Military Engineer Services Tender

If you want to inquire about any e-tender the Haryana government has posted, Bidassist gives a one-stop solution i.e. being a registered bidder you will find every eprocurement Haryana tender on BidAssist.There is no need to enter all the details on the website of etender.up.nic.in as BidAssist helps you find the specific Haryana etender you're looking for. Read further to learn how to search and bid for etender Haryana.

Military Engineer Services - MES Tender

Works
Electrical Generators And Transformers
Electrical and Electronics
Eprocure
Opening Date3 Sep 2024
Closing Date12 Oct 2024
Tender Amount₹ 17,15,000 
Notes
Download

Costs

Summary

Cwe/af Amb/amb-33/2024-25 Repair / Maint Of Ht Cable, Transformers, Vcbs And Connected Items At Afs Patiala Under Ge (af) Ambala

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
REPAIR / MAINT OF HT CABLE, TRANSFORMERS, VCBs AND CONNECTED ITEMS AT AFS PATIALA UNDER GE (AF) AMBALA
REPAIR / MAINT OF HT CABLE, TRANSFORMERS, VCBs AND CONNECTED ITEMS AT AFS PATIALA UNDER GE (AF) AMBALA
REPAIR / MAINT OF HT CABLE, TRANSFORMERS, VCBs AND CONNECTED ITEMS AT AFS PATIALA UNDER GE (AF) AMBALA
Report Missing Document

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Removal of excavated soil to a distance not exceeding 50 mtr & depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified & directed.

23.91

-

-

... More
M&L double wall corrugated (DWC) HDPE pipe, outer dia 120mm, having corrugations on the outer surface and plain at inner surface, confirming to IS 14930(Part I & II) as in trenches/under road/under floor including cutting road/floor and making good wherever necessary or fixed to wall/pole with fixing arrangement for cable protection complete all as specified & directed. Note: Excavation & Earth work shall be measured & paid seperately.

410

-

-

... More
M&L boring/augering of holes under road, pavement, taxi track, hardstanding for passing/crossing pipes/cables upto size 80mm dia/bore at suitable depth (not below than 600mm) by any means using necessary machinery / equipments complete without damaging the surface and removing excavated soil /material to a distance not exceeding 50mtr including supply & inserting GI pipe 80mm bore medium grade complete all as specified & directed. Note: One RM of boring & one RM of GI pipe shall be measured as one unit.

12

-

-

... More
M&L plain cement concrete (PCC) 1:4:8, type D-2, using 40mm graded mechanically crushed stone aggregates as in foundations, filling and mass concrete etc. complete all as specified & directed.

0.22

-

-

... More
M&L plain cement concrete (PCC) 1:3:6, type C-2, using 40mm graded mechanically crushed stone aggregates as in coping to pole etc. including necessary formwork to exposed surface finished even & smooth complete all as specified & directed.

2.39

-

-

... More
M&L plain cement concrete (PCC) 1:2:4, type B-1, using 20mm graded mechanically crushed stone aggregates as in coping to pole etc. including necessary formwork to exposed surface finished even & smooth complete all as specified & directed.

0.49

-

-

... More
Taking out / down faulty, unserviceable 11KV HT UG cable from trenches/duct/ HT poles, nominal cross sectional area from 95 sqmm to 120 Sqmm including disconnecting of cable and taking out PCC covers of any description complete all as specified & directed. Notes: (i) Excavation & Earth work shall be measured & paid separately. (ii) Serviceable cable covers will be kept aside for re-use and the unserviceable one shall be credited to contractor.

442

-

-

... More
Supply, laying, jointing, testing & commissioning heavy duty, HT 11 KV ( E), XLPE insulated cable with aluminium conductor, screened with extruded semi conducting layer, insulation screening with copper tape cover laid up with PVC (ST-2) extruded inner sheathed GI strip armoured PVC (ST-2) out sheathed, ISI marked confirming to IS-7098 (Part-II), Size cross sectional area 95 Sqmm & 3 core laid as in trenches/pipes/ducts or fixed along poles/wall/equipment etc. complete all as specified & directed.

275

-

-

... More
Description all as per BOQ item No.11.00 here-in-above but Size cross sectional area 120 Sqmm & 3 core.

167

-

-

... More
S&F in repair Cable jointing kit for 11 KV (Earthed) grade HT cable for indoor termination heat shrink type joint complete with jointing material & accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm to 185 Sqmm complete all as specified & directed.

1

-

-

... More
S&F in repair Cable jointing kit for 11 KV (Earthed) grade HT cable for outdoor termination heat shrink type joint complete with jointing material & accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm to 185 Sqmm complete all as specified & directed.

1

-

-

... More
S&F in repair Cable jointing kit for 11 KV (Earthed) grade HT cable for indoor termination heat shrink type joint complete with jointing material & accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm complete all as specified & directed.

2

-

-

... More
S&F in repair Cable jointing kit for 11 KV (Earthed) grade HT cable for outdoor termination heat shrink type joint complete with jointing material & accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm complete all as specified & directed.

2

-

-

... More
S&F in repair Cable jointing kit for 11 KV (Earthed) grade HT cable for straight through heat shrink type joint complete with jointing material & accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 Sqmm complete all as specified & directed.

1

-

-

... More
S&F in repair Cable jointing kit for 11 KV (Earthed) grade HT cable for straight through heat shrink type joint complete with jointing material & accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified & directed.

2

-

-

... More
S&F cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed duly painted with two coats of aluminium paint over & including one coat of zinc oxide primer including dismantling of old unserviceable cross arms as existing complete all as specified & directed.

0.5

-

-

... More
S&F Disc type insulator, porcelain, vitreous 145mm high and 255mm dia ball and socket type, white, brown or green, Two-in-series' assembly for tension with tension clamps for conductors, working pressure 11000 volts complete all as specified & directed.

2

-

-

... More
Disconnecting electric connections of underground HT cable,11 KV, any size/type, from both sides and locating/detecting of pin point fault in cable with fault locating machine comprising impulse generator, acoustic fault locator & reflectometer (Laptop based) in the entire length with modern fault detector equipment by expert Engineers including reconnecting & commissioning the cable to make it functional complete all as specified & directed. Notes: (i) The work will be executed after obtaining proper shutdown from main power house after liasoning with Engineer-in-charge. (ii) The fault location machine / equipments shall be arranged as early as possible by contractor but not later than 12 hours after intimation from AGE/JE concerned , failing which a penalty of Rs. 500/- every 12 hours shall be leived. (iii) Excavation and Earthwork shall be measured & paid seperately.

2

-

-

... More
S&F in repair cable route indicator made of mild steel plate of size 100mm x 150mm, 6mm thick welded with MS angle 40mm x 40mm x 4mm, one meter long, "Cable HT" embosed on MS plate, grouted in PCC 1:2:4 type B-1 using 20 mm graded mechanically crushed stone aggregates block of size 300 mm x 300mm x 300mm as in foundation including necessary form work complete all as specified & directed. Notes: (i) Necessary earth work & PCC work including form work included in quoted rates. (ii) Steel surface shall be painted with two coat of synthetic enamel / aluminum paint over & including one coat of zinc oxide primer and quoted rated are deemed to be included for this aspect.

8

-

-

... More
S&F in replacement 11KV Drop out fuse(set of three) single pole 200 Amp with insulators, barrel and suitable rating of fuse element as per site requirement complete all as specified & directed.

2

-

-

... More
Supply, fixing & testing in replacement, single pole zinc oxide (gap less surge type), heavy duty, station class, self supporting outdoor type lighting arresters having rated voltage 09 KV (RMS), discharge current 10 KA insulation level 28/75 KV/KVp (peak) suitable for rated system voltage of 12 KV supply system with maximum continuous operating voltage not less than 7.65 KV (RMS) with highly non linear ceramic resister made of zinc oxide in hermetically sealed container, complete with metal base, base insulator and suitable terminals for ground connections and pressure relieving arrangement complete all as specified & directed. Note: The lighting arresters shall be of set of three

3

-

-

... More
S&F in replacement switch Air break gang operated, triple pole, for horizontal or vertical operation, mechanically operated, outdoor type, mounted on 12 insulators and steel frame with operating mechanism & operating rod of 25mm bore, heavy grade GI pipe from ground level with & including locking arrangement & minumum 02 Nos. eye hook, 400 Amps current rating 11000 volts working pressure including making electrical connections to make it functional after testing complete all as specified & directed.

2

-

-

... More
M&L in repair danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour, fixed with MS clamps, bolts and nuts on pole, for HT(11/33 KV) of 25cm x 20cm size confirming to IS 2551 complete all as specified & directed.

8

-

-

... More
M&L true vertical steel tubular, swaged welded pole conforming to IS-2713 part II , type 410 SP 55, 11 metre long complete with mild steel base plate of 6 mm thick of size 300 X 300 mm, finial taper plug, cap, bolts, nuts, washer and screws hole of required size and Nos. for fixing cross arms including painting externally with two coats of aluminium paint over & including one coat of zinc oxide primer for exposed surface and two coats of black bituminious paint for embeded portion in concrete as well as throughout internally including provision of blue & orange(AF pattern) colour strips with fluorescent paint upto 1.5 mtr height & nubmering of pole including dismantling / taking down of existing old steel pole complete all as specified & directed. Notes:- (i) Demolition of PCC as in coping of pole included in quoted rate. (ii) Excavation, earth work & new PCC shall be measured & paid separately.

4

-

-

... More
Supply, installation, testing & commissioning of battery bank made out of MS Sheet 1.6 mm (minimum) thick and angle iron frame including two coats of synthetic enamel paint over & inlcuding one coat of red oxide primer on steel surfaces with 12 Nos of maintenance free batteries each of 2 Volts and 100 AH complete connected in series including powder coated Battery charging panel with voltmeter, ammeter and variable type rotary transformer ( automatic battery charging system ) suitable for input of 230 Volts, AC, 50 Hz, single phase and having adjustable charging rate upto 100 Amp at 24 volt DC complete including copper control cable interconnection etc. including dismantling of complete battery bank alongwith batteries complete all as specified & directed.

1

-

-

... More
M&L Servicing/checking/setting of Relay of 11KV SF6 breaker and calibration by primary injection and secondary injection including Service Cleaning of 11KV CB Limb, Cleaning & Lubrication of Mechanism, Cleaning & Crack observation of Porcelain Parts, Tightness Check of Electrical Control Wiring, checking of SF 6 Gas pressure(fill if required) including IR Testing, Coil Resistance Test, Operation Test Auto/Manual, Space heater and Indication Lamp Check complete all as specified & directed. Notes :- (i) Minor parts shall deemed to be included in quoted rates however major Spare parts shall be measured & paid seperately. (ii) The above job will be carried out at perodicity of six month (i.e first time within one month from the date of commencement of work and second time within seven months) (iii) Two times serviceing & calibration of each SF6 breaker shall be considered as 'One unit'. (iv) Payment of this item will be made after successful completion of second time serviceing & calibration, however a partial payment after first time serviceing & calibration could be made at the discretion of GE.

5

-

-

... More
S&F in replacement IDMT relay with numerical relay for VCB tripping system (3 OC + 01 earth fault & high set instantaneous protection in single unit) suitable for operation on 24 volt to 110 volt DC all as per model No CGI14N of CG or equivalent in Seimens/Hager/Schneider complete all as specified & directed. Note :- Existing relay are IDMT type electromagnetic type hence any modification in the wiring & panel sheet enclosure required is deemed to be included in the quoted rates.

1

-

-

... More
S&F in replacement Motor 230 Volts AC charged independent spring closing / tripping trip free operating mechanism with manual closing tripling push buttons and mechanical breaker “closed / open” spring charged / discharged indication complete all as specified & directed.

1

-

-

... More
S&F in replacement Electrical releases coil, 24 volts DC complete all as specified & directed.

1

-

-

... More
S&F in replacement Shunt trip coil, 24 volts DC complete all as specified & directed. .

1

-

-

... More
S&F in replacement Auxiliary switch complete all as specified & directed. .

2

-

-

... More
S&F in replacement 230 Volts AC single phase 80 watt rated strip type heater with toggle switch and thermostat complete all as specified & directed.

5

-

-

... More
S&F in replacement Tri-vector energy meter class 0.5 with RS 485 Port complete all as specified & directed.

1

-

-

... More
S&F in replacement11KV metering CT, single core single ratio epoxy resin cast copper wound primary type with rate burden 5VA, class 0.5S confirming to IS-2705 complete all as specified & directed.

2

-

-

... More
S&F in replacement Resin cast CT of ratio 100-50/5+5 class 1.0, 5P, 10 burden 15VA as per relevant IS complete all as specified & directed.

1

-

-

... More
S&F in replacement Potential transformer(set of three) ratio three single phase 11 KV/rt 3/110V/rt 3 class 0.5-3, with burden 50 VA and insulation level 28 / 75 conforming to IS – 3156 complete all as specified & directed.

1

-

-

... More
S&F in replacement indication lamp (LED type) Red/Yellow/Blue/Green colour suitable for VCB etc. complete all as specified & directed.

9

-

-

... More
M&L in replacement isolating contact assembly (set of 6 Nos.) suitable for VCB 11000 volts, 400/630 Amps rating ,13.1 KA including necessary connection & testing as per existing make and specification, complete all as specified & directed

1

-

-

... More
M&L in replacement breaker phase barrier suitable for VCB 11000 volts, 400/630 Amps rating 13.1 KA including neccesary connection and testing as per existing make and specification complete all as specified & directed .

1

-

-

... More
M&L in replacement Earthing contact assembly suitable for VCB 11000 volts, 400/630 Amps rating 13.1 KA including neccesary connection and testing as per existing make and specification complete all as specified & directed .

1

-

-

... More
M&L in replacement drive link assembly with adjuster(set of three) suitable for VCB 11000 volts, 400/630 Amps rating 13.1 KA including neccesary connection and testing as per existing make and specification complete all as specified & directed .

1

-

-

... More
S&F in replacement digital ammeter meter with shunt suitable for VCB 11000 volts , 400/630 Amp complete all as specified & directed .

1

-

-

... More
S&F in replacement digital frequency meter with shunt suitable for VCB 11000 volts , 400/630 Amp complete all as specified & directed .

1

-

-

... More
S&F in replacement TNC switch as per existing make & specifications suitable for VCB 400/630 Amps,11 KV including neccessary connection & testing complete all as specified & directed.

1

-

-

... More
S&F in replacement closing coil assembly as per existing make & specifications suitable for VCB 400/630 Amps,11 KV including neccesarry connection & testing complete all as specified & directed

1

-

-

... More
S&F in replacement Triping coil assembly as per existing make & specifications suitable for VCB 400/630 Amps,11 KV including neccesarry connection & testing complete all as specified & directed

1

-

-

... More
S&F in replacement Ammmeter selector switch four step one off position as per existing make & specification suitable for VCB 400/630/800 Amps, 11 KV including necessary connection & testing complete all as specified & directed

1

-

-

... More
S&F in replacement Voltmeter selector switch four step one off position as per existing make & specification suitable for VCB 400/630/800 Amps, 11 KV including necessary connection & testing complete all as specified & directed

1

-

-

... More
S&F in replacement LV porcelain bushing of transformer(set of four) 1.1 KV with metal parts brass as per IS 3347 (Part III) and 4 Nos hexagonal nuts, upto 160 KVA transformer complete all as specified & directed.

1

-

-

... More
S&F in replacement HV porcelain bushing of transformer(set of three) 12KV /250 Amp with metal parts brass as per IS 3347 (Part III) and IS 2009 complete all as specified & directed.

1

-

-

... More
Shifting of defective transformer upto 160 KVA from sub station to MES yard and installation of serviceable transformer from other location, placing on foundation / floor, connecting HV / LV and earthing strip complete all as specified & directed. Notes :- (i) Distance of substation to MES yard is not more than 5Km. (ii) All petty parts including nut, bolts, lugs for cable and any other minor works and material required for re-assembling are deemed to be included the rate quoted. (iii) The rate for transport and lifting of transformer by crane deemed to be included in the rate quoted. (iv) Oil testing of transformers deemed to be included in the rate quoted.

1

-

-

... More
De-hydration & filtration of transformer oil by using dehydration and filtration plant by means of Ultra High Vaccum double stage machine to remove impurities from oil such as moisture, dirt, air and other gases at site of installation in running condition of transformer including testing the oil before and after centrifuging from top and bottom of transformer to achieve the Break Down Voltage(BDV) value minimum 60KV at 2.5mm gap between electrode withstand for one minute including filling in transformer of any capacity complete all as specified & directed. Notes:- (i) Dehydration will be carried out at site in presence of MES rep and contractor will submit the dehydration report of each transformer. A record should be maintained by the contractor and should submit with RAR. (ii) Oil Test value record register shall be prepared in presence of AGE/JE and handed over the register to sub division on completion of work.

2000

-

-

... More
Supply & filling transformer oil of dielectric strength not less than 60KV to comply with IS-335 of 1993 complete all as specified & directed.

250

-

-

... More
Preparation of external surfaces of existing transformer of capacity 63 KVA to 160 KVA for painting including fins/radiators, removal of all existing paint/ rust/oil/grease and unwanted material and applying two coats of synthetic enamel metallic paint, smoke grey, by means of spray gun at site of installation of transformer including writing SM/MES number, capacity of transformer etc with black synthetic enamel paint complete all as specified & directed.

10

-

-

... More
Supply & filling silicagel in granular form for transformer's air breather of capacity 63 KVA to 160 KVA complete all as specified & directed.

10

-

-

... More
S&F in repair transformer top cover gasket for capacity upto 160 KVA complete all as specified & directed.

1

-

-

... More
Supply only electrical rubber hand gloves ( Kamfet class-2 , Electrical Insulated Hand gloves), Proof Voltage 20000 Volt, Working Voltage 17000 Volt, as Per IEC 60903-2014, Red Colour, Size 8,9,10,11 / Length 360mm complete all as specified & directed.

2

-

-

... More
Supply only fibre glass discharge rod suitable for 11 KV working pressure including all accessories complete all as specified & directed.

2

-

-

... More
Supply & laying in replacement fire retardant/exinguishing Electric insulated mat 2.5 mm(INSULATICA 2000) 2.5mm thick + 10% conforming to IS:3043, IS:5216 (Part1, 2 & 3), IS:8437 and IEC 479 pub-1, tested for breakdown strength, Tensile/ Elongation ageing properties, insluation resistance, effects of acid, alkaline, diesel & transformer oil, leakage current tests, fire test etc having min width of 1000mm +20mm. All allied materials such as pu-resin, chemical bound (Hardener), Spl PVC adhesive, liquid primer etc of required quantity to complete the job as per site requirement for all voltage not exceeding 11 KV system complete all as specified & directed.

2

-

-

... More
M&L 25mm x 4mm galvanized iron(GI) strip as earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other situation for loop earthing etc. complete all as specified & directed.

20

-

-

... More
Dismantling and taking out /down existing unserviceable GI strip as in earth continuity conductor or main earthing lead complete all as specified & directed.

20

-

-

... More
M&L earthing complete with galvanized steel earth plate electrode 60 cm X 60 cm, 6mm thick buried vertically in ground to depth not less than 2.25 mtr below ground level, with top edge of earth plate not less than 1.5 mtr below ground level, connected to GI earth lead strip 32mm x 6mm upto 7.5 mtr long by means of bolts, nuts, check nuts and washers of galvanized iron and connection to earthing test point & earth dolly & watering pipe GI 20 mm bore medium grade 1.5 mtr long including protection pipe GI light grade 40mm bore upto 7.5 mtr long, wire mesh, funnel,lugs, salt, charcoal dust, excavation & earthwork in any type of soil and refilling, pit chamber with PCC 1:3:6 type C-1 using 20 mm graded mechnically crushed stone aggregates , RCC 1:2:4 type B-1 using 20 mm graded mechnically crushed stone aggregates pit cover slab 50 mm thick reinforced with 8 mm dia TMT bars @ 15 cm c/c both ways including necessary form work all as shown in electrical plate No 3 of MES SSR Part-I, including testing on completion at site including dismantling/taking out/down of old existing earthing any type complete all as specified & directed. Notes:- (i) On testing if the desired earth resistance(i.e. less than 3 ohm) is not obtained, earthing will be generated at No extra cost, till the desired earth resistance is obtained. (ii) The chamber shall be constructed atleast 1.5 mtr away from the earth electrode.

2

-

-

... More
M&L testing of 11/0.433KV transformer at site, checking of breather and other accessories, dielectric strength test of oil, insulation registance test of winding, Earth resistance test of connected earthing of transformer and submitting report complete all as specified & directed . Note: The testing will be carried out from the approved agency of PSPCL / UHBVN / State Electricity Board

5

-

-

... More
M&L preparation of surfaces and painting of steel tubular poles upto 1.5 mtr height from pedestal, with two coats of synthetic enamel paint in 30 cm wide strip (five strips), painting pattern shall be as per Airforce colour code including painting of pole coping with black paint and writing pole numbers with white paint on black circular base including marking of HT/LT with Painting of pole cross arms bracket with two coats of aluminum paint over & including one coat of red oxide primer complete all as specified & directed.

20

-

-

... More
Disconnecting HT/LT cables & Earthing connections of burnt /defective transformer of capacity 63 KVA to 160 KVA, 11KV/433 volts, 3 phase, any make, from 2/4pole structure / floor/platform mounted / CSS, taking down from site of installation carefuly & transporting the same to workshop for repair, opening, draining out transformer oil, dismantling complete & taking out core assembly & removing burntout windings, cleaning /washing of tank removing the dirt sludge and sticky materials from all parts of the transformer including core tank and cooling tubes, removal of damaged parts, dehydrating the core assembly, re-assembling after replacement of damaged parts of the transformer after repairs, making connections and filling dehydradated/fresh transformer oil and testing for all type of tests(routine test & full load test) including transportation back & reinstallation/connection of transformer at site complete all as specified & directed. Notes:- (i) Minor parts shall deemed to be included in quoted rates however major Spare parts shall be measured & paid seperately. All parts/components replaced shall be identical to those specified by original manufacturer. (ii) Taking out old/burnt winding of transformer included in quoted rates, however new winding shall be measured & paid separately. (iii) The draining of old transformer oil is deemed to included in quoted rates but filling new transformer oil and dehydration & refilling of old transformer oil shall be measured & paid separately.

1

-

-

... More
M&L winding of transformer any capacity at HT/LT side with super enamelled copper wire of gauge & weight as exists, varnishing & drying by vaccum impregnating, provinding insulating material, fixing the coil in the position in core assembly and making connection as per original pattern complete all as specified & directed.

210

-

-

... More
S&F in replacement PVC air breather of make & specifications as exist at site filled and with & including silica gel suitable for upto 100 KVA capacity transformer complete all as specified & directed.

1

-

-

... More
Description all as per BOQ item No. 70.00 here-in-above but exceeding 100 KVA & upto 163 KVA capacity transformer.

1

-

-

... More
S&F in replacement temperature gauge 0-100 degree celcius range round type complete all as specified & directed.

2

-

-

... More
For Credit Schedule, refer tender documents. The amount of credit schedule shall be deducted from total quoted amount of BOQ to arrive contract sum.

-

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.