Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2024_GU_16080_1Bid Award Id
ViewTender No
GU/9/2024-2025/Engg and Tech Div/70Tender Authority
Goa University ViewPurchaser Address
-Website
http://eprocure.goa.gov.in
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand: 4 graded granitic or basaltic stone aggregate 40 m nominal size) excluding cost of centering, shuttering and finishing : a) All works upto plinth level
27.06
-
-
Brick work using fly ash bricks in cement mortar 1:4 ( 1 cement : 4 coarse sand) with bricks of class designation 40 kg/ cm2 in superstructure up to floor five level
-
-
-
(b) 230 x 110 x 80 mm
34.09
-
-
Supply and fixing chemical 8mm Rebar fastening with Hilti machine of 150 depth and complete as per manufacturer specification.
40
-
-
Centering and shuttering including strutting , propping & removal of forms for
-
-
-
iv) sides / soffits of beams, beam haunchings, cantilevers, girders, bressumers and lintels plinth beams not exceeding 1M in depth
13.14
-
-
Providing TMT steel reinforcement bars of (SAIL, TATA. VIZAG, JSW Steel Ltd.) ) (Confirming to IS 1786 of 1986) for RCC work (conforming to I.S. 1786 of 1986) including bending, binding & placing in position in all the floors along with the factory made precast concrete cover blocks of specified sizes whose compressive strength is not less than that of surrounding concrete in the structural member.
131
-
-
Providing and laying in position (1:11/2:3) Reinforced cement conrete excluding the cost of centering, shuttering, finishing and reinfrocement (1 cement: 1½ coarse sand:3 graded stone agg 20mm nominal size)
-
-
-
b) In walls (any thickness), including attached
pilasters, buttresses, plinth and string courses,
fillets, columns, pillars, piers, abutments, posts
and structs etc. upto floor five level ( column)
1.31
-
-
12mm cement plaster 1: 3 (1 cement ; 3 coarse sand) finished with a floating coat of neat cement.
292.88
-
-
Removing dry or oil bound distemper by scrapping sand papering and preparing the surface smooth including necessary repairs to scratches etc. complete.
304.72
-
-
Providing and applying white cement based putty of average thickness 1.00mm of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
515.76
-
-
Applying one coat of cement primer of approved brand and manufacture on wall surface
515.76
-
-
Wall painting (two or more coats) with plastic emulsion paint of approved brand and
manufacture on new work to give an even shade.
515.76
-
-
Painting three or more coats with acryllic exterior paint of approved brand and manufacture (Such as Dulex/ Asian Paints/ Sherwin Willians) including applying one coat of cement primer and one coat of surface treatment etc. complete.
120
-
-
Applying one or more coat of Zinc epoxy zinc rich primer on steel work of approved brand & manufactured(Asian/Berger) on New work to give an even shade.
100
-
-
Painting two or more coats (excluding priming coat) of Epoxy Paint on Steel Work of approved brand( Asian/ berger) on New work to give an even shade.
100
-
-
Providing and fixing vitrified matt finished (600x600) and 10mm thick tiles in floor, treads of steps, landing on 25mm thick bed of cement mortar 1:3 and jointed with cement slurry complete.
60.4
-
-
Providing and fixing vitrified matt finished (600 X 600) and 10 mm thick tiles in floor , treads of steps, and landings with cement based high polymer modified quick -set tile adhesive( water based) conforming to IS-15477, using 5kg adhesive per sq.m of tile area, in average 3mm thickness (Johnson, somany ,kajaria).
119
-
-
Providing and fixing Vitrified tiles in different sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps and dados, join
-
-
-
a)600 x 600 mm - Dark Shades
15.96
-
-
Providing woodwork in frames of doors, windows, clerestory windows trusses & other
frames wrought framed and fixed in positon
-
-
-
c) First class matti wood
0.27
-
-
Providing flat iron hold fast 40 cm including fixing to frame with 10mm dia bolts , nuts and wooden plugs and embedded in cement concrete blocks 30 x 10 x 15 cm 1:3:6 mix ( 1 cement : 3 coarse sand : 6 stone aggregate 20 mm nominal size
-
-
-
b) 40 x3 mm flat iron hold fast, 15 cm long
36
-
-
Providing and fixing 38 mm thick panelled glazed or panelled and glazed shutters for doors, windows and clerestory window including anodized aluminium butt hinges with necessary screws:
-
-
-
Second class Indian teak wood
25.2
-
-
Applying priming coat with ready mixed primer of approved brand and manufacture on WOOD WORK complete
65.52
-
-
Painting two or more coats (excluding priming coat ) with superior quality ready mixed paint(satin finish) for WOOD WORK of approved brand & manufacture in all shades on NEW WORK to give an even shade
65.52
-
-
Providing and fixing anodized aluminium flat latch
-
-
-
b) 200mm
12
-
-
Providing and fixing aluminium tower bolt (barrel type) anodised or dyed to required colour or shade with screws etc complete.
-
-
-
( ISI mark, Heavy )
-
-
-
a) 300x10 mm
12
-
-
Providing and fixing aluminium handle anodized or dyed to required colour or shade with screws etc. ( ISI mark, Round, Heavy)
-
-
-
a)125mm
24
-
-
Providing and fixing 150 mm. bright finished
brass floor door stopper with rubber cushion
screws etc. to suit shutter thickness complete.
12
-
-
Providing and fixing brass hydraulic door closer of make Everest universal 68 or equivalent with necessary screws and fittings complete.
3
-
-
Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels. Granite of any colour and shade, area of slab over 0.50 sqm
-
-
-
a) Jet Black
2.7
-
-
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in recessed PVC conduit(heavy) with modular switch, modular plates,suitable size modular GI box of specified Category and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
-
-
-
(f) Group C -- with Cat B Modular Accessories
16
-
-
Wiring for group controlled light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in recessed PVC conduit(heavy) and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
14
-
-
Supplying and fixing suitable size modular GI box with modular plate and cover in front on surface or in recess including providing and fixing 3 pin 5/6 A modular socket outlet and 5/ 6 A modular switch connection painting etc. as required.
-
-
-
(b) Cat B
13
-
-
Supplying and fixing suitable size modular GI box with modular plate and cover in front on surface or in recess including providing and fixing 3 pin 15/16 A modular socket outlet and 15/16 A modular switch connection painting etc. as required. (b) Cat B
8
-
-
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor single core cable in the independent recessed PVC conduit (heavy)of appropriate size as required.
-
-
-
(b)2 x 2.5 sq.mm + 1 x 2.5 sq.mm earthwire (20mm Conduit)
363
-
-
(c) 2 x 4 sq.mm + 1 x 4 sq.mm earthwire (20mm Conduit)
229
-
-
(k) 4 x 10 sq.mm + 2 x 10 sq.mm earthwire (40mm Conduit)
20
-
-
Supplying and erecting LED Panel Light(600mm X 600mm) Max. 35 W having CRCA powder coated housing, polystyrene diffuser having system lumens output of Min 4200 Lumens, min. efficacy of 120 lumen/W, CRI80, CCT upto 6500K, Beam Angle of 120 deg., max. ripple of 5%, THD10%, p.f. 0.95, operating range of 120-270V, surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50 including driver, having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty.
11
-
-
as per drawing
-
-
-
Supplying & erecting LED 40W tube light fitting (4 feet) with polycarbonate housing, heat sink,with industrial grade heavy duty driver complete Havels STOUTPLUS100BS40WLED840SPCWH OR EQUIVALENT (including lamp).
19
-
-
as per drawing
-
-
-
Numbering of ceiling fan/ exhaust fan/ fluorescent fittings as required
20
-
-
Supplying and erecting slotted angles, frames, strips, etc. for fixing of trays/DBs etc complete with bending, cutting, drilling and welding complete erected at the position with necessary materials such as nut bolts,etc duly painted with one coat of red oxide and two coats of enamel paint to match the structures or as per directions
75
-
-
for trays
-
-
-
Supplying and fixing B series SP MCB 240V, suitable for lighting and other loads of following poles in the existing MCB DB complete with connections testing and commissioning etc as required"
-
-
-
(c )5A TO 32A, Cat B
96
-
-
IN THE DBS
-
-
-
Supplying and fixing 63 A, C series MCB suitable for lighting and other loads of following poles in the existing MCB DB complete with connections testing and commissioning etc as required.
-
-
-
(i) TP Cat B
4
-
-
Supplying and fixing following way TPN sheet steel, double door, Verticle type MCB distribution board 415 V on surface/ recess complete with tinned copper busbar neutral busbar earth bar dinnbar detachable gland plate interconnections phosphotized and powder painted including earthing etc. as required ( but without MCB/RCCB/Isolator)interconnection between incomer MCB and busbars of following ways (but without MCBs as required)
-
-
-
(b) 8 way (8+24), double door, Vertical type, Cat A
4
-
-
FOR 2 LDB, 1 PDB & 1 ACDB
-
-
-
Supplying installation testing and commissioning of surface/ recess mounting vertical type 415 V TPN, double door MCB DB of sheet steel dust protected duly phosphatised and powder painted inclusive of 200 A tinned copper busbar common neutral link earth bar din bar for mounting MCBs detachable gland knock out plate and with 100 A 10 KA MCCB as incomer interconnection between incomer MCCB and busbars of following ways (but without MCCB/MCBs as required)
-
-
-
(a) 4 way with 100A MCCB as Incomer, double door, Cat A
1
-
-
Supply installation testing and commissioning of flush mounted metal plug and socket , conforming to IS 8623-1&3 of CRCA sheet , powder coated to RAL 9003, suitable for three phase FP mcb 32A(3P+N+E) without mcb
-
-
-
32A TP metal clad socket as above
2
-
-
for odu & industrial socket
-
-
-
Supplying and fixing 6 A to 32 A, C series MCB suitable for lighting and other loads of following poles in the existing MCB DB complete with connections testing and commissioning etc as required.
-
-
-
(j) TPN, Cat B
5
-
-
Supplying and fixing following rating four pole (triple pole and neutral) 415 V RCCB having a sensitivity current upto 300mA in the existing MCB DB complete with connections testing and commissioning etc as required
-
-
-
(e) 40 A, Cat B
5
-
-
Providing and fixing following rating and breaking capacity adjustible 4 pole MCCB inside the existing cubicle panel board including drilling holes in cubicle panel making connections etc as required
-
-
-
(d) 200 A Adjustable 35/40 KA, CAT B
1
-
-
Providing and fixing 25 mm x 5 mm copper strip on surface or in recess for coneections etc. as required
120
-
-
Supply of 3 1/2 core armoured PVC/XLPE insulated, PVC sheathed aluminium conductor cable of 1.1 KV grade with ISI mark conforming to IS:1554(Part I),IS:7098(Part I) with latest amendments of following size.
-
-
-
(1) 3 1/2cx25 sq.mm
85
-
-
(5) 3 1/2 Core 95 sq.mm
20
-
-
(8) 31/2 Core 185 sq.mm
30
-
-
from main panel to ups room
-
-
-
Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of size not exceeding 25 sq.mm in existing RCC/HUME /Stoneware /Trench/Metal pipe etc complete as required.
85
-
-
Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of size exceeding 25 sq.mm but not exceeding 400 sq.mm in the existing masonry open duct, etc. complete as required
50
-
-
Supplying and making cable end terminations with brass compression gland and copper lugs for following sizes of 3 1/2 Core PVC insulated PVC sheathed/XLPE aluminium conductor cable of 1.1 KV grade, complete as required.
-
-
-
(1) 3 1/2cx25 sq.mm
8
-
-
(5) 3 1/2 x 95 Sq. mm.
2
-
-
(8) 3 1/2 x 185 Sq. mm.
2
-
-
Supplying and drawing of Cat - 6 UTP, 4 pair annealed tinned copper conductor PVC insulated, PVC sheathed, unarmoured data cable in existing surface/recessed steel/PVC conduit of appropriate size including connection, etc. complete as required
-
-
-
(a) Cat 6
47
-
-
Supplying, installation and testing of suitable size modular GI box , modular plate and cover complete with RJ-45 connector(modular LAN socket TX1000/ CAT6) including concealed metal box/surface GI/PVC Box, modular plate, punching, identifying, complete as required.
-
-
-
b)CAT B
4
-
-
Supplying and fixing tool-less shutter keystone jack (RJ-45) in provided patch panel complete as per specification no. WG-NAS/KJ
4
-
-
Supplying and fixing 9U wall mount rack (Dimension-DxWxH – 500x600x500
mm) as per specification No. WG-NAS/RAK
1
-
-
Supplying and fixing 24 port patch panel with tool-less keystone jacks in provided U Rack complete as per specification no. WG-NA
1
-
-
Supplying and Installing following size perforated type 16 SWG, M.S.cable tray of GI pregalvanised/hot dip galvanised/ powder coated finish, in convenient sections, joined with connectors, suspended from the ceiling with suitable MS suspenders including bolts and nuts, painting suspenders etc, complete as required.
-
-
-
a)100mm width x 50mm depth
60
-
-
Supplying and Installing following size welded ladder type , 75mm depth, M.S.cable tray of GI pregalvanised/hot dip galvanised/ powder coated finish, in convenient sections, joined with connectors, suspended from the ceiling with suitable MS suspenders including bolts and nuts, painting suspenders etc, complete as required.
-
-
-
(d)300 mm width X 75 mm depth with runner size20x75x20mmmm, rung size 20x40x20mm with rungs at 250mm c/c.(12SWG)
50
-
-
Supplying and Installing following size welded ladder type , 75mm depth, M.S.cable tray bend of GI pregalvanised/hot dip galvanised/ powder coated finish, in convenient sections, joined with connectors, suspended from the ceiling with suitable MS suspenders including bolts and nuts, painting suspenders etc, complete as required.
-
-
-
300 mm width X 75 mm depth with runner size20x75x20mmmm, rung size 20x40x20mm with rungs at 250mm c/c.(12SWG)
3
-
-
Supplying and Installing following size perforated type , M.S.cable tray bends of GI pregalvanised/hot dip galvanised/ powder coated finish, in convenient sections, joined with connectors, suspended from the ceiling with suitable MS suspenders including bolts and nuts, painting suspenders etc, complete as required.
-
-
-
(a)100mm width x 50mm depth (16 SWG)
4
-
-
Supplying and Installing following size welded ladder type , 75mm depth, M.S.cable tray tees of GI pregalvanised/hot dip galvanised/ powder coated finish, in convenient sections, joined with connectors, suspended from the ceiling with suitable MS suspenders including bolts and nuts, painting suspenders etc, complete as required.
-
-
-
300 mm width X 75 mm depth with runner size 20x75x20mmmm, rung size 20x40x20mm with rungs at 250mm c/c.(12SWG)
1
-
-
Supplying and Installing following size perforated type , M.S.cable tray tees of GI pregalvanised/hot dip galvanised/ powder coated finish, in convenient sections, joined with connectors, suspended from the ceiling with suitable MS suspenders including bolts and nuts, painting suspenders etc, complete as required.
-
-
-
100mm width x 50mm depth (14 SWG)
2
-
-
Supplying, erecting, testing and commissioning 8 HP, VRF / VRV air conditioning system, out door unit (ODU) complying type-IV OEM standards working on HFC free refrigerant R410A or other required/suitable green equivalent refrigerant, for cooling capacity delivering 100% at 42 deg. celcius and non stop cooling even at 56 deg. celsius and coefficient of performance (COP) 3.00 to 4.00, modular type horizontal/vertical hot air discharge suitable for total piping length upto 1000 metre operation in cooling mode with inverter based VRF/VRV technology microprocessor based control compressor starter/control panel complete with scroll compressor, air cooled anti corrosive copper condenser coil of suitable shape for increasing maximum heat transfer area, built in oil separator, accumulator and oil receiver, copper tube aluminium fin air cooled condenser, condenser fan with motor suitable for 415V ± 10%, 50 Hz, 3 phase power supply, internal copper refrigerant piping, internal wiring and first charge of refrigerant, etc. all housed in powder coated weather proof cabinet on provided angle iron frame or suitable foundation connected to the system in approved manner complete
1
-
-
OUTDOOR UNIT FOR THE AC
-
-
-
Supply, installation, testing and commissioning of VRF/VRV based Hi-wall type indoor unit (IDU) of nominal cooling capacity min capacity 2.0TR (620 cfm) to 2.2TR (655 cfm) having EER as per BEE standards and specifications with multiple speed evaporator fan with motor, copper tube aluminium fin evaporator coil, washable air filter, insulated drain tray, expansion device, cordless remote control with necessary controls, with 3-core copper flexible cord of required length and electrical terminal to receive power supply, etc. IDU shall have anti-corrosive coating suitable for coastal area. Unit shall be suitable for indoor wall mounting, having an electronic control console, provided with suitable mounting brackets with any additional refrigerant and oil charge as per the requirement during installation, connected to the system complete.
1
-
-
IDU OF NEW UPS ROOM
-
-
-
Supply, installation, testing and commissioning of VRF/VRV based Hi-wall type indoor unit (IDU) of nominal cooling capacity min 1.5TR (485 cfm) to 1.7TR (586 cfm) having EER as per BEE standards and specifications with multiple speed evaporator fan with motor, copper tube aluminium fin evaporator coil, washable air filter, insulated drain tray, expansion device, cordless remote control with necessary controls, with 3-core copper flexible cord of required length and electrical terminal to receive power supply, etc. IDU shall have anti-corrosive coating suitable for coastal area. Unit shall be suitable for indoor wall mounting, having an electronic control console, provided with suitable mounting brackets with any additional refrigerant and oil charge as per the requirement during installation, connected to the system complete.
3
-
-
IDU OF LAB 1 & LAB2
-
-
-
Supplying, laying / fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 22.22 mm dia (OD) for liquid line / suction line supply and return piping of suitable gauge ( hard drawn copper pipe for liquid main line and for refrigerant ) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19 mm thick elastomeric nitrile rubber along with application of multicoating suitable for use with VRV / VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations complete with OEM standards of VRV / VRF air conditioning system. (Pipe sizing to be Verified as per OEM standards and invoiced as per actual measurement.)
1
-
-
FOR ACs
-
-
-
Supplying, laying / fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 19.1 mm dia (OD) for liquid line / suction line supply and return piping of suitable gauge ( hard drawn copper pipe for liquid main line and for refrigerant ) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19 mm thick elastomeric nitrile rubber along with application of multicoating suitable for use with VRV / VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations complete with OEM standards of VRV / VRF air conditioning system (Pipe sizing to be Verified as per OEM standards and invoiced as per actual measurement.)
9
-
-
FOR ACs
-
-
-
Supplying, laying / fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 15.9 mm dia (OD) for liquid line / suction line supply and return piping of suitable gauge ( hard drawn copper pipe for liquid main line and for refrigerant ) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19 mm thick elastomeric nitrile rubber along with application of multicoating suitable for use with VRV / VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations complete with OEM standards of VRV / VRF air conditioning system (Pipe sizing to be Verified as per OEM standards and invoiced as per actual measurement.)
8
-
-
FOR ACs
-
-
-
Supplying, laying / fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 12.7 mm dia (OD) for liquid line / suction line supply and return piping of suitable gauge ( hard drawn copper pipe for liquid main line and for refrigerant ) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19 mm thick elastomeric nitrile rubber along with application of multicoating suitable for use with VRV / VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations complete with OEM standards of VRV / VRF air conditioning system (Pipe sizing to be Verified as per OEM standards and invoiced as per actual measurement.)
6
-
-
FOR ACs
-
-
-
Supplying, laying / fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 9.5 mm dia (OD) for liquid line / suction line supply and return piping (OD) for liquid line / suction line supply and return piping of suitable gauge ( hard drawn copper pipe for liquid main line and for refrigerant ) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19 mm thick elastomeric nitrile rubber along with application of multicoating suitable for use with VRV / VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations complete with OEM standards of VRV / VRF air conditioning system. (Pipe sizing to be Verified as per OEM standards and invoiced as per actual measurement.)
26
-
-
FOR ACs
-
-
-
Supplying, laying / fixing, testing and commissioning of appropriate nominal refrigerant copper pipe of 6.4 mm dia (OD) for liquid line / suction line supply and return piping (OD) for liquid line / suction line supply and return piping of suitable gauge ( hard drawn copper pipe for liquid main line and for refrigerant ) along with necessary supports, hangers, clamps, vibration isolators and fittings such as bends, tees, valves, gauges, strainers with insulation of 19 mm thick elastomeric nitrile rubber along with application of multicoating suitable for use with VRV / VRF piping for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations complete with OEM standards of VRV / VRF air conditioning system. (Pipe sizing to be Verified as per OEM standards and invoiced as per actual measurement.)
15
-
-
FOR ACs
-
-
-
Supplying and installation of high pressure grade required size copper connection Y or T- Joints / refnet for liquid and suction line complete erected on wall/ceiling with supports/raceways, Nitrile rubber insulation, painting etc. with brazing and testing for leakages confirming the normal operation of the VRV / VRF air conditioning system.
3
-
-
FOR ACs
-
-
-
Supplying, installing, testing and commissioning split type variable speed Inverter technology room Air conditioning unit 2 TR capacity having ISEER minimum 3.50 to maximum 3.99 suitable to operate on 250V, 50 cycles, A.C. supply having 1 no. of air handling unit hi-wall/ floor mounting type complete with Refrigerants R410 A/R32 and copper condenser at position.
specification no. AP-AC/SAC (UPS room Stand by unit)
1
-
-
FOR UPS ROOM AC
-
-
-
Supplying & erecting soft drawn copper pipe suitable for refrigeration system having 22 SWG thickness and inner dia / size 12 mm complete. (Pipe sizing to be Verified as per OEM standards and invoiced as per actual measurement.)
128
-
-
FROM ODU TO IDU OF LAB1 &LAB 2
-
-
-
Supplying & erecting soft drawn copper pipe suitable for refrigeration system having 22 SWG thickness and inner dia / size 16 mm complete. (Pipe sizing to be Verified as per OEM standards and invoiced as per actual measurement.)
128
-
-
FROM ODU TO IDU OF UPS ROOM
-
-
-
Design , supply ,installation testing and commissioning of LAB incomer panel , cubical type,indoor type, wall mounted , front access ,fully compartmentalised with cable entry at top/ bottom, all mccbs with rotary handles with thermal magnetic releases. Steel sheets used in the construction shall be 2 mm thick. All sheet steel work shall undergo a process of degreasing, pickling in acid, cold-rinsing, phosphating, passivating and then sprayed with a high corrosive resistant primer. The finishing treatment shall be by application of two coats of synthetic enamel paint or powder coating of Red for incomer and RAL7032 for all other. The panel shall be of adequate size with a provision of 25% spare space to accommodate possible future switch gear.The cable terminations shall be suitable for cable sizes as shown on the drawing as required etc suitable for outgoing cable sizes as shown on the drawing as required with
-
-
-
Incomer 200A 4P 50KA microprocessor based adjustable mccb with RYB lamp set suitable for 31/2Cx185sqm cable
-
-
-
1 sets of digital multifunction meter with Amps, Volts, Kwh, Hz,PF etc with scada connectivity with necessary cts and suitable RS485/232 port
-
-
-
400A 4P copper bus bars of 99.9% purity electrolytic copper
-
-
-
Outgoings
-
-
-
1 set of 160A , 36KA TPN MCCB suitable for 31/2cx`185sqmm armoured cable
-
-
-
2 set of 63A , 36KA TPN MCCBs suitable for 31/2cx95sqmm armoured cable
-
-
-
6 sets of 10A sp MCB
-
-
-
LAB AC main incomer panel as above
1
-
-
Supplying and erecting PVC conduit 32 mm dia. with PVC accessories on wall till the AHU room floor drain with 10 mm thick elastomeric nitrile rubber along with application of multicoating for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations complete with OEM standards of VRV / VRF air conditioning system.
12
-
-
Supplying and erecting PVC conduit 25 mm dia. with PVC accessories on wall till the AHU room floor drain with 10 mm thick elastomeric nitrile rubber along with application of multicoating for protection against mechanical damages, fungal growth, flame spread, water permeance and ultra violet radiations complete with OEM standards of VRV / VRF air conditioning system and HI wall split unit
7
-
-
Supply and Installation VRF/VRV Communication shielded Cabling 2C x 1.5sqmm between indoor and outdoor units
128
-
-
Supply and Installation VRF/VRV Power Cabling from Indoor unit to power socket 3C x 1.5sqmm
10
-
-
Supply and Installation Control Cabling 4C x 2.5sqmm between indoor and outdoor units for Hi Wall Split units
128
-
-
Disconnection of existing 1.5 TR indoor unit in existing UPS room and and installation in new ups room location