Military Engineer Services Tender

If you're typing tender ID over and again or finding it difficult to go through the cumbersome government websites for looking at Delhi tenders online. We have come up with a solution i.e. we have collated every eprocurement Delhi tender on BidAssist. Also, for any queries related to an e-tender Delhi, like the bidding process, registration process, etc., the same are explained below.

Military Engineer Services - MES Tender

Works
Electrical Generators And Transformers
Electrical and Electronics
Eprocure
Opening Date20 Nov 2023
Closing Date9 Dec 2023
Tender Amount₹ 49,77,000 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
(m) Tranformer losses shall not exceed the loses mentioned in Table 6 of IS: 1180 of 2014 Part - I with energy Effeciency level - III. (n) Oil temperator indicator , winding temperature indicator, marshlig box single window, double flit buchoiz relay with alarm and trip contact including connection to existing RMU/VCB relay with PVC insulated PVC sheathed cable galvanized steel strip or wire armoured electric control cables (Heavy duty) with stranded copper conductor of size 1.5 sq mm 10 core 1100 volts grade.

-

-

-

... More
NOTE :- (i) Rate quoted includes the cost of making and Testing of controll wiring connection at the Transformer and RMU/VCB for the Temperature alarm/Trip, Gas alarm/Trip. (ii) Controll cable shall be measured and paid seperatly. (iii) The cost of Plinth shall be included in the quoted rate by theContractor.

-

-

-

... More
Supply, laying and testing cable HT XLPE insulated , screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 11000 volts grade with stranded aluminium conductor of size 185 Sqmm 3 core.

100

-

-

... More
Supply, Laying, connecting, testing and commissioning of LT XLPE cable of PVC sheathed armoured aluminium conductor 1100 V graded 630 sqmm single core complete all as specified and directed.

60

-

-

... More
Supply, laying and testing cable XLPE insulated , screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 185 Sqmm 3.5 core.

300

-

-

... More
Supply, laying and testing cable XLPE insulated , screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 120 Sqmm 3.5 core.

250

-

-

... More
Supply, laying and testing cable XLPE insulated , screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 95 Sqmm 3.5 core

400

-

-

... More
Supply, laying and testing cable XLPE insulated , screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 50 Sqmm 3.5 core.

500

-

-

... More
Excavation in trenches not exc. 1.5 m wide and not exc 1.5 mtr deep in soft loose soil for laying / taking up/ taking down of cables and getting out and levelling of bottom suface to required level all as specified and directed by Engineer- in- Charge.

573.75

-

-

... More
Returning filling in,. Including spreading, levelling,. Watering and well ramming soil in layers not exceeding 25 cm thick all as specified and directed.

357.62

-

-

... More
Removing excavated material (ie soil) from site to a distance n. exc 50 mtrs away and depositing where directed at a level n. exc. 1.5 mtr above the starting point all as specified and directed by Engineer-in-Charge.

216.13

-

-

... More
Material and labour for river washed and screened, dry sand for filling in trenches below and around underground cables for cushioning of cables etc, complete all as specified and directed. Note : -Only Punned sand shall be measured and paid for.

145.64

-

-

... More
Supplying and laying un-reinforced precast concrete cable cover, class HV, type 1, flat size 300mmx 180mm x 40mm. Complete all as specified and directed.

278

-

-

... More
S&F sub class B bricks having minimum compressive strength 75 Kg/ Sqcm laid in trenches for cable protection etc complete all as directed by Engineer-in-Charge.

15486

-

-

... More
Supply and laying galvanised iron pipe 80 mm bore light grade fixed to poles with steel clamps laid under road crossing fixed to wall etc complete all as specified and directed. Note : -Clamps shall be measured and paid separately

12

-

-

... More
Supply and laying galvanised iron pipe 50 mm bore light grade fixed to poles with steel clamps laid under road crossing fixed to wall etc complete all as specified and directed. Note : -Clamps shall be measured and paid separately

12

-

-

... More
M/L for GI Tubes,of size 40 mm dia light grade, galvanised, with all fitting , laid in trenches for protection of cable in road /drain crossing complete all as specified and as directed.

24

-

-

... More
M&L for GI earth strip of size 32 x 6 mm laying in trench, fix to Pole with necessary clamp and nut bolt etc including taking out of unsv earth wire.

20

-

-

... More
Supply, installing, testing and commissioning of factory made and tested (including CPRI type tested certified panel) LT Panel board ,cubical compartmentalized , out door type double door , plate form mounted, suitable for 415 volts, 3 phase, 4 wire, 50 HZ AC supply system having bus bar chamber with insulated aluminium bus bars four pole installed on porcelain/SMC insulator. The panel shall be dust and vermin proof. IP-65 class protection and shell be made of 3.15 mm CRCA MS sheet, and 50x50x6mm thick MS angle iron frame work, powder coated finish over one coat of red oxide primer on outside surface and painted inside with two coats of red oxide primer, front and rear opening type, with apron for cable entry closing locking arrangement including internal wiring with PVC insulated solid, copper conductor FRLS cable, IS-694 marked, 1100 volts grade of appropriate size ( but not less than 2.5 Sqmm) and comprising of the following :- Location -Trasformer Main Panel ) (a) Incoming :- (i) ACB 4 pole, 800 Amp, 50 KA, 415 Volt AC Horizontal draw out type motorized, front operated with Micro processor based LCD protection release for adjustable over current, short circuit and earth fault protection-01 No (ii) Voltmeter digital type with 4 way rotary selector swicth -01 No. (iii) Ammeter digital type with 4 way rotary selector switch-01 No. (iv) CTs ratio 800/5 A ,class 1, ISI marked -01 sets of three (v) Indicating lamp- 01 set of three (vi) Aluminium bus bar of rating 1600 Amp- set of four

1

-

-

... More
(b) Outgoing (i) MCCB 4 pole , 400 Amps,50 Hz,415 Volts, 50 KA with microprocessor release - 01 Nos (ii) MCCB 4 pole , 315 Amps,50 Hz,415 Volts, 36 KA with microprocessor release - 01 Nos (iii) MCCB 4 pole , 250 Amps,50 Hz,415 Volts, 36 KA with microprocessor release - 01 Nos (iii) MCCB 4 pole , 200 Amps,50 Hz,415 Volts, 36 KA with microprocessor release - 02 Nos (c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level. Note :- (i) All out going feeder shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iii) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947-II/IS 13947-II (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer

-

-

-

... More
All as in item No 18 here-in-before but comprising of the following :- Location : Main Panel Area HQ S/S -01) (a) Incoming :- (i) MCCB 4 pole , 630 Amps,50 Hz,415 Volts, 50 KA, with thermal & Magnetic release - 01 Nos (ii) Onload changeover 630 Amps -01 No (iii) Voltmeter 0-500 volts digital type with 4 way rotary selector swicth -01No (iv) Ammeter digital type with 4 way rotary selector switch-01No (iv) CTs ratio 630/5 A ,class 1, ISI marked -01 sets of three (v) Indicating lamp- 01 set of three (vi) Aluminium bus bar of rating 1200A - set of four (b) Outgoing (i) MCCB 4 pole , 400 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 01 Nos (ii) MCCB 4 pole , 315 Amps,50 Hz,415 Volts, 25 KA with thermal magnetic release - 02 Nos (iii) MCCB 4 pole , 200 Amps,50 Hz,415 Volts, 16 KA with thermal magnetic release - 02 Nos (c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level. Note :- (i) All out going feeder shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iii) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993 (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer . (iv) Energy meter is not included in the present scope of work and shall be shifted from Old LT Panel to New LT Panel. The rate for shifting is also deemed to be included in the quoted rates.

1

-

-

... More
All as in item No 18 here-in-before but comprising of the following :- Location : Behind GOC Office (a) Incoming :- (i) MCCB 4 pole , 400 Amps,50 Hz,415 Volts, 50 KA, with thermal & Magnetic release - 01 Nos (ii) Onload changeover 400 Amps -01 No (iii) Voltmeter 0-500 volts digital type with 4 way rotary selector swicth -01No (iv) Ammeter digital type with 4 way rotary selector switch-01No (iv) CTs ratio 400/5 A ,class 1, ISI marked -01 sets of three (v) Indicating lamp- 01 set of three (vi) Aluminium bus bar of rating 800A - set of four (b) Outgoing (i) MCCB 4 pole , 250 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 01 Nos (ii) MCCB 4 pole , 200 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 01 Nos (iii) MCCB 4 pole , 160 Amps,50 Hz,415 Volts, 35 KA with thermal magnetic release - 02 Nos (c) Platform of Panel. Platform for the panel with PCC 1:4:8 type D-2 with 40 mm graded crushed stone, 15 cm thick in foundation, brick work in CM 1:6 with sub class 'B', old size bricks, rendering 15 mm thick in CM 1:6 on exposed surfaces and 100 mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45 cm above the nearest road level. Note :- (i) All out going feeder shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint. (iii) All MCCB with adjustable protection for over load and short circuit and conforming to IEC60947/IS 13947/Pt.II/1993 (Latest Version). The MCCB should have Ics=100%Icu. The MCCBs shall have spreader links and barriers as standard feature of manufacturer . (iv) Energy meter is not included in the present scope of work and shall be shifted from Old LT Panel to New LT Panel. The rate for shifting is also deemed to be included in the quoted rates.

1

-

-

... More
All as in item No 18 here-in-before but comprising of the following :- Location : Near Rajendra Singh Hall ) (i) MCCB 4 pole , 315 Amps,50 Hz,415 Volts, 35 KA, with thermal and magnetic release - 01 Nos (ii) Onload changeover 250 Amps -01 No (iii) Voltmeter 0-500 volts digital type with 4 way rotary selector swicth -01No (iv) Ammeter digital type with 4 way rotary selector switch-01No (v) CTs ratio 400/5 A ,class 1, ISI marked -01 sets of three (vi) Indicating lamp- 01 set of three (vii) Aluminium bus bar of rating 500 Amps - set of four (b) Outgoing (i) MCCB 4 pole , 200 Amps,50 Hz,415 Volts, 25 KA with thermal and magnetic release - 01 Nos (ii) MCCB 4 pole , 160 Amps,50 Hz,415 Volts, 25 KA with thermal and magnetic release - 02 Nos (iii) MCCB 4 pole , 100 Amps,50 Hz,415 Volts, 25 KA with thermal and magnetic release - 02 Nos

1

-

-

... More
All as in item No 18 here-in-before but comprising of the following :- Location : HQ Delhi Area Camp line ) (i) MCCB 4 pole , 200 Amps,50 Hz,415 Volts, 35 KA, with thermal and magnetic release - 01 Nos (ii) Voltmeter 0-500 volts digital type with 4 way rotary selector swicth -01No (iii) Ammeter digital type with 4 way rotary selector switch-01No (iv) CTs ratio 250/5 A ,class 1, ISI marked -01 sets of three (v) Indicating lamp- 01 set of three (vi) Aluminium bus bar of rating 400 Amps - set of four (b) Outgoing (i) MCCB 4 pole , 125 Amps,50 Hz,415 Volts, 25 KA with thermal and magnetic release - 02 Nos (ii) MCCB 4 pole , 100 Amps,50 Hz,415 Volts, 25 KA with thermal and magnetic release - 02 Nos (iii) MCCB 4 pole , 63 Amps,50 Hz,415 Volts, 25 KA with thermal and magnetic release - 02 Nos

1

-

-

... More
Supply and fix Cable end jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of 185 Sqmm 3 Core.

1

-

-

... More
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of 185 Sqmm 3 Core.

1

-

-

... More
M&L for plate Earthing complete with galvanized steel earth plate electrode 600x600x6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to galvanized earth strip 32 x 6 mm by means of bolts and nuts checknuts and washers of galvanized iron electric arc welding all joints all as specified and shown in electrical plate No 3 of SSR part I including necessary excavation and earth work in any type of soil PCC 1:3:6 type C1 chamber with RCC 1:2:4 type B1 40 mm thick cover with MS rod 8mm dia 150mm long reinforcement, watering funnel, 40 mm dia light grade for protection of earth electrode 20 mm dia for watering all as specified and directed and tested on completion.

9

-

-

... More
Supply and fixing outdoor type wall mounted bus bar chamber having 04 pole bus bar of rating 400 Amps fitted with MCCB 200 Amps 4 Pole, 35 KA, 50 HZ as incomer inclding suitable hole in bus bar for outgoing cable connection including suitable size nut bolt and fastener complete all as specified and directed.

5

-

-

... More
Supply and fixing outdoor type wall mounted bus bar chamber having 04 pole bus bar of rating 320 Amps fitted with MCCB 160 Amps 4 Pole, 25 KA, 50 HZ as incomer inclding suitable hole in bus bar for outgoing cable connection including suitable size nut bolt and fastener complete all as specified and directed.

5

-

-

... More
M&L for boring of holes under road/pavement/hard standing by trenchless technology using ultra sound technique and necessary machine including material and labour for HDPE pipe of 100 mm to150 mm dia suitable for 06 Kg/cm working pressure. Wall thickness of pipe not less than 8 mm suitable for 33 KV HT Cable complete all as specified and directed.

200

-

-

... More
Supply, laying, testing and commissioning of LT XLPE underground PVC insulated, armoured heavy duty electric cable, 1100 volts grade with stranded aluminium conductor of 16 sqmm 4 core in replacement complete including dismantling of old unserviciable cable.

400

-

-

... More
Supply, laying, testing and commissioning of LT XLPE underground PVC insulated, armoured heavy duty electric cable, 1100 volts grade with stranded aluminium conductor of 50 sqmm 4 core in replacement complete including dismantling of old unserviciable cable.

100

-

-

... More
Supply & installing steel tubular swaged poles type 410 SP-31 (9 mtr long) of apprx wt.147 kg conforming to IS 2713 (Part-II) including excavation, earth work, PCC foundation, base plate,PCC coping,GI pipe for cable protection etc. and GI bracket for fitting mounting of flood light fittings , complete all as per manufacturer's instructions and as specified and as directed by E-in-charge. NOTE:- The unit rate in this item is deemed to be included the cost of exacavation and earth work in any type of soil,PCC foundation 1:4:8 type D-2 , PCC coping 1:2:4 type B-1 as in steel tubular pole and GI bracket made of Channel /flat iron incl nut bolts,clamps etc , 1.5 mtr x 1.5 mtr long for fixing of LED Flood light fitings . The steel pole shall be painted by bituminious paint total lenth inside and up to planting depth outside

10

-

-

... More
Supply & fixing 90 Watt LED flood light fittings made up of pressure die cast housing with toughned glass and individual high power LEDs with secondary optics, IP66 protection complete all as specified and directed.

10

-

-

... More
S&F in replacement KIOSK box wheather proof including made out of one piece mounted SMC base and door pole mounted hinged door size 333x233x120mm out side and 300x200x105mm inside dimensions comprising of aluminium bus bar 4 strips for 3 phase and neutral 63 Amps and 15 Amps fuse grip with base including embossing/painting of danger notice of size not less than 10cm x 7.5cm with letters, figures and conventional skull and bones in signal red colour on front face of KIOSK box body complete all as specified and directed.

10

-

-

... More
Supply, drawing, connecting & testing of 3 core, 2.5 Sqmm PVC insulated and PVC rounded sheathed, copper conductor (flexible) industrial cable 1100 Volts gradde conforming to IS-694 in steel tubular pole from KIOSK box to light fittings including providing suitable copper lugs all as specified and directed. Note : Steel tubular pole shall be measured and paid separetely.

60

-

-

... More
S&F time switches astro type in having longitude and latitude of Indian cities in memory 415 V three phase 20 Amp rating with 20 Amps, 415 Volts, three pole contactor fitted inside factory made 2mm thick steel enclosure duly powder coated paint complete all as specified and directed.

1

-

-

... More
Note : contractor should procure and provide 50 % of the material as listed above within 15 days of the placing of work order and shall be verified by the Eng-in-charge

-

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.