical and Electronics
Electrical Works
Eprocure
Opening Date30 Oct 2024
Closing Soon20 Nov 2024
Tender Amount₹ 41,26,000 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Returning filling in (soil) including spreading, levelling, watering and well ramming in layers n.exc 25cms thick in any type of soil complete all as specified and directed.

289.1

-

-

... More
Removing excavated materials/ soils, not exceeding 50mtrs and depositing where directed at a level not exceeding 1.50mtrs, complete all as specified and directed.

241

-

-

... More
PCC 1:3:6 (nominal mix) type C-2 (using 40mm graded crushed stone aggregates) as in foundation filling and mass concrete complete all as specified and directed.

0.49

-

-

... More
Plain cement concrete 1:4:8 ( nominal mix ) type D-2 (using 40 mm graded crushed stone aggregates) as in base of pole complete all as specified and directed.

13.51

-

-

... More
XLPE LT insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 1100 volts grade cross sectional area 150 sqmm 3.5 core, laid in trenches or passing through pipes/ ducts or fixed to walls/ poles complete including testing and taking out old unservicable cable, cable covers complete all as specified and directed. Note:- Excavation & Earth work, brick cable cover, GI pipe and sand cushioning shall be measured and paid separetly.

460

-

-

... More
XLPE LT insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 1100 volts grade cross sectional area 120 sqmm 3.5 core, laid in trenches or passing through pipes/ ducts or fixed to walls/ poles complete including testing and taking out old unservicable cable, cable covers complete all as specified and directed. Note:- Excavation & Earth work, brick cable cover, GI pipe and sand cushioning shall be measured and paid separetly.

888

-

-

... More
XLPE LT insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 1100 volts grade cross sectional area 95 sqmm 3.5 core, laid in trenches or passing through pipes/ ducts or fixed to walls/ poles complete including testing and taking out old unservicable cable, cable covers complete all as specified and directed. Note:- Excavation & Earth work, brick cable cover, GI pipe and sand cushioning shall be measured and paid separetly.

528

-

-

... More
XLPE LT insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 1100 volts grade cross sectional area 50 sqmm 3.5 core, laid in trenches or passing through pipes/ ducts or fixed to walls/ poles complete including testing and taking out old unservicable cable, cable covers complete all as specified and directed. Note:- Excavation & Earth work, brick cable cover, GI pipe and sand cushioning shall be measured and paid separetly.

90

-

-

... More
XLPE LT insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 1100 volts grade cross sectional area 35 sqmm 3.5 core, laid in trenches or passing through pipes/ ducts or fixed to walls/ poles complete including testing and taking out old unservicable cable, cable covers complete all as specified and directed. Note:- Excavation & Earth work, brick cable cover, GI pipe and sand cushioning shall be measured and paid separetly.

245

-

-

... More
XLPE LT insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 1100 volts , grade cross sectional area 25 sqmm 3.5 core, laid in trenches or passing through pipes/ ducts or fixed to walls/ poles complete including testing and taking out old unservicable cable, cable covers complete all as specified and directed. Note:- Excavation & Earth work, brick cable cover, GI pipe and sand cushioning shall be measured and paid separetly.

170

-

-

... More
XLPE LT insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables with aluminium conductor, 1100 volts grade cross sectional area 16 sqmm 4 core, laid in trenches or passing through pipes/ ducts or fixed to walls/ poles complete including testing and taking out old unservicable cable, cable covers complete all as specified and directed. Note:- Excavation & Earth work, brick cable cover, GI pipe and sand cushioning shall be measured and paid separetly.

1000

-

-

... More
XLPE LT insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminium conductor, 1100 volts , grade cross sectional area 6 sqmm 2 core, laid in trenches or passing through pipes/ ducts or fixed to walls/ poles complete including testing and taking out old unservicable cable, cable covers complete all as specified and directed. Note:- Excavation & Earth work, brick cable cover, GI pipe and sand cushioning shall be measured and paid separetly.

150

-

-

... More
Dismantling and taking out stay assembly complete of any size complete all as specified.

6

-

-

... More
Dismantling cross-arms of M.S. channel or angle sections etc. complete all as specified.

1.52

-

-

... More
Dismantling insulators any type, any size. complete all as specified.

48

-

-

... More
Taking out old/bent/straight/ tilted LT pole any capacity, any size, any type poles after breaking the PCC complete all as directed.(The rate quoted shall include the cost of excavation,dismantling of conductor, cross-arms and insulators)

6

-

-

... More
Fixing only Steel tubular swagged poles complete with GI base plate, finial taper plug, bolts, nuts and screws specified type 410 SP-31(9 mtrs long) duly painted with aluminium paint two coat over a coat of red oxide, and pasting three layer reflector tape on pole including necessary earth work ,PCC for foundation and PCC for coping as specified and directed by Engr-In-Charge. Note: Steel pole retrieved from above sr item no 19 shall be used )

6

-

-

... More
Sand cushioning to protection of underground cables, laid 8 Cm before laying and 15 Cm after laying of cable, and punned to form an overall layer of 18 Cms thick, complete all as specified and directed Note: Punned thickness shall be measured.

206.31

-

-

... More
Supplying and laying reinforced precast concrete cable cover, class LV, type 1 , flat, size 250mm x 150mm x 40mm complete all as specified and directed.

16980

-

-

... More
Mild steel galvanised iron tubing light grade for cable protection as in road crossing, along poles, walls, floors, drain of 40mm size fixed with MS clamps, nuts and bolts required complete all as specified and directed.

66

-

-

... More
Mild steel galvanised iron tubing light grade for cable protection as in road crossing, along poles, walls, floors, drain of 80mm size fixed with MS clamps, nuts and bolts required complete all as specified and directed.

50

-

-

... More
Steel tubular swaged poles complete with base plate 8mm thick welded with pole, finial taper plug, bolt, nut and screws as specified type 410 SP-31 (9m long) including one coat of red-oxide zinc chrome primer and two coats of aluminium paint on surfaces exposed to view and pasting three layer reflector tape upto 1.5 metre height on pole external surface including numbering with black paint and painting with bituminous paint internally complete and externally for portion embedded in PCC , complete all as specified and directed. Note:- Earth work & excavation and PCC shall be measured and paid under respective Items of BOQ.

12

-

-

... More
LED Street light 60 watt High pressure die cast aluminum hosing with toughened glass having efficiency (110 Lm/W) and heat resistant complete with driver, lamp with impact and corrosion resistant includng thermal management in multiple optic complete with IP66 protection, complete all as specified. Make:- HPL Cat Part No. HPLLEDSL60CWGLA or its equivalent make in Appendix

35

-

-

... More
GI mounting bracket (suitable for mounting street light) made out of GI light grad tubing of 40 mm dia light grade bend to shape and angle of 120 dgree and having total length not more than 120 cm including fixing clamps, nut and bolts, two coat of aluminium paint complete all as specified and required and as directed.

35

-

-

... More
SMC cable junction box of size 200x140x95mm suitable for street light/PTL, square type , weather proof , IP-54 including fixing of 10Amp MCB SP and clamps , nuts , bolts , washers suitable for fixing to pole/GI pipes including suitable arrangement for cable entry and exit with twin core 2.5 Sqmm PVC Cable laying through PVC conduit from junction box to street light fitting complete all as specified and directed. Make : Sintex Cat Part No. GSJB-2014 or its equivalent approved make. Note : Twin Core PVC Cable 2.5 Sqmm from Junction box to Street Light fitting shall be measured under respective item of BOQ.

35

-

-

... More
Twin core PVC insulated multistranded 1100 volt grade copper conductor cable of size 2.5 sqmm with complete cable connection on street light fitting to looping box complete all as specified and directed.

280

-

-

... More
20mm dia Rigid non-metallic PVC conduit heavey duty , fixed on pole with 04 Nos MS Clamps size 20x2mm, from junction box to fitting complete all as specified and directed.

160

-

-

... More
Supply and fix Meter Box consisting space to fix MCCB as incomer and 02 Nos meter and providing 02 Nos MCB RCBO 40 Amps 100m,. Meter Box shall be double door fixed type wall mounted CRCA approved FACTORY MADE, 3 mm thick sheet enclosure outdoor type. The quoted rate shall include taking down old meter and connecting in new panel with required wires with out any extra cost complete all as spcified and directed. The panel should cosists of the following :- INCOMING : (i) MCCB 63 Amp 4P 16KA thermal magnetic based with o/c, s/c protection & ROH-01 Nos (ii) Indicating lamps RYB -01 Set OUT GOING : (i) 40 Amp MCB RBCO 100 mA with enclosure -02 Nos (ii) Space for refixing existing electrical meter -02 Nos. Note :- Contractor should visit the site and to prepare panel as per size required to fit in outside wall of Offr Mess guest room complete all as specified and directed by Engr-in-Charge.

1

-

-

... More
Outdoor type factory made bus bar chamber of size 0.75x0.45x0.40 meter depth made out of CRCA sheet 3.15 mm thick with 4 Nos aluminium busbars of capacity 200 Apms, with colour code supported on incoming and outgoing under ground cables with LED R,Y,B indicator lamp, panel having angle iron frame made of 40x40x6mm angle iron and 50 cms long legs embeded upto 20 cms in PCC & 30 cms clear above ground compelte including painting with two coat of powder coated paint over a coat of red oxide primer on exterior and interior faces, errection of Bus Bar chamber duly grouted with PCC including earth work complete all as specified and directed by Engr-in-Charge.

3

-

-

... More
Street light timer panel 3 phase maximum load capacity 6 kw capacity, Contract Rating 32 Amps TP, MCB rating 40 Amps TPN with 24 hours working digital timer switch outdoor type panel with canopy and locking arrangement of panel with all incoming and outgoing cable connection and complete testing all as specified and directed by Engr-in-Charge . Make - Havells/ Legard/ L&T.

2

-

-

... More
Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 metre deep below normal ground level) with top edge of plate not less than 1.5 metre below ground level, connecting to galvanised iron strip 32X6 mm size (as earth lead strip), by means of bolt, nuts, check nuts and washer of galvanised and earth wire protected by provision of galvanised iron pipe light grade, 40 mm bore including provn of concrete pit in plain cement concrete M-15 type B-1 using 20mm graded crushed stone aggregates with 40mm thick cover of rainforced cement concrete M-15 reinforced with XPM (weight not less than 4 kg/Sqm) and frame of angle iron 25x25x3mm with lugs 2 Nos and with 6mm dia mild steel bar handle made to shape, galvanised iron medium grade 20mm bore pipe for watering perforated at bottom 1.75 metre long placed on top edge of earth plate, common salt and charcoal filling, test point made out of phosphorous bronze with fixing arrangement, funnel, wire mesh and including earth work in any type of soil, returning filling in and removal of surplus soil to a distance not exceeding 50 metre, all as per electrical plate No. 3 of SSR 2009 Part-I and connection to earth test point all as specified and testing on completion.

22

-

-

... More
Supply, installation , Commissiong and Testing of totally enclosed LT panel box outddor type, CPRI approved, LT 440 Volts, 50 Hz , 3 Phase 4 wire supply system, double door type, having independent cabin including locking arrangement for each MCCBs, floor mounted factory fabricated weather and vermin proof protection class IP 55 made out of 3.15 mm thick MS Sheet CRCA Sheet on angle iron 50X50X6mm frame of size suitable to incorporate and including following accessories with front and rear opening doors, handle type locking arrangement powder coated internally and externally shall have angle iron legs made out of angle iron 40x40x6mm and embeded in PCC foundation of size as required or approved by manufacturers in PCC 1:3:6 Type C-2 , using 40 mm graded crushed stone aggregate ( 150mm below GL and 100mm above GL) as recommended by manufacturer or directed including earth work complete comprising of following:-

1

-

-

... More
Incoming:- (a) MCCB having current rating 320 Amps with rupturing cap 36 KA (Adjustable Thermal & Adjustable Magnetic) , AC 415 Volts,four pole, complete with spreader links. (Qty -01 No)

-

-

-

... More
Outgoing:- (a) MCCB having current rating 200 Amps with rupturing cap 25 KA (Adjustable Thermal & Adjustable Magnetic) , AC 415 Volts,four pole, complete with spreader links. (Qty -01 No) (b) MCCB having current rating 100 Amps with rupturing cap 25 KA (Adjustable Thermal & Adjustable Magnetic) , AC 415 Volts,four pole, complete with spreader links. (Qty -02 Nos) (c) MCCB having current rating 630 Amps with rupturing cap 25 KA (Adjustable Thermal & Adjustable Magnetic) , AC 415 Volts,four pole, complete with spreader links. (Qty -02 Nos) (d) Multifunctional digital panel meter with LCD display flush mounting type of size 96x96mm, accuracy class 1, suitable for CTs with secondary current 5A having provision of display parameters such as voltage, Amp, Power factor , KW, KV etc. ( Qty-01 No) (e) Current transformer ratio of 200/5 Amps, Current rating primary upto 200 Amps and secondary 5 Amps, accuracy class 1, VA burden 10 VA including necessary wiring using PVC insulated copper conductor cable of appropriate size as per standard engineering practice ( Qty- 01 set of three) (f) LED phase indicator lamp ( Qty- 01 set of three) (f) 300 Amp rated Bus bar chamber comprising 4 Nos Aluminium Strip bus bars PVC insulated made of aluminium strip of size (40 x 5) mm. PVC sheathed with colour coding.

-

-

-

... More
Note : (i) Incoming and outgoing cables shall be fixed with appropriate size of thimble. (ii) Apron shall be provided at bottom of protection of cable to avoid entry of vermins, raptiles. (iii) Entries of all sizes of cables in panel should be done through adequate size of metallic cable glands. (iv) Layout diagram of panel shall be produced by contractor for approval of AGE (I) before placing order to manufacturer and panel shall be brought at site as per approved drawing

-

-

-

... More
Location : LT Panel Near Garden P-06 Bldg

-

-

-

... More
Supply, installation , Commissiong and Testing of totally enclosed LT panel box outddor type, CPRI approved, LT 440 Volts, 50 Hz , 3 Phase 4 wire supply system, double door type, having independent cabin including locking arrangement for each MCCBs, floor mounted factory fabricated weather and vermin proof protection class IP 55 made out of 3.15 mm thick MS Sheet CRCA Sheet on angle iron 50X50X6mm frame of size suitable to incorporate and including following accessories with front and rear opening doors, handle type locking arrangement powder coated internally and externally shall have angle iron legs made out of angle iron 40x40x6mm and embeded in PCC foundation of size as required or approved by manufacturers in PCC 1:3:6 Type C-2 , using 40 mm graded crushed stone aggregate ( 150mm below GL and 100mm above GL) as recommended by manufacturer or directed including earth work complete comprising of following:-

1

-

-

... More
Incoming:- (a) MCCB having current rating 200 Amps with rupturing cap 36 KA (Adjustable Thermal & Adjustable Magnetic) , AC 415 Volts,four pole, complete with spreader links. (Qty -01 No)

-

-

-

... More
Outgoing:- (a) MCCB having current rating 160 Amps with rupturing cap 25 KA (Adjustable Thermal & Adjustable Magnetic) , AC 415 Volts,four pole, complete with spreader links. (Qty -01 No) (b) MCCB having current rating 630 Amps with rupturing cap 25 KA (Adjustable Thermal & Adjustable Magnetic) , AC 415 Volts,four pole, complete with spreader links. (Qty -02 Nos) (c) Multifunctional digital panel meter with LCD display flush mounting type of size 96x96mm, accuracy class 1, suitable for CTs with secondary current 5A having provision of display parameters such as voltage, Amp, Power factor , KW, KV etc. ( Qty-01 No) (d) Current transformer ratio of 200/5 Amps, Current rating primary upto 200 Amps and secondary 5 Amps, accuracy class 1, VA burden 10 VA including necessary wiring using PVC insulated copper conductor cable of appropriate size as per standard engineering practice ( Qty- 01 set of three) (e) LED phase indicator lamp ( Qty- 01 set of three) (f) 400 Amp rated Bus bar chamber comprising 4 Nos Aluminium Strip bus bars PVC insulated made of aluminium strip of size (40 x 5) mm. PVC sheathed with colour coding.

-

-

-

... More
Note : (i) Incoming and outgoing cables shall be fixed with appropriate size of thimble. (ii) Apron shall be provided at bottom of protection of cable to avoid entry of vermins, raptiles. (iii) Entries of all sizes of cables in panel should be done through adequate size of metallic cable glands. (iv) Layout diagram of panel shall be produced by contractor for approval of AGE (I) before placing order to manufacturer and panel shall be brought at site as per approved drawing

-

-

-

... More
Location : LT Panel Near Sub Station No. 02

-

-

-

... More
Supply, installation , Commissiong and Testing of totally enclosed LT panel box outddor type, CPRI approved, LT 440 Volts, 50 Hz , 3 Phase 4 wire supply system, double door type, having independent cabin including locking arrangement for each MCCBs, floor mounted factory fabricated weather and vermin proof protection class IP 55 made out of 3.15 mm thick MS Sheet CRCA Sheet on angle iron 50X50X6mm frame of size suitable to incorporate and including following accessories with front and rear opening doors, handle type locking arrangement powder coated internally and externally shall have angle iron legs made out of angle iron 40x40x6mm and embeded in PCC foundation of size as required or approved by manufacturers in PCC 1:3:6 Type C-2 , using 40 mm graded crushed stone aggregate ( 150mm below GL and 100mm above GL) as recommended by manufacturer or directed including earth work complete comprising of following:-

1

-

-

... More
Incoming:- (a) MCCB having current rating 160 Amps with rupturing cap 25 KA (Adjustable Thermal & Adjustable Magnetic) , AC 415 Volts,four pole, complete with spreader links. (Qty -01 No)

-

-

-

... More
Outgoing:- (a) MCCB having current rating 100 Amps with rupturing cap 25 KA (Adjustable Thermal & Adjustable Magnetic) , AC 415 Volts,four pole, complete with spreader links. (Qty -02 Nos) (b) MCCB having current rating 63 Amps with rupturing cap 25 KA (Adjustable Thermal & Adjustable Magnetic) , AC 415 Volts,four pole, complete with spreader links. (Qty -01 No) (c) Multifunctional digital panel meter with LCD display flush mounting type of size 96x96mm, accuracy class 1, suitable for CTs with secondary current 5A having provision of display parameters such as voltage, Amp, Power factor , KW, KV etc. ( Qty-01 No) (d) Current transformer ratio of 200/5 Amps, Current rating primary upto 200 Amps and secondary 5 Amps, accuracy class 1, VA burden 10 VA including necessary wiring using PVC insulated copper conductor cable of appropriate size as per standard engineering practice ( Qty- 01 set of three) (e) LED phase indicator lamp ( Qty- 01 set of three) (f) 200 Amp rated Bus bar chamber comprising 4 Nos Aluminium Strip bus bars PVC insulated made of aluminium strip of size (40 x 5) mm. PVC sheathed with colour coding.

-

-

-

... More
Note : (i) Incoming and outgoing cables shall be fixed with appropriate size of thimble. (ii) Apron shall be provided at bottom of protection of cable to avoid entry of vermins, raptiles. (iii) Entries of all sizes of cables in panel should be done through adequate size of metallic cable glands. (iv) Layout diagram of panel shall be produced by contractor for approval of AGE (I) before placing order to manufacturer and panel shall be brought at site as per approved drawing

-

-

-

... More
Location : LT Panel Near Bldg No. BK-14

-

-

-

... More
Supply, installation , Commissiong and Testing of totally enclosed LT panel box outddor type, CPRI approved, LT 440 Volts, 50 Hz , 3 Phase 4 wire supply system, double door type, having independent cabin including locking arrangement for each MCCBs, floor mounted factory fabricated weather and vermin proof protection class IP 55 made out of 3.15 mm thick MS Sheet CRCA Sheet on angle iron 50X50X6mm frame of size suitable to incorporate and including following accessories with front and rear opening doors, handle type locking arrangement powder coated internally and externally shall have angle iron legs made out of angle iron 40x40x6mm and embeded in PCC foundation of size as required or approved by manufacturers in PCC 1:3:6 Type C-2 , using 40 mm graded crushed stone aggregate ( 150mm below GL and 100mm above GL) as recommended by manufacturer or directed including earth work complete comprising of following:-

1

-

-

... More
Incoming:- (a) MCCB having current rating 100 Amps with rupturing cap 25 KA (Adjustable Thermal & Adjustable Magnetic) , AC 415 Volts,four pole, complete with spreader links. (Qty -01 No)

-

-

-

... More
Outgoing:- (a) MCCB having current rating 63 Amps with rupturing cap 25 KA (Adjustable Thermal & Adjustable Magnetic) , AC 415 Volts,four pole, complete with spreader links. (Qty -02 Nos) (b) Multifunctional digital panel meter with LCD display flush mounting type of size 96x96mm, accuracy class 1, suitable for CTs with secondary current 5A having provision of display parameters such as voltage, Amp, Power factor , KW, KV etc. ( Qty-01 No) (c) Current transformer ratio of 200/5 Amps, Current rating primary upto 200 Amps and secondary 5 Amps, accuracy class 1, VA burden 10 VA including necessary wiring using PVC insulated copper conductor cable of appropriate size as per standard engineering practice ( Qty- 01 set of three) (d) LED phase indicator lamp ( Qty- 01 set of three) (e) 200 Amp rated Bus bar chamber comprising 4 Nos Aluminium Strip bus bars PVC insulated made of aluminium strip of size (40 x 5) mm. PVC sheathed with colour coding.

-

-

-

... More
Note : (i) Incoming and outgoing cables shall be fixed with appropriate size of thimble. (ii) Apron shall be provided at bottom of protection of cable to avoid entry of vermins, raptiles. (iii) Entries of all sizes of cables in panel should be done through adequate size of metallic cable glands. (iv) Layout diagram of panel shall be produced by contractor for approval of AGE (I) before placing order to manufacturer and panel shall be brought at site as per approved drawing

-

-

-

... More
Location : LT Panel Near Bldg No. P-29

-

-

-

... More
Supply, installation , Commissiong and Testing of totally enclosed LT panel box outddor type, CPRI approved, LT 440 Volts, 50 Hz , 3 Phase 4 wire supply system, double door type, having independent cabin including locking arrangement for each MCCBs, floor mounted factory fabricated weather and vermin proof protection class IP 55 made out of 3.15 mm thick MS Sheet CRCA Sheet on angle iron 50X50X6mm frame of size suitable to incorporate and including following accessories with front and rear opening doors, handle type locking arrangement powder coated internally and externally shall have angle iron legs made out of angle iron 40x40x6mm and embeded in PCC foundation of size as required or approved by manufacturers in PCC 1:3:6 Type C-2 , using 40 mm graded crushed stone aggregate ( 150mm below GL and 100mm above GL) as recommended by manufacturer or directed including earth work complete comprising of following:-

1

-

-

... More
Incoming:- (a) MCCB having current rating 250 Amps with rupturing cap 25 KA (Adjustable Thermal & Adjustable Magnetic) , AC 415 Volts,four pole, complete with spreader links. (Qty -01 No)

-

-

-

... More
Outgoing:- (a) MCCB having current rating 160 Amps with rupturing cap 25 KA (Adjustable Thermal & Adjustable Magnetic) , AC 415 Volts,four pole, complete with spreader links. (Qty -01 No) (b) MCCB having current rating 63 Amps with rupturing cap 25 KA (Adjustable Thermal & Adjustable Magnetic) , AC 415 Volts,four pole, complete with spreader links. (Qty -03 Nos) (c) Multifunctional digital panel meter with LCD display flush mounting type of size 96x96mm, accuracy class 1, suitable for CTs with secondary current 5A having provision of display parameters such as voltage, Amp, Power factor , KW, KV etc. ( Qty-01 No) (d) Current transformer ratio of 200/5 Amps, Current rating primary upto 200 Amps and secondary 5 Amps, accuracy class 1, VA burden 10 VA including necessary wiring using PVC insulated copper conductor cable of appropriate size as per standard engineering practice ( Qty- 01 set of three) (e) LED phase indicator lamp ( Qty- 01 set of three) (f) 200 Amp rated Bus bar chamber comprising 4 Nos Aluminium Strip bus bars PVC insulated made of aluminium strip of size (40 x 5) mm. PVC sheathed with colour coding.

-

-

-

... More
Note : (i) Incoming and outgoing cables shall be fixed with appropriate size of thimble. (ii) Apron shall be provided at bottom of protection of cable to avoid entry of vermins, raptiles. (iii) Entries of all sizes of cables in panel should be done through adequate size of metallic cable glands. (iv) Layout diagram of panel shall be produced by contractor for approval of AGE (I) before placing order to manufacturer and panel shall be brought at site as per approved drawing

-

-

-

... More
Location : LT Panel Near Bldg No. P-27

-

-

-

... More
Deduct Credit Amount as per Schedule of credit as details given on Srl Page No 27 of tender doucments.

-

-

-16585



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements

Past Bidders
This list is curated from the bidders of the similar tenders in the past

Unlock the Tender details for free
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.