Military Engineer Services Tender
View complete overview of Goa MES Tender
Costs
EMD
₹ 1,15,000Document Cost
₹ 1,000Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_MES_669918_1Bid Award Id
ViewTender No
85812/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
BOQ Items
Supply, jointing & testing in repair of Indoor end termination cable joininting kit, heat shrinkable type 11 KV HT joint kit suitable for PVC / XLPE insulated stranded aluminium conductor of size 3 core 120 sqmm to 185 Sqmm all as specified and as directed. Make : Raychem Cat No .EPKT 4685 or equivalent as approved by GE.
4
-
-
Supply, jointing & testing in repair Indoor end termination cable joininting kit, heat shrinkable type 11 KV HT joint kit suitable for PVC / XLPE insulated stranded aluminium conductor of size 3 core 400 Sqmm all as specified and as directed. Make : Raychem Cat No .EPKT 4685 or equivalent as approved by GE.
2
-
-
Supply, jointing & testing in repair of straight through type cable joininting kit heat shrinkable 11 KV HT joint kit suitable for 3 core 95 Sqmm PVC / XLPE insulated stranded aluminium conductor all as specified and as directed. Make : Raychem Cat No HVS-3-2152 or equivalent as approved by GE.
2
-
-
Supply, jointing & testing in repair of straight through type cable joininting kit heat shrinkable 11 KV HT joint kit suitable for 3 core from 120 Sqmm to 185 sqmm PVC / XLPE insulated stranded aluminium conductor all as specified and as directed. Make : Raychem Cat No HVS-3-2152 or equivalent as approved by GE.
4
-
-
Supply, jointing & testing in repair straight through type cable joininting kit heat shrinkable 11 KV HT joint kit suitable for 3 core 400 Sqmm PVC / XLPE insulated stranded aluminium conductor all as specified and as directed. Make : Raychem Cat No HVS-3-2152 or equivalent as approved by GE.
2
-
-
M&L for Testing of faulty HT UG cable upto 400 Sqmm by checking the insulation resistance using 5000v / 10000v fault insulation locator tester, identify any number of cable fault in a single stretch (from source to load) having minimum length of 1000 RM and pin point the fault location complete all as specified & as directed. Note: In single stretch having minimum length 1000 RM whatsoever Nos of fault shall be paid as each job
4
-
-
M&L for Testing of faulty HT UG cable upto 400 Sqmm by checking the insulation resistance using 5000v / 10000v fault insulation locator tester, identify any number of cable fault in a single stretch (from source to load) having length more than 1000 RM and pin point the fault location complete all as specified & as directed. Note : In single stretch having length more than 1000 RM whatsoever Nos of fault shall be paid as each job
4
-
-
M&L for testing of resistance by using earth test resister of earthpits of transformer,panels etc after testing the report shall be furnished in standard format approved by Engineer-in Charge.
30
-
-
M & L for Opening the front and rear cabinet of the RMU panel 3 way / 4 way / 5 way 630 / 800 Amps 11 KV de-carbonizing moving and fixed contacts if required and including lubricating, checking the pressure of SF-6 gas, inspecting the wiring of micro processor EF / OC relay, tripping coil electrical and checking for manual / auto tripping system, checking cable in and out position, replacing unserviceable nuts , bolts, cleaning the entire panel and placing the SF-6 VCB and isolating unit in its original position complete all as specified and directed. Notes:-
(i) Spares will be measured and paid seperately.
(ii) The quoted rate is deemed to be included for copper wire, nuts and bolts, CRC spray, grease and other cleaning materials.
10
-
-
Supply and fixing in repair plug in type voltage presence indicator system (VPIS) type WIM for 11 KV RMU complete all as specified and directed
5
-
-
Supply and fixing in repair SF-6 ring main unit fuse 11 KV by opening fuse canisters of RMU positioned behind interlocking cover complete all as specified and as directed
12
-
-
Supply and fixing in repair terminal contact piece with silicone coupling for SF-6 ring main unit 11 KV by opening the terminal cover complete all as specified and directed
5
-
-
Supply and fixing in repair trifurcation boot 11 KV capacity for cable termination joint of RMU incoming and outgoing terminals complete all as specified and directed
5
-
-
Supply and fixing in repair HT bushing with gaskit for SF-6 Ring main unit 11 KV complete all as specified and directed
12
-
-
M&L callibration of microproccessor E/F and O/C relay of RMU complete and including calibrating with portable relay test kit to set time and fault level and adjustment of setting with according to load & time with main tech area power house and including replacement of relay battery for proper functioning complete all as specified and directed.
12
-
-
S&F in replacement of earth fault protection and indicator relay for ring main unit and including callibrating the relay with existing load and tripping timming complete all as specified and directed
10
-
-
S&F in replacement of pottential transformer (PT) 3 phase, 3 limb indoor type primary voltage 11 KV and secondary voltage 110 volts type VA class complete all as specified and directed
3
-
-
S&F in replacement of PT bush housing for connecting to voltage transformer (PT) to RMU panel 3 phase, 3 limb indoor type and including necessary connecting materials i.e. bus bar, nuts and bolts etc, complete all as specified and directed.
3
-
-
Supply only SF-6 gas for filling in RMU/SF6 breakers all as specified and directed.
10
-
-
S & Fixing in replacement & testing and commissioning tripping coil operated by ac or dc supply complete with electric copper wire of suitable all as specified and directed
9
-
-
S & Fixing in replacement &testing and commissioning closing coil operated by ac or dc supply complete with electric copper wire of suitable all as specified and directed
9
-
-
S & Fixing in replacement bakelite kitkat complete with HRC fuse 2-20 amps of suitable suitable for HT panel grey in colour including necessary nuts for fixing in position all as specified and directed
10
-
-
M&L for Strip Opening the busbar of the HT 11 KV VCB panel from 800 Amps to 2000 Amps, removing the old teared/ unsv insulation from the bus bar,checking the IR value before fixing the HT sleeve and refixing the heat shrinkable insulating tape sleeve suitable for 11 kv busbar not less than 3mm thick having dielectric strength not less than 15kv/mm and HT insulation tapefor CT/ PT connection complete with a certificate from NABL lab. and checking the IR value before testing and commissioning the bus bar all as specified . Note :- Test sheet of IR value shall be submitted by the contractor, no cost extra shall be paid by the department and all testing requirement shall be borne by the contractor including transportation and T&P.
7
-
-
M&L for Servicing of dry cast Transformer upto 2000KVA of Make:Voltamp, 11 KV/433V by disconnecting incoming & outgoing power supply, opening up, cleaning the transformer internally & externally with the electric blower to remove all the dust deposition inside the cabopy of the transformer,inspecting all the metering equipments, tightening all electrical connections, checking & recording insulation resistance on both LT & HT sides, checking & recording earth resistance complete, inspecting the duct type bus bar chamber on LT side for any loose connection and tightening the nuts and bolts through authorised service engineer of OEM all as specified & as directed. Note:- a) The above quoted rate includes dismantling of the existing HT cable connected with the transformer and carrying out the meggering test on both HT/LT side and reconnecting the existing HT cable with the transformer.
b) The above quoted rate includes all the T&P required for testing and servicing work all as specifed and direcetd.
c) The above quoted rate includes all the minor parts required for the servicing i.e. Nuts and bolts, washers, cotton waste, grease etc.
d) The above quoted rate includes the rectifying the vibration noticed in the trasnformer by providing backelit insulating wedges at required position and testing the transformer complete all as specified and directed.
6
-
-
M&L for Servicing of dry cast Transformer upto 3500KVA of Make:Kirloskar, 11 KV/433V by disconnecting incoming & outgoing power supply, opening up, cleaning the transformer internally & externally with the electric blower to remove all the dust deposition inside the cabopy of the transformer,inspecting all the metering equipments, tightening all electrical connections, checking & recording insulation resistance on both LT & HT sides, checking & recording earth resistance complete, inspecting the duct type bus bar chamber on LT side for any loose connection and tightening the nuts and bolts through authorised service engineer of OEM all as specified & as directed. Note:- a) The above quoted rate includes dismantling of the existing HT cable connected with the transformer and carrying out the meggering test on both HT/LT side and reconnecting the existing HT cable with the transformer.
b) The above quoted rate includes all the T&P required for testing and servicing work all as specifed and direcetd.
c) The above quoted rate includes all the minor parts required for the servicing i.e. Nuts and bolts, washers, cotton waste, grease etc.
d) The above quoted rate includes the rectifying the vibration noticed in the trasnformer by providing backelit insulating wedges at required position and testing the transformer complete all as specified and directed.
2
-
-
M&L for Servicing of dry cast Transformer upto 800KVA of Make:AMES IMPEX ELECTRICALS(P) Ltd, 11 KV/0.188V by disconnecting incoming & outgoing power supply, opening up, cleaning the transformer internally & externally with the electric blower to remove all the dust deposition inside the cabopy of the transformer,inspecting all the metering equipments, tightening all electrical connections, checking & recording insulation resistance on both LT & HT sides, checking & recording earth resistance complete, inspecting the duct type bus bar chamber on LT side for any loose connection and tightening the nuts and bolts through authorised service engineer of OEM all as specified & as directed. Note:- a) The above quoted rate includes dismantling of the existing HT cable connected with the transformer and carrying out the meggering test on both HT/LT side and reconnecting the existing HT cable with the transformer.
b) The above quoted rate includes all the T&P required for testing and servicing work all as specifed and direcetd.
c) The above quoted rate includes all the minor parts required for the servicing i.e. Nuts and bolts, washers, cotton waste, grease etc.
d) The above quoted rate includes the rectifying the vibration noticed in the trasnformer by providing backelit insulating wedges at required position and testing the transformer complete all as specified and directed.
1
-
-
M&L for carrying out caliberation of HT VCB panel of capacity 1250 Amps of make: ABB after obtaining shut down from the Engr-In-Charge and disconnecting the existing incomer HT cables connected with the VCB, Caliberation of the earth fault realy and overload realy as per directions of Engr-In-Charge, checking of all alignment of VCB isolating contacts, servicing of operating mechanism including tripping and closing system of the breakers, dehydarting by spraying of anti corrosive and anti moisture liquid, decarbonising of panel by angle grinder/emery paper, bus section and circuit section incl incoming/outgoing cable and necessary HT insulation at joints, removing perished monoplus compound cleaning and reinsulating with HT taps wherever necessary with and incl replacement of worn out/defective spares like tesnion springs, tortion springs, nut bolts, washers of suitable size etc. Note:-
(i) The above quoted rate deemed to include all minor spares etc.
(ii) Any burnt out/defective items like movingfixed contacts, tripping coils, earth fault realy etc will be meausured and paid seperately under appropriate items of BOQ.
(iii) Spare parts required other than mentioned in here -in-after shall be deemed to be incl in the quoted rate
(iv) The caliberation test certificate to be submitted after servicing & testing in presence of Engr-In-Charge.
7
-
-
M&L for maintenance and overhauling of 11 KV VCB including opening, checking, cleaning wih CTC, cleaning wiping of insulating components, primary & secondary circuits, spouts, busbars, supports, CT, PT,check oil for leaking, cleaning contact tips, cover the exposed portion of busbsr with HT tape & heat shrinkable sleeves, cleaning of bushes, spout insulators for visible crack, tightness old fasteners holding moving contacts, check and correct the buffer gap adjustment & mechanism settings, testing, cleaning & overhauling of complete operating mechnism for smooth functioning, checking of control panel wiring for operation and protection for tripping & closing & rectifying the defects including Deoxidizing of all electrical contacts replacement unserviceable wiring with ferrule & lugs, reassembling & testing of complete VCB all as directed.
Note: (i) Required part for replacement will be measured and paid under relevant item
(ii) Cost of labour & cleaning material like Urethrene, gasket remover, lubricant etc for replacement is deemed to be included in quoted rate
7
-
-
Supply and fixing in replacement 24 pin plug assembly suitabe for ABB HT Breakers of cap 1250 Amps 11KV all as specified.
2
-
-
Supply and fixing in replacement cable stem article suitabe for ABB HT Breakers of cap 1250 Amps 11KV all as specified.
2
-
-
Supply and fixing in replacement contact system VD4-1250Amps (12 finger) suitabe for ABB HT Breakers of cap 1250 Amps 11KV all as specified.
2
-
-
Supply and fixing in replacement front cove/shutter assembly suitabe for ABB HT Breakers of cap 1250 Amps 11KV all as specified.
2
-
-
Supply and fixing in replacement spring drum suitabe for ABB HT Breakers of cap 1250 Amps 11KV all as specified.
2
-
-
Supply and fixing in replacement spring v4207 suitabe for ABB HT Breakers of cap 1250 Amps 11KV all as specified.
2
-
-
Supply and fixing in replacement roller chain v4208 suitabe for ABB HT Breakers of cap 1250 Amps 11KV all as specified.
2
-
-
Supply and fixing in replacement torsion spring V4710/4711 suitabe for ABB HT Breakers of cap 1250 Amps 11KV all as specified.
2
-
-
Supply and fixing in replacement Lever assembly V6014 suitabe for ABB HT Breakers of cap 1250 Amps 11KV all as specified.
2
-
-
Supply and fixing in replacement motor cut off switch suitabe for ABB HT Breakers of cap 1250 Amps 11KV all as specified.
2
-
-
Supply and fixing in replacement spring charging motor suitabe for ABB HT Breakers of cap 1250 Amps 11KV all as specified.
2
-
-
Supply and fixing in replacement breaker control switch (Triple-neutral-close) 4 Pole/4 Terminal 660 V AC/DC pistol grip type complete complete all as directed and specified.
4
-
-
Supply and fixing in replacement of vacuum inturupter 1250 Amps, 11 KV rating suitable for HT VCB of make ABB complete all as directed and specified.
6
-
-
M&L for replacement of old unsv digital voltmeter, DC, with phase range 200mv to 600V with built in resistance of size 96x96mm, accuracy class 0.5 complete complete all as directed and specified.
4
-
-
M&L for replacement of old unsv digital ammeter, digital type, of size 96x96mm, accuracy class 0.5 complete complete all as directed and specified.
3
-
-
M&L for replacement of old unsv earth fault and over load realy suitable for HT vcb of cap 1250 Amps as per existing make of abb all as specified.
4
-
-
M&L for Taking out ACB of capacity upto 4000Amps /5000 Amps of Make: Merlin Gerin or any existing make, 3pole , 415 volts,125 KA indoor type from its sub cubicle and carrying out routine maintenance as per manufacturer maintenance manual, examine the moving isolating contacts for any discolouration, cluster contacts, remove the arc chutes, check the SMC moulding are intacts, examine the moving contacts main contacts silver tips, spring mechanism, clean all contacts with a suitable solvent and contacts regreased with HP multipurpose grease, all contacts setting checked, readjusted if required, and regreased with HP multipurpose grease, all tripping device like manual trip, under voltage, shunt trip release, over current and earth fault tripping device to be tested, readjusted and confirm all tripping device is in healthy condition, check and record IR value of ACB, with 1.1. KV LT megger calibrating ground fault / short ckt, overload relays for tripping & timing complete and rendering test report all as specified and as directed.
13
-
-
NOTES for item Nos 48: (i) The scope of work includes following :- (a) Inspection & cleaning the mechanism house
(b) Operation of door interlock, interlocking plate & shutter operation inside of panel.
(c) Check the Mechanical ON-OFF function, electrical & mechanical operation and damage part of VCB/ACB.
(d) Re-greasing and oiling of breaker mechanism, adjustment of various mechanism setting as required, checking contact tightness, contact erosion pins, manually vaccum check of VCB/ACB.
(e) Racking-Rack out operation in Test & service position of VCB/ACB trolley.
(f) Megger test (IR value - 1KV / 2.5KV) E-RYB, RY-YB, BR-R'R, Y'Y, B'B.
(g) CRM Test (contact resistance) of Vacuum Interrupter R, Y, B in on condition outside of panel.
(h) Time test of contract pole by Test kit (in mili second).
(j) Function of closing coil, Trip coil, spring charging motor, auxiliary contact, limit switches etc.
(k) Checking & lubrication of various interlocks.
(l) Submission of test report in standard format of vacuum circuit breaker.
-
-
-
(ii) Tools and plants and testing instruments required for servicing of VCB/ACB shall be arranged by the contractor.
(iii) The unit rate quoted shall be deemed to include the cost of grease, lubricating material, cleaning material etc as required.
(iv) After servicing, report shall be furnished in standard format approved by Engineer-in-Charge.
-
-
-
Supply and fixing in replacement digital LCD/LED diplay multifunction meter suitable for ACB of capacity 4000 Amps of MAKE: Merlin Gerin having digital display of ampheres, voltage, including setting for the tripping current and over voltage in case of ant earth fault or over current in the circuit all as specified nad directed by Engr-In-Charge.
7
-
-
Supply and fixing in replacement of MCCB 3 Pole, 415 V, with Microprocessor release 160 Amps with breaking capacity 36 KA including all connected accessories complet complete all as directed and specified. Note:- The above rate quotate includes the neccessery materials required for fixing of MCCB with the existing busbar of the LT panel alongwith carring out cutting drilling and joining work.
10
-
-
All as per ser Item No 50 above but having capacity of 250 Amps and breaking capacity 36 KA complete all as directed and specified.
7
-
-
All as per ser Item No 50 above but of size 630 Amps and breaking capacity 50 KA complete all as directed and specified.
2
-
-
Supply and fixing in replacement MCCB 3 pole, suitable for upto 1000 volts DC supply with microprocessor release adjustable type overload & short circuit setting including disconnecting the incoming/ outgoing cable connections and re-connecting with suitable aluminum lugs/ ferrules etc. after taking out the existing unserviceable and making good the disturbed surface for 630 Amps with breaking capacity 100 KA complete all as specified and directed. Make : Merlin Gerin/ABB/Schnieder or as approved by GE
Note:- The cutting/welding job required for the modification of the existing busbar according to the fixing requirement of the MCCB with the LT panel is included in the above quoted rate.
3
-
-
M&L for servicing of LT panel of capacity upto 4000 Amp/5000 Amps suitable for AC supply (ACB upto 03 Nos and bus coupler upto 02 Nos) by strip opening the doors of the panel and carrying out the cleaning of the panels with CRC spray and tightening the loose connections of the panel including repalcement of the cable glands wherever required, replacement of the old teared/ unsv insulation from the bus bar,checking the IR value before fixing the LT sleeve and refixing the heat shrinkable insulating tape sleeve suitable for 1.1 kv busbar not less than 3mm thick having dielectric strength not less than 1.1kv/mm and LT insulation tapefor CT/ PT connection complete with a certificate from NABL lab. and checking the IR value before testing and commissioning the bus bar all as specified, rectifying the internal wiring of the panel alongwith control wiring between ACB, MCCB, CT, PT, Earth fault relay, over current relay and digital multi function meter, paintting of the LT paels inner and outer surface with the two coat of synthetic enammelled paint over a coat of red oxide primer all as specified and directede by Engr - in- charge. Note:- (a) The above quoted rate includes the cost of the insulators, nuts, bolts, washers and cable gland required for the repair of the panel
4
-
-
M&L for servicing of LT panel of capacity upto 4000 Amps suitable for DC supply distribution (ACB-01No and DC MCCB 630 Amps-15 Nos) by strip opening the doors of the panel and carrying out the cleaning of the panels with CRC spray and tightening the loose connections of the panel including repalcement of the cable glands wherever required, replacement of the old teared/ unsv insulation from the bus bar,checking the IR value before fixing the LT sleeve and refixing the heat shrinkable insulating tape sleeve suitable for 1.1 kv busbar not less than 3mm thick having dielectric strength not less than 1.1kv/mm and LT insulation tapefor CT/ PT connection complete with a certificate from NABL lab. and checking the IR value before testing and commissioning the bus bar all as specified, rectifying the internal wiring of the panel alongwith control wiring between ACB, MCCB, CT, PT, Earth fault relay, over current relay and digital multi function meter, paintting of the LT paels inner and outer surface with the two coat of synthetic enammelled paint over a coat of red oxide primer all as specified and directede by Engr - in- charge. Note:- (a) The above quoted rate includes the cost of the insulators, nuts, bolts, washers and cable gland required for the repair of the panel
1
-
-
Supplying and laying in replacement of old unsv synthetic Rubber insulated mats 3 mm thick for voltage upto 11 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m. complete all as specified and as directed.
10
-
-
S/F in repair of 11 KV bus bar supporting spout / insulators 130 MM LONG 60 MM DIA /as per sample single pole for indoor use 400 to 800 Amp suitable for existing panel complete all as directed and specified.
7
-
-
S/F in repair of fuse indoor type, 11 KV, type PTAVT, Amps 3.15, 50hz, current ratio 800-400, including removing of old unsv fuse complete all as directed and specified.
6
-
-
Supply and fixing in repair of old unsv HRC fuse assembly of any type and size all as per existing having capacity 200 Amps-400 Amps all as specified and directed.
10
-
-
M&L for earthing complete in repairs with galvanized steel earth plate electrode 600x600x6mm thick buried in ground vertical to a depth not less than 2.25 mtrs deep below ground level with top edge of plate not less than 1.5 mtr below normal ground level connected to galvanized GI strip of size 32 X 6 mm and 40 mm dia bore 7.5 mtr long light grade GI protection pipe for earth strip and GI watering pipe 40 mm dia medium grade from the top edge of earth plate fixed with deep cut on one end of pipe and fix from earth plate up to one feet above ground level of other end and plugged watering pipe at top with MS cap and grouted in PCC 1:2:4 of size 30 X 30 X 30 CM etc and 15 CM alternate layer of charcoal and salt around all sides of earth plate all as shown in electric plate no 3 of SSR part I of 2009. Note :- All joints either strip to strip of strip to earth plate are fixed with welded joints.
5
-
-
REPAIR TO SHORE SUPPLY
-
-
-
Supply and fixing in replacement of switch suitable for indutrial plug and socket of capacity 16 Amps, Single pole type sutable for 230 V AC supply confirming to Schneider Cat Part No 56SW116LE-GY complete all as directed and specified.
10
-
-
Supply and fixing in replacement of switch suitable for indutrial plug and socket of capacity 32 Amps, Triple pole type sutable for 500 V AC supply confirming to Schneider Cat Part No 56SW332LE-GY complete all as directed and specified.
10
-
-
Supply and fixing in replacement of switch suitable for indutrial plug and socket of capacity 63 Amps, Triple pole type sutable for 500 V AC supply confirming to Schneider Cat Part No 56SW363LE-GY complete all as directed and specified.
8
-
-
Supply and fixing in replacement of socket suitable for indutrial plug and socket of capacity 16 Amps, 5 Pin type sutable for 230 V AC supply confirming to Schneider Cat Part No 56SO316RP-LE-GY-EX complete all as directed and specified.
10
-
-
Supply and fixing in replacement of socket suitable for indutrial plug and socket of capacity 32 Amps, 5 Pin type sutable for 500 V AC supply confirming to Schneider Cat Part No 56SO532 LE-GY complete all as directed and specified.
10
-
-
Supply and fixing in replacement of socket suitable for indutrial plug and socket of capacity 63 Amps, 5 Pin type sutable for 500 V AC supply confirming to Schneider Cat Part No 56SO550 LE-GY complete all as directed and specified.
8
-
-
Supply and fixing in replacement of mounting enclosure suitable for switch and socket of indutrial type of capacity 16 Amps suitable for 230 V AC supply all as specified and directed confirming to Scneider Cat part No 56E2-GY complete all as directed and specified.
12
-
-
Supply and fixing in replacement of mounting enclosure suitable for switch and socket of indutrial type of capacity 32/63 Amps suitable for 230 V AC supply all as specified and directed confirming to Scneider Cat part No 56E4-GY or equivalent in ABB/L&T/Hensel or as approved by GE
12
-
-
Supply and fixing in replacement of old unsv industrial power switch and socket combination of capacity 63 Amps suitable for 500V AC supply confirming to Schneider Cat Part No 66CB563-RG complete all as directed and specified.
4
-
-
M&L for servicing to industrial power sockets of capacity 500 Amps upto 500 V AC fixed at the cope points of the shore supply confirming to Make:- Crouse Hinds Cat part No M24368/2, including dismantling the complete socket assembly from the fixed position, checking for the loose connection in lugs, tightening the copper cable with the lugs and with the socket assembly, decarbonising the lugs, making sure all the conncetion are tightened properly, servicing to the Pin contacts of the socket complete all as directed and specified. Note:-(a) The supply only items will be measured and paid seperately under relevant items of Sch'A' as under
45
-
-
M&L for servicing to industrial power sockets of capacity 3 phase, DC Voltage upto 220 V /380 V DC fixed at the cope points of the shore supply confirming to Make:- Crouse Hinds or other make including dismantling the complete socket assembly from the fixed position, checking for the loose connection in lugs, tightening the copper cable with the lugs and with the socket assembly, decarbonising the lugs, making sure all the conncetion are tightened properly, servicing to the Pin contacts of the socket complete all as directed and specified. Note:-(a) The supply only items will be measured and paid seperately under relevant items of Sch'A' as under
20
-
-
Supply and fixing in replacement gasket suitable for shore supply receptable power socket of Make:- Crouse Hinds Cat part No M24368/2 having gasket cat part No 40342 complete all as directed and specified.
20
-
-
Supply and fixing in replacement silver coated pin contact electrical suitable for shore supply receptable power socket of Make:- Crouse Hinds Cat part No M24368/2 having pin contact cat part No 40340 complete all as directed and specified.
84
-
-
Supply and fixing in replacement silver coated contact pin electrical suitable for shore supply receptable cope point power socket of Make:- Crouse Hinds Cat part No M24368/1 having pin contact cat part No 30353 complete all as directed and specified.
43
-
-
Supply and fixing in replacement contact sleeve assembly electrical suitable for shore supply receptable cope point power socket of Make:- Crouse Hinds Cat part No M24368/1 having pin contact cat part No 30380 complete all as directed and specified.
10
-
-
Supply and fixing in replacement retaining plate electrical suitable for shore supply receptable cope point power socket of Make:- Crouse Hinds Cat part No M24368/1 having pin contact cat part No 30369 complete all as directed and specified.
10
-
-
Supply and fixing in replacement switch suitable for shore supply receptable power socket of Make:- Crouse Hinds Cat part No M24368/2 having switch cat part No 40384 complete all as directed and specified.
10
-
-
Supply and fixing in replacement Flat washer suitable for shore supply receptable power socket of Make:- Crouse Hinds Cat part No M24368/2 having Flat washer cat part No 30364/30337 complete all as directed and specified.
10
-
-
Supply and fixing in replacement lock washer suitable for shore supply receptable power socket of Make:- Crouse Hinds Cat part No M24368/2 having loack washer cat part No 40355/40403 complete all as directed and specified.
10
-
-
Supply and fixing in replacement slotted binding machine screw suitable for shore supply receptable power socket of Make:- Crouse Hinds Cat part No M24368/2 having screw cat part No 40375 complete all as directed and specified.
10
-
-
Supply only WD 40 electrical contact cleaner sprey (400 ml capacity) for removing of out dirt, dust, oil, flux residue and moisture fron sensitive electrical parts and equipments all as specified and as directed.
10
-
-
Supply and fixing in replacement shore supply receptable power socket assembly, Three-phase, Current rating: 0 - 500 amp, Voltage rating: 500V, available with 3 bussed contacts, Fits 400/500 MCM cable sizes as per existing, Reinforced ribbed receptacle housing , Temperature range:-55°C to +80°C (-67°F to 185°F), Meets MIL-C-24368 in both the properly mated and unmated conditions of Make:- Crouse Hinds Cat part No M24368/2 complete all as directed and specified.
2
-
-
Supply and fixing in replacement shore supply Plug assembly, Three-phase, Current rating: 0 - 500 amp, Voltage rating: 500V, available with 3 bussed contacts, Fits 400/500 MCM cable sizes as per existing, Reinforced ribbed receptacle housing , Temperature range:-55°C to +80°C (-67°F to 185°F), Meets MIL-C-24368 in both the properly mated and unmated conditions of Make:- Crouse Hinds Cat part No M24368/2 complete all as directed and specified.
2
-
-
Supplying & laying in repair including testing of XLPE insulated, armoured, heavy duty, HT UG electric cable in ternches/wall/cable tray/saddling/GI pipe or specified as per site requirement with stranded aluminum conductor 11 KV grade of 3 core 185 sqmm all as specified and directed.
110
-
-
Supplying & laying in repair including testing of XLPE insulated, armoured, heavy duty, PVC inner sheathed, LT UG electric cable in ternches/wall/cable tray/saddling/GI pipe or specified as per site requirement with stranded copper conductor 1100V grade of 3.5 core 25 sqmm all as specified and directed.
50
-
-
Supply, installation, commissioning and testing in replacement , Air circuit breaker (ACB ), 3 Pole as per existing, 415 V, Manual Drawout type with microprocessor release of capacity 2500 Amps as per existing make complete mechanism making connection complete all as specified and as directed by Engr-in-charge.
1
-
-
Supply, installation, commissioning and testing in replacement , Air circuit breaker (ACB ), 3 Pole as per existing, 415 V, Manual Drawout type with microprocessor release of capacity but having capacity of 4000/5000 Amps, Masterpact NW50 H1 type, rated insulation voltage of 1000 volt, impluse withstand voltage of 12 kV, rated operational voltage (V AC 50/60 Hz) of 690 volts with braking capacity 100kA/1s, Cat. 'B', including micrologic 6.0 A and mechanical & electrical durability as per IEC 60947-2/3, make of schneider electric including making connections all as specified.
1
-
-
Evaluation Notes How It Works ?
Potential Partner
Select Your Requirements