Military Engineer Services Tender

Search for the latest Gujarat tenders online related to civil works, road & transport, pipelines and more easily here on BidAssist. Here you can get any and every tender that is posted on the eProcurement Gujarat website, minus the clutter. No need for a tender ID, as on BidAssist, you can view any Gujarat tender by merely typing Gujarat in the search box.

Military Engineer Services - MES Tender

Works
Electrical and Electronics
Electrical Works
Eprocure
Opening Date19 Dec 2023
Closing DateCancelled
Tender Amount₹ 38,00,000 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
Removing of excavated materials not exceeding 50 metre and depositing where directed by Engr in Charge at a level not exceeding 1.5 metre above the starting point complete all as specified and as directed by Engr-in-charge.

109.6

-

-

... More
Supplying and laying unreinforced precast cement concrete cable covers, Class LV, Type- 1, Flat, size 250 mm x 150 mm x 40 mm in trenches for cable protection, embossed with "LT 1100 VOLTS ELECTRIC" on the top surface complete all as specified and as directed by the Engineer - in - Charge.

4500

-

-

... More
M & L clean dry river sand in trenches/ducts for cushioning to cable, 8 cm in depth before laying the cable and 15 cm in depth after laying the cable complete all as specified. Note:- Punned thickness shall be measured and paid.

60

-

-

... More
M & L for Cement Concrete 1:4:8 (40mm graded aggregate) as Lean Concrete in Foundation of Poles etc, including Formwork (as if required), complete all as specified and as directed by Engr-in-charge.

10

-

-

... More
M & L for Cement Concrete 1:3:6 (20 mm graded aggregate) as in coping of pole etc including form work & finishing the surfaces even & smooth with out using extra cement complete all as specified and as directed by Engr-in-charge.

8

-

-

... More
Dismantling unserviceable PCC poles of any description and any size including demolition of Cement Concrete (as/ if required) and made good disturbed Ground complete all as specified and as directed by Engr-in-charge. Note : Unsv Poles will be dismantled at Ground Level and disturbed ground will made good as directed for which Earthwork, demolition of cement concrete, etc. will not be measured and paid separately.

15

-

-

... More
Taking down existing old extg unserviceable LT UG cable of any description and size complete all as specified and as directed by Engr-in-charge.

855

-

-

... More
S & F for Prestressed concrete poles of 9.0 meter long having 102 mm x 152 mm at top and 102 mm x 289 mm at bottem, class 10 with necessary excavation, foundation and coping including applying two coats of of exterior weather proof paint (Cement based paint) of approved colour to pole and to MS cross arms, cable protection pipe, brackets etc with two coats of Aluminium Paint over a coat of red oxide primer including Synthetic enamel Painting in alternate lines of Yellow & Black Strips min of 6 Nos (each Strip 200 mm wide) at bottom of polecomplete all as specified and as directed by Engr-in-charge. Note:- Earthwork, Cement Concrete etc. will be measured and paid under approprite Items.

10

-

-

... More
S & F for PVC/ Fibre Separator for LT Lines 1100 Volts OH Conductor 4 Wire system for horizontal spacing of Conductor, fixing with Nuts, Bolts, Washers, etc., complete all as specified and as directed by Engr-in-charge.

30

-

-

... More
Supply & Laying, testing & commissioning of LT UG cable XLPE sheathed PVC insulated,screened PVC bedded, galvanised steel strip of wire armoured electric power cable heavy duty with stranded aluminium conductor 1100 volts grade, laid in trenches/ surface of wall/ in GI pipe along with pole for connection to OH lines,including brass cable glands,clamps,etc as required of following sizes complete all as specified :-

-

-

-

... More
(a) 4 core x 16 Sqmm

200

-

-

... More
(a) 4 core x 25 Sqmm

280

-

-

... More
(b) 3.5 core x 35 Sqmm

200

-

-

... More
(c) 3.5 core x 50 Sqmm

175

-

-

... More
Supply, fixing, connecting and testing MCCBs in existing LT Panel of the following capacity, 415V, Adjustable thermal magnetic setting with extended terminals type, complete incl removal of exiting unsv all as specified and directed :-

-

-

-

... More
(a) 200 Amps, 4P, 35 KA.

2

-

-

... More
(b) 160 Amps, 4P, 35 KA.

3

-

-

... More
(c) 125 Amps, 4P, 25 KA.

3

-

-

... More
(d) 100 Amps, 4P, 16 KA.

6

-

-

... More
(e) 63 Amps, 4P, 16 KA.

6

-

-

... More
Dismantling Insulators like Pin type, Shackle type from existing Electric Poles of any description and any size complete all as specified and as directed by Engr-in-charge.

62

-

-

... More
Dismantling ACSR Conductors from the Disturbed Span including Line Spacer, etc., complete all as specified and as directed by Engr-in-charge.

6

-

-

... More
Dismantling Cross-Arms of Mild Steel Channel or Angle Sections, etc, including Mild Steel Bolts, Nuts, Washers, etc., complete all as specified and as directed by Engr-in-charge.

1

-

-

... More
Dismantling Earth Wire, Cradle Guarding, etc, complete all as specified and as directed by Engr-in-charge.

1

-

-

... More
S & F Insulator Pin type Porcelain, Vitreous, White, Brown or Green including one Galvanised Mild Steel Spindle, Two Galvanised Iron Washers and One Galvanised Iron Nut, 100mm Height, 65mm dia for 1100 Volt grade complete all as specified and as directed by Engr-in-charge.

28

-

-

... More
S & F Shackle type, Porcelain, Vitreous, White or Brown Insulator of size 100mm height 115mm dia including Galvanised Mild Steel 31x5mm Strap, 14mm dia Insulator Bolts, Nuts, Washers, etc. for Working Pressure 1100 Volt, complete all as specified and as directed by Engr-in-charge.

18

-

-

... More
S & F Aluminium Conductor Steel Reinforced (ACSR) (sizes as ordered) with permissible Sags and providing Jumper, etc fixing on Electric Poles and binding to Insulators with Aluminium Binding Wire as in OH Conductors including stringing, tightening, etc., complete all as specified and as directed by Engr-in-charge. Note : Cost of Binding Wire is deemed to be included in the quoted Unit Rate.

6

-

-

... More
Labour for Releasing ACSR Conductor of existing OH Lines by un-binding from Insulator of any description, re-fixing after stretching, re-stringing the Conductor, removing excess Sag, maintaining proper distance between Conductors as ordered, and binding to insulators with Aluminium Binding Wire complete all as specified and as directed by Engr-in-charge. Note : Cost of Binding Wire as a conductor of existing size with insulators and jumpers is deemed to be included in the Quoted Unit Rate.

13

-

-

... More
M & L Cross-arms, Bracings, Supports, Clamps and Back Plates fabricated from Structural Steel Sections including Nuts, Bolts, Washer, welding, bending cold or hot, drilling holes for Bolts, in any shape or size as indicated/ directed and inclusive of one coat of Aluminium Primer one Under Coat and One Finishing Coat of Aluminium Paint, complete all as specified and as directed by Engr-in-charge.

1

-

-

... More
S & F Cradles, hexagonal/rectangular fabricated with Galvanised Steel Wire with 4.00mm dia including binding with Aluminium Binding Wire, complete all as specified and as directed by Engr-in-charge. Note :- Cost of Binding Wire is deemed to be included in the Quoted Unit Rate.

1

-

-

... More
S&F LED indicating lamp (Red & Yellow) incl removal of existing unsv one complete all as specified and as directed by Engr-in-charge.

4

-

-

... More
S&F LED indicating lamp (Blue) incl removal of existing unsv one complete all as specified and as directed by Engr-in-charge.

2

-

-

... More
S&F and testing for Voltmeter range 0 to 500V , with Selector switch complete all as specified and as directed by Engr-in-charge.

2

-

-

... More
S&F and testing for Ammeter range 0 to 100Amp with selector switch same as per sample produce complete all as specified and as directed by Engr-in-charge.

2

-

-

... More
Supply & lay GI tubing (Light grade) in protection of cable at road crossing /hard standing as per site requirement etc all as specified and directed of following sizes :-

-

-

-

... More
(a) 80 mm dia bore.

24

-

-

... More
(b) 50 mm dia bore.

16

-

-

... More
(c) 40 mm dia bore.

16

-

-

... More
Supply, install and testing for maintenance free chemical earthing of dual pipe technology of 3 mtr long with outer pipe dia 88 mm and inner pipe dia 48 mm, the pipes are properly galvanised for 80-120 micron and wall thickness of inner pipe 3 mm and 2 mm of outer pipe. There is additional copper coating on outer surface. There should be terminal for connection of 75 x 6 mm with 2 holes of 14 mm dia. Fast Electrode is duly filled with highly conductive material with sealing at boath ends with lead terminal of 75 x 6 mm at top along with 2 bags of 25 Kgs each of earth enhancing compound. The chemical compound should be tested and certified by any international accredited and BIS accredited laborartory. The testing laboratory should be an ISO 9001 and 14001 certified. The earth enhancing compound should be tested reffering to protocol IS 1350 and IEC 62321/111/54/CDV. The ph value of compound should be 7-8. The content of mercury and hexa chromium should be below detection level. The electrode should be tested for salt spray test as per BIS 117-09 for corrosion for minimum 500 Hrs. The electrode should be duly tested and certified by CPRI Govt of India for a min short circuit current of 42 k amps for 1 Sec with initial pick of 8.2 K amp connected to copper strip 20 x 3 mm thick earth strip by means of bolts, nuts, check nuts and washers of copper with 40 mm dia medium grade GI pipe as a protection up to 7.5 mtr long and RCC pit with cover complete and connected to earthing test point all as specified or indicated including testing on completion, complete all as specified and as directed by Engr-in-charge. Model FE 88, 3 Mtr (copper) of Make Fast Electrode or its equivalant specifications appoved make by Garrison Engineer.

16

-

-

... More
M&L for Earthing complete with galvanized steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground earth pit not less than 2.25mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below ground level connected to galvanized iron strep 32 x 6 mm as earthing lead by mean of nut/bolt and washer of galvanized iron or steel drawn through 40 mm dia light grade GI pipe as shown in electrical plate no 3 of SSR part I of 2009 including necessary excavation and earth work GI pipe 20mm dia light grade for watering PCC chamber with PCC cover in cement concrete 1:2:4 Type B1(20mm graded aggregate), funnel, wire mesh, charcoal dust, salt etc, connected to panel board as indicated including testing complete. Note for item No 30 & 31 :- Earth strip and GI protection pipe upto 7.5 mtr from earth plate is deemed to be included in rate quoted.

10

-

-

... More
Cutting existing road surface or hard standing, bituminous topping 15 cm but not exceeding 30 cm girth for laying of pipes/ Cables and making good distrubed surface with PCC to match with existing complete all as specified and as directed. Note:- PCC will be measured and paid seperately.

12

-

-

... More
Dismantling unserviceable PCC poles of any description and any size including demolition of Cement Concrete (as/ if required) and made good disturbed Ground complete all as specified and as directed. Note : Unsv Poles will be dismantled at Ground Level and disturbed ground will made good as directed for which Earthwork, demolition of cement concrete, etc. will not be measured and paid separately.

5

-

-

... More
Taking down existing old extg unserviceable HT UG cable of any description and size complete all as specified and directed.

100

-

-

... More
S & F for Prestressed concrete poles of length 11.0 meter long having 152 mm x 152 mm at top and 152 mm x 260 mm at bottom, class 9 with necessary excavation, foundation and coping including applying two coats of of exterior weather proof paint (Cement based paint) of approved colour to pole and to MS cross arms, cable protection pipe, brackets etc with two coats of Aluminium Paint over a coat of red oxide primer including Synthetic enamel Painting in alternate lines of Yellow & Black Strips min of 6 Nos (each Strip 200 mm wide) at bottom of polecomplete all as specified and as directed. Note:- Earthwork, Cement Concrete etc. will be measured and paid under approprite Items.

5

-

-

... More
Supply and lay test and commissioning HT XLPE cable, insulated, screended, PVC bedded, galvanised steel strip or wire armoured, electic power cable (heavy duty) with multistaranded aluminium conductor, conforming to IS : 7098 (Part II), 11000 Volts "E" grade, cross sectional area 3 core x 95 sqmm (Earthed) laid in trenches/ ducts/under plinth floors passing through pipes etc, fixed on wall complete all as specified and directed.

100

-

-

... More
Supply and fix cable jointing kit for 11 KV grade cable for straight through cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sq mm, indoor/outdoor type complete all as specified and directed.

4

-

-

... More
Supply and fix cable jointing kit for 11 kV grade cable for outdoor termination, cold shrink type, joint complete with joining material and accessories suitable for 3 core XLPE armoured, aluminium conductor cable of size 95 sq mm complete all as specified and as directed.

6

-

-

... More
Disconnecting and dismantling the existing indoor type VCB11 KV horizontal fixed type VCB trolly of capacity 400/ 630 Amps from location and repair/ overhauling including replacement of damaged minor spare parts and carrying out with the following all as specified and as directed. Note :- Major spare parts will be measured & paid seperately (i) Inspecting/ overhauling of manual/ motorised spring drive mechanism by checking mechanism, motor and gear assembly, big gear assembly, stop bolt assembly, main shaft interlocking assembly, closing spring assembly, small cam with screw, motor cut -off limit switch, butter fly switch assembly, replacement of damaged control wiring DC/ AC for smooth function of VCB, testing of contact resistance, insulation resistance and applying multi grease lubricant to function smoothly. (ii) Inspecting/ overhauling of tripping assembly, earth fault release assembly, tripping coil, auxiliary switch and checking of electrical wiring system, replacment of control wire fuse, MCB and connected accesories all as specfied and directed by Engineer-in-Charge. (iii) Inspecting/ overhauling/ cleaning and inspecting through insulators, vacuum interuptors by carbon cleaner solution and applying dry graphite conductive sealant for electrical contacts to avoid carbon deposits on contact surfaces. (iv) Assembling all items/ components parts to the respective position & testing the breaker with High Voltage (DC) and meggering before and after high voltage test complete. (v) Overhauling, calibration and secondary injection of over current earth fault relays/ release on each multiple setting readjustment by artificial load complete all as specified including testing complete. (vi) Contarctor should contact PGVCL for proper tripping paramters and same should be set such that proper coordination is maintained in tripping between PGVCL VCB and MES incoming VCB and between sub feeder VCB in MES powerhouse and the same to be record and submitted to Engineer-in-Charge.

27

-

-

... More
Material and labour for opening the bus-bar chamber, CT chamber, PT Chamber and Meter chamber of HT 11 KV, panel board and carrying out following complete all as specified and as directed. Note :- Spare parts shall be measured & paid seperately (i) Inspecting/ cleaning/ overhauling of bus bar chamber by checking of bus bars, spout insulators, space heaters and removing dust with vacuum cleaner/ Blower and moisture by hot air blower and checking tightness of bus bars, insulators and applying STRIPPEX (A), STRIPPEX (B) and HT tape and test with High Voltage (DC) and meggering before and after high voltage test complete. (ii) Inspecting/ cleaning/ overhauling metering chamber by checking of entire wiring system, all meters, selector switches, control fuses and removing dust with vacuum cleaner/ blower and moisture by hot air blower and checking tightness of wiring system. (iii) Inspecting/ cleaning/ overhauling of CT/ PT chamber by checking of Bus bars, spout insulators, space heaters and checking of wiring system and removing dust with vacuum cleaner/ blower and moisture by hot air blower and checking tightness of bus bars, insulators and applying anti tracking paint on CT's and insulators and HT Tape.

14

-

-

... More
Opening the top cover of the transformer carefully at site and draining of transformer oil, and removing the core and windings for finding out the fault and refixing the same after repairs and supply and filling and or topping up with new transformer oil confirming to IS-335 of 1993 having suitable dielectric strength as approved by Engineer-in-Charge complete of the follwing sizes:- Note : Transformer oil shall be measured and paid separetely.

-

-

-

... More
(a) 100/160 KVA

1

-

-

... More
(b) 200 KVA

1

-

-

... More
(c) 250/ 315 KVA

1

-

-

... More
(d) 400/ 500 KVA

1

-

-

... More
Supply and replacement of transformer oil confirming to IS 335, having dielectric strength 60 KV completely including opening of top plate of transformer and refixing all as specified and as directed.

800

-

-

... More
Supply and fixing replacement of defective 11 KV HT brass spindle for terminal on HT side threaded complete with nut, washers etc of suitable dia with new porcelain 11 KV bushing for transformer in door/ out door type of various capacity complete all as specified and as directed

9

-

-

... More
Supply and fixing replacement of defective 433 Volts rass spindle for terminal on LT side threaded complete with nut, washers etc of suitable dia with new porcelain 433 Volts LT bush porcelain insulator for transformer in door/ out door type of various capacity complete all as specified and as directed

16

-

-

... More
Supply and fixing of Temperature gauge all as per existing/ equivalent model complete all as specified and as directed.

10

-

-

... More
Supply and fixing Gun metal gate valve 25 mm dia heavy duty high pressure with crutch or butterfly handle screwed both ends for iron pipes along with suitable gavanised iron plug complete all as specified and as directed.

2

-

-

... More
Supply and fixing Gun metal gate valve 40 mm dia heavy duty high pressure with crutch or butterfly handle screwed both ends for iron pipes along with suitable galvanised iron plug complete all as specified and as directed.

2

-

-

... More
Supply and fixing replacement of cracked/ wornout synthetic rubberized cork gasket 10 mm thick for top cover of transformer capacity upto 250 KVA complete all as specified and as directed

6

-

-

... More
Supply and fixing replacement of cracked/ wornout synthetic rubberized cork gasket 10 mm thick for HT/ LT bushes complete all as specified and as directed

25

-

-

... More
Supply and fixing ,replacement of silica gel breather assembly complete with silicagel upto 250 KVA transformer complete all as specified and as directed

10

-

-

... More
Supply and fixing ,replacement of silica gel in existing breather as required all as directed and as specified.

10

-

-

... More
Supply only spare parts suitable for ABB, Siemens, Areva makes of VCBs VCB Panels Boards, Rating 11 KV, 400/ 630A, indoor type complete all as specified and as directed.

-

-

-

... More
(a) Multi Function meters, Digital type 96 x 96 mm, Aux Supply 230 Volts AC, including conncetions and testing complete all as specified and as directed.

1

-

-

... More
(b) Opening/ Closing Push Button Assembly complete all as specified and as directed.

2

-

-

... More
(c) Motor Charging mechanism gear Drum box complete all as specified and as directed.

4

-

-

... More
(d) Vaccume Interupter assembly complete all as specified and as directed.

4

-

-

... More
(e) Limit Switches complete all as specified and as directed.

10

-

-

... More
(f) Closing Coil Assembly 30V DC complete all as specified and as directed.

3

-

-

... More
(g) Spring Charging Motor 230 Volts complete all as specified and as directed.

3

-

-

... More
(h) Spring return latch complete all as specified and as directed.

4

-

-

... More
(j) Tripping Coil assembly 30 Volts DC complete all as specified and as directed.

4

-

-

... More
(k) Auxiliary Switch with link complete all as specified and as directed.

4

-

-

... More
(l) Spout Insulator assembly (3 Phase) feeder side complete all as specified and as directed.

3

-

-

... More
(m) Spout Insulator assembly (3 Phase) Bus bar side complete all as specified and as directed.

3

-

-

... More
(n) Potential Transformer, Resin cast dry type 11 KV/ 110 Volt ,100 VA burden, Class 1 Accuracy, Trolly mounted complete all as specified and as directed.

3

-

-

... More
(o) Current Transformers,resin cast dry type, 60/ 5A Class 0.5 and 5p10, 15VA complete all as specified and as directed.

2

-

-

... More
(p) TNC Switch, 25A, Type:BCA02P004E86/S (Kaycee) complete all as specified and as directed.

2

-

-

... More
(q) Indicating Lamps LED type, 30 Volts DC Make: Teknic or equivalent complete all as specified and as directed.

10

-

-

... More
(r) Indicating Lamps LED type,110 Volts AC Make: Teknic or equivalent complete all as specified and as directed.

10

-

-

... More
(s) Ammeter, Digital type, CTR 50/ 30/ 5 Amps Class 1 acuracy, Aux Supply 230 Volts AC type:DM3258 Conzerv (Schneider Electric) complete all as specified and as directed.

2

-

-

... More
(t) Voltmeter, Digital type, Voltage 11 KV, PTR 11 KV/ 110V, class 1 acuracy, Aux Supply 230 Volts AC, Type:DM 3257 Make Conserv (Schnieder electric) complete all as specified and as directed.

2

-

-

... More
(u) Relay Nuemerical IDMTL+Inst O/C & E/F, suitable to exisiting relay complete all as specified and as directed.

1

-

-

... More
(v) Master trip relay Tripping relay suitable to exisiting relay complete all as specified and as directed.

1

-

-

... More
Dehydration/ filtration of transformer oil by means of centrifugal filtration plant to achieve the specified dielectric strength of 35 to 40 KV at 2.5 mm gap in existing position of transformer of any capacity and transformer oil for topping up at various sub station complete all as specified and as directed. (Note:- Transformer oil used for TOP UP measured and paid separately)

3000

-

-

... More
Supply and fix of suitable type and size FRP bus bar support insulator (Bridge Insulator) for fixing the extended aluminium/ copper bars, for cable terminations, duly fixed in the body of the panel board including galvanized steel bolts, nuts, washers and necessary drillings, in the panel body, complete all as specified and as directed.

20

-

-

... More
Material and labour for bring the van mounted full automated underground cable fault locator machine at site for find out HT/ LT cable fault in underground completely all as specified and as directed. Note: (a) Fault machine, cable & T&P required shall be arranged by the contractor. (b) Cable jointing kit for HT/ LT is measured separately.

10

-

-

... More
Maintaning of HT over head lines by trimming the of tree branches touching to the HT/ LT over head conductors lines upto 03 meter away from the live conductors surrounding area complete all as specified and as directed. Note :- Cost of labours deemed to be including cutting the tree branches and depositing the tree branches 50 Meter away from the poles or as directed by Enginner in-charge complete.

300

-

-

... More
S& F for HT 11 KV, Pin type, porcelain, vitreous, white, brown insulator on pole or any structure including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150 mm height, 150 mm dia for 11000 volts grade including removing old damaged insulator from pole complete all as specfied and as directed.

24

-

-

... More
S & F HT 11 KV, Disc type insulator, porcelain, vitreous 145mm high and 255mm dia ball and socket type, white, brown or green, two in series for tension with tension clamps for conductors assembly, working pressure 11000 volts complete all as specified and directed. .

6

-

-

... More
supply and fix porcelain Loop type insulator, vitreous porcelain, white, brown or green:Large size, with overall dimensions 90 mm x 140 mm, clearance of hole 25.5 mm complete all as specified and as directed.

10

-

-

... More
S & F for Galvanised Stay strand of size 7/4.0 mm dia to keep the pole in true vertical position complete all as specified.

1

-

-

... More
M & L Stay Assembly complete with Accessories as show in Electrical Plate No. 1 of MES Schedule Part-I, diameter of Stay Rod 20 mm, size of Plate 230 x 230 x 6 mm complete all as specified and as directed. Note : Earthwork, Cement Concrete, Mild Steel Stay Clamps with Bolts, Nuts, Stay Strand, Loop Insulator etc. will be measured and paid under approprite Items.

4

-

-

... More
M & L for Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT, 25 x 20 cm size complete all as specified and directed.

20

-

-

... More
Material and Labour for painting of transformer after cleaning the body surface of transformer of any capacity by rubbing with emery Paper to remove oil stains, dust etc and applying one coat of snthetic enamel paint by spray paint incl writing SM No/ MES No in white colour of suitable font complete all as specified and as directed.

23

-

-

... More
M & L preparing old painted surfaces by scraping and removing old paints, rust, etc. from Pre-stressed Concrete of HT Pole (above the planting depth and PCC copings) and MS cross arms, cable protection pipe, brackets etc and applying two coats of of exterior weather proof paint (Cement based paint) of approved colour to pole and to MS cross arms, cable protection pipe, brackets etc with two coats of Aluminium Paint over a coat of red oxide primer including Synthetic enamel Painting in alternate lines of Yellow & Black Strips min of 6 Nos (each Strip 200 mm wide) at bottom of pole complete all as specified and as directed by Engr- in- Charge.

100

-

-

... More
Removing HT connection from VCB and rearrange of Each HT cable in trench and fixing of cable with galvanised iron strip along the trench wall including removing unservicable HT cable from VCB room complete all as specified and as directed.

6

-

-

... More
Material and labour for disconnecting of 11 KV/ 433 Volts transformer out door type including all necessary HT/ LT connections of bothside, earth teriminals and taking down carefully from Two/ four pole structure/ Platform mounted etc and shifting of transformer at new location of substation and installation on two pole structure or PCC platform etc including connceting incoming HT and LT line complete all as specified and as directed.

2

-

-

... More
Material and labour for lightning arresters nominal discharge current Peak 65 KA rating, suitable for operation on HT 11000 volts system, comprising of zinc oxide disks, electrodes, fibre re-in forced composite structure, non tracking weather resistant shedded heat shrinked polymeric housing for withstanding from the effects of pollution, rain, heat and with moisture seal , stainless steel bolts and nuts, stainless steel end fitting cups and fixing arrangements complete all as specified and as directed. Make-Bhel/ Jaipurya brothers/ National.

4

-

-

... More
Supply and fix switch air break gang operated HT 11 KV Volt grade triple pole with 09 Polymer based insulators, 200 amps rating mounted on Polymer based insulator and fitted on steel frame horizontally operated mechanism from ground level consisting of operating rod of 25 mm bore Heavy grade GI pipe of suitable length worked from ground level and with locking arrangement flat iron clamp 50 mm x 6 mm including MS channel of suitable size and length for fixing GOD including bolts, nuts, and washers also removal of old extg unsv one complete all as specified and directed.

3

-

-

... More
Repairing/ servicing/ overhauling of gang operated device 11000 volts, 200/ 400 Amps including greasing all the moving parts and applying white petroleum jelly at the contact points tightening all jointing/ bolts nuts including replacing wornout the bolt and nuts commissioning and testing including dismantling and replacing the unserviceable parts/ spares all as directed. Note: All the spares replaced will be measured & paid separately (labour cost for replacement of spares not covered berein below is also deemed included in the above quoted rate. Supply only the following spares for replaceing in reapirs/ servicing.

4

-

-

... More
(a) Moving contact blades

2

-

-

... More
(b) Fixed contact jaw copper

3

-

-

... More
(c) PG clamps of suitable size as per site requirement.

20

-

-

... More
Supplying and laying unreinforced precast cement concrete cable covers, Class HV, Type- 1, Flat, size 300 mm x 180 mm x 40 mm in trenches for cable protection, embossed with "HT 1100 VOLTS ELECTRIC" on the top surface complete all as specified and as directed by the Engineer - in - Charge.

500

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.