Military Engineer Services Tender

If you're typing tender ID over and again or finding it difficult to go through the cumbersome government websites for looking at Delhi tenders online. We have come up with a solution i.e. we have collated every eprocurement Delhi tender on BidAssist. Also, for any queries related to an e-tender Delhi, like the bidding process, registration process, etc., the same are explained below.

Military Engineer Services - MES Tender

Works
Electrical and Electronics
Electrical Works
Eprocure
Opening Date22 Nov 2024
Closing Date4 Dec 2024
Tender Amount₹ 1,08,00,000 
Notes
Download

Costs

Description

Unlock the Tender details for free
Scription for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user this is tender description for unregistered user

Contact

Unlock the Tender details for free
GEM & Bid Advisory Services
Get portal registration, tender bidding, product/service listing or vendor/MSME certification services at a nominal cost

BOQ Items

... More
DO_NOT_SHOW

-

-

-

View all details for FREE
... More
(xiii) Replace the jaw contacts, If required. (xiv) Improvement of resistance of epoxy insulator and epoxy body by applying post heated varnish. (xv) Replacement of Dashpot/shock absorbers . (xvi) Replacement of carbon brush of spring charging motor (b) The following test shall be carried out:- (i) Primary Injection Test of CT / PT (ii) Closing & Opening Timing Test for all three poles. (iii) IR Test with megger in open and closed condition. (iv) Contact resistance test for all three poles (v) Closing coil resistance (vi) Tripping coil resistance. (c) Testing of following relays of control panel with Secondary Injection Kit ,checking and programming of relay :- (i) Over current and earth fault relay (d) Testing of following Aux relay (i) DC Supply supervision relay. (ii) Master trip relay

-

-

-

... More
Supply installation, testing and commissioning in replacement Potential Transformer (PT) oil cooled out door single phase ( Earthed type) of voltage ratio 33 KV/110 V class 3P - 0.5-3, burden 50 VA insulation level of 70/170 KV as specified below:- (a) Normal System Voltage-33 KV (b) Highest System Voltage-36 KV (c) Rated Primary voltage- 33 KV/√3 (d) Rated secondary voltage- 110 V/√3 (e) Nos of Lt winding 2 (f) Metering Core Accuracy class - 0.5 (g) Metering Core Rated Burden- 50 VA (h) Nos of Phase- Single (Earthed Type) (j) Protection core accuracy class - 3P (k) Protection core rated Burden - 50 VA (l) Rated Voltage Factor - 1.2 continuous & 1.5 for 30 Sec (m) Insulation Level- 36/70 KV.170 KVP (n) Temp rise at rated continuous thermal current over ambient at site - 45 0C (o) Porcelain Bushing type - Hollow Cylinder (p) 1.2/50 micro second impulse withstand test vol -170 KV (Peak) (q) Creepage distance of HV bushing - 900 mm (min) (r) Primary & Secondary winding material - Copper

1

-

-

... More
Supply, installation, testing and commissioning in replacement 33 KV current transformer oil cooled out door single phase, oil immersed and self cooled type of ratio 800-400/1-1-1-1 suitable for metering and protection equipment installed on control panels terminal block as specified below :- (a) Normal System Voltage-33 KV (b) Highest System Voltage-36 KV (c) Rated Primary current- 800-400 Amp (d) Rated secondary current- 1 Amp (e) Nos of Core - 4 (f) Core01: Accuracy class 5P10, 10VA, ALF ≥10 (g) Core02: Accuracy Class 1.0, 10VA, ISF ≤ 5 (h) Core 03 Protection core accuracy class -PS, Protection knee point voltage- 300 Volt at lower ratio (j) Core 04-Spare (k) Continuous thermal current rating 120 % of rated primary current (l)Temp rise at rated continuous thermal current over ambient at site - Less than or equal to 45 degree C (m) Insulation Level- 36/70 KV.170 KVP (n) 1.2/50 Micro second impulse withstand test voltage- 170 KV (peak) (o) Short time thermal current rating for one second - 25 KA/1 Second (p) Dynamic Current Rating - 62.5 KA ( peak) (q) Porcelain Bushing type - Hollow Cylinder (r) Creepage distance of HV bushing - 900 mm (min) (s) Primary & Secondary winding material - Copper

1

-

-

... More
Material and labour for stretching/tightening of loose ACSR conductor including fixing of conductor accessories such as clamp etc. as per site condition of Zebra/Dog/Goat/Panther/ Wolf conductor of 33 KV lines complete all as specified and directed. Note : Length of indl conductor shall be measured.

3

-

-

... More
Material and labour Jointing of ACSR conductor of any type with mid span joint through compression joint machine of 33 KV lines complete all as specified and directed.

4

-

-

... More
Trimming and cutting of tree branches(not more than 25mm girth) coming across 33 KV HT over head line clearing the line around 2m single/both sides and and disposal of branches from site exceeding 50m and not exceeding 250m from site complete all as specified and directed. Note : - (i) Length of span is approx 200 to 225 RM. (ii) Due care is to be given while trimming/cutting the tree branches that there should no damage to over head line conductor/pole. In case due to any negligence, damage is caused to be make good/renewal by the contractor from his own resources and nothing extra is admissible. (iii) All Safety to labourer must be adhered by the contractor during trimming and cutting of tree branches.

15

-

-

... More
Supplying and fixing , Stretching, Securing, Connecting & testing of Aluminium Conductor Steel Reinforced (ACSR) of size Zebra/Panther/Wolf for 33 KV lines/33 KV yard complete including taking out old unserviceable conductor complete all as specified and directed.

3

-

-

... More
Material and labour for removing of grass/vegetation bushes from inside of 33 KV towers and upto a distance of 1.5 meter outside the tower complete all as specified as directed .

5

-

-

... More
Material and labour in replacement of damage single/ double/triple tension disc insulators and hardware fitting and fixing in position including tightening of bolts & nuts, complete after dismantling and lowering of damage conductor/disc insulator by taking tension of conductor on a separate arrangement including opening & providing of jumpers of 33 KV tension towers complete all as specified and directed.

4

-

-

... More
Material and labour in replacement of damage single/ double /triple disc suspension disc insulator by re-arranging with good/new disc insulators after taking the load of conductor on alternate arrangement including proper clamping etc. as per site requirement of 33 KV tower complete all as specified and directed.

4

-

-

... More
Testing the cables with high voltage DC testing machine and locating the fault in the cables by fault locating machine to pin point exact position of fault, disconnecting faulty 33 KV HT cables of different sizes from both ends, removal of Fault, Re-connections and testing of cables after removal of fault complete all as specified and directed. Note-: (a) 33 KV HT cable & joints shall be measured and paid for separately under respective items of schedule. (b) Retrieved old serviceable cable cover will be laid in trenches for cable protection. If extra PCC cover and sand required at site shall be measured and paid separately under respective items of BOQs. (c) Excavation and earth work will be measured and paid for separately under respective items of schedule.

15

-

-

... More
Material and labour for emergency maintenance work of 33 KV overhead line during breakdown by deploying skilled labourer and electricians at faulty site having Gang of minimum 6 persons and transportation including hydraulic machine and other tools and plant required at site for fault rectification. Note:- Contractor or his rep shall come to the site of breakdown within one hour of notification of breakdown . In case the rep or contractor shall not come to the site of breakdown and start attending breakdown within 1.00 hour a penalty of Rs 1000 per fault per hour will be imposed over contractor and will be deduct from his dues.

10

-

-

... More
All as per Item No 13 here-in -before above but Gang of minimum 3 persons except hydraulic machine.

10

-

-

... More
Supply & Fixing in replacement dead end clamps aluminium cast alloy for both terminals suitable for ACSR conductor of type Zebra/Dog/Goat/Panther/Wolf of 33 KV yard/33 KV towers with GI nuts bolts complete all as specified and directed

18

-

-

... More
Supply & Fixing in replacement 33 circuit breaker clamp aluminium cast alloy for both terminals suitable for ACSR conductor of type Zebra/Dog/Goat/Panther/Wolf for 33 KV yard with GI nuts bolts complete all as specified and directed

18

-

-

... More
Supply & Fixing in replacement CT clamps aluminium cast alloy for both terminals suitable for ACSR conductor of type Zebra/Dog/Goat/Panther/Wolf for 33 KV yard with GI nuts bolts complete all as specified and directed

18

-

-

... More
Supply & Fixing in replacement PT clamps aluminium cast alloy for both terminals suitable for ACSR conductor of type Zebra/Dog/Goat/Panther/Wolf for 33 KV yard with GI nuts bolts complete all as specified and directed

18

-

-

... More
Supply, Laying, jointing, testing and commissioning of 33 KV (earth) grade of size 400 Sqmm 3 Core (Heavy duty) with stranded compacted circular aluminium conductor screened with extruded semi- conducting compound in combination with copper tape, cores laid up, inner sheath of thermoplastic tape, PVC bedded galvanised steel strip, armoured and overall FRLS PVC sheathed confirming to IS-70298, Part-II with latest amendments laid in cable Ducts/Trays/ Tranches/Encased in GI pipe/RCC/DWC HDPE pipes complete all as specified and directed.

300

-

-

... More
Supply, Laying, jointing, testing and commissioning of 33 KV (earth) grade of size 300 Sqmm 3 Core (Heavy duty) with stranded compacted circular aluminium conductor screened with extruded semi- conducting compound in combination with copper tape, cores laid up, inner sheath of thermoplastic tape, PVC bedded galvanised steel strip, armoured and overall FRLS PVC sheathed confirming to IS-70298, Part-II with latest amendments laid in cable Ducts/Trays/Tranches/Encased in GI pipe/RCC/DWC HDPE pipes complete all as specified and directed.

250

-

-

... More
Supply, Laying, jointing, testing and commissioning of 11 KV (earth) grade of size 300 Sqmm 3 Core (Heavy duty) with stranded compacted circular aluminium conductor screened with extruded semi- conducting compound in combination with copper tape, cores laid up, inner sheath of thermoplastic tape, PVC bedded galvanised steel strip, armoured and overall FRLS PVC sheathed confirming to IS-70298, Part-II with latest amendments laid in cable Ducts/Trays/Tranches/Encased in GI pipe/RCC/DWC HDPE pipes complete all as specified and directed.

300

-

-

... More
Supply, Laying, jointing, testing and commissioning of 11 KV (earth) grade of size 240 Sqmm 3 Core (Heavy duty) with stranded compacted circular aluminium conductor screened with extruded semi- conducting compound in combination with copper tape, cores laid up, inner sheath of thermoplastic tape, PVC bedded galvanised steel strip, armoured and overall FRLS PVC sheathed confirming to IS-70298, Part-II with latest amendments laid in cable Ducts/Trays/Tranches/Encased in GI pipe/RCC/DWC HDPE pipes complete all as specified and directed.

400

-

-

... More
Supply, Laying, jointing, testing and commissioning of 11 KV (earth) grade of size 185 Sqmm 3 Core (Heavy duty) with stranded compacted circular aluminium conductor screened with extruded semi- conducting compound in combination with copper tape, cores laid up, inner sheath of thermoplastic tape, PVC bedded galvanised steel strip, armoured and overall FRLS PVC sheathed confirming to IS-70298, Part-II with latest amendments laid in cable Ducts/Trays/Tranches/Encased in GI pipe/RCC/DWC HDPE pipes complete all as specified and directed.

250

-

-

... More
Supply, Laying, jointing, testing and commissioning of 11 KV (earth) grade of size 150 Sqmm 3 Core (Heavy duty) with stranded compacted circular aluminium conductor screened with extruded semi- conducting compound in combination with copper tape, cores laid up, inner sheath of thermoplastic tape, PVC bedded galvanised steel strip, armoured and overall FRLS PVC sheathed confirming to IS-70298, Part-II with latest amendments laid in cable Ducts/Trays/Tranches/Encased in GI pipe/RCC/DWC HDPE pipes complete all as specified and directed.

290

-

-

... More
Supply, Laying, jointing, testing and commissioning of 11 KV (earth) grade of size 120 Sqmm 3 Core (Heavy duty) with stranded compacted circular aluminium conductor screened with extruded semi- conducting compound in combination with copper tape, cores laid up, inner sheath of thermoplastic tape, PVC bedded galvanised steel strip, armoured and overall FRLS PVC sheathed confirming to IS-70298, Part-II with latest amendments laid in cable Ducts/Trays/Tranches/Encased in GI pipe/RCC/DWC HDPE pipes complete all as specified and directed.

350

-

-

... More
Supply, Laying, jointing, testing and commissioning of 11 KV (earth) grade of size 1000 Sqmm 1 Core (Heavy duty) with stranded compacted circular aluminium conductor screened with extruded semi- conducting compound in combination with copper tape, cores laid up, inner sheath of thermoplastic tape, PVC bedded galvanised steel strip, armoured and overall FRLS PVC sheathed confirming to IS-70298, Part-II with latest amendments laid in cable Ducts/ Trays/Tranches/Encased in GI pipe/RCC/DWC HDPE pipes complete all as specified and directed.

280

-

-

... More
Supplying & laying reinforced precast concrete cable cover, class EHV, type 1 with peak, size 450mm x 230mm x 50mm in trenches for protecting under ground cable as per IS (for 33 KV Cable) complete all as specified and directed.

1800

-

-

... More
All as per srl item No 27 here-in-before but using old reinforced precast concrete cable cove obtained under srl item No 66 here in before.

352

-

-

... More
Supplying and laying un-reinforced precast concrete cable cover, class HV, type 1, flat size 300mmx 180mm x 40mm.

8500

-

-

... More
All as per srl item No 29 here-in-before but using old un-reinforced precast concrete cable cover obtained under srl item No 66 here in before.

850

-

-

... More
Supply & Fixing in replacement Isolators clamps aluminium cast alloy for both terminals suitable for ACSR conductor of type Zebra/Dog/Goat/Panther/Wolf for 33 KV yard with GI nuts bolts complete all as specified and directed

12

-

-

... More
Supply and fix Cable jointing kit for 33 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following size :-

-

-

-

... More
400 sqmm 3 core.

8

-

-

... More
300 sqmm 3 core.

6

-

-

... More
Supply and fix Cable jointing kit for 33 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following size :-

-

-

-

... More
400 sqmm 3 core.

5

-

-

... More
300 sqmm 3 core.

4

-

-

... More
Supplying and Fixing in replacement, Post insulator with hardware fittings, 33 KV Grade, for isolator complete all as specified and directed.

8

-

-

... More
Supplying and fixing in replacement, Disc insulators with hardware fittings, 33 KV Grade for 33 KV yard complete all as specified and directed.

8

-

-

... More
Supply & Fixing in replacement of pin insulator with hardware fittings 33 KV grade complete all as specified and directed

8

-

-

... More
Material and labour for replacement of aluminium jumper made of ACSR conductor of type Zebra/Dog/Goat/ Panther/Wolf conductor of 33 KV towers/33 KV yard complete all as specified as directed .

15

-

-

... More
Material & labour for cleaning of the bay/yard (82.5 RM x 26.5 RM) manually without damaging any equipments, cable or parts of the 33 KV Grid bays, removing of dusts/ grass/herbs etc. complete all as specified as directed .

1

-

-

... More
Material and labour for spreading of stone aggregate of nominal size not more than 40mm from the bay/yard manually without damaging any equipments, cable or parts of the 33 KV Grid bays, spreading & levelling of finished gravel uniformly in layers n. exc. 15 cm thick watered and rammed to true surface complete all as specified and directed

7

-

-

... More
Material and labour for cutting and removing grass, vegetation bushes etc. from inside boundary wall and outside boundary wall of 33/11 KV Sub Stn, around 33 KV towers and removing all rubbish to a distance not exceeding 50 m complete all as specified as directed .

1200

-

-

... More
Material and labour for Servicing & Repairs to Air-break switch (isolator) off load, rotating type, 33 KV, 800 Amps to 1250 Amps capacity, with proper alignment of isolator rotating blades, with fixed contact jaws, arcing horns, applying petroleum jelly to moving mechanism, cleaning and lubricating to isolator gear box assembly, tightening all nuts, bolts and clamps of jumpers etc., repairing to isolator gear box assembly and making in proper serviceable condition for smooth functioning, testing and commissioning on load complete all as specified and directed.

11

-

-

... More
Supplying and fixing in repairs, male/moving contact/ rotating blade of HDE copper silver plated of Air Brake, off load isolator switch, rotating type, 33 KV, 1250/800 Amps capacity with all fixing nuts, bolts etc. complete all as specified and directed.

8

-

-

... More
Supplying and fixing in repairs, Fixed Contacts, made of HDE copper, silver plated, of Air Brake, off load isolator switch, rotating type, 33 KV, 1250/800 Amps capacity with all fixing nuts, bolts etc. complete all as specified and directed.

8

-

-

... More
Supplying and fixing of terminal pad for Air Brake, off load isolator switch, rotating type, 33 KV, 1250/800 Amps capacity.

8

-

-

... More
Supplying and fixing of arching horn for Air Brake, off load isolator switch, rotating type, 33 KV, 1250/800 Amps capacity.

8

-

-

... More
Supply , installation, testing and commissioning in replacement of 33 KV air brake off load line isolator switch rotating type manually gear drive mechanism operated highest system voltage 36 KV rated current 1250 Amps triple pole with earthing device each pole consist of insulating pedestals 03 Nos on galvanized steel base as per BSS /IS including rotating blade of HDE copper and fixed contacts of same material , spring loaded arcing horns of adequate section to brake magnetizing current of transformer as directed with adequate 50mm dia GI operating pipe for operation from ground level and operating handle complete with both off and on positions complete all as specified and directed.

1

-

-

... More
All as per item No 46 above but bus isolator without earthing device

1

-

-

... More
Supplying ,fixing , testing of master trip relay , 50/24 Volt DC in control panel including wiring and taking down old UNSV relay complete all as specified and directed.

3

-

-

... More
Supplying ,fixing , testing of Trip circuit supervision relay , 50/24 Volt DC in control panel including wiring and taking down old UNSV relay complete all as specified and directed.

2

-

-

... More
Supplying ,fixing , testing of DC supervision relay relay , 50/24 Volt DC in control panel including wiring and taking down old UNSV relay complete all as specified and directed.

4

-

-

... More
Supplying ,fixing , testing of SF 6 gas pressure supervision relay , 50/24 Volt DC in control panel including wiring and taking down old UNSV relay complete all as specified and directed.

6

-

-

... More
Supplying and fixing in replacement PT fuse for 11 KV/110 V PT complete as directed at site.

8

-

-

... More
Supply & Fixing steel structure with ISMB/Channel/Angle iron/flat , clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint at 33 KV yard for fixing of isolator/CT/PT and for fixing of GO/DO etc. complete all as specified and directed .

7

-

-

... More
Supplying, installation, commissioning and testing in replacement of 11 KV Current Transformer (CT`s), indoor type, epoxy cast bar Primary type having ratio 1200/600/5-5-5 Amps , core -1, Class 10 P20 , 15 VA for protection , Core 2 Class 0.5 , 15 VA for metering, core -3 for differential protection , Short circuit time rating 18.4 kA for 3 Sec including associated wiring including taking down old UNSV CTs complete all as specified and directed.

1

-

-

... More
Supplying, installation, commissioning and testing in replacement of 11 KV Current Transformer (CT`s), indoor type, epoxy cast bar Primary type having ratio 800/400/5-5-5 Amps , core -1, Class 10 P20 , 15 VA for protection , Core 2 Class 0.5 , 15 VA for metering including associated wiring including taking down old UNSV CTs complete all as specified and directed.

1

-

-

... More
Material & labour for repair /servicing of RTCC panel of OLTC control panel of 33KV/11KV Power transformers of capacities 20MVA including repair /replacement to control wiring, repair to operation of OLTC from RTCC and checking of following and testing complete all as specified and directed :- (a) Digital Winding temp meter. (b) Digital oil temp meter. (c) Digital remote tap position indicator. (d) Indicator lamps. (e) Space Heater. (f) Fan auto working switch. (g) Analog to digital convertor and other spares required for displaying winding and oil temp.

1

-

-

... More
All as per item ser No 56 here-in-before but 33KV/11KV Power transformers of capacities 16MVA

1

-

-

... More
All as per item ser No 56 here-in-before but 33KV/11KV Power transformers of capacities 10MVA

2

-

-

... More
Supply only transformer oil of approved quality as per IS having dielectric strength of 45-60 KV in 2.5mm gap for filling in transformer or for topping up as required and directed.

3500

-

-

... More
Cable jointing kit for 11KV (earth) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size:-

-

-

-

... More
120 Sqmm to 185 Sqmm

4

-

-

... More
240 Sqmm to 300 Sqmm

4

-

-

... More
400 Sqmm

2

-

-

... More
Cable jointing kit for 11KV (earth) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size:-

-

-

-

... More
120 Sqmm to 185 Sqmm

5

-

-

... More
240 Sqmm to 300 Sqmm

3

-

-

... More
400 Sqmm

2

-

-

... More
Cable jointing kit for 11KV (earth) grade cable for straight through termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size:-

-

-

-

... More
120 Sqmm to 185 Sqmm

5

-

-

... More
240 Sqmm to 400 Sqmm

4

-

-

... More
Supply and fixing in replacement of ACB 4 Pole 800 Amps,50 KA 415 Volt, Horizontal , Manual draw out type motorized, front operated with microprocessor based LCD protection release and adjustable over current and earth fault protection complete all as specified and directed.

1

-

-

... More
Supply and fixing in replacement of ACB 4 Pole , 1250 Amps,50 KA 415 Volt, Horizontal draw out type motorized, front operated with microprocessor based LCD protection release and adjustable over current and earth fault protection

1

-

-

... More
Supply and fixing in replacement of ACB 4 Pole , 1600 Amps,50 KA 415 Volt, Horizontal draw out type motorized, front operated with microprocessor based LCD protection release and adjustable over current and earth fault protection

1

-

-

... More
Excavation in trenches not exceeding 1.5m wide & not exceeding 1.5m in depth and n.exc 10 sqm on plan for foundations , laying of LT under ground cables/ GI pipes and steel tubular poles etc. and getting out as in soft / loose soil complete all as specified and directed.

1160

-

-

... More
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cm deep as in soil complete all as specified and directed.

873

-

-

... More
Removal of excavated material n. exc 50 mtr and depositing where directed at a level n.exc 1.5 mtr above in starting point.

287

-

-

... More
Supply & Fixing common burnt bricks as mechanical protection of this cables using old size sub class ‘B’ bricks laid dry flat over the cable width equal to the length complete all as specified and directed.

7.04

-

-

... More
Sand filling in trenches for cushioning of UG cables as layers of 8 cm before laying and 15 cm after laying of cables all as directed.

242

-

-

... More
M/L for GI Tubes, of size 40 mm dia light grade, galvanised, with all fitting , laid in trenches for protection of cable in road /drain crossing complete all as specified and as directed.

24

-

-

... More
M/L for GI Tubes, of size 50 mm dia light grade, galvanised, with all fitting , laid in trenches for protection of cable in road /drain crossing complete all as specified and as directed.

24

-

-

... More
Supply, laying, testing and commissioning in replacement LT XLPE UG cable insulated, armoured heavy duty electric cable, 1100 volts grade with stranded aluminium conductor of 16 Sqmm 4 core complete including dismantling of old unserviceable cable.

400

-

-

... More
Supply, laying, testing and commissioning in replacement LT XLPE UG cable insulated, armoured heavy duty electric cable, 1100 volts grade with stranded aluminium conductor of 25 Sqmm 4 core complete including dismantling of old unserviceable cable.

500

-

-

... More
Supply & installing in replacement of steel tubular swaged poles type 410 SP-31 (9 mtr long) of apprx wt.147 kg conforming to IS 2713 (Part-II) including excavation, earth work, PCC foundation, base plate, PCC coping, GI pipe for cable protection etc. and GI bracket for fitting mounting of flood light fittings , complete all as per manufacturer's instructions and complete all as specified and as directed. NOTE:- The unit rate in this item is deemed to be included the cost of excavation and earth work in any type of soil, PCC foundation 1:4:8 type D-2 , PCC coping 1:2:4 type B-1 as in steel tubular pole and GI bracket made of Channel /flat iron incl nut bolts, clamps etc., 1.5 mtr x 1.5 mtr long for fixing of LED Flood light fittings . The steel pole shall be painted by bituminous paint total length inside and up to planting depth outside.

16

-

-

... More
Supply & fixing in replacement of 90 Watt LED flood light fittings made up of pressure die cast housing with toughened glass and individual high power LEDs with secondary optics, IP66 protection complete all as specified and directed.

16

-

-

... More
Supply & Fixing in replacement KIOSK box weather proof including made out of one piece mounted SMC base and door pole mounted hinged door size 333x233x120mm out side and 300x200x105mm inside dimensions comprising of aluminium bus bar 4 strips for 3 phase and neutral 63 Amps and 15 Amps fuse grip with base including embossing/ painting of danger notice of size not less than 10cm x 7.5cm with letters, figures and conventional skull and bones in signal red colour on front face of KIOSK box body complete all as specified and directed.

16

-

-

... More
Supply, drawing, connecting & testing in replacement of 3 core, 2.5 Sqmm PVC insulated and PVC rounded sheathed, copper conductor (flexible) industrial cable 1100 Volts grade conforming to IS-694 in steel tubular pole from KIOSK box to light fittings including providing suitable copper lugs all as specified and directed. Note : Steel tubular pole shall be measured and paid separately.

140

-

-

... More
Supply & Fixing of time switches astro type in having longitude and latitude of Indian cities in memory 415 V three phase 20 Amp rating with 20 Amps, 415 Volts, three pole contactor fitted inside factory made 2mm thick steel enclosure duly powder coated paint complete all as specified and directed.

1

-

-

... More
Supply and fix LED Flood light 200W including all fixing accessories completed all as per specified and directed.

20

-

-

... More
Supply & Fixing 4 mm dia MS wire 150 mm x 100 mm mesh, made upto into mattress or cages appx 1.5 mtr height and fixed with flat iron/angle by welding in position and directed including complete all as specified and directed. Note:- MS angle/MS flat will be measured and paid separately.

30

-

-

... More
Material and labour for two coats of synthetic enamel paint of silver colour on steel surfaces over a coat of red oxide primer including preparation of surfaces complete all as specified and directed.

30

-

-

... More
Material and labour for cement concrete type D-2, 1:4:8 (using 40 mm graded crushed stone aggregate) for sub floors, sub-bases, floors, foundation and paving etc. complete all as specified and directed .

1

-

-

... More
Material and labour for MS work of angles for post and struts of fencing around transformer plinth etc. drilling holes, flat iron fillet for securing wire mess by welding to angle iron frame and framed work as in door/ gate of angle and wire mess. Door to be fixed by 03 Nos 100mm long hinges and one sliding door bolt of 300mm long for locking arrangement complete all as specified including.

1

-

-

... More
Boring of hole under road/pavement/hard standing or any other situation by manual means and suitable for passing of GI pipe 50 to 100 mm bore and making good both ends all specified and directed

60

-

-

... More
Supply and installation of Decorative pole as per Lustre Item No. Li-8440. The total height of the Decorative pole shall be 3870 mm nominal above the ground. The pole and base plate dia are 114mm and 250mm respectively. The pole is made out of mild steel tube with built in Service window at the bottom part of the pole to accommodate the 6 amp. SPMCB & 32 AMP. Heavy duty connector for mains connections. The MCB and connector shall be provided in the service window duly fitted on a suitable size heavy duty bakelite plate. The decorative arm and fixture is made of Aluminium. A toughened glass protector shall be fitted on the top of the fixture. The top reflector is made of Aluminium. The body of decorative pole should be machined & polished properly to give it a smooth surface. The decorative pole shall be duly pre-treated by Shot Blasting Process & painted in UV ray resistant P.U. top coating in approved finish. Decorative pole shall be installed at desired location including foundation of the pole by making cement concrete foundation of 1:2:3( 1 cement: 3 course sand : 6 graded stone aggregate 40mm nominal size) with the help of anchor bolts and 38mm G.I sleeve as required.

12

-

-

... More
Supply of GI structure mounted three pole gang operated 33KV live tank Outdoor Vacuum Circuit breaker , 2000A, 1.5KA for 3 sec Fault current, Rated voltage 36 KV, frequency 50 Hz, Insulation Level 70 KV/170 KV PK, single capacitor bank switching current 400A with Hydrophobic Cycloaliphatic Epoxy Resin (HECP) post insulator complete with terminal pad. The VCB shall have IP54 complied CRCA made enclosure inside which CB mechanism, manual operation handle, Spring charging motors are available. The VCB hall have electrical ON.OFF, Spring Charge Indication apart from mechanical indication and suitable 230V AC & 48 V DC input. The VCB must be equipped with 2 Nos Trip coil & 1 No Close coils.

1

-

-

... More
Material and Labour for shifting of 33 KV Isolator from PT Bus isolator to line isolator and shifting of 33 KV Line Isolator to Bus PT Isolator carefully without damaging any equipment by disconnecting of Electrical Connections by taking proper Shut down Complete all as specified the isolator is deemed to be included in the quoted rate

2

-

-

... More
Supply & Fixing in replacement Feeder Protection relay suitable for 11 KB VCB, Model WO CSEPRO-1A/5A-50/60 Hz,

1

-

-

... More
Supply & Fixing in replacement Electronic Trivector Meter ER 300 P, 3 Phase 4 wire, 3 x 63.5 V, Principal unit : Kwh/KVARH, Frequency: 50 Hz, Pulse rate 10000 Imp/Kwh, 10000 Imp/KVArh, Class : 0.5 s for Active 1.0 s for Reactive complete all as specified and as directed.

2

-

-

... More
Supply & Fixing in replacement Amp Meter Suitable for 11 Kv CTR 400/200/5 + 5 Amp as per Sample

6

-

-

... More
Supply & Fixing in replacement volt meter suitable for 33 KV VCB Panel, auxiliary supply 50 V DC as per sample.

2

-

-

... More
Supply & Fixing in replacement over current relay suitable for 11 Kv VCB control Panel. Model No CSE NEX-1A/5A-50/60 Hz.

2

-

-

... More
Boring of hole under road/pavement/hard standing or any other situation by trenches Technology using ultra sounding Technique and necessary machine including HDPE pipe of 160mm dia suitable for 0.6 MPA working pressure complete all as specified and directed.

90

-

-

... More
(xi) All existing earthing of the lifts shall be maintained and made fully functional by the contractor to the entire satisfaction of the Engr-in-Charge.

-

-

-



Evaluation Notes How It Works ?

Potential Partner

Select Your Requirements
Disclaimer: BidAssist has made every reasonable effort to ensure that the information is accurate and authentic however it cannot be held liable for any third-party claims or losses of any damages. BidAssist makes no warranty, expressed or implied, as to the results obtained from the use of the information. If you think you may have noticed any error or omission, please let us know by contacting contact@bidassist.com.