Military Engineer Services Tender

View complete overview of Goa MES Tender

Military Engineer Services - MES Tender

Works
Machinery and Tools
Eprocure
Opening Date2 Dec 2024
Closing Soon30 Dec 2024
Tender Amount₹ 79,68,000 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
M&L for Lifting out Vertical Mounted, Heavy duty Jockey Fire Pump, CNE 14/7 Stage type set capacity of 125 HP/90 KW Cast iron body, Make of mather+platt, including connected pipe connection/delivery lines, nuts, bolts, washer etc for repair/replacement of unserviceable spare parts including transportation to the workshop and re-installing the same after repair work & testing all as specified and as directed.

2

-

-

... More
M&L for Complete Overhauling of Main fire pump capacity of 270 HP/ 200 KW, CNE 14x7 stage vertical mounted type, Make: Mather+platt for general inspection of impeller, shaft all bearings and sleaves, and re-installation of Pump after replacing all sleaves, bearings,seals and with SS nut bolts, metalising the shafts and re threading bottom plate by lathe work including body repairs, welding works and complete testing all as specified and as directed.

2

-

-

... More
M&L for Complete Overhauling of Main fire pump capacity of 125 HP/ 90 KW, CNE 14x7 stage vertical mounted type, Make: Mather+platt for general inspection of impeller, shaft all bearings and sleaves, and re-installation of Pump after replacing all sleaves, bearings,seals and with SS nut bolts, metalising the shafts and re threading bottom plate by lathe work including body repairs, welding works and complete testing all as specified and as directed.

2

-

-

... More
Supply & fixing in replacement of Casing and Diffuser of CF3M type as per part 1030 complete suitable for CNE 14X7 Stage pump all as specified and directed by Engr-in-charge.

2

-

-

... More
Supply & fixing in replacement of Rising Main Pipe (Bottom), SS 316L type as per part no 1150, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

1

-

-

... More
Supply & fixing in repair of Rising Main Pipe (Int.), SS 316L type as per part no 1151, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

2

-

-

... More
Supply & fixing in repair of Rising Main Pipe (Top), SS 316L type as per part no 1152, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge. .

1

-

-

... More
Supply & fixing in repair of Neck Ring of CF3M type as per part no 1181, CNE 14x7 stage vertical mounted typecomplete all as specified and directed by Engr-in-charge.

5

-

-

... More
Supply & fixing in repair of Impeller CF3M type as per part no 1504, CNE 14x7 stage vertical mounted typecomplete all as specified and directed by Engr-in-charge.

7

-

-

... More
Supply & fixing in repair of Impeller Nose Cap CF3M type as per part no 1651, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

10

-

-

... More
Supply & fixing in repair of Imepller Distance Piece SS 316L type as per part no 1704, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

6

-

-

... More
Supply & fixing in repair of Pump Shaft SS 316L type as per part no 1802, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

1

-

-

... More
Supply & fixing in repair of Top Shaft SS 316L type as per part no 1804, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

2

-

-

... More
Supply & fixing in repair of Intermediate Shaft SS 316L type as per part no 1805, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

1

-

-

... More
Supply & fixing in repair of Adjusting ring of M.S. as per part no 1822, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

6

-

-

... More
Supply & fixing in repair of Ratchet Bush EN24H type as per part no 2001, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

4

-

-

... More
Supply & fixing in repair of Ratchet Mounting Plate M.S. type as per part no 2003, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

4

-

-

... More
Supply & fixing in repair of Ratchet Pin EN 24 type as per part no 2004, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

5

-

-

... More
Supply & fixing in repair of Solid Muff Coupling SS 316L type as per part no 2050, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

2

-

-

... More
Supply & fixing in repair of Split Collar of SS 316L type as per part no 2060, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

3

-

-

... More
Supply & fixing in repair of Gland Sleeve of SS 316L type as per part no 2106, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

2

-

-

... More
Supply & fixing in repair of Logging Ring (split) of CF3M type as per part no 2301, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

3

-

-

... More
Supply & fixing in repair of Gland Split of CF3M type as per part no 2311, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

5

-

-

... More
Supply & fixing in repair of Gland Packing Graph. Cotton as per part no 2410, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

4

-

-

... More
Supply & fixing in repair of Spherical roller thrust bearing MFG. STD. as per part no 2602, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

2

-

-

... More
Supply & fixing in repair of Int Bearing Bracket of CF3M type as per part no 2800, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

2

-

-

... More
Supply & fixing in repair of Int Bearing Bush Finocot B as per part 2801, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

5

-

-

... More
Supply & fixing in repair of Oil Retainer Bush LTB Type 5 2810, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

1

-

-

... More
Supply & fixing in repair of Oil retainer plate SS 316L type as per part no 2811, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

1

-

-

... More
Supply & fixing in repair of Bearing Bush (Pump) Finocot B type as per part no 2830, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

6

-

-

... More
Supply & fixing in repair of Pump Bearing Sleeve SS 316L type as per part no 2832, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

4

-

-

... More
Supply & fixing in repair of Intermediate bearing sleeve SS 316L type as per part no 2834, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

4

-

-

... More
Supply & fixing in repair of Thrust Brg Cover C.I as per part no 2881, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

2

-

-

... More
Supply & fixing in repair of Thrust Brg Housing C.I as per 2882 type, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

1

-

-

... More
Supply & fixing in repair of Thrust Block EN 8 type as per part no 2883, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

1

-

-

... More
Supply & fixing in repair of Thrust Brg Lock Nut EN 8 as per part no 2901, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

1

-

-

... More
Supply & fixing in repair of Sleeve Nut SS 316L type as per part 3032, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

4

-

-

... More
Supply & fixing in repair of Key for Impeller SS 316L type as per part 3210, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

8

-

-

... More
Supply & fixing in repair of Key For Flexible coupling SS 316L type as per part 3250, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

2

-

-

... More
Supply & fixing in repair of Key for Muff coupling SS 316L type as per part 3260, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

8

-

-

... More
Supply & fixing in repair of Key for Thrust Block SS 316L type as per part 3280, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

4

-

-

... More
Supply & fixing in repair of Gasket for oil ret.plate/brg.hsg. Champion AF1204080 type, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

5

-

-

... More
Supply & fixing in repair of O ring for csg. & diffuser Nit. Rubber 4250 type, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

8

-

-

... More
Supply & fixing in repair of Suction Strainer SS 316L type as per part no 4900, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

1

-

-

... More
Supply & fixing in repair of Suction Bell Mouth CF3M 4910 type, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

1

-

-

... More
Supply & fixing in repair of Motor Stool M.S. 4680 type, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

1

-

-

... More
Supply & fixing in repair of Fan M.S. 4971 type, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

1

-

-

... More
Supply & fixing in repair of Air Duct (Split) M.S. 4972 type, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

2

-

-

... More
Supply & fixing in repair of Key- Fan SS 316L 3280-1 type, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

4

-

-

... More
Supply & fixing in repair of O ring for Int Brg Bracket & RM pipe top Nit. Rubber 4250-1, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

8

-

-

... More
Supply & fixing in repair of O ring for oil retainer plate/bush Nit. Rubber 4250-2, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

8

-

-

... More
Supply & fixing in repair of Flexible coupling (PH+MH) C.I. 4830, 4660, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

1

-

-

... More
Supply & fixing in repair of Fasteners SS 316L, suitable for CNE 14x7 stage vertical mounted pump complete all as specified and directed by Engr-in-charge.

1

-

-

... More
Supply and fixing in repair bearing No 6205/6206/6207/6208/6209/6310/6312/6313 type all as specified and as directed.

10

-

-

... More
M&L in repair of Rubber coupling of size L-150/L-225/L-226 including complete testing all as specified and as directed.

4

-

-

... More
S&F in repair Pressure gauge as per existing dia range 0-10 kg/Sqcmall as specified and as directed. Note : Rate quoted shall be deemed to be included for providing adopter/Ferrule/check nut etc required for fixing of pressure guage.

2

-

-

... More
S&F in repair single phase preventer VSP 2 of make Minilec or equivalent all as specified and as directed.

3

-

-

... More
S&F in repair phase failure relay VMR 2 of make Minilec or equivalent all as specified and as directed.

3

-

-

... More
Supply and laying, in repair PVC insulated flexible industrial, Unarmoured copper cable 4 core, 10 sqmm for voltage grade up to 1100V, submersible pump sets including taking down of old existing one all as per site requirement as per IS 694:1990 all as specified and as directed.

30

-

-

... More
Supply and laying, in repair PVC insulated flexible industrial, Unarmoured copper cable 4 core, 6 sqmm for voltage grade up to 1100V, submersible pump sets including taking down of old existing one all as per site requirement as per IS 694:1991, all as specified and as directed.

30

-

-

... More
M&L for Taking out ACB of capacity upto 4000 Amps of Make : ABB or any existing make, 3pole , 415 volts, 75 KA indoor type from its sub cubicle and carrying out routine maintenance as per manufacturer maintenance manual, examine the moving isolating contacts for any discolouration, cluster contacts, remove the arc chutes, check the SMC moulding are intacts, examine the moving contacts main contacts silver tips, spring mechanism, clean all contacts with a suitable solvent and contacts regreased with HP multipurpose grease, all contacts setting checked, readjusted if required, and regreased with HP multipurpose grease, all tripping device like manual trip, under voltage, shunt trip release, over current and earth fault tripping device to be tested, readjusted and confirm all tripping device is in healthy condition, check and record IR value of ACB, with 1.1. KV LT megger calibrating ground fault / short ckt, overload relays for tripping & timing complete and rendering test report all as specified and as directed.

2

-

-

... More
M&L for servicing of LT panel (7F Type) of capacity upto 4000 Amps suitable for AC supply (ACB upto 03 Nos, 200 KW VFD upto 02 Nos and bus chamber upto 02 Nos) by strip opening the doors of the panel and carrying out the cleaning of the panels with CRC spray and tightening the loose connections of the panel including repalcement of the cable glands wherever required, replacement of the old teared/ unsv insulation from the bus bar,checking the IR value before fixing the LT sleeve and refixing the heat shrinkable insulating tape sleeve suitable for 1.1 kv busbar not less than 3mm thick having dielectric strength not less than 1.1kv/mm and LT insulation tapefor CT/ PT connection complete with a certificate from NABL lab. and checking the IR value before testing and commissioning the bus bar all as specified, rectifying the internal wiring of the panel alongwith control wiring between ACB, MCCB, CT, PT, Earth fault relay, over current relay and digital multi function meter, paintting of the LT paels inner and outer surface with the two coat of synthetic enammelled paint over a coat of red oxide primer all as specified and directede by Engr - in- charge. Note:- a) The above quoted rate includes the cost of the insulators, nuts, bolts, washers and cable gland required for the repair of the panel

1

-

-

... More
M&L for Taking out VFD 200 KW, 415 volts, 65 KA, ACS880-04-505A-3 indoor type make of ABB, from its sub cubicle for detect major faults like software error, power communication erroe, circuit board error and Repairs it through OEM/ authorised agency and carrying out to routine maintenance as per manufacturer maintenance manual, examine the moving isolating contacts for any discolouration, cluster contacts, chokes for reducing harmonics, examine the EH 370 , 3 Pole magnetic contector and EMC filter,cabling clamps and banet communication,PID controller, bluetooth device display, termination switch, time setting switch and bias registors switch, clean all contacts and air cooling fan with a suitable solvent, all contacts setting checked, readjusted if required, and all tripping device like manual trip, under voltage, over current and earth fault tripping device to be tested, readjusted and confirm all tripping device is in healthy condition, check ground fault / short ckt, overload relays for tripping & timing and re-installation with complete IGI swire & cable connection all as specified. Note : Rates deemed to be included transportation to workshop and re-installing at the same position after repair work all as specified and directed by Engineer-in-Charge.

1

-

-

... More
Supply and fixig in repair 20 amps, 415 volt rating HD 20 type fuse for VFD of 200 kw capacity Make : ABB or any existing make with testing and commissioning complete all as specified and directed

2

-

-

... More
M&L for Opening /checking and servicing the 3 phase, 415 volt Soft starter control panel board cubical type suitable for 200HP/125 HP Capacity pumps, cleaning the bus duct chamber, inspect the complete panel, tighten the nuts & bolts of incoming, outgoing MCCBs/SFU of different capacity and cleaning/removal of moisture with CRC electrical parts cleaner, applying thick coating of Z931 strippex B and Z 955 strippex (SL) high temperature tape for preventing from flash over & fire hazard including replacement of 3mm thick gasket, closing of all holes and changing of the same complete all as specified and as directed. Note : The quoted rate deemed to be included the nut & bolts, washer and similar items required for proper functioning of the LT Panel board.

2

-

-

... More
S&F in repair MCCB 400 Amps (DN3-400-M Type) 3 Pole 50 KA breaking capacity, 415 volts AC with adjustable thermal magnetic release for motor pumps panel complete all as specified and directed.

2

-

-

... More
S&F in repair MCCB 400 Amps 3 Pole, 50 KA breaking capacity, 415 volts AC with Advanced motor protection including rotary door handle of suitable lenght with all connected accessories for motor pumps panel complete all as specified and directed.

1

-

-

... More
S&F in repair MCCB 250 Amps 3 Pole, 50 KA breaking capacity, 415 volts AC with microprocessor base short circuit protection including rotary door handle of suitable lenght with all connected accessories for motor pumps panel complete all as specified and directed.

2

-

-

... More
S&F in repair MCB TPN, 40-100 Amps, C series 415 Volts, 10 KA breaking capacity of complete all as specified and directed.

5

-

-

... More
S&F in repair MCB TP, 25 to 63 Amps, 'C' series 415 Volts, 10 KA breaking capacity of complete all as specified and directed.

8

-

-

... More
S&F in repair of 110-140 Amps, 3 Pole Power Contractor, MNX Type, 415Volts AC Coil complete all as specified and directed.

3

-

-

... More
S&F in repair of Thermal Overload Relay 28-46 A, MN12 Type complete all as specified and directed.

2

-

-

... More
Supply and fix in repair contactor 70 Amps, 3 Pole , CM 70, AC 3 type suitable for switching electrical power circuit as per site requirement complete all as specified and directed by Engr-in-Charge.

2

-

-

... More
M & L for disconnecting Actuator make: Auma epac from o/p pipe supply, mannual and automatic valve control for complete servicing and cleaning including check screw type termination compartment connection, motor wiring connection, switch compartment of limit and torque switches, grease filled housing, worm gearing, worm shaft, springs on worm shaft, lever and hand wheel, mounting flange , power supply module, relay module, thermal overload protection, check blinker switch wiring connection for running indication, adjustable disc in mechanical position indicator, reduction gear unit, greasing for hammer blow, check space heater connection for continuous duty, thermo switches to protect motor against over heating, sensor for actuator, check reversing contactor connection, fuse connection, automatic phase correction, stem nut, plug sleeve,cable gland, dog coupling, replace anti condensation, hand wheel spring push mechanism if required, including welding work for leakage and complete testing all as specified and directed.

1

-

-

... More
M & L for Scrapping old paint from motor pump of capacity 125/270HP, coupling guard MS common base frame, connected pipe line, starter, LT Panel and any steel structure inside fire pump house at jetty area and painting two coats of synthetic enamel paint of approved quality and colour as per existing detailed below all as specified and as directed, for the following:- (a)Motor pump (b) Coupling guard and motor air grill (c) Common base frame, (d) LT Panels/control panels (e) connected pipe lines.

1

-

-

... More
M & L for disconnecting elctric motor from Actuator make: Auma epac suitable for opreating 3 phase, 415 volts, 50 Hz, induction motor shall be totally enclosed non ventilated type and motor housing and covers to be made of sea water resistant aluminum, F class insulation (155 degree) for cutting/removing the existing burnt winding and rewinding by using super enamelled copper winding wire of existing wire gauge incl other allied items such as varnish tape, sleeve, greasing, bearing, bushes etc of suitable size, including neecessary repairing of dog coupling shafts if required and refixing the same in original position with testing and commissioningcomplete all as specified and directed.

1

-

-

... More
M & L for in replacement old unsv Earthing of PVC insulated unsheathed bright annealed bare copper conductor single core, 1.1kv, 10sqmm PVC round flexible industrial cable in green colour including suitable size of copper lugs complete all as specified and directed.

30

-

-

... More
S&F in repair, Cast iron sluice valve, class PN-1.6, ISI mark, flanged ends drilled having stainless steel spindle with cast iron wheel at top with nuts, bolts,washers and gaskets etc of 300 mm bore suitable for fire water line complete all as specified and as directed.

1

-

-

... More
All as per item no 81.00 here-in-above, but having dia of 200 mm.

2

-

-

... More
All as per item no 81.00 here-in-above, but having dia of 150 mm.

2

-

-

... More
All as per item no 81.00 here-in-above, but having dia of 100 mm.

3

-

-

... More
M&L in repair, Non Return Valves (NRV) dia of 100mm, PN16, screwed flanged end DI/CI type as per site require, bolted type as per existing make including all connected acessories suitable for heavy duty fire water line complete all as specified and directed.

2

-

-

... More
All as per item no 85.00 here-in-before, but having dia of 150 mm.

2

-

-

... More
All as per item no 85.00 here-in-before, but having dia of 200 mm.

1

-

-

... More
All as per item no 85.00 here-in-before, but having dia of 300 mm.

2

-

-

... More
M&L in repair Gear Operated butterfly valves of size 300 mm, PN 16, screwed flanged end DI/CI type as per site require, as per existing make including connected acessories suitable for heavy duty fire water line all as specified and directed.

2

-

-

... More
All as per item no 89.00 here-in-before, but having dia of 200 mm.

1

-

-

... More
All as per item no 89.00 here-in-before, but having dia of 150 mm.

2

-

-

... More
S&F in repair, Duct Iron pipe dia of 300 mm having screwed flanged end, including necessary fitting such as minimum 3 mm thickness flange rubber gasket, joint, bend, elbow, Nut bolts laying in tunnel complete all as specified and directed.

6

-

-

... More
All as per item no 92.00 here-in-before but dia of 200 mm.

15

-

-

... More
All as per item no 92.00 here-in-before but dia of 150 mm.

12

-

-

... More
All as per item no 92.00 here-in-before but dia of 100 mm.

18

-

-

... More
M&L, Cement concrete 1:2:4, type B-1 (using 20 mm graded crushed stone aggregate) as in support of, foundation and hard standing, finishing surfaces even and fair without using extra cement all as specified and as directed.

1

-

-

... More
M&L for CI/DI Special fittings of any type ISI marked such as bends (any type, radius and angle), Taper any type, (straight, bend, increasing, decreasing or double socket etc), Tee pieces single branch. "Y" junction, double branch, cross (all socket or socket and spigot), collar, caps and plugs upto 300 mm bore complete all as specified and directed by Engineer-in-Charge.

760

-

-

... More
M&L for repair to water leakage with high pressure from joint/valve/end flanged of heavy duty DI/CI Pipe having dia of 100 mm to 350 mm, fixed on floor and upto 1mtr height from floor inside tunnel and pump house at Pier I, including cutting pipe, nut bolts as per existing size, rubber or fiber board gasket, flanged end cover plate etc. replace if as required at site and making good/ leakless the existing joint, testing the joint complete all as specified and as directed. Note:- welding/cutting equipment shall be brought at site for joint by the Contractor and the cost for the same is deemed to be included in the rate.

10

-

-

... More
Supply & Fixing in repair, Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint, complete all as specified and as directed.

4

-

-

... More
M&L for Dismantling, Lifting up/out vertical mounted, drainage submersible grinder pump/ High trade or low trade waste water pump of capacity 12.5HP/15HP, head 59 meter, cast iron body, from bottom of tunnel sump tank located at pier-1, depth upto 5 mtr Make of MBH, including connected pipe connection/delivery lines, nuts, bolts, washer etc for repair/replacement of unserviceable spare parts including transportation to the workshop and re-installing the same after repair work & testing all as specified and as directed.

4

-

-

... More
M&L for complete overhauling of drainage submersible grinder pump of capacity 12.5HP, head 59 meter, cast iron body, Make: ABB for general inspection of impeller, shaft all bearings and sleaves, and re-installation of Pump after replacing all sleaves, bearings,seals and with SS nut bolts, metalising the shafts and re threading bottom plate by lathe work including body repairs, welding works and complete testing all as specified and as directed.

4

-

-

... More
M&L for Opening of 3 phase, 440 Volt motor of 12.5 HP capacity submersible grinder pump, 1486 rpm / High trade or low trade waste water pump of existng Make or cutting/removing the existing burnt winding and rewinding by using super enamelled copper winding wire of existing wire gauge incl other allied items such as varnish tape, sleeve, greasing, bearing, bushes etc of suitable size, including neecessary repairing of rotor shafts if required with testing and commissioning complete all as specified and directed. Note:- Rates deemed to be included for decoupled and coupling pump with motor, the cost of transportation charges for carrying the motor/pump from site to workshop and back, Nothing extra shall be admissible.

4

-

-

... More
M&L for replacing, Lubricating oil for CNE 14x7 Stage type vertical mounted pumps, all as specified and directed.

70

-

-

... More
M&L in repair for Carbon steel body three piece ball valve with RF flanges dia of 100 mm, max rated pressure 40 bars, stainless ball, lokable handle, stem seal with PTFE ring and O-ring FKM, axial blow out proof coating with black painting colour suitable existing line including taking out old damage valve complete all as specified and as directed.

10

-

-

... More
S&F, in repair UPVC heavy duty pipes of pressure rating 8 to 10 kgf/sqcm, fixed to walls, ceilings or in floors etc. dia of 110 mm with necessary fittings such as coupler, joint, bend, elbow complete all as specified and as directed.

24

-

-

... More
Manning and Operation of Fire pumps house installation at pier -01 jetty area (NSRY), in 03 (three) shifts of 8 hours by One Nos skilled electrician/ Fitter general mechanic operator per shift of 08 hours (Total 03 Nos Fitter general per day) and One Nos semi skilled/Helper per shift of 08 hours (Total 03 valve operator per day), each on all days including Sundays and holidays including minor maintenance / checks, all as specified and directed by Engineer-in-Charge. The installation comprises of following equipments :-

11

-

-

... More
(a) Fire main pump, 14 x 7 stage vertical type, 200 KW/270 HP, Head- 110 mtr, discharge - 180 cum/Hr, RPM-1485 Make - Mather + platt , coupled with 3 Phase squirrel cage Induction motor, RPM-1485,

-

-

-

... More
(a) Fire jockey pump 14 x 7 stage vertical type, 90 KW/125 HP, Head- 110 mtr, discharge - 180 cum/Hr, RPM-1485 Make - Mather + platt , coupled with 3 Phase squirrel cage Induction motor, RPM-1485, Make- ABB - 2 Nos.

-

-

-

... More
(b) Drain/sewage water Lifting pump capacity of - 12.5 HP, Head- 11.5mtr, discharge - 10 cum/Hr Make -M/S MBH Pumps coupled with Induction motor 3 phase, 415 volt - 14 Nos.

-

-

-

... More
(c) Main switch control panel consist 13 folder (1 to 13) including main incomer of 4000 Amp capacity with 200 KW VFD control Panels of capacity 250 Amps, 415 Volts - 02 Nos, including, control wiring & all connected accessories - 1 set

-

-

-

... More
(d) 3 Phase, 415 volt PLC Panel for 3 phase motor - 02 Nos

-

-

-

... More
(e) CI/DI piping Network with sluice/gate/butterfly valves of jetty fire pump house and connected area at NSRY.

-

-

-

... More
(f) Soft starter for sewage pump of 12.5 HP capacity-07 Nos

-

-

-

... More
(g) Low pressure waste water pumps -10 Nos and High pressure waste water pump- 02 Nos

-

-

-

... More
Notes for item No 1 above :-

-

-

-

... More
(a) One Nos skilled electrician/ Fitter general mechanic operator per shift of 08 hours (Total 03 shifts per day) havining minimum ITI qualification in respective trade from Govt recognised institute with adequate knowledge with minimum two years experience in maint & operation of water supply installation. The operator must be competent to carry out the minor Maint of water supply installation all as directed by Engr-in-Charge.

-

-

-

... More
(b) One Nos Valve men per shift of 08 hours (Total 03 shifts per day) having minimum ITI qualification in respective trade from Govt recognised institute with adequate knowledge with minimum two years experience in maint & operation of water supply pipes & valves. The operator must be competent to carry out the minor maint of water supply pipe line & valves all as directed by Engr-in-Charge.

-

-

-

... More
(c) The unit rate quoted shall be demmed to include for daily minor/routine maintenance of trouble free functioning of installation, checking and rectification of any water leakage, loose connection, cleaning and general up keep of pump house room and area around it

-

-

-

... More
(d) Power supply for operation of electric equipments & pump sets shall be made available by the department free of cost.

-

-

-

... More
(e) The contractor shall not employ same tradesman continuously for more than 11 months during the contract period of 11 months.

-

-

-

... More
(f) The unit rate quoted shall deemed include for maintenance for earthpits, cutting & removing of vegitation and upkeep of the surrounding area all around the bldg upto 6m from the plinth protection all as directed by Engr-in-Charge. In case of failure, a penalty of Rs 2000/- per month per installation will be levied and recovered from dues.

-

-

-

... More
(g) The contractor shall provide 02 pair uniforms (Paint, shirt, shoes, cap, belt and name plate) to each operator/valveman within 15 days from the date of commencement of the contract and design of uniform shall be approved by Engr-in-Charge. In case of failure, a penalty of Rs 1200/- per uniform shall be recovered and levied from dues of contractor.

-

-

-

... More
(h) The rate quoted shall deemed to be inclusive of safety gear & required tools for minor maintenance. The contractor shall provide 02 Pairs of Gum Boot, 02 pair of helment & 02 Pairs of Hand Gloves & 01 set of complete tool kit (adjustable spanner, cutting pliers, pipe wrench, screw drivers, chargeable torch & tester etc) of reputed make as approved by Engr-in-Charge. In case of failure to provide tools kit & safety kit a penalty of Rs 5000/- per installation as mentioned under Item No. 1 shall be recovered and levied from dues of contractor.

-

-

-

... More
(j) The contractor shall maintain proper records of all kinds of daily, weekly, monthly, quarterly, half yearly and yearly or whatsoever maint is carried out during contract period in a binded book / register and shall obtain the signature of Engr-in-Charge every fortnightly. In case of failure to maintain proper records a penalty of Rs 1000/- per month per installation as mentioned under Item No. 1 shall be recovered and levied from dues of contractor.

-

-

-

... More
(k) In case of absence of operative staff, the contractor shall be liable to pay compensation at twice the cost of a day’s Manning & Operation derived from pro rata rate of Sch ‘A’ quoted rates.

-

-

-

... More
(l) The contractor shall pay the wages to the operator through e-payment i.e Aadhar linked bank accounts and credit to their bank account. The wages shall not be less than prevailing minimum wages fixed/ increased at time of payment by state Govt or central Govt whichever is more. The contractor shall pay the full wages of every month to the employees/operators within 07 days of next month without fail. If contractor fails to pay the wages to the employees/operators within 07 days of next month, a penalty of Rs 500/- per day per operator shall be recovered and levied from dues of contractor.

-

-

-

... More
(m) The contractor shall pay the full wages to the employees/operators and EPF to concerned authority as per existing rules and produce the necessary proof of the same before claiming/submission of RAR/Bill.

-

-

-

... More
(n) Each shift duration shall be 8 hours & duty timing shall be decided by Engr-in-Charge.

-

-

-

... More
(p) In case of any abnormal noise/complaint the plant should be put off same should be brought to the notice of Engr-in-Charge.

-

-

-

... More
(q) The operator shall check the gland, vibration, nut bolts daily & tightening up as and when required.

-

-

-

... More
(s) The operator employed by the contractor shall be capable of carrying out minor repair/maintenance & should have well experience in electrical panel, motor, pump set & fire fightings field etc.

-

-

-

... More
(t) The quoted rate is deemed to be inclusive of cleaning material like cotton waste, broomstick, ladder etc & contractor shall ensure general area cleanliness and upkeep of the installation on daily basis.

-

-

-

... More
(u) The routine preventive maintenance /checks shall be strictly carried out by the operator all as stipulated in the operation & maintenance manual.

-

-

-

... More
(v) The contractor shall maintain the attendance register, duty roaster and produce the same to Engr-in-Charge on daily basis. If contractor fails to produce the same, a penalty of Rs 1000/- per month per installation shall be recovered and levied from dues of contractor.

-

-

-

... More
(w) If user raised any complaint in verbal/writing on disciplene ground in respect of any operator, the contractor shall remove the said operator from his job/duty forthwith and provide the suitable replacement.

-

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements

Past Bidders
This list is curated from the bidders of the similar tenders in the past

Unlock the Tender details for free
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
  • Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
  • Awarded Ratexx%
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.