Military Engineer Services Tender
Search for the latest Gujarat tenders online related to civil works, road & transport, pipelines and more easily here on BidAssist. Here you can get any and every tender that is posted on the eProcurement Gujarat website, minus the clutter. No need for a tender ID, as on BidAssist, you can view any Gujarat tender by merely typing Gujarat in the search box.
Costs
EMD
₹ 79,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2023_MES_634436_1Tender No
8948/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Supply, installing, testing and commissioning, in repair factory made and tested LT Panel, outdoor type floor mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 50x50x6mm thick angle iron base frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, both side opening type, with aprons for cable entry, with double door and locking arrangement and including earth work. The panel consisting of the following:- (a) Aluminum bus bar four strips 480 Amps ,415 volts, fixed horizontally, duly insulated with heat shrinkable sleeves in colour code - 01 Set.
(b) MCCB, 04 Pole, 350 Amps with ultimate breaking capacity 36 KA - 01 No (Incoming) (c) MCCB, 04 pole, 160 Amps with breaking capacity 25KA - 01 Nos (d) MCCB, 04 Pole, 100Amps with breaking capacity 25 KA -01 Nos (e) MCCB, 04 Pole, 40Amps with breaking capacity 25 KA - 06 Nos
(g) Digital Volt meter 0-500 volt with coil and selector switch - 1 No.
(h) Digital ammeter 0-500Amps with CT coil and selector switch - 01 No
(j) Indication lamps R,Y,B LED type – 1 set of three (jk Internal wiring with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled and aluminum strips for MCCB's.
(l) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, cemented block/brick work in CM 1:6 with sub class `B', old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 30cm above and 15 Cm below the ground level. (Note :- Near Post Office ) -Compartmentalized Panel Dimensions (1220mmx1545mmx450mm)(W*H*D)
-Aluminum strip required above100A MCCB's. & Copper Flexible cable Upto 100A.
-160A O/G MCCB Compartment size:- 350mm(H)*300mm(W)
-100A O/G MCCB Compartment size:- 300mm(H)*300mm(W)
-40A O/G MCCB Compartment size:- 275mm(H)*300/350mm(W) IEC 61439-1&2 TYPE PANEL
1
-
-
... More
Supply, installing, testing and commissioning, in repair factory made and tested LT Panel, outdoor type floor mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 50x50x6mm thick angle iron base frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, both side opening type, with aprons for cable entry, with double door and locking arrangement and including earth work. The panel consisting of the following:- (a) Aluminum bus bar four strips 600 Amps ,415 volts, fixed horizontally, duly insulated with heat shrinkable sleeves in colour code - 01 Set.
(b) MCCB, 04 Pole, 400 Amps with ultimate breaking capacity 36 KA - 01 No (Incoming) (c) MCCB, 04 pole, 160 Amps with breaking capacity 25KA - 02 Nos (d) MCCB, 04 Pole, 100 Amps with breaking capacity 25 KA -01 Nos (e) MCCB, 04 Pole, 63 Amps with breaking capacity 25 KA - 02 Nos (g) Digital Volt meter 0-500 volt with coil and selector switch - 1 No.
(h) Digital ammeter 0-500Amps with CT coil and selector switch - 01 No
(j) Indication lamps R,Y,B LED type – 1 set of three (jk Internal wiring with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled and aluminum strips for MCCB's.
(l) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, cemented block/brick work in CM 1:6 with sub class `B', old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 30cm above and 15 Cm below the ground level. (Note :- Out side PH) -Compartmentalized Panel Dimensions (970mmx1895mmx450mm)(W*H*D)
-Aluminum strip required above100A MCCB's. & Copper Flexible cable Upto 100A.
-160A O/G MCCB Compartment size:- 300mm(H)*400mm(W)
-100A O/G MCCB Compartment size:- 275mm(H)*400mm(W)
-63A O/G MCCB Compartment size:- 275mm(H)*400mm(W) IEC 61439-1&2 TYPE PANEL
1
-
-
... More
Supply, installing, testing and commissioning, in repair factory made and tested LT Panel, outdoor type floor mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 50x50x6mm thick angle iron base frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, both side opening type, with aprons for cable entry, with double door and locking arrangement and including earth work. The panel consisting of the following:- (a) Aluminum bus bar four strips 750 Amps ,415 volts, fixed horizontally, duly insulated with heat shrinkable sleeves in colour code - 01 Set.
(b) MCCB, 04 Pole, 500Amps with ultimate breaking capacity 36 KA - 01 No (Incoming) (c) MCCB, 04 pole, 200Amps with breaking capacity 25KA - 01 Nos (d) MCCB, 04 pole, 100Amps with breaking capacity 25KA - 04 Nos (e) MCCB, 04 pole, 63Amps with breaking capacity 25KA - 02 Nos (f) MCCB, 04 pole, 40Amps with breaking capacity 25KA - 02 Nos (g) Digital Volt meter 0-500 volt with coil and selector switch - 1 No.
(h) Digital ammeter 0-500Amps with CT coil and selector switch - 01 No
(j) Indication lamps R,Y,B LED type – 1 set of three (jk Internal wiring with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled and aluminum strips for MCCB's.
(l) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, cemented block/brick work in CM 1:6 with sub class `B', old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 30cm above and 15 Cm below the ground level. (Note :- SS 1 MRS) -Compartmentalized Panel Dimensions (1320mmx1770mmx500mm)(W*H*D)
-Aluminum strip required above100A MCCB's. & Copper Flexible cable Upto 100A.
-200A O/G MCCB Compartment size:- 350mm(H)*400mm(W)
-100A O/G MCCB Compartment size:- 275/350mm(H)*300/400mm(W)
-63A O/G MCCB Compartment size:- 275mm(H)*400mm(W IEC 61439-1&2 TYPE PANEL
1
-
-
... More
Supply, installing, testing and commissioning, in repair factory made and tested LT Panel, outdoor type floor mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 50x50x6mm thick angle iron base frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, both side opening type, with aprons for cable entry, with double door and locking arrangement and including earth work. The panel consisting of the following:- (a) Aluminum bus bar four strips 750 Amps ,415 volts, fixed horizontally, duly insulated with heat shrinkable sleeves in colour code - 01 Set.
(b) MCCB, 04 Pole, 500 Amps with ultimate breaking capacity 36 KA - 01 No (Incoming) (c) MCCB, 04 pole, 200 Amps with breaking capacity 25KA - 02 Nos (d) MCCB, 04 pole, 125 Amps with breaking capacity 25KA - 01 Nos (e) MCCB, 04 pole, 100 Amps with breaking capacity 25KA - 02 Nos (f) MCCB, 04 pole, 40 Amps with breaking capacity 25KA - 02 Nos (g) Digital Volt meter 0-500 volt with coil and selector switch - 1 No.
(h) Digital ammeter 0-500Amps with CT coil and selector switch - 01 No
(j) Indication lamps R,Y,B LED type – 1 set of three (jk Internal wiring with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled and aluminum strips for MCCB's.
(l) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, cemented block/brick work in CM 1:6 with sub class `B', old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 30cm above and 15 Cm below the ground level. (Note :- 753 SU) -Compartmentalized Panel Dimensions (1670mmx1520mmx500mm)(W*H*D)
-Aluminum strip required above100A MCCB's. & Copper Flexible cable Upto 100A.
-200A O/G MCCB Compartment size:- 400mm(H)*400mm(W)
-160A O/G MCCB Compartment size:- 300mm(H)*400mm(W)
-100A O/G MCCB Compartment size:- 275mm(H)*350mm(W)
-40A O/G MCCB Compartment size:- 275mm(H)*350mm(W) IEC 61439-1&2 TYPE PANEL
1
-
-
... More
Supply, installing, testing and commissioning, in repair factory made and tested LT Panel, outdoor type floor mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 50x50x6mm thick angle iron base frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, both side opening type, with aprons for cable entry, with double door and locking arrangement and including earth work. The panel consisting of the following:- (a) Aluminum bus bar four strips 225 Amps ,415 volts, fixed horizontally, duly insulated with heat shrinkable sleeves in colour code - 01 Set.
(b) MCCB, 04 Pole, 160Amps with ultimate breaking capacity 36 KA - 01 No (Incoming) (c) MCCB, 04 pole, 63 Amps with breaking capacity 27KA - 4 Nos (d) MCCB, 04 pole, 40 Amps with breaking capacity 27KA - 00 Nos (g) Digital Volt meter 0-500 volt with coil and selector switch - 1 No.
(h) Digital ammeter 0-500Amps with CT coil and selector switch - 01 No
(j) Indication lamps R,Y,B LED type – 1 set of three (jk Internal wiring with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled and aluminum strips for MCCB's.
(l) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, cemented block/brick work in CM 1:6 with sub class `B', old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 30cm above and 15 Cm below the ground level. (Note :- Dispersal 3004) -Compartmentalized Panel Dimensions (820mmx1420mmx350mm)(W*H*D)
-Aluminum strip required above100A MCCB's. & Copper Flexible cable Upto 100A.
-63A O/G MCCB Compartment size:- 275mm(H)*350mm(W) IEC 61439-1&2 TYPE PANEL
1
-
-
... More
Supply, installing, testing and commissioning, in repair factory made and tested LT Panel, outdoor type floor mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 50x50x6mm thick angle iron base frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, both side opening type, with aprons for cable entry, with double door and locking arrangement and including earth work. The panel consisting of the following:- (a) Aluminum bus bar four strips 300 Amps ,415 volts, fixed horizontally, duly insulated with heat shrinkable sleeves in colour code - 01 Set.
(b) MCCB, 04 Pole, 200 Amps with ultimate breaking capacity 36 KA - 01 No (Incoming) (c) MCCB, 04 pole, 40 Amps with breaking capacity 27KA - 08 Nos (g) Digital Volt meter 0-500 volt with coil and selector switch - 1 No.
(h) Digital ammeter 0-500Amps with CT coil and selector switch - 01 No
(j) Indication lamps R,Y,B LED type – 1 set of three (jk Internal wiring with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled and aluminum strips for MCCB's.
(l) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, cemented block/brick work in CM 1:6 with sub class `B', old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 30cm above and 15 Cm below the ground level. (Note :- Armoury ) -Compartmentalized Panel Dimensions (1170mmx1570mmx400mm)(W*H*D)
-Aluminum strip required above100A MCCB's. & Copper Flexible cable Upto 100A.
-40A O/G MCCB Compartment size:- 275mm(H)*300mm(W) IEC 61439-1&2 TYPE PANEL
1
-
-
... More
Supply, installing, testing and commissioning, in repair factory made and tested LT Panel, outdoor type floor mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 50x50x6mm thick angle iron base frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, both side opening type, with aprons for cable entry, with double door and locking arrangement and including earth work. The panel consisting of the following:- (a) Aluminum bus bar four strips 600 Amps ,415 volts, fixed horizontally, duly insulated with heat shrinkable sleeves in colour code - 01 Set.
(b) MCCB, 04 Pole, 400 Amps with ultimate breaking capacity 36 KA - 01 No (Incoming) (c) MCCB, 04 pole, 100 Amps with breaking capacity 25KA - 06 Nos (d) Wuroload changeover switch (4 pole) 400 Amps) - 01 nos (g) Digital Volt meter 0-500 volt with coil and selector switch - 1 No.
(h) Digital ammeter 0-500Amps with CT coil and selector switch - 01 No
(j) Indication lamps R,Y,B LED type – 1 set of three (jk Internal wiring with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled and aluminum strips for MCCB's.
(l) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, cemented block/brick work in CM 1:6 with sub class `B', old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 30cm above and 15 Cm below the ground level. (Note :- 101 SS) -Compartmentalized Panel Dimensions (920mmx1970mmx500mm)(W*H*D)
-Aluminum strip required above100A MCCB's. & Copper Flexible cable Upto 100A.
-100A O/G MCCB Compartment size:- 275mm(H)*350mm(W) IEC 61439-1&2 TYPE PANEL
1
-
-
... More
Supply, installing, testing and commissioning, in repair factory made and tested LT Panel, outdoor type floor mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 50x50x6mm thick angle iron base frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, both side opening type, with aprons for cable entry, with double door and locking arrangement and including earth work. The panel consisting of the following:- (a) Aluminum bus bar four strips 375 Amps ,415 volts, fixed horizontally, duly insulated with heat shrinkable sleeves in colour code - 01 Set.
(b) MCCB, 04 Pole, 250 Amps with ultimate breaking capacity 36 KA - 01 No (Incoming) (c) MCCB, 04 pole, 100 Amps with breaking capacity 36KA - 01 Nos (d) MCCB, 04 Pole, 63 Amps with breaking capacity 25 KA - 03 Nos (e) MCCB, 04 Pole, 40 Amps with breaking capacity 25KA - 02 Nos (f) Euroload changeover switch (4pole) 250 Amps - 01 Nos
(g) Digital Volt meter 0-500 volt with coil and selector switch - 1 No.
(h) Digital ammeter 0-500Amps with CT coil and selector switch - 01 No
(j) Indication lamps R,Y,B LED type – 1 set of three (jk Internal wiring with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled and aluminum strips for MCCB's.
(l) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, cemented block/brick work in CM 1:6 with sub class `B', old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 30cm above and 15 Cm below the ground level. (Note :-DSS 24 End) -Compartmentalized Panel Dimensions (870mmx1970mmx450mm)(W*H*D)
-Aluminum strip required above100A MCCB's. & Copper Flexible cable Upto 100A.
-Upto 100A O/G MCCB Compartment size:- 275mm(H)*350mm(W) IEC 61439-1&2 TYPE PANEL
1
-
-
... More
Supply, installing, testing and commissioning, in repair factory made and tested LT Panel, outdoor type floor mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 50x50x6mm thick angle iron base frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, both side opening type, with aprons for cable entry, with double door and locking arrangement and including earth work. The panel consisting of the following:- (a) Aluminum bus bar four strips 480Amps ,415 volts, fixed horizontally, duly insulated with heat shrinkable sleeves in colour code - 01 Set.
(b) MCCB, 04 Pole, 200 Amps with ultimate breaking capacity 36 KA - 01 No (Incoming) (c) MCCB, 04 pole, 100 Amps with breaking capacity 25KA - 01 Nos (d) MCCB, 04 Pole, 40 Amps with breaking capacity 25 KA -01 Nos (e) Euroload changeover switch (4pole) 200 Amps - 01 Nos (g) Digital Volt meter 0-500 volt with coil and selector switch - 1 No.
(h) Digital ammeter 0-500Amps with CT coil and selector switch - 01 No
(j) Indication lamps R,Y,B LED type – 1 set of three (jk Internal wiring with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled and aluminum strips for MCCB's.
(l) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, cemented block/brick work in CM 1:6 with sub class `B', old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 30cm above and 15 Cm below the ground level. (Note :- ACRR 3 ) -Compartmentalized Panel Dimensions (1220mmx1270mmx450mm)(W*H*D)
-Aluminum strip required above100A MCCB's.& Copper Flexible cable Upto 100A.
-Upto 100A O/G MCCB Compartment size:- 300mm(H)*400mm(W)
-200A O/G MCCB Compartment size:- 350mm(H)*400mm(W) IEC 61439-1&2 TYPE PANEL
1
-
-
... More
Supply, installing, testing and commissioning, in repair factory made and tested LT Panel, outdoor type floor mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 50x50x6mm thick angle iron base frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, both side opening type, with aprons for cable entry, with double door and locking arrangement and including earth work. The panel consisting of the following:- (a) Aluminum bus bar four strips 300 Amps ,415 volts, fixed horizontally, duly insulated with heat shrinkable sleeves in colour code - 01 Set.
(b) MCCB, 04 Pole, 200 Amps with ultimate breaking capacity 36 KA - 01 No (Incoming) (c) MCCB, 04 pole, 40 Amps with breaking capacity 25KA - 08 Nos (g) Digital Volt meter 0-500 volt with coil and selector switch - 1 No.
(h) Digital ammeter 0-500Amps with CT coil and selector switch - 01 No
(j) Indication lamps R,Y,B LED type – 1 set of three (jk Internal wiring with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled and aluminum strips for MCCB's.
(l) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, cemented block/brick work in CM 1:6 with sub class `B', old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 30cm above and 15 Cm below the ground level. (Note :- ATC Tower ) -Compartmentalized Panel Dimensions (1170mmx1470mmx400mm)(W*H*D)
-Aluminum strip required above100A MCCB's. Copper Flexible cable Upto 100A.
-40A O/G MCCB Compartment size:- 275mm(H)*300mm(W) IEC 61439-1&2 TYPE PANEL
1
-
-
... More
Supply, installing, testing and commissioning, in repair factory made and tested LT Panel, outdoor type floor mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 50x50x6mm thick angle iron base frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, both side opening type, with aprons for cable entry, with double door and locking arrangement and including earth work. The panel consisting of the following:- (a) Aluminum bus bar four strips 600 Amps ,415 volts, fixed horizontally, duly insulated with heat shrinkable sleeves in colour code - 01 Set.
(b) MCCB, 04 Pole, 400 Amps with ultimate breaking capacity 36 KA - 01 No (Incoming) (c) MCCB, 04 pole, 250 Amps with breaking capacity 25KA - 02 Nos (d) MCCB, 04 Pole, 63Amps with breaking capacity 25 KA -05 Nos (e) MCCB, 04 Pole, 40 Amps with breaking capacity 25 KA - 08Nos (g) Digital Volt meter 0-500 volt with coil and selector switch - 1 No.
(h) Digital ammeter 0-500Amps with CT coil and selector switch - 01 No
(j) Indication lamps R,Y,B LED type – 1 set of three (jk Internal wiring with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled and aluminum strips for MCCB's.
(l) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, cemented block/brick work in CM 1:6 with sub class `B', old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 30cm above and 15 Cm below the ground level. (Note :- MOF) -Compartmentalized Panel Dimensions (1970mmx2020mmx500mm)(W*H*D)
-Aluminum strip required above100A MCCB's. Copper Flexible cable Upto 100A.
-200A O/G MCCB Compartment size:- 350mm(H)*400mm(W)
-63A O/G MCCB Compartment size:- 275mm(H)*400mm(W)
-40A O/G MCCB Compartment size:- 275/350mm(H)*300/400mm(W) IEC 61439-1&2 TYPE PANEL
1
-
-
... More
Supply, installing, testing and commissioning, in repair factory made and tested LT Panel, outdoor type floor mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 50x50x6mm thick angle iron base frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, both side opening type, with aprons for cable entry, with double door and locking arrangement and including earth work. The panel consisting of the following:- (a) Aluminum bus bar four strips 960 Amps ,415 volts, fixed horizontally, duly insulated with heat shrinkable sleeves in colour code - 01 Set.
(b) MCCB, 04 Pole, 400 Amps with ultimate breaking capacity 36 KA - 01 No (Incoming) (c) MCCB, 04 pole, 160 Amps with breaking capacity 25KA - 01 Nos (d) MCCB, 04 Pole, 100 Amps with breaking capacity 25 KA -01 Nos (e) MCCB, 04 Pole, 63 Amps with breaking capacity 25 KA - 04 Nos (g) Digital Volt meter 0-500 volt with coil and selector switch - 1 No.
(h) Digital ammeter 0-500Amps with CT coil and selector switch - 01 No
(j) Indication lamps R,Y,B LED type – 1 set of three (jk Internal wiring with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled and aluminum strips for MCCB's.
(l) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, cemented block/brick work in CM 1:6 with sub class `B', old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 30cm above and 15 Cm below the ground level. (Note :- Base OPS) -Compartmentalized Panel Dimensions (920mmx2045mmx500mm)(W*H*D)
-Aluminum strip required above100A MCCB's. Copper Flexible cable Upto 100A.
-Upto 100A O/G MCCB Compartment size:- 275mm(H)*350mm(W)
- 160A O/G MCCB Compartment size:- 350mm(H)*350mm(W) IEC 61439-1&2 TYPE PANEL
1
-
-
... More
Supply, installing, testing and commissioning, in repair factory made and tested LT Panel, outdoor type floor mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 50x50x6mm thick angle iron base frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, both side opening type, with aprons for cable entry, with double door and locking arrangement and including earth work. The panel consisting of the following:- (a) Aluminum bus bar four strips 600 Amps ,415 volts, fixed horizontally, duly insulated with heat shrinkable sleeves in colour code - 01 Set.
(b) MCCB, 04 Pole, 200 Amps with ultimate breaking capacity 36 KA - 01 No (Incoming) (c) MCCB, 04 pole, 63 Amps with breaking capacity 25KA - 02 Nos (d) MCCB, 04 Pole, 40 Amps with breaking capacity 25 KA -04 Nos (g) Digital Volt meter 0-500 volt with coil and selector switch - 1 No.
(h) Digital ammeter 0-500Amps with CT coil and selector switch - 01 No
(j) Indication lamps R,Y,B LED type – 1 set of three (jk Internal wiring with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled and aluminum strips for MCCB's.
(l) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, cemented block/brick work in CM 1:6 with sub class `B', old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 30cm above and 15 Cm below the ground level. (Note :- SNF) -Compartmentalized Panel Dimensions (1120mmx1195mmx400mm)(W*H*D)
-Aluminum strip required above100A MCCB's. Copper Flexible cable Upto 100A.
-Upto 100A O/G MCCB Compartment size:- 275mm(H)*300mm(W) IEC 61439-1&2 TYPE PANEL
1
-
-
... More
Supply, installing, testing and commissioning, in repair factory made and tested LT Panel, outdoor type floor mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 50x50x6mm thick angle iron base frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, both side opening type, with aprons for cable entry, with double door and locking arrangement and including earth work. The panel consisting of the following:- (a) Aluminum bus bar four strips 600 Amps ,415 volts, fixed horizontally, duly insulated with heat shrinkable sleeves in colour code - 01 Set.
(b) MCCB, 04 Pole,400 Amps with ultimate breaking capacity 36 KA - 01 No (Incoming) (c) MCCB, 04 pole, 160 Amps with breaking capacity 25KA - 02 Nos (d) MCCB, 04 pole, 100 Amps with breaking capacity 25KA - 02 Nos (g) Digital Volt meter 0-500 volt with coil and selector switch - 1 No.
(h) Digital ammeter 0-500Amps with CT coil and selector switch - 01 No
(j) Indication lamps R,Y,B LED type – 1 set of three (jk Internal wiring with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled and aluminum strips for MCCB's.
(l) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, cemented block/brick work in CM 1:6 with sub class `B', old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 30cm above and 15 Cm below the ground level. (Note :- SS No 8) -Compartmentalized Panel Dimensions (970mmx1895mmx450mm)(W*H*D)
-Aluminum strip required above100A MCCB's. Copper Flexible cable Upto 100A.
-160A O/G MCCB Compartment size:- 300mm(H)*400mm(W)
--100A O/G MCCB Compartment size:- 275mm(H)*400mm(W) IEC 61439-1&2 TYPE PANEL
1
-
-
... More
Supply, installing, testing and commissioning, in repair factory made and tested LT Panel, outdoor type floor mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 50x50x6mm thick angle iron base frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, both side opening type, with aprons for cable entry, with double door and locking arrangement and including earth work, disconnecting old connections and taking out old panel and reconnecting new panel etc. The panel consisting of the following:- (a) Aluminum bus bar four strips 300 Amps ,415 volts, fixed horizontally, duly insulated with heat shrinkable sleeves in colour code - 01 Set.
(b) MCCB 04 Pole, 200 Amps with breaking capacity 36 KA - 01 No (Incoming) (d) MCCB, 04 Pole,63 Amps with breaking capacity 25 KA - 02 Nos (e) MCCB, 04 Pole,40 Amps with breaking capacity 25 KA - 08Nos (e) Digital Volt meter 0-500 volt with coil and selector switch - 1 No.
(f) Digital ammeter 0-500Amps with CT coil and selector switch - 01 No
(g) Indication lamps R,Y,B LED type – 1 set of three (j) Internal wiring with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled and aluminum strips for MCCB's.
(k) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, cemented block/brick work in CM 1:6 with sub class `B', old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 30cm above and 15 Cm below the ground level. (Note :- Main Gd Room -Compartmentalized Panel Dimensions (1120mmx1695mmx450mm)(W*H*D)
-Aluminum strip required above100A MCCB's. Copper Flexible cable Upto 100A.
-Upto 100A O/G MCCB Compartment size:- 275mm(H)*300mm(W) IEC 61439-1&2 TYPE PANEL
1
-
-
... More
Supply, installing, testing and commissioning, in repair factory made and tested LT Panel, outdoor type floor mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 50x50x6mm thick angle iron base frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, both side opening type, with aprons for cable entry, with double door and locking arrangement and including earth work. The panel consisting of the following:- (a) Aluminum bus bar four strips 600 Amps ,415 volts, fixed horizontally, duly insulated with heat shrinkable sleeves in colour code - 01 Set.
(b) MCCB, 04 Pole, 400 Amps with ultimate breaking capacity 36 KA - 01 No (Incoming) (c) MCCB, 04 pole, 250 Amps with breaking capacity 25KA - 02 Nos (d) MCCB, 04 Pole, 63Amps with breaking capacity 25 KA -05 Nos (e) MCCB, 04 Pole, 40 Amps with breaking capacity 25 KA - 08Nos (g) Digital Volt meter 0-500 volt with coil and selector switch - 1 No.
(h) Digital ammeter 0-500Amps with CT coil and selector switch - 01 No
(j) Indication lamps R,Y,B LED type – 1 set of three (jk Internal wiring with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled and aluminum strips for MCCB's.
(l) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, cemented block/brick work in CM 1:6 with sub class `B', old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 30cm above and 15 Cm below the ground level. (Note :-MES IB -Compartmentalized Panel Dimensions (1970mmx2020mmx500mm)(W*H*D)
-Aluminum strip required above100A MCCB's. Copper Flexible cable Upto 100A.
-200A O/G MCCB Compartment size:- 350mm(H)*400mm(W)
-63A O/G MCCB Compartment size:- 275mm(H)*400mm(W)
-40A O/G MCCB Compartment size:- 275/350mm(H)*300/400mm(W) IEC 61439-1&2 TYPE PANEL
1
-
-
... More
Supply, installing, testing and commissioning, in repair factory made and tested LT Panel, outdoor type floor mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 50x50x6mm thick angle iron base frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, both side opening type, with aprons for cable entry, with double door and locking arrangement and including earth work. The panel consisting of the following:- (a) Aluminum bus bar four strips 480 Amps ,415 volts, fixed horizontally, duly insulated with heat shrinkable sleeves in colour code - 01 Set.
(b) MCCB, 04 Pole, 350 Amps with ultimate breaking capacity 36 KA - 01 No (Incoming) (c) MCCB, 04 pole, 100 Amps with breaking capacity 25KA - 01 Nos (d) MCCB, 04 Pole, 63Amps with breaking capacity 25 KA -04 Nos (e) MCCB, 04 Pole, 40 Amps with breaking capacity 25 KA - 04Nos (g) Digital Volt meter 0-500 volt with coil and selector switch - 1 No.
(h) Digital ammeter 0-500Amps with CT coil and selector switch - 01 No
(j) Indication lamps R,Y,B LED type – 1 set of three (jk Internal wiring with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled and aluminum strips for MCCB's.
(l) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, cemented block/brick work in CM 1:6 with sub class `B', old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 30cm above and 15 Cm below the ground level. (Note :- MFU CCU ) -Compartmentalized Panel Dimensions (1170mmx1695mmx450mm)(W*H*D)
-Aluminum strip required above100A MCCB's. Copper Flexible cable Upto 100A.
-Upto 100A O/G MCCB Compartment size:- 275mm(H)*300mm(W) IEC 61439-1&2 TYPE PANEL
1
-
-
... More
M&L for earthing complete with galvanised steel earth plate electrode size 600 x 600 x 6.0 mm thick, burried directly in ground, (Earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below ground level connected to galvanised iron strip 32 x 6 mm as earthing lead wire by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 3 connected to earthing test point all as specified or indicated including testing on completion, surrounded from all sides by mixture of charcoal and common salt and electrode by means of steel and GI pipe light grade 40mm dia bore for watering funnel with wire mesh. CI cover with frame, PCC chamber pit with PCC 1:3:6 type C-2 excavation and earth work all as shown in electrical plate No 3 connected to earthing test point all as specified and directed.
NOTE:-
1. The unit rate includes for protection GI pipe and watering pipe of 40 mm bore including excavation for earth pit in any type of soil/ disintegrate rock.
2. Contractor has to bring agriculture soil from outside of defence land and fill in earth pit to achieve desired result as the soil resistiviy is very high.
3.The cost of GI strip of size 32 X 6 mm from top of earth plate upto 7.5 meter above ground level is deemed to be included in the unit rate of above item.
4. All the joints in GI strip and connection with Earth Plate to be welded and in addition by proving brass nut bolt and washer.
5. Cost of welding and nut bolts are deemed to be included in the unit rate. 6. Contractor has to disposeoff the excavated soil in open land up to a distance of 600 mtr from earth pit.
52
-
-
... More
S & F in replacement of MCCB 3 Pole, 415 V, fixed type, 25 to 100 Amps with breaking capacity 16 KA complete all as directed
15
-
-
... More
S & F in replacement of MCCB 3 Pole, 415 V, fixed type, 160 Amps with breaking capacity 36 KA complete all as directed
12
-
-
... More
S & F in replacement of MCCB 3 Pole, 415 V, fixed type, 200 Amps with breaking capacity 36 KA complete all as directed
12
-
-
... More
S & F in replacement of MCCB 3 Pole, 415 V, fixed type, 250 Amps with breaking capacity 36 KA complete all as directed
8
-
-
... More
S&F in replacement of MCCB 4 Pole, 415 V, Adjustable type, 160 Amps with breaking capacity 36 KA complete all as directed
8
-
-
... More
S&F in replacement of MCCB 4 Pole, 415 V, Adjustable type, 200 Amps with breaking capacity 36 KA complete all as directed
8
-
-
... More
S&F in replacement of MCCB 4 Pole, 415 V, Adjustable type, 250 Amps with breaking capacity 36 KA complete all as directed
8
-
-
... More
S&F in replacement of MCCB 4 Pole, 415 V, Adjustable type, 350 Amps with breaking capacity 36 KA, complete all as directed
5
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements