Military Engineer Services Tender
View complete overview of Goa MES Tender
Costs
EMD
₹ 40,000Document Cost
₹ 500Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2025_MES_706218_1Tender No
85936Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
... More
g) Dehydration and filtration of transformer oil from Transformer (s) to achieve di-electric strength not less than 40 KV on 4mm over gap for a period of one minute and testing of acidity of oil and dielectric strength (before and after dehydration / filtration) complete all as specified and as directed by the Engineer-in-Charge.
-
-
-
... More
Supply and fix in repair gate valve made of brass (heavy duty) both end threaded with wheel of size 25 mm.
2
-
-
... More
Excavation in trenches not exceeding 1.5 metre wide and not exc 1.5 metre in depth for foundation of pole / stay, or cable trenches and getting out in soft/loose soil complete all as specified and as directed by the Engineer in charge
110
-
-
... More
Material and labour galvanized iron tubing 100 mm bore (light grade) with all fittings for protection of cables, laid in trenches all as specified and as directed by the Engineer –in-charge (Note : Excavation and earth work will be measured and paid separately )
12
-
-
... More
Supply only LT termination porcelain bush of outdoor / indoor transformer of capacity ranging from 100 to 160 KVA as per site requirement.
2
-
-
... More
Removing excavated materials to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 metre above the starting point all as specified and as directed by the engineer –in- charge.
24
-
-
... More
Material and labour for taking up relaying HT UG Cable excluding necessary earth work , PCC cover sand cushning etc complete
100
-
-
... More
Supply and fix cable jointing kit for 11 KV(Earthed) grade cable for outdoor termination heat shrink type joint joint complete with jointing material and accessories suitable for 3 core XLPE armored AI conductor cable of size 50 Sq mm to 95 sqmm.
5
-
-
... More
d) Cleaning of LT and HT Bushing, Replacement of burnt out bushing stud made out of brass, washer, nut, porcelain bushing of existing size, terminals, oil indication glass of conservator, top gasket and drain valve etc as directed by the Engineer-in-Charge.
-
-
-
... More
Note :
-
-
-
... More
h) Top up new transformer oil up to desired level.
-
-
-
... More
All as per Item no 01 above but for capacity 100 to 160 KVA capacity
2
-
-
... More
Dehydration and filtration of transformer oil from Transformer (s), installed at various Sub Station (s) to achieve di-electric strength not less than 40 KV on 4mm over gap for a period of one minute and testing of acidity of oil and dielectric strength (before and after dehydration / filtration) complete all as specified and as directed by the Engineer-in-Charge. Note: (i) Contractor has to arrange the Necessary T & P for filtration plant including the power supply arrangement for run the filtration plant, No electricity will b provided by department for filtration plant. (ii) Contractor has to submit the details of di- electric strength of transformer oil before and after filtration.
4500
-
-
... More
f) Filling up the transformer with existing taken out transformer oil carefully,
-
-
-
... More
Supply and fix cable jointing kit for 11 KV(Earthed) grade cable for outdoor straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armored AI conductor cable of size 50 Sq mm to 95 sqmm.
4
-
-
... More
All as per item No. 4.01 above but capacity ranging 315 KVA to 400 KVA
1
-
-
... More
Material and labour for laying graded aggregate of size 20 mm in E/M installation all as directed.
20
-
-
... More
Material and labour for painting on new Mild steel plates, plain or chequered along with two coat of priming with red oxide and one finishing coat of synthetic enamel paint complete
250
-
-
... More
Material and labour for surface excavation at E/M installations ,main receiving substation yard not exceeding 30 cm deep and averaging 15 cm deep and getting out soft / loose soil removing shrubs, small trees height up to 1.0 Mtrs , removing the grass from route as directed , Note : (i) Rate includes removing all waste material and grass not exceeding 250 Mtrs distance from installation ,depositing where directed at a level not exceeding 1.5 Mtrs above the starting point and cleaning of yard , Complete all as specified and directed by EIC.(ii) Repeated cleaning in each installation shall be measured and paid separately with time interval of minimum 2 months.
2500
-
-
... More
Supply and fix in replacement DO fuse unit 11 KV suitable for vertical mounting fixed type , including complete with 6 insulators and drop out fuse elements complete including connection from Incoming/ Out ground HT Cable termination and Bus Bar complete all as specified and directed.
2
-
-
... More
Returning filling in including spreading, leveling watering and well ramming in layers not exceeding 25 cm in soft loose soil complete all as specified and as directed by the Engineer in charge
86
-
-
... More
Material and labour for painting 4 pole structure complete with painting HT pole including preparation of old painted surface of PCC pole of height Max up to 9.5 Mtrs from ground / pole copping and painting with cement base paint and applying new coating along with two coat of priming with red oxide and one finishing coat of synthetic enamel paint on surfaces of cross arm / support frame structure of 4 pole complete all as specified and as directed.
9
-
-
... More
(v) Cost of copper winding wire shall be measured and paid separately
-
-
-
... More
b) Opening of top cover of transformer and keeping aside and re-fixing the same after tightening of all LT and HT terminal joints (both inside and out side of transformer) including supply and fixing of all gasket of bushing (6 mm thick rubberized cork sheet) to make leak proof.
-
-
-
... More
Supply and fix cable jointing kit for 11 KV(Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armored AI conductor cable of size 120 sq mm.
2
-
-
... More
Material and labour for Repair / servicing of transformer in situ of any make, any type, any capacity 315 KVA to 400 KVA (step up or down) 11 KV / 0.433 Volt installed at various location and in comprising with the following works :-
1
-
-
... More
iii) Any minor parts such as gasket, nuts, bolts, washers etc that are required to be replaced for satisfactory repair shall be provided by the contractor and rate for the same shall be deemed to be included with the unit rate.
-
-
-
... More
Supply and fix galvanised iron strip 32x6 mm as earhing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as connected to earthing test point/equipment all as specified .
50
-
-
... More
Supply only HT 11 KV terminals stud with nuts, washers made out of brass of suitable size as per site requirement for transformer ranging from 100 KVA to 160 KVA
3
-
-
... More
Material and labour for laying grade aggregate of size 40 mm in E/M installation all as directed.
20
-
-
... More
Material and labour for preparation of old painted surface of on Mild steel plates, plain or chequered plate cable protection cover /steel surfaces of cross arm / support frame and apply new coating along with two coat of priming with red oxide and one finishing coat of synthetic enamel paint complete
300
-
-
... More
All as per item No. 4.04 above but capacity ranging 315 KVA to 400 KVA
2
-
-
... More
Supply only following items to incorporate against different items of Sch ‘A’ (Fixing charges are deemed to be included with connected Sch ‘A’ items where the parts are required to replace :-
-
-
-
... More
Supply and fixing breather assembly for transformer of capacity 100 KVA to 250 KVA including taking down unserviceable one all as specified and directed by the Engineer-in-Charge.
4
-
-
... More
Material and labour for laying graded aggregate of size 12.5 mm in E/M installation all as directed.
20
-
-
... More
Material and labour for earthing complete with galvanised steel earth plate 600x600x6mm thick buried directly in ground (Earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level, connected to galvanised steel strip of size 32 x 6 mm as earthing lead up to equipment/ pole/panel by means of bolts, nuts, check nut and washers of galvanised iron or steel as shown in electrical plate No-3 of SSR Part I, including excavation and earth work in any type of soil, GI pipe 40 mm dia light grade as protection pipe, charcoal filling, common salt ,PCC 1:3:6 type CI using 20 mm graded stone aggregate as in chamber, MS angle iron frame 40x40x6mm and RCC precast cover 40mm thick (1:2:4) type B-1 using 20mm dia graded stone aggregate reinforced with 8mm dia TMT bars @ 75 mm c/c both ways with MS handle 12mm dia, CI funnel and wire mesh, 20mm dia GI pipe medium grade for watering, connected to earth test point including testing complete all as specified and directed. Note : GI Strip of size 32 x 6 mm from earthing to HT Panel/ test terminal along with protection GI Pipe 40 mm dia up to 7.5 Mtrs shall be included in the quoted rates.
5
-
-
... More
All as per item No. 4.10 above but capacity ranging from 315 KVA to 400 KVA.
2
-
-
... More
Supply and fix cable jointing kit for 11 KV(Earthed) grade cable for outdoor termination heat shrink type joint type joint complete with jointing material and accessories suitable for 3 core XLPE armored AI conductor cable of size 120 sqmm to 185 Sq mm
2
-
-
... More
Supply and filling silica gel in breather assembly of 50 KVA to 500 KVA capacity transformer all as specified and directed by the Engineer-in-Charge.
20
-
-
... More
Supply and fix cable jointing kit for 11 KV(Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armored AI conductor cable of size 50 Sq mm to 95 sqmm.
4
-
-
... More
Supply, laying, jointing and commissioning of cable XLPE insulated circular aluminium conductor, conductor screen with extruded semi conducting compound, insulation screening with extruded semi conducting compound in combination with copper tape cores laid up, inner sheath of PVC tape, galvanised steel flat strip armoured and overall PVC sheathed cable conforming to IS ,11000 volts (E), grade cross sectional area 95 sqmm 3 core complete all as specified and directed.
150
-
-
... More
S & F danger notice plate of 1.6 mm thick mild steel sheet , vitreous enameled white , with letters figures and conventional skull and bones in signal red colour and fixed with MS clamps on HT poles / Cross arm sections , bolts and nuts of approved size for HT 25 X 20 cm complete all as specified
20
-
-
... More
Supply only HT porcelain bush set 11 KV for out door transformer of any size as per site requirement of capacity ranging from 100 to 160 KVA
1
-
-
... More
Material and labour for replacement of copper winding wire for HT/ LT side of distribution transformer of voltage rating 11 KV/ 440 Volt of rating up to 400 KVA including taking down existing widing wire from burned out transformer complete all as directed.
80
-
-
... More
All as per item No. 4.01 above but capacity ranging from 200 KVA to 250 KVA
1
-
-
... More
Supplying and laying reinforced precast concrete cable cover, class HV, Type 1, flat, size 300mmx l80mm x 40mmcomplete.
800
-
-
... More
Dismantling cross arm of MS channel or angle section etc complete and setting aside for credit
1
-
-
... More
Material and labour for Mild steel plates, plain or chequered, 5mm thick or over in thickness Fe 410-W (Gde-E- 250) quality-A
1500
-
-
... More
Supply and fixing breather assembly for transformer of capacity 315 KVA to 400 KVA including taking down unserviceable one all as specified and directed by the Engineer-in-Charge
2
-
-
... More
Material and labour Lifting the existing precast cement concrete cable cover/Serviceable bricks obtained during excavation of existing cable and laying the same covers, in trenches for cable protection, complete all as specified and as directed by the engineer-in -charge. ( For SL Item No- 05)
550
-
-
... More
Supply and fix in replacement out door type gang operated air-break switch 11 KV suitable for vertical mounting fixed type , including operating mechanisem worked from ground level complete with 9 insulators of rating 200 Amps complete including connection from Incoming/ Out ground HT cable termination and Bus Bar complete all as specified and directed.
3
-
-
... More
a) Taking out transformer oil up to required level and keeping in empty container with safe custody for re-use after Dehydration.
-
-
-
... More
c) Checking of tap changing switch connections and tightening and soldering properly for smooth functioning.
-
-
-
... More
Supply and fix in repair gate valve made of brass (heavy duty) both end threaded with wheel of size 20 mm.
2
-
-
... More
ii) New transformer oil shall be measured separately under respective items..
-
-
-
... More
All as per Item no 01 above but for capacity 200 KVA to 250 KVA capacity
2
-
-
... More
All as per item No.4.10 above but capacity ranging from 200 KVA to 250 KVA.
2
-
-
... More
Material and Labour for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under aluminium coat and one aluminium finishing coat of paint complete for base support frame for water tanks at roof top/ground floor complete all as specified and as directed by Engineer - in - Charge.
1
-
-
... More
iv) Cost for dehydration and filtration of transformer oil shall be shall be deemed to be included with the unit rate.
-
-
-
... More
Supply only LT terminals stud made out of brass with nut and washer, suitable for transformer of capacity ranging from 100 to 160 KVA
3
-
-
... More
e) Cleaning of oil tank of transformer, conservator, core, vent pipes, cooling pipe / fins by desludging, decarbonizing and finally washing with transformer oil and drying complete.
-
-
-
... More
All as per item No 4.07 above but capacity ranging form 315 KVA 400 KVA
2
-
-
... More
Supply and filling up transformer oil (Grade ‘B’) for topping up / complete replacement of oil in existing transformer , installed at various Sub Station , having Di-electric strength not less than 40 KV on 4mm over gap for a period of one minute complete all as specified and as directed by the Engineer-in-Charge. Note: The New oil shall be brought in to sealed container at site during the commencement of work )
Make : GULF/INDIAN/OIL/HP
840
-
-
... More
i) Replacement of unserviceable bushing (HT/LT) and terminals shall be measured and paid separately under respective item, under respective items.
-
-
-
... More
Material and labour for disconnecting the transformer 11 KV/ 440 Volt of Rating from 100 KVA to 400 KVA from existing sub station Indoor/ Out door type after taking Prior shut down , and transport to factory for repair / replacement of any spare / rewinding and install in existing location with HT /LT cable and earthing connection complete with necessary T & P . Rate include cost of transportation from INS Mandovi to factory and Back to HT Substation inside the INS Mandovi and necessary installation at Substation.
1
-
-
... More
S & L quarry ' M ' sand for cushioning for cable protection in trenches 8 cm before laying cable and 15 cm deep over the cable complete
( Note: Punned thickness shall be taken for measurement)
22
-
-
... More
All as per item No 4.04 above but capacity ranging from 200 KVA to 250 KVA
2
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements
Past BiddersThis list is curated from the bidders of the similar tenders in the past
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%
- Bidder NameThis Information is for unsubscribed user This Information is for unsubscribed user
- Awarded Ratexx%