Military Engineer Services Tender
If you want to inquire about any e-tender the Haryana government has posted, Bidassist gives a one-stop solution i.e. being a registered bidder you will find every eprocurement Haryana tender on BidAssist.There is no need to enter all the details on the website of etender.up.nic.in as BidAssist helps you find the specific Haryana etender you're looking for. Read further to learn how to search and bid for etender Haryana.
Costs
EMD
₹ 95,800Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_659958_1Bid Award Id
ViewTender No
CA NO GE(H)-23/2024-25Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
S&F PVC connection 450 mm long suitable for 15 mm bore GI pipe including PTMT nuts on both sides complete all as specified.
210
-
-
S&F 15mm bore, CP Angle valves complete all as specified and as directed. Cat Part No MQT-526KN of ESSCO Jaquar / Somany/ Prayag
174
-
-
M & L for HT cable XLPE insulated, screened PVC bedded, galvanised steel strip armourd cable (heavy duty) 11000 volt grade (Earthed) with aluminium conductor having cross sectional area 95 Sq mm 3 core conforming to IS-7098 (Part-II -1988) laid in trenches/ ducts/ through pipes/ in floors / under roads/ hard standing /along poles and testing complete all as specified.
30
-
-
Supply & fix Cable jointing kit for 11KV (earthed) grade cable for outdoor termination hot shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductror cable for size 95 Sq. mm complete all as specified.
2
-
-
M & L Factory fabricated, pre-stressed concrete poles 11 metre long, 152 mm x 152 mm at top and 152 mm x 260 mm at bottom, class-9 complying with requirements of IS-1678-1978 including necessary painting complete all as specified.
2
-
-
M & L for Air Break gang operated switch suitable for 11000 volt, Triple pole, mechanically operated,mounted on insulator and steel frame, with operating mechanism worked from ground level for current rating upto 200 Amp with drop out fuse unit complete all as specified. NOTE: The gang operated switch shall be of 12 insulator fixed contacts of phosphorous bronze and moving contacts of copper manually operated from ground level using medium grade GI tubing of 25 mm bore with locking arrangements including a set (Set of Three) of drop out fuse assembly, necessary jumper connections of ACSR (mink), clamps all as speciifed for vertically mounting.
1
-
-
M & L Lightning arrestor HT 11KV 65 kA Non linear expulsion type transmission class complete with standard fittings confirming to IS-3070 (Part-I) 1985 complete all as specified.
1
-
-
M&L for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminium paint complete all as specified.
1.5
-
-
Supply & laying or fixing or laid in trench/ducts/through pipes/in floors/under roads/under hard standing/along poles and testing cross linked polytehylene (XLPE) LT cable XLPE insulated, PVC inner sheathed, bedded, galvanised steel strip armoured heavy duty 1100 V grade with stranded aluminium conductor having cross sectional area 300 Sqmm 3.5 core conforming to IS-7098(Part-I 1988) or as per latest amendments.
30
-
-
Supply & laying light grade GI Pipe of size 80 mm bore, ISI marked in trench for cable protection complete all as specified and directed.
7
-
-
M & L for earthing complete with Galvanized Steel earth plate electrode 60cm x 60cm x 6mm thick, buried directly in ground (earth pit not less than 2.25 M deep below ground level) with top edge of the plate not less than 1.5 M below normal ground level, connected to and including GI iron strip of size 32x6 mm flat by means of GI bolts, nuts, and washers, protected by 40mm bore GI light grade ISI marked pipe upto and including test points. Earthing plate shall be surrounded by alternate layers 15cm thick of charcoal or coke and common salt all around bottom and top, 20mm dia GI medium grade pipe for watering and including funnel, wire mesh, PCC chamber pit made with PCC (1:3:6) type C2 (using 20mm graded crushed store aggrgate) including necessary form work, excavation and earth work in any type of soil, returning filling in and disposal of surplus soil to a distance not exceed ing 50 M, pit cover 40 mm thick made with RCC (1:2:4) type B-1 (using 20mm graded crushed store aggrgate) including TMT reinforcement 80 mm dia @ 75 mm C/C both way, MS handle of 12 mm dia, cover rest on MS angle iron frame 40x40x6mm embeded in concrete duly painted with two coats of synthetic enamel paint over a coat of red oxide primer, complete all as specified and as shown in electrical plate No-3 of SSR Part-I and all as directed. Note:- (i) PCC chamber shall be constructed at least 1.5 metre away from the earth electrode and pipe for watering shall be provided in slanting manner. (ii) Protection pipe and earthing strip upto test point from top of the earth plate and further upto body of electrical equipment shall be including in the unit rate of this item. (iii) The earth testing arrangement should be done by the contractor as per direction of Engr-in-charge. No extra payment shall be made on this account.
16
-
-
Supply, installation, commissioning and testing of LT panel box (Kiosk), out door type, platform mounted, suitable for 415 Volts, 50 Hz , 3 phase, 4 wire supply, CPRI approved, factory assembled, having bus bar chamber with insulated Copper bus bar 900 Amps rating installed on porcelain insulators, the panel shall be dust and vermin proof double door made out of 3.15mm CRCA MS sheet, outer & inner and individual compartment for MCCB / MCB & Volt meter / Ammmeter and 50 x50 x 6mm thick angle iron for base frame work, LT panel box should be powder coated including internal wiring with PVC insulated solid copper conductor FRLS cable of appropriate sizes but not less than 4 sqmm, front opening type with approx for cable enty with double door shutter including locking arrangement as per manufacturers with 2 keys complete including and comprising of the following complete all as specified and directed including taking down existing u/s LT panel :- (Main Panel: MP):-
(a) MCCB 4 Pole 630 amps ,415 Volt of breaking capacity not less than 50 KA (Ics=100 % of Icu) with thermally and magnetically adustable - 01 No for incoming.
(b) Aluminium Bus Bar of current rating capacity not less than 1.5 times of incoming MCCB duly sleeve insulated for set of 3 phase, 4 wire system and branch connection of suitable size of outgoing current rating of MCCBs - 01 Set.
OUTGOING
(c) MCCB 4 Pole 250 amps ,415 Volt of breaking capacity not less than 36 KA (Ics=100 % of Icu) with adjustable thermal and fixed magnetic setting - 01 Nos.(d) MCCB 4 Pole 200 amps ,415 Volt of breaking capacity not less than 36 KA (Ics=100 % of Icu) with adjustable thermal and fixed magnetic setting - 01No.
(e) Provision of 01 spare compartment to accomodate 250 Amp MCCB 4 pole.
(f) MCB SPN 10 Amp, 415 V, 10 KA, C-series - 01 Nos (for spare)
(g) Digital Ammeter 0-350 A with selector switch & CTs of suitable capacity - 01 set.
(h) Digital volt meter 0-500 V with selector switch - 01 No.
(j) LED Indicating Lamps R,Y,B - 01 Set
1
-
-
Excavation in trenches in soft/loose soil not exceeding 1.5 mtr wide and not exceeding 1.5mtr depth for foundation etc or for shafts, wells, cesspits, manholes, pier holes etc and getting out complete all as specified.
56
-
-
All as per ser no.16.00 above but exceeding 1.5mtr depth and not exceeding 3mtr depth complete all as specified and directed
32.35
-
-
Returning filling in including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick complete all as specified
46
-
-
Removing excavated soil to a distance not exceeding 50 metere and depositing where directed at a level not exceeding 1.5 metre above the starting point complete all as specified.
11
-
-
M&L for Sand cushioning using clean local tibba fine sand for underground cable 8 cm before laying cable and 15 cm after laying and punned to 18 cm after laying of cable completed all as specified. ( Note: punned thickness shall be considered for payment)
5
-
-
M&L for Factory made unreinforced precast concrete cable covers conforming to IS:5820, class HV type 1 size 300x180x40 mm for cable protection complete all as specified
200
-
-
Factory made unreinforced precast concrete cable covers conforming to IS:5820, class LV type 1 size 250x150x40 mm for cable protection complete all as specified.
200
-
-
Supply, installing, testing and commissioning of level 2 transformer, step down,11/0.433 KV (at no load), out door type , copper wounded, with first filling of transformer oil, outdoor type, 3 Phase 4 wire with off load tappings on HT side to vary secondary voltage within limit of capacity 400 KVA , 3 phase,4 wire,50 C/S, oil immersed naturally cooled with external cooling tubes/fin, delta connection on HT side and star connection on LT side with tapping of HT side to vary secondary voltage at (+/-) 2.5% to (+/-) 7.5% in step including first filling of transformer oil, all fittings and accessories complete all as specified and all as per IS-1180. complete with standard fittings complete all as specified.
1
-
-
Material and labour for construction of Sub station (9Mtr x 9 Mtr) , outdoor type incl necessary excavation, leveling, spreading of greavels etc. complete with comprising the followings :-(a) Platform for Transformer :- M & L for Size 2500X2500X1500 mm (500 mm below GL & 1000 mm above GL) for installation of transformer with, PCC 1:4:8 type D2 as in foundation, brick wall of 230 mm incl plastering with cement Mortar 1:4 incl filling undr floor,s watering and well ramming with soil and 100 mm PCC 1:2:4 coping on the top of platform and two coats of Cement based paint over a coat of Primer incl preparation of newly plastered surfacs. 1.5 Mtr wide ramp on one side of platform to Path with slope of 60 degree (b) S & F Galvanised chainlink fencing of size 100 x 100 x 4mm dia, 2.1 Mtr high with swan neck, angle Iron post of 50x50x5mm with 40x4mm flat Iron fixed with nut & bolts, 10 mm dia roundeded bars as in spacers and two coats of synthetic enamel paint over a coat of zinc oxide along with GI 2 strand barbed wire,PCC 1:3:6 Type C2 as in foundation incl necessary excavation and earth work. (c) M&L for 100 mm thick PCC 1:4:8 Type D2 (Using 40 mm graded stone agg) as in Sub base, 50 mm thick PCC 1:2:4 Type B1(Using 20 mm graded stone agg) incl necessary excavation and earth work. 1 Mtr wide along both side of fencing all around the sub station. (d) M&L for 4 Mtr wide Steel gate with RCC Pillars, two coats of Synthetic enamel paint on steel surfaces over a coat of Zinc oxide primer incl preparation of surface incl necessary excavation and earth work, incl two coats of Cement based paint on plillars. As per TD No. TD/2008/101 sheet No 1/3, 2/3 & 3/3. (e) M&L for PCC path 4 Mtr wide and 10 Mtr long using PCC 1:4:8 Type D2 (Using 40 mm graded stone agg) 100 mm thick as in sub base, 100 mm thick PCC 1:2:4 Type B1 (Using 20 mm graded stone agg) as in paths incl construction and expansion joints and necessary excavation and erath work. (f) Greavels of 40 mm upto 100 mm hight all around the Platform, path and inside the fencing of Sub Station. (g) Danger notice plate 02 Nos on the gate & fencing of Sub Station
1
-
-
Shifting of transformer from plinth structure to plinth, Isolating 11 KV HT supply from the substation and earth the complete system properly, disconnecting complete electric system of the transformer from HT and LT side including earthing strips, disconnecting removing taking down out door transformer of capacity upto 400 KVA from plinth structure and refixing, installing, commissioning & testing the transformer on plinth complete all as specified directed by Engineer -in-charge.
Note:- (a) The rates quoted is deemed to be included for hydra, T&P and man power and other items required for sifting of transformer.
(b) Plinth work shall measured and paid separetely under items of sch of work here-in-after.
1
-
-
Material & Labour for jumper/bus bar made of ACSR conductor of existing size on HT two/four/six pole structure including bus bar with PVC sleeve , lugs , nut bolts and washers complete all as directed.
0.25
-
-
Material & Labour for fixing pin type,prorcelain,vitreous, white brown or green insulator including one galvanised mild steel spindle,two galvanised iron washer and one galvanised nut,100 mm height, 65 mm dia for 1100 volts grades complete all as directed.
3
-
-
M&L Anticlimbing device spikes type fabricated out of MS bars (round, square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit cross section of the pole and painting with two coat of aluminium pain over a coat of primer.
0.25
-
-
M&L for point wiring for 15 Amp independent socket controlled by one 16 Amp switch from MCB DB with 2.50 Sqmm single core PVC insulated and unsheathed multistranded copper conductor FRLS cable 1100 Volt grade including 2.50 Sqmm single core PVC insulated and unsheathed multistranded copper conductor FRLS cable 1100 Volt grade as continuous earth wire in green colour to common earth and connected to earth dolly laid/drawn into and including concealed PVC rigid non metallic conduit of dia not lesss than 20mm dia or suitable size medium grade (ISI marked) with all fittings such as tees, bends etc including sunk type modular pressed steel box covered with modular cover plate and frame for housing switch, socket , fan regulators etc complete, all as specified & directed. (Note :- Switches,sockets etc shall be measured and paid for separately under appropriate items of BoQ' ).
113
-
-
Supply and fixing modular type switch 1 way 16Amp, 230Volts 2 module complete all as specified and directed
105
-
-
Supply and fixing modular type socket 6Amp/16 Amp - 6 pin combined 2 module 230 volts AC complete all as specified and directed
105
-
-
S & F MCB SP, 20 Amps 240 Volts , 'C' curve, 10 KA, IS-8828 marked for fixing in DB complete all as specified & directed.
105
-
-
Supplying,installing,testing & commissioning, storage water heater (geyser), 25 litres and 2 KW capacity, standing loss less than 0.562 kwh per day for 45 C difference of temperature as per IS 2082 ( five star rated as per BEE), reheating time less than 60 minutes, mixing factor less than 20%, shock proof high density PUF insulation body material, glass lined inner tank material having warranty 5 years minimum for tank material, 4 years on heating element and 2 years on other spare parts including comprising following fittings:-
(a) Capillary type thermostat.
(b) Digital display unit.
(c) Thermal cutout.
(d) Multifunction valve
(e) Flexible cable of suitable length with three pin plug 16 A capacity.
(f) Drain plug
(g) Fusible plug fitted on the crown of water heater with operating temperature between 40 degree centigrate to 75 degree centigrate including fixing by grouting and fastener complete all as specified and directed.
113
-
-
Supply, laying, jointing and testing XLPE insulated armoured heavy duty LT under ground electric cable with aluminium stranded conductor 1100 Volt grade cross sectional area 16 sqmm 4 core laid in trenches/ducts, through pipe, under floors or roads/ along poles etc including taking out existing u/s cable complete all as specified.
Note : Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.
147
-
-
Supply and laying double wall corrugated pipe (DWC) conforming to IS 19430 Part - I of size 50mm outer dia and 38 mm inner dia with coupler complete all as specified and as directed
142
-
-
Material and labour for 16 mtr long High galvanised mast (in two sections) 360mm Bottom 150mm top 4/3 mm section thickness PCD 460 mm with base plate of 560x25 mm light suitable for 9 lantern symmetrically fitted along with their control gear and having two point suspension system with stainless steel wire rope of 6mm dia 97/19 guage and double drum winch will luminaire mounting arm, pulley assemble, aviation obstruction light, lightining arrester spike including RCC foundation as per height complete all as specifeid and directed.
Note :- the scope includes raising & lowering system (R&L), trailing cable, power tool, feeder pillar for switching operation of luminaires, lightning finial and aviation obstruction light. The R&L system will comprise of double drum winch, SS wire rope not less than 6mm, head frame and lantern carriage. The job also includes RCC foundation work as per manufacturer's instructions suitable for 16 mtr long Hight mast light.
2
-
-
S&F high mast light fitting LED flood light fitting of cap 120 Watt, with IP 66 protection and efficacy _ 110 /120 LPW 240 Volts, energy saving, environmental friendly, long life, exclusive innovative, die cast aluminium flood light suitable for highlighting architectural facade and general purpose lighting complete with accessories, pre-wired upto a terminal block and mounting attachment complete all as specified and directed.
Make: Cat Part No TFS 504-120-57-60D-HL2-GL-NSG of Crompton ,Cat Part No SLE FL 120W IP66 LMS NEO of Surya , Havells, Orient Cat Part No LFLDSLM120XC of Jaquar
18
-
-
Supply and fix of outdoor mounted feeder pillar 32 A TPN MCB incomer, single dial time switch, 25 TP contactor for the automatic switching of luminaries, power tool control with 2 Nos 9A contractors and riase lower push button, incoming 35 Sqmm and outgoing 16 & 2.5 Sqmm terminals.
2
-
-
S&F sheet metal enclosure Double pole and neutral with a two pin and earth plug and socket complete with and including one 20 Amp SPN MCB 'C' curve complete all as specified.
8
-
-
S&F CPVC pipes of bore size 16mm) SDR 11 & Plain CPVC SDR 11 fittings laid on wall / ceiling or laying in floor complete all as specified with all fittings / connections and making good to required surfaces by using white cement / masonry works complete all as specified and directed.
Note :- Rates quoted shall deemed to be included for making hole / nitch for replacement of pipe and making good distrubed surfaces to match with existing surface and finish all as directed.
75
-
-
S&F 15mm bore stop valve, cast copper alloy, screwed down, high pressure with crutch or butterfly handle screwed both ends for iron pipe or for unions.
16
-
-
S&F 15 mm bore bib tap, cast copper alloy, chromium plated, fancy type with capstan head, screwed down, screwed for iron pipe or for brass ferrule.
8
-
-
S&F Sub main wiring with two single core cable PVC insulated unsheathed of copper multi stranded conductor FRLS cable of size 6.00 sqmm, 1100 votls grade drawing through and EXISTING concealed conduit 25 mm dia medium duty including acessories such as Tee, bend, Elbow etc, ISI marked with and including PVC insulated 6.00 sqmm unsheathed multistranded FRLS copper conductor cable for earth continuity and connected to common earth dolly including cutting chasing of wall, if required and making good disturbed surface in CM (1:3) and finishig the surface to match with existing surface, etc complete all as specified and directed including taking down old unserviceable submain wiring. Note:- Two lengths of 6.00 Sqmm cable, one length of 6.00 Sqmm cable and one length of PVC conduit will be measured as one length.
160
-
-
S&F in replacement sheet metal enclosure distribution board SP&N, 4 way, double door, powder coated, protection class IP-42, suitable for mounting MCB, DBs confirming to IS-13032, IS-8632, BS-5484 with min 200 Amp rating copper bus bar, complete all as specified & directed.
4
-
-
S&F MCB SPN, 32 Amps 240 Volts , type 'C' curve, 10 KA, IS-8828 marked fixing in DB complete all as specified & directed. Note :-Make of MCB shall be same of that DB.
4
-
-
S&F MCB SP, 6 to 32 Amps 240 Volts , 'C' curve, 10 KA, IS-8828 marked fixing in DB complete all as specified & directed. Note :-Make of MCB shall be same of that DB.
8
-
-