Himachal Pradesh Irrigation And Public Health Department Tender

Bidassist allows us to explore new opportunities across the whole world so as to support the growth of the business. It is designed in such a manner that if we need any kind of information about any government e-tender the Himachal Pradesh government has posted on its website, Bidassist provides the same in a very hassle-free manner. As BidAssist is designed as a very user-friendly website which helps us find the specific Himachal Pradesh etender we are looking for.

Himachal Pradesh Irrigation And Public Health Department - HPIPH Tender

Works
Civil Works Water Works
Eprocure
Opening Date27 Jun 2020
Closing Date20 Jul 2020
Tender Amount₹ 12,80,000 
Notes
Download

Costs

Summary

Restoration Rain Damages To Lis Hukkal In Tehsil Dharampur District Mandi Hp

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Total dynamic head : 144.85 Mtr.

-

-

-

... More
(a) LWL in sump well (h) : 500.41 Mtr.

-

-

-

... More
(b) Shaft level : 500.30 Mtr.

-

-

-

... More
(c ) Level at discahrge point : 637.11 Mtr.

-

-

-

... More
(d) Suction lift : Mtr. +VE

-

-

-

... More
(e) Residual head : Mtr.

-

-

-

... More
(f) Static head : 136.81 Mtr.

-

-

-

... More
(i) Rising Main :

-

-

-

... More
(a) Length: 136.81 Mtr.

-

-

-

... More
(b) Dia. : 200 mm

-

-

-

... More
(iv) Pumping Hours : 20 hr.

-

-

-

... More
(v) Altitude of installation above MSL :

-

-

-

... More
(vi) Characteristics of water :

-

-

-

... More
(a) Temperature : 21°C

-

-

-

... More
(b) Ambient temperature : 42°C

-

-

-

... More
(c ) Turbidity: 500 PPM

-

-

-

... More
(d) Alkalinity : Mg/Ca

-

-

-

... More
(e) Size of the solids : mm

-

-

-

... More
(f) Other

-

-

-

... More
Providing ICTP Main Switch with HRC fuses/Side handled operated Change over switch of L&T/Crompton/Standard/Havells make suitable capacity Operational rating as per BIS: 4064 (Part -II)-1978 with up to date amendments immediately after the power meter of HPSEB.

2

-

-

... More
Providing M.S. sheet, steel fabricated floor mounted closed ( Almirah type) switch board including angle iron post of suitable height and size ISA 40x40x6mm, duly painted, with steel sheet of 16 gauge comprising, capable of mounting the following accessories with all internal connections:-

2

-

-

... More
O.C.B. Havell/MDS/Standard of make of suitable capacity on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage releases as per BIS: 2516 (Part -II)-1985 with up to date amendments with.

2

-

-

... More
E.L.R of Havell/MDS/INDETEC/DATAR make as per IS: 2516 (Part -II) -1977 with upto date amendment which should have control box operating handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the circuit breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tape etc. It should also be lifted with earth fault for tripping of breaker on occurrence of earth fault on off breaker load side end.

2

-

-

... More
The voltage monitor relay of L&T/AE make three phase with all protection and usual indicator and electric siren against single phasing low voltage, high voltage, reverse phasing, over loading and phase voltage difference as per IS: 3842 ( Latest edition).

2

-

-

... More
100 mm square type A.C. supply voltmeter of AE/L&T Rishab make of suitable range with selector switches as per BIS: 4064 (Part -II) -1978 with up to date amendments.

2

-

-

... More
Power factor meter of AE/L&T Rishab make as per IS: 1248 (Part-V) 1983 (Latest Edition) with up to date amendments of suitable rating.

2

-

-

... More
Frequency meter of AE/ L&T Rishab make as per IS: : 1248 (Part-V) 1983 (Latest Edition) with up to date amendments of suitable rating.

2

-

-

... More
Bus bar chamber with copper strips having three bars of suitable rating for full length equal to the width of the board for three live phases and suitable for induced current, one copper bar of half the rating of full length for neutral phase as per IS: 8084-1976 and IS: 11353-1985 read with BIS 5578-1985 with up to date amendments suitable cap.

3

-

-

... More
ICTP switches with HRC fuses of L&T/ Standard/Havells make and of suitable capacity as per BIS: 4064 (Part -II) -1978 with up to date amendments.

2

-

-

... More
Three phase indicator lamps complete with toggle switches for individual motors as per BIS: 3452 ( P-I &II) -1966 with up to date amendments.

2

-

-

... More
100mm Square type AC supply Ammeter of AE /L&T Rishab make of suitable range with selector switches and CTS operated as per BIS:1248 (Part -II)1983 with up to date amendments.

2

-

-

... More
Capacitor of L&T/Bajaj/Assian/Crompton make as per IS:2834-1986 with up to date amendments to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVAR rating according to HP offered including cables as per relevant ISI code ( of Siemens / Glocter /IEC make) from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per IS: 4064 (Part-II) 1978 with upto date amendments

2

-

-

... More
Providing Suitable oil emerged star delta Starter of Standard make as per IS: 8544 (Part-___)with up to date amendments for squirrel cage motor mounted on panel board with magnetic type overload release and dashpot time lag, under voltage release with or without initial oil filling as the case may be with single phase preventer as per IS 1248 (P-V)-1983 with up to date amendments.

2

-

-

... More
Providing Hour run meter of recommended make of suitable capacity as per IS: 722 (Latest edition)

2

-

-

... More
Providing double flanged Cast Iron (PN-1.00) sluice valve of Leader/Kirloskar make of 200 mm dia for the suction pipe and capable of withstanding the normal seat pressure as per IS: IS : 780 - 1984 with up to date amendments.

2

-

-

... More
Providing double flanged Cast Steel ASA-150 sluice valve Leader/Kirloskar make and size one dia higher to delivery of the pump and capable of with standing the normal seat pressure of 21.00 kg/cm2 and as per BS-1414-API-600.

2

-

-

... More
Providing double flanged (Swing type) Cast Steel ASA-150 reflux valve Leader/Kirloskar make and size one dia higher to delivery of the pump and capable of with standing normal seat pressure 21 kg/cm2 as per BS-1868 API-600.

2

-

-

... More
Providing double flanged Cast Steel ASA-150 non return valve of Leader/ Kirloskar make and of 200 mm dia. having bye pass arrangement for rising main and capable of with standing normal seat pressure 21 kg/cm2 as per BS-1868 API-600

1

-

-

... More
Providing 100mm dia. circular dial pressure gauge of Fiebig make complete with all accessories such as stop cock, copper tubing etc. as per IS: 3624-1987 with up to date amendments range 0-21 Kg/cm2

2

-

-

... More
Installation of all the items appearing at Serial No. 1 to 8 as per the systematic drawing attached with the tender documents ( Drg.No.1)

1

-

-

... More
Providing and fixing double flanged below mensioned dia piping work layout to be approved by the Engineer-in-Charge for suction and delivery pipes suitable to pump(s) offered and common header as per the rising main respectively complete with all specials such as bends ,tees reducers/ increasers with companion flanges matching with the relevant specifications of the accessories as indicated in the drawing No.2 including rubber/asbestos gasket of minimum 3mm thickness as per BIS 2712-1979 and required number of nuts and volts as per IS: 1364-1983. The pipes shall be as per relevant IS Code and to withstand 1.50 times total head stipulated under item No.1.

-

-

-

... More
The size of the various components to be as under:-

1

-

-

... More
(i) Suction pipe 200 mm dia Min. Length = 15 mtr. Flanged with Table-5

-

-

-

... More
(ii) Delivery pipe 150 mm dia -Do- = 5 mtr. Flanged with Table-17

-

-

-

... More
(iii) Common Header 200 mm dia -Do- = 10 mtr. Flanged with Table-17

-

-

-

... More
Providing and laying copper PVC insulated armoured power cable ( one cable carrying all the three phases) of suitable size and capacity to and all other electrical equipments as per IS: 1554 (P-I)1988 or latest with upto date amendments of Siemens/Havells/National make including all other accessories such as thimbles, flexible, pipes solder, nuts and bolts, cable glands etc. laid in pipes or trenches under floor.

-

-

-

... More
Motor side: Suitabe Size Min. Length =

20

-

-

... More
Supply side: Suitable Size Min. Length =

20

-

-

... More
Providing and fixing double loop earthing and G.I. plate 600 mm x 600 mm x 3 mm thick electrode complete with material such as thimbles, nuts and bolts, charcoal and common salt, __ mm x __ mm GI strips & GI wire as per IS: 3043-1987 with up to date amendments for motors and other electrical equipments and digging of pits etc. complete in all respect.

-

-

-

... More
Supply of submersible pumping set of KSB/Calama/SU/Johnston make, to comprising to latest relevant BIS Code. The pump should be fitted with bronze impeller of suitable alloys as per IS 8034-1976/ IS 5659-1970 latest suitable for Clear / Raw Water having greased packed bearings and shaft with wound stator on motor side and with soft protection sleeve on pump side ensuring better life for shaft coupled to a submersible squirrel cage electric induction motor (water proof type) of required HP, RPM 2900 / 1450 of reputed make conforming to BIS: 9283-1979 latest with upto date amendments, totally dust and water proof for submersible duty isolated from the pump by intermediate casing with double mechanical seal in oil chamber and grease packed lubricated bearings and provided with stainless steel thrust bearing plate to with stand non vertical loads with minimum wear and tear. It should also be fitted with a device to take up expansion of water with the heating of motor. The pump set should include water level guards, erection clamps , cable clips and depth gauge etc. and suitable for operation on data given below:-

2

-

-

... More
(A) SITE CONDITIONS:-Location of site:- Soan Khad ____________

-

-

-

... More
The altitude of place in which the motor is intended to work in ordinary service.- 490.00mtrs.

-

-

-

... More
Humidity:- Humid during rainy season

-

-

-

... More
Nature of atmosphere:- Normal

-

-

-

... More
Detail of quality of water:- Raw water

-

-

-

... More
Water free from sand or not:- Free from Sand

-

-

-

... More
Water corrosive or not:- Not corrosive

-

-

-

... More
Turbidity:- 500 PPM

-

-

-

... More
Type of well:- Intake site

-

-

-

... More
Inside dia of well:-

-

-

-

... More
Depth of water during HFL in the well:-

-

-

-

... More
Maximum draw down:-

-

-

-

... More
Depth of well :-

-

-

-

... More
Any other information if required.

-

-

-

... More
(B) OPERATING CONDITIONS:- Type of current:- AC. Three phase

-

-

-

... More
Operating frequency 50 Hz

-

-

-

... More
Rated voltage 400(+/-)

-

-

-

... More
System of earthing if any to be adopted-Double loop earthing as per BIS: 3243-1987 latest with upto date amendments .

-

-

-

... More
Speed of revolution-To be quoted by tenderer

-

-

-

... More
Direction of rotation-To be quoted by tenderer .

-

-

-

... More
No. of working hours per day. -Hours

-

-

-

... More
The maximum temperature of cooling air and water in the place in which the pump set is intended to work in ordinary service - Temperature of place to be specified 20°C to 42°C.

-

-

-

... More
(C) MOTOR:- Ref. to BIS code-BIS: 9283-1979 with upto date amendments

-

-

-

... More
Type of enclosure of motor.-As per BIS:4691-1985 (Latest)

-

-

-

... More
Type of duty : Continuous

-

-

-

... More
Mechanical output in KW-Suitable for driving submersible pumps required for duties specified against pumps. To avoid overloading of motor a margin of about 15-20% may be kept in the rated output to prime Mover.

-

-

-

... More
Class of insulation- Class –B

-

-

-

... More
Max. Permissible temp. Rise of motor reqd. if different from that given in 8 (viii) above. To be specified by the tenderer.

-

-

-

... More
Particulars of test reqd. & where they are to be conducted.-AS per terms and conditions attached.

-

-

-

... More
Particulars as to whether voltage limiting device will be employed.-Oil immersed star delta starter to be installed between bus bar and motor. Shunt capacitor is also proposed to be installed for improving the power factor at site.

-

-

-

... More
Type of motor-As per BIS 9283-1979 or latest.

-

-

-

... More
Details of shaft extension required:-

-

-

-

... More
Break way torque in terms of rated load torque and the corresponding break-way starting current which may be taken from the supply with the starting apparatus in circuit. -Break way torque to be given by the tenderer but the starting current should not exceed 2.5 times of the full load current.

-

-

-

... More
Nature of load and any information regarding the driven machine which has a bearing upon the torque reqd. during the accelerated period, the kinetic energy of the moving parts to be accelerated and No. of starts during a specified period. -To work the pump offered

-

-

-

... More
Where possible fault capacity of the system to which the motor is connected.-The motor should be able to withstand initial current of 2.5 times the rated current for two minutes without suffering damages or permanent deformations.

-

-

-

... More
(D) PUMPS:-Nos. of pumps required.-2 Nos. pumps, both the pumps will work in parallel.

-

-

-

... More
Spare parts required.-For two years normal maintenance as recommended by manufacturer.

-

-

-

... More
Type of drive.-Electric induction motor.

-

-

-

... More
Optional fittings required

-

-

-

... More
Pump Operating conditions Total

-

-

-

... More
Capacity :16.97 LPS for each pump

-

-

-

... More
Total head in meters: 18.52 Mters

-

-

-

... More
Static head :11.51 Meter

-

-

-

... More
Minimum depth of water- Meter

-

-

-

... More
Variation in water level- Meter

-

-

-

... More
Ground level to Max. water level:

-

-

-

... More
Ground level to delivery point - Meter

-

-

-

... More
Pressure in the suction tank.- Meter

-

-

-

... More
Pressure in the delivery tank

-

-

-

... More
Length of rising main- 77 Meter

-

-

-

... More
Dia of rising main - 200.00 mm

-

-

-

... More
Turbidity of water- 500 PPM

-

-

-

... More
Drive type-Electric driven

-

-

-

... More
Limits of total head in which the pump is required to operate.-(-)25% (+)10% of total head at duty points

-

-

-

... More
Suction/Delivery size of pump-To be specified by the tenderer.-To be specified by the tenderer.

-

-

-

... More
Efficiency of pump at -To be specified by the tenderer.

-

-

-

... More
a)     Duty head

-

-

-

... More
b)     ( + ) 10% head.

-

-

-

... More
c)      ( - ) 15% head.

-

-

-

... More
Material of construction-To be specified by the tenderer (manufacturers certificate to be appended.

-

-

-

... More
Supply of direct online starter of reputed make conforming to BIS : 8544 - ( Part-__)1979 or latest with upto date amendments for squirrel cage induction motor (make to be specified by the tenderers) mounted on panel board with magnetic type over load release and gas-pots, time legs, under voltage release & initial oil filing suitable for required HP motor.

2

-

-

... More
Supply of MS. Angle iron steel sheet 16 SWG fabricated floor mounting closed (Almirah type) switch board comprising and capable of mounting the following accessories and with all internal electric connections, duly painted. The drawing of panel board shall be subject to approval of Engineer-in-Charge.

1

-

-

... More
Ammeter AC supply, 100 mm square type auto electric of AE/ L&T Rishab make of suitable capacity for above motor with selector switches conforming to IS:1248 (Part - II)-1983 latest with upto date amendments.

2

-

-

... More
Voltmeter AC supply, 100 mm square type auto electric AE/ L&T Rishab make of 0 - 500 Volts range for above motor with selector switches conforming to IS-1248 (Part - II)-1983 latest with upto date amendments.

1

-

-

... More
ICTP switches with HRC fuses of Havells/L&T/standard /cromption make for required motor of suitable capacity and conforming to IS: 4064 (part - II)1978 latest with upto date amendments.

2

-

-

... More
Bus bar chamber having 3 copper bars of suitable rating for full length of 3 phases and one bar of half the rating of full length for neutral conforming to IS: 8084–1976 and 11354-1985 read with 5578-1985 all latest with upto date amendmentsof suitable rating.

1

-

-

... More
MCB of suitable capacity of Havells/standard/L&T make to feed motors offered by the tenderer conforming to IS: 2516 (Part-II) 1985 latest with upto date amendments with neutral linked under voltage release.

1

-

-

... More
3 phase indicator lamps complete with toggle switches for individual motors conforming ti IS 3452 part I & II latest with up to date amendments of 15 watts.

1

-

-

... More
50 mm dial Hour run meter of CEE / NEE make of suitable range as per relevant IS specifications.

1

-

-

... More
Supply of Kirloskar/ Leader make dia. Cast iron (class 1.0) double flanged sluice valve of one dia higher to delivery of the pump and capable of with standing nominal seat pressure of 10.20 kg/cm2 as per IS: codes.

2

-

-

... More
Supply of Kirloskar /Leader make one dia higher to delivery of the pump Cast iron (class PN 1.0) double flanged Swing check/Reflux/Non Return valve having bye pass arrangement and capable of with standing nominal seat pressure of 10.20 kg/cm2 as per IS : codes.

2

-

-

... More
Providing and laying suitable size copper PVC insulated armoured power 3.5mm core cable conforming to BIS:1554 (Part-I)–1988 of latest with upto date amendments siemen/Havells/National make form meter of HPSEB to MCB and form MCB to Bus bar switch and starter (one cable carrying all three phases) including all other electrical equipment / accessories such as thimbles, flexible pipe solder, nuts and bolts, cable glands, etc. laid in pipes of trenches under floor. The type, size and make will be subject to approval of HPSEB authorities. In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer.

1

-

-

... More
Supply side :- Suitable size

-

-

-

... More
Supply of Leader /Kirloskar make 200 mm dia. Cast iron, Class PN 1.0 double flanged Swing check/Reflux/Non Return valve valve having bye pass arrangement and 200 mm dia. of rising i.e. 200 mm for withstanding nominal seat pressure of 10.20 Kg/Cm 2 as per IS: codes.

1

-

-

... More
Supply of PVC joint less flat water proof cable as per IS: 694-1990 latest with upto date amendments suitable for the pump sets offered from __CB to motor including all other electrical equipment / accessories such as thimbles, flexible pipes solder, nuts and bolts, cable glands etc laid in pipes of trenches under floor. The type, size and make will be subject to approval of HPSEB authorities & in case of non acceptance by HPSEB authorities it shall have to be replaced by tender.

1

-

-

... More
Providing and laying double loop earthing with G.I. wire & G.I plate complete with material such as charcoal, common salt, GI. Pipes, thimbles, nuts and bolts, digging of pits, GI. Wiring and aluminum strips of required capacity conforming to BIS: 3043-1987 latest with upto date amendments for above motors and other electrical equipment’s.

1

-

-

... More
Supply of standard make circular dial pressure gauge 0-11 kg/cm2 range of feibig make with all accessories such s stop cock, copper tubing etc, conforming to IS: 3624-1987 latest with upto date amendments.

2

-

-

... More
Providing and laying delivery pipe 150 mm dia. and common header 200 mm dia.as per IS: 1239-2004 jointed with MS flanges of table -5 as per IS: 6392-1971 (upto a length of 20 mtrs ) including rappers, flanges, rubber gaskets, nuts and bolts and specials upto 5 mtrs away from the outer wall of pump houses as per layout drawings approved by Engineer-in-Charge.

1

-

-

... More
Supply of floor/wall mounted power factor shunt capacitor conforming to BIS:2834-1986 latest with upto date amendments Bajaj / L&T / Asian / cromption make to raise the prevailing power factor at site to 0.95 for direct connection to induction motor individually of suitable rating each including cable of siemens/Havells/National make form bus bar chamber to capacitor and also including L&T/LK/Kilburn make ICTP switches conforming to IS :4064 (Part-II)-1978 or latest with HRC fuses (range to be specified by the tendrerer)

2

-

-

... More
Supply of suitable cable for water level guard.

1

-

-

... More
Supply of supporting clamps.

1

-

-

... More
supply of cable clips of required size.

1

-

-

... More
Erection of all equipment including cost of tees, bends, tapers and any other fittings required as per site conditions and as per direction of Engineer-in-charge.

1

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.