Military Engineer Services Tender
If you're typing tender ID over and again or finding it difficult to go through the cumbersome government websites for looking at Delhi tenders online. We have come up with a solution i.e. we have collated every eprocurement Delhi tender on BidAssist. Also, for any queries related to an e-tender Delhi, like the bidding process, registration process, etc., the same are explained below.
Costs
EMD
₹ 1,76,500Document Cost
₹ 1,000Tender Fee
Refer Documents
Description
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user
Contact
Tender Id
2020_MES_387400_1Bid Award Id
ViewTender No
89035/CWE(U)/D-26/2020-21/E8Tender Authority
Military Engineer Services ViewPurchaser Address
-Website
http://http://mes.gov.in/
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost
Documents
BOQ Items
... More
Supply and erect steel Structures to support 33 KV cable with ISMB/Channnel/Angle iron/Flat including necessary hard ware in any shape or size including GI Nut, bolts,washers, clamps suitable for above structure/equipments and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed.
10
-
-
... More
Material and Labour for Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 200 mm dia suitable for 0.6 mpa working pressure complete all as specified & as directed.
1300
-
-
... More
Dismantling of 33 KV ACSR conductor from 33 KV steel structures tower ccomplete all as specified & as directed.
16
-
-
... More
Dismantling insulators any type, any size from 33 KV steel structures tower complete all as specified & as directed.
72
-
-
... More
Excavation in trenches not exc. 1.5 m wide and not exc 1.5 mtr deep in soft / loose soil for laying / taking up/ taking down of cables and getting out and levelling of bottom suface to required level complete all as specified & as directed.
407
-
-
... More
Returning filling in,. Including spreading, levelling,. Watering and well ramming soil in layers not exceeding 25 cm thick all as specified and directed.
255
-
-
... More
Removing excavated material (ie soil) from site to a distance n. exc 50 mtrs away and depositing where directed at a level n. exc. 1.5 mtr above the starting point complete all as specified & as directed.
152
-
-
... More
Material and labour for river washed and screened, dry sand for filling in trenches below and around underground cables for cushioning of cables etc, complete all as specified & as directed. Note : Only Punned Sand shall be measured and paid for.
98
-
-
... More
Supplying and laying un-reinforced precast concrete cable cover, class HV, type 1, flat size 300mmx 180mm x 40mm complete all as specified & as directed.
4700
-
-
... More
Laying only old un-reinforced precast concrete cable cover, class HV, type 1, flat size 300mmx 180mm x 40mm obtained under this work complete all as specified & as directed.
2000
-
-
... More
Supplying, laying, testing and connecting in replacement XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, 11 KV Earthed grade, IS 7098 marked, suitable for HT 11 KV(E) system, laid in trenches / ducts / encased in GI pipe / fixed to pole, including jointing & testing complete all as specified and directed of following sizes:- Note : Excavation, Earth work, Cable protection, sand filling and Cable Joints shall be measured and paid separately in respective item of this BOQ.
-
-
-
... More
95 sqmm 3 core.
195
-
-
... More
120 sqmm 3 core.
225
-
-
... More
150 Sqmm 3 Core
240
-
-
... More
185 sqmm 3 core
285
-
-
... More
240 sqmm 3 core
270
-
-
... More
300 sqmm 3 core
295
-
-
... More
Material and Labour for Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.6 mpa working pressure complete all as specified & as directed
300
-
-
... More
Material and Labour for Boring of hole under road/pavement/hard standing or any other situation by mannual means and suitable for passing of GI pipe 100 to 150 mm bore and making good both ends all specified and directed. Note For Sr No 5, 15 & 16 Above : The Rate for taking permission from concerned authorities like MTNL, Army Signal , BSES and other utility authority are deemed to be included in the quoted rates. If any utilities services like road are damaged during execution of work , the same will be repaired/replaced/ made good by the Contractor without any additional payment by the Department.
100
-
-
... More
S&F in replacement GI Pipe (light grade) with necessary accessories/ fittings for cable protections/pole for crossing of culverts/nallah of 150mm bore size complete all as specified & as directed.
50
-
-
... More
S&F in replacement GI Pipe (light grade) with necessary accessories/ fittings for cable protections/pole for crossing of culverts/nallah of 100mm bore size complete all as specified & as directed.
50
-
-
... More
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable complete all as specified & as directed of following sizes :-
-
-
-
... More
70 Sqmm to 120 Sqmm 3 core.
4
-
-
... More
150 Sqmm to 185 Sqmm, 3 core.
4
-
-
... More
240 Sqmm to 300 Sqmm 3 core
4
-
-
... More
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable complete all as specified & as directed of following sizes :-
-
-
-
... More
70 Sqmm to 120 Sqmm 3 core.
5
-
-
... More
150 Sqmm to 185 Sqmm, 3 core.
5
-
-
... More
240 Sqmm to 300 Sqmm 3 core
5
-
-
... More
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable complete all as specified & as directed of following sizes :-
-
-
-
... More
70 Sqmm to 120 Sqmm 3 core.
6
-
-
... More
150 Sqmm to 185 Sqmm, 3 core.
6
-
-
... More
240 Sqmm to 300 Sqmm 3 core
6
-
-
... More
Supply and fix in replacement air break switch, gang operated, tripple pole, mechanically operated mechanism, switch air break gang operated mounted on 15 Nos insulator and steel frame with operating rod of 25 mm bore GI Pipe and locking arrangements worked from ground level for current rating 400 Amps, HT 11 KV grade including drop out fuses and necessary silver coper coating jumpers and making all electrical connections complete all as specified & as directed.
10
-
-
... More
Earthing complete with galvanized steel earth plate electrode of size 60cmx60cmx6 mm thick, buried directly in ground (earth pit not less than 2.10 m below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level, connected to galvanized iron strip 32 x 6mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel as shown in electrical plate No 3 of SSR Part I, connected to earth test point and the equipment on the other nuts and washers of galvanised ironside complete all as specified, including testing and commissioning complete all as directed.
Note : (a) The unit rates quoted against this item shall be deemed to include the cost of excavation and earth work in any type of soil, common salt & charcoal dust in alternate layers, PCC 1:3:6 as in pit, precast RCC 1:2:4 type B-1 with necessary reinforcement as in cover & frame for pit, funnel, watering pipe 20 mm bore GI pipe light grade, protection pipe 40 mm bore GI pipe medium grade etc.
(b) The quoted rates shall also deemed to include the cost of earth test point and earth strip/GI lead wire and protection pipe upto 7.5 meter beyond the earth plates electrode.
16
-
-
... More
M & L for 2 coat of aluminium painting over a coat of red oxide to steel surfaces of HT 4/6 pole sturcture (Angle Iron/MS channel /MS clamp etc) including preparation of old surface complete all as specified & as directed.
6
-
-
... More
Material & Labour for replacement of jumper/bus bar made of ACSR conductor of existing size on HT Four/Six pole structure having 2/3 incoming/outoing feeder including bus bar with PVC sleeve , lugs , nut bolts and washers complete all as specified & as directed.
6
-
-
... More
All as per Serial item No 25 here-in-before but 4/6 incoming/outoing feeder
4
-
-
... More
S&F in replacement Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers,welding, bending cold or hot,drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminium paint on 4/6 pole 11 KV HT structure .
6
-
-
... More
M & L for cutting and removing grass, vegetation bushes etc from surrounding 4 pole/6 pole HT structure , outside area of HT installation and removing all rubbish to a distance not exceeding 50 m complete all as specified & as directed.
1000
-
-
... More
Material and labour for filling and spreading of stone aggregate of nominal size not more than 25mm under 4/6 pole HT structure /surounding area of outdoor RMU manually without damaging any equipments, cable or parts , spreading & levelling of finished gravel uniformaly in layers n. ecc. 15 cm thick rammed to true surface all as specified and directed
15
-
-
... More
Suplying and laying as replacement in sub station 3.3 to 11 KV electrical insulation mat (IS Marked) complete all as specified & as directed.
20
-
-
... More
Supplying and fixing in replacement male contact/moving contact for gang operated air break device 11 KV complete all as directed at site by Engr-in-charge.
12
-
-
... More
Supplying and fixing in replacement female contact /fix contact jaw for gang operated air break device 11 KV complete all as specified & as directed.
12
-
-
... More
Supplying and fixing in replacement tinned copper flexible jumper 200 Amp/400 Amp for gang operated air break device 11 KV complete all as specified & as directed.
12
-
-
... More
Supplying and fixing in replacement MS jumper carrier for gang operated air break device 11 KV complete all as specified & as directed.
18
-
-
... More
Supplying and fixing in replacement back connector plate for gang operated air break device 11 KV complete all as specified & as directed.
18
-
-
... More
Supplying and fixing in replacement porcelain post insulator for gang operated air break device 11 KV complete all as specified & as directed.
18
-
-
... More
Supplying and fixing in replacement drop out fuse element 5 to 25 Amp complete all as specified & as directed.
15
-
-
... More
Supplying and fixing in replacement drop out fuse element 50 Amp complete all as specified & as directed.
15
-
-
... More
Supplying and fixing in replacement drop out fuse element 60 Amp complete all as specified & as directed.
15
-
-
... More
Supplying and fixing in replacement drop out fuse element 100 Amp complete all as specified & as directed.
15
-
-
... More
Supply installation & commissioning in replacement of 24V/40A Float Cum Boost Battery Charger unit including battery bank comprising 02 Nos of 12 Volts-100 AH sealed maintenance free battery. The CCCV battery charger consisting of copper wound, air cooled transformer, 01 Set single phase full wave bridge rectifier consisting of diodes and SCRs, liberally rated mounted on heat sink and complete with resistor/condenser network for surge supperssion . During auto float mode automatic changeover shall take place from float mode to boost mode and vice versa, 01 Set of solid state constant potential controller to stabilize the DC output voltage of the float cum boost charger, 01 No electronic controller , DC digital ammeter , DC digital voltmeter, Potentiometer , DC, MCB for reverse battery protection . The charger should have alarm annunciation with visual and audible alarm with manual reset facility for fuse fail alarm. Float cum boost battery charger and DC distribution board shall be housed in powder coated sheet steel cubicle with panels of 1.6mm thickness , louvers for ventilation , gland plate will be provided for cable entry from bottom .
2
-
-
... More
The battery charger shall be divided into two compartments. The upper compartment shall house the battery charger & DCDB with all necessary controls. The lower compartment shall be suitable for housing the batteries. Tech specification shall be as under:-
-
-
-
... More
(a) Input working voltage-180 -270 Volts (b) Nominal Input Voltage - 230 V , AC , 50 Hz,1
(c) On load input power factor - 0.8
(d) On load unit watt efficiencies- 80% (e) No load losses of complete charge- 10% (f) Ripple contents on the load (RMS)= 1% to 5% (g) Over load - 110% for 30 minutes and will give visual indication for over load condition. (h) Boost charging - 2.4 V/Cell .
(j) Float charging -2.15 V/Cell
(k) Float cum boost charging-Automatically changes from one state to another state as per battery condition and will give the visual indication for either float or boost based on charging mode.
(l) Reverse polarity -No damage will caused . A visual indication for reverse polarity will appear with an audio alarm.
(m) Short circuit-MCB protecton provided.
Make of battery charger. Statcon/Sinetrac/Amar Raja
Make of batteries. Exide/Amaron/Okaya
-
-
-
... More
S&F in replacement pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers nd one GI nut,150 mm height, 150mm dia, 11000 volts grade complete all as specified & as directed.
12
-
-
... More
S&F in replacement for Danger Notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white , with letters, figures and conventional skull and bobes in signal red colour and fixed with MS clamps, bolts and nuts of approved size, for HT, 25x20 cm size including taking down old one complete all as specified & as directed.
15
-
-
... More
S&F in replacement Lightening arrestors expulsion type with all fittings, transmission class, discharge capacity 30 kilo Amps suitable for 11000 voltscomplete all as specified & as directed.
12
-
-
... More
Re-Adjustment, Cleaning of Contact, greasing and testing of out door type Air break switch 11 KV, current rating upto 400 Amps for desired alignment to smooth operation from ground level and replacement of unserviceable parts in position. Note : Replacement of unserviceable parts shall be measured and paid separately under relevant items, complete all as specified & as directed.
12
-
-
... More
M&L for painting with two coat of superior aluminium paint including necessary preparation of surfaces of steel fencing by brushing/cleaning complete steel structure/frame/ gate for 11 KV transformer/2 pole to 8 pole structure/ HT panels/Sub Station above 20 Sqmm area complete all as specified and directed.
12
-
-
... More
Supplying and fixing (in replacement) 4 mm dia MS wire 75x75mm mesh, made upto into mattress or cages appx 2.00 m height and fixed with flat iron/angle as per existing by welding in position complete all as specified and directed
100
-
-
... More
S&F in replacement ACB 4 pole, 800 Amp, 50 KA, 415 Volt AC Horizontal draw mannual out type , front operated with Micro processor based LCD protection release for adjustable over current, short circuit and earth fault protection
2
-
-
... More
Supply and installation , testing and commissioning of 11 KV, 630 Amps, 21 KA/3 sec outdoor type Ring main unit IP 54 protection plug in type extensible on one side SF 6 gas insulated two incoming and three outgoing (5 way ) with metering plate form mounted compact switch gear consisting of 02 Nos load break switch as incommer and 03 Nos outgoing VCBs , all live parts, bus bars VCB will be enclosed in robotically/manual welded minimum 2 mm thick stainless steel tank filled with SF 6 gas IP 67 Degree of protection and tested for internal arc 20 KA/1 sec as per latest IEC 62271-200 complete installed on plateform as recommended by OEM, including the cost of PCC foundation for placing of RMU on plinth complete all as specified and directed. The unit shall include the following with all necessary standard fitting required at site complete all as specified & as directed.
1
-
-
... More
(A) Incoming Load Break Module - 02 Nos each switching unit shall be designed as a three position switch. This three function switch combines the functions of switch disconnector and earthing switch cables switch 12 KV, 630 Amp, 21 KA - 01 Set. Snap action mechanism for motorised and manual(Both) operation with integrated earthing switch - 01 Nos. Cable bushing 630 Amp standard C bushing - 01. Fault passage indicator, On(N-1) load break switch where n= no of load break switch s/c & E/F FPI with digital display to be added for detection of cable fault. ON, OFF, EARTH mechanical indication on the front mimic of the panel - 01. Capacitive voltage indication fixed type LED display - 01. ON, OFF, TRIP mechanical indication on the front mimic of the panel - 01. Cable box for termination of cable up to 1 No. x 185 sq.mm - 01. Cable cover standard - 01. Set of 12kV Cable Termination Boots - 01. Cable entry bottom, front - 01
-
-
-
... More
(B) (i) Out going VCBs - 03 No consisting of following - function unit consist of vaccum circuit breaker in combination with a three position switch. The three position switch fulfills the operation of the disconnector function and earthing function circuits breaker unit is equipped with an over current transformer for the protection of distribution Transformer/circuit vaccum circuit breaker 12 KV, not less than 400 A, 21 KA - 01. Spring assisted closing with stored Energy triping mechanism for motorised operation with integrated earthing switch - 01. live cable LED indicators thrugh capacitor voltage dividers mounted on the bushings push button for breaker trip - 01 sec O/C + E/F self powered numerical protection relay with low and High set for Over current and earth fault Relay should have facility to display the maximum loaded phase current also current also relay shall record minimum 5 fault records with time stamping - 01 Alaram trip indication 6 window annunciator for transformer faults Mechanical ON/OFF/EARTH indication -01.
-
-
-
... More
Auxliary contacts on load switch are 1 No+2NC & Auxiliary conract on earth switch is 1 No+ 1NC-01. Self powered electronic numerical protection relay providing 3 over-currents & 1 E/F protection - 01, shunt trip coil 24 V DC-01 capactive voltage indication fixed type LED display -01 ON/OFF/Trip mechanical indication on the front mimic of panel-01 cable box for termination boots-01. Metering Equipment incl. 01 x Digital Voltmeter (Acc.Cl.0.5), 01 x Digital Ammeter (Acc.Cl.0.5), 01 x Tri-VectorMeter (Acc.Cl.0.5) Auxliary relay for transformer protection -06 Nos. (C ) Additional equipment deliverd separately or mounted seperatly, Bus connected with battery charger and inbuilt battries for motor power supply-01 (i) PT ratio 11KV/3/110/v3, 100 va, 0.5 class for measurement with volts meter(ii) Auxliary transformer of 11KV/230V, 1 KVA for powering the motors and battery charger (iii ) 24 V DC battery charger and battries for motor power supply. Standard mano meter -01, Operating handle - 02 , cable clamping provision(standard)-01 Operation and maintance manual - o1, installation and commissioning manual - 01, cost of PCC works for placing RMU on plinth is deemed to be included in the cost, Height of plinth shouldnot be less than 0.45 mtrs from ground level.
-
-
-
... More
NOTE :- (a)The above module consisting of two Load break Switch and 03 VCBs shall be alligned appropriately and must have electrical and mechanical interlocking as per latest electrical safety norms including installation on plateform as recommended by OEM complete.
-
-
-
... More
Dismantling complete 4 pole structure after installation of RMU , alongwith insulators, cross arms bracings support, angle iron, channels. Nuts & bolts, clamps and GO/DO system complete all as specified and directed